ARCHITECTUREELEVEN 18 · 2016. 11. 28. · piping penetrations of rated floors and walls shall be...
Transcript of ARCHITECTUREELEVEN 18 · 2016. 11. 28. · piping penetrations of rated floors and walls shall be...
-
M1
DEA
GOB
KMP
AS NOTED
ME
CH
AN
IC
AL S
PE
CIF
IC
AT
IO
NS
,
SC
HE
DU
LE
S A
ND
D
ET
AILS
SPECIFICATIONSABBREVIATIONS
LEGEND
DESIGN DATA
GENERAL NOTES
SUPPLY BRANCH &FLEX DUCT SCHEDULE
AIR DISTRIBUTIONSCHEDULE
VENTILATION AIR SCHEDULE
6304 N
. IN
TE
RN
AT
IO
NA
L D
R O
RLA
ND
O, F
L 32819
RE
V#
DA
TE
RE
VIS
IO
N
DR
AW
IN
G T
IT
LE
11-16-16
160451
PROJ. NO. :
SCALE
DATE
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING NO.
CO
CO
T
HA
I
PH
EC
HG
UE
CH
T
AIN
G
ENGINEER OF RECORD
DAVID E. ALLEY, PEPE #55008
cons
ultin
g en
gine
ers
NGIN
EERI
NG
ONS
TRUC
TION
GEC
ROUP
tel. 3
21.25
3.122
1fa
x. 32
1.253
.3123
2651
wes
t eau
gallie
, suite
a m
elbou
rne, fl
329
35
www.
cege
ngine
ering
.com
A W
OM
EN'S
BU
SIN
ESS
ENTE
RPRI
SE
424
E. C
entr
al B
lvd.
#54
2O
rland
o, F
L 3
2801
ww
w.e
leve
n18a
rchi
tect
ure.
com
Lice
nse:
AA
2600
1884
ELEV
EN 18
ARC
HIT
ECTU
RE
Mar
k A
dam
s: 4
07-7
56-2
119
Kim
Day
: 40
7-41
6-99
60N
eke
Whi
te:
407-
416-
9965
licen
se #
0008
097
DX ROOFTOP UNIT SCHEDULE
DUCT SUPPORT DETAIL
TURNING VANE DETAIL CABINET CEILING FAN DETAILBRANCH DUCT DETAIL
RTU CURB DETAILP-TRAP DETAIL
ROOF PIPESUPPORT DETAIL
UPBLAST EXHAUSTROOF FAN DETAIL
EQUIPMENT CURB DETAIL
AutoCAD SHX Text1.0 BASIC MATERIAL AND METHODSBASIC MATERIAL AND METHODS
AutoCAD SHX Text1.1 SCOPE OF WORK SCOPE OF WORK PROVIDE LABOR AND MATERIALS AS REQUIRED TO PROVIDE A FULLY FUNCTIONING AND COMPLETE SYSTEM AS INDICATED ON DRAWINGS. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT. FINAL LOCATIONS OF EQUIPMENT SHALL BE FIELD DETERMINED. ALL DISCREPANCIES ON DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN WRITING PRIOR TO SUBMISSION OF BIDS.
AutoCAD SHX Text1.2 GENERAL AND SPECIAL CONDITIONS GENERAL AND SPECIAL CONDITIONS ALL DIVISION 1 SPECIFICATIONS AND ARCHITECTURAL GENERAL AND SPECIAL CONDITIONS OUTLINED IN THE CONTRACT DOCUMENTS APPLY TO MECHANICAL SYSTEMS. ADDITIONALLY, WORK SHALL COMPLY WITHFLORIDA BUILDING FLORIDA BUILDING CODE AND REGULATIONS OF THE LOCAL AUTHORITY HAVING JURISDICTION, NATIONAL FIRE PROTECTION ASSOCIATION, AND NATIONAL ELECTRICAL CODE. ALL EQUIPMENT SHALL CARRY THE UNDERWRITER'S LABORATORIES (UL) SEAL WHERE APPLICABLE.
AutoCAD SHX Text1.3 QUALITY CONTROL QUALITY CONTROL UNLESS OTHERWISE NOTED, PROVIDE NEW MATERIALSFREE FREE OF DEFECTS. WHERE NO SPECIFIC WEIGHTS OR GRADES ARE SPECIFIED, PROVIDE MATERIALS OF AN ACCEPTED STANDARD WEIGHT AND GRADE ACCORDING TO CODE AND GOVERNING STANDARDS BY ASHRAE, SMACNA, NFPA, AND UL. INSTALL ALL EQUIPMENT, PIPING, DUCTWORK, AND CONTROLS IN ACCORDANCE WITH CODES, GOVERNING STANDARDS, AND MANUFACTURER'S RECOMMENDATIONS. FIRE PERFORMANCE CHARACTERISTICS OF INSTALLED MATERIALS SHALL BE RATED RATED IN ACCORDANCE WITH ASTM E84. MAXIMUM FLAME SPREAD RATING SHALL BE 25 AND MAXIMUM SMOKE DEVELOPED RATING SHALL BE 50.
AutoCAD SHX Text1.4 COORDINATION COORDINATION COORDINATE ALL WORK FOR PROPER LOCATION, POWER, AND UTILITY REQUIREMENTS. SCHEDULE INSTALLATIONS TO AVOID CONFLICT AMONG TRADES. ADDITIONS TO THE CONTRACT FOR TRADES. ADDITIONS TO THE CONTRACT FOR COORDINATION AMONG TRADES WILL NOT BE ALLOWED.
AutoCAD SHX Text1.5 PENETRATIONS, CUTTING AND PATCHING PENETRATIONS, CUTTING AND PATCHING SEAL ALL PIPING AND DUCT PENETRATIONS OF WALLS IN ACCORDANCE WITH ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. PIPING PENETRATIONS OF RATED FLOORS AND WALLS SHALL BE SEALED WITH FIRESTOPPING MATERIAL. FLASH ALL ROOF AND WALL PENETRATIONS IN ACCORDANCE WITH ARCHITECTURAL DRAWINGS. PROVIDE FIRE DAMPERS AT ALL RATED PENETRATIONS.
AutoCAD SHX Text1.6 HANGERS AND SUPPORTS HANGERS AND SUPPORTS PROVIDE HANGERS AND SUPPORTS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT IN ACCORDANCE WITH SMACNA, MSS, ASME, AND ASHRAE STANDARDS. SUPPORT ALL ITEMS FROM INTEGRAL BUILDING STRUCTURAL MEMBERS. DO NOT HANG ITEMS FROM ROOF DECKING.
AutoCAD SHX Text2.0 CONDENSATE PIPING CONDENSATE PIPING CONDENSATE PIPING SHALL BE SCH-40 PVC WITH SOLVENT WELDS, ROUTE TO THE CONDENSATE DRAIN. ALL INTERIOR PIPING SHALL BE INSULATED WITH 3/4" THICK ARMAFLEX INSULATION. EXTERIOR PIPING SHALL BE COATED WITH UV PROTECTIVE COATING.
AutoCAD SHX Text3.0 DUCTWORK AND ACCESSORIESDUCTWORK AND ACCESSORIES
AutoCAD SHX Text3.1 AIR DUCTS - SUPPLY AND RETURN AIR DUCTS - SUPPLY AND RETURN GALVANIZED SHEET METAL WITH LOCK-FORMINGQUALITY QUALITY ASTM A653, G90 COATING, MILL PHOSPHATIZED FINISH FOR DUCTS EXPOSED TO VIEW. CLASS DESIGNATION SHALL BE ADEQUATE FOR PRESSURE IN DUCT SYSTEM PER TOTAL PRESSURE AS SCHEDULED FROM EQUIPMENT SHOP DRAWINGS. INSULATE SUPPLY, RETURN AND OUTSIDE AIR INSULATE SUPPLY, RETURN AND OUTSIDE AIR DUCTS WITH MINERAL FIBERGLASS BLANKETS BONDED WITH A THERMOSETTING RESIN. ASTM C 553, TYPE II, WITHOUT FACING AND WITH ALL-SERVICE JACKET MANUFACTURED FROM KRAFT PAPER, REINFORCING SCRIM, ALUMINUM FOIL, VINYL FILM. DENSITY SHALL BE MIN. 1.5 LB/CUFT. THICKNESS TO MAINTAIN AN R VALUE OF 6.
AutoCAD SHX Text3.2 DEDUCTIVE ALTERNATE DEDUCTIVE ALTERNATE PROVIDE RIGID FIBERGLASS DUCTS FOR SUPPLY AND RETURN AIR ACCORDING TO THE FOLLOWING: RIGID FIBERGLASS DUCTS WITH INTERIOR ACRYLIC COATING, CONFORMING TO SMACNA FGSDCS GUIDELINES. R BONDED WITH THERMOSETTING RESIN. FIRE-RESISTANT, REINFORCED, FOIL-SCRIM KRAFT PAPER FACE. UL-181, UL CLOSURE, EI LABEL ON FACE. VAPOR BARRIER WITH 0.02 PERMEANCE. NOISE REDUCTION OF 0.65 MIN COEFFICIENT. 250°F RATED. CLOSURE SHALL BE WITH PRESSURE SENSITIVE TAPE, PLASTIC STRAPS AND GASKETING CONFORMING TO ENERGY CODE. (OWENS CORNING ENDURACOAT OR EQUAL). FITTINGS ARE TO CONFORM TO NAIMA STANDARDS.
AutoCAD SHX Text3.3 AIR DUCTS - EXHAUST AIR AIR DUCTS - EXHAUST AIR 26 GA GALVANIZED SHEET METAL DUCT SYSTEM WITH LOCK FORMING QUALITY. (SNAP-LOCK)
AutoCAD SHX Text3.5 FLEXIBLE CONNECTIONS FLEXIBLE CONNECTIONS PROVIDE FLEXIBLE CONNECTIONS AT ALL EQUIPMENT CONNECTIONS.
AutoCAD SHX Text4.0 TESTING, ADJUSTING AND BALANCING TESTING, ADJUSTING AND BALANCING BALANCE AIRFLOWS FOR EQUIPMENT, INLETS AND OUTLETS. TEST AND BALANCE ALL SYSTEMS INSTALLED TO MATCH INDICATED AIRFLOWS WITHIN ± 10% OF INDICATED VALUES. BALANCE AIR INLETS AND OUTLETS AS INDICATED. ADJUST SYSTEMS WHERE NECESSARY. PROVIDE TEST AND BALANCE REPORT INDICATING ALL INTERMEDIATE AND FINAL VALUES. NEBB OR AABC CERTIFICATION OF TEST AND BALANCE PERSONNEL AND REPORT IS REQUIRED ON THIS PROJECT.
AutoCAD SHX Text5.0 SUBMITTALS SUBMITTALS PROVIDE 6-SETS (EACH) OF MANUFACTURER'S DATA, O&M MANUALS, ELECTRICAL DATA, DIMENSIONAL DATA AND CLEARANCES, CONNECTION DATA, COLOR SAMPLES (IF REQUIRED), AND TEST DATA FOR THE FOLLOWING: ROOFTOP UNITS, EXHAUST FANS, AIR DISTRIBUTION, T&B REPORT. SHOP DRAWINGS MUST BE SUBMITTED AND APPROVED PRIOR TO ORDERING OF EQUIPMENT. ENGINEER WILL REQUIRE 7 WORKING DAYS TO REVIEW DRAWINGS.
AutoCAD SHX Text3.4 VOLUME CONTROL DAMPERS VOLUME CONTROL DAMPERS PROVIDE VOLUME CONTROL DAMPERS AT EACH BRANCH DUCT AND AS NECESSARY FOR PROPER SYSTEM BALANCING. PROVIDE FACTORY FABRICATED VOLUME CONTROL DAMPERS COMPLETE WITH REQUIRED LOCKING HARDWARE AND ACCESSORIES.
AutoCAD SHX Text(NOT ALL ARE USED)
AutoCAD SHX TextACAIR CONDITIONING AIR CONDITIONING AFFABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFMSAIR FLOW MONITORING STATION AIR FLOW MONITORING STATION AGABOVE GRADE ABOVE GRADE AHUAIR HANDLING UNIT AIR HANDLING UNIT ADACCESS DOOR ACCESS DOOR APPROXAPPROXIMATELY APPROXIMATELY BDDBACK DRAFT DAMPER BACK DRAFT DAMPER BODBOTTOM OF DUCT BOTTOM OF DUCT BTUBRITISH THERMAL UNIT BRITISH THERMAL UNIT CAPCAPACITY CAPACITY CDCONDENSATE DRAIN CONDENSATE DRAIN CFMCUBIC FEET PER MINUTE CUBIC FEET PER MINUTE CMUCONCRETE MASONRY UNIT CONCRETE MASONRY UNIT COCLEAN OUT CLEAN OUT CONNCONNECTION CONNECTION CUCONDENSING UNIT CONDENSING UNIT CVCONSTANT VOLUME CONSTANT VOLUME DBDRY BULB DRY BULB DGDOOR GRILLE DOOR GRILLE DIDIGITAL INPUT DIGITAL INPUT DNDOWN DOWN DODIGITAL OUTPUT DIGITAL OUTPUT EATENTERING AIR TEMPERATURE ENTERING AIR TEMPERATURE EERENERGY EFFICIENCY RATIO ENERGY EFFICIENCY RATIO EFEXHAUST FAN EXHAUST FAN EGEXHAUST GRILLE EXHAUST GRILLE ELECELECTRICAL ELECTRICAL EMSENERGY MGMT. SYSTEM ENERGY MGMT. SYSTEM EXEXHAUST EXHAUST ENTENTERING ENTERING ESPEXTERNAL STATIC PRESSURE EXTERNAL STATIC PRESSURE FFAHRENHEIT FAHRENHEIT FAFILTER ACCESS FILTER ACCESS FACPFIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL FCDFLOW CONTROL DAMPER FLOW CONTROL DAMPER FDFIRE DAMPER FIRE DAMPER FLAFULL LOAD AMPACITY FULL LOAD AMPACITY FPMFEET PER MINUTE FEET PER MINUTE FPMBFAN POWER MIXING BOX FAN POWER MIXING BOX FSFIRE STAT FIRE STAT HPHORSEPOWER HORSEPOWER HZHERTZ HERTZ IN-H2OINCHES OF WATER INCHES OF WATER KWKILOWATT KILOWATT LATLEAVING AIR TEMPERATURE LEAVING AIR TEMPERATURE LATLATENT LATENT LDLOUVERED DOOR LOUVERED DOOR LRALOCKED ROTOR AMPS LOCKED ROTOR AMPS LVGLEAVING LEAVING MAXMAXIMUM MAXIMUM MBH1000xBTU 1000xBTU MCAMINIMUM CIRCUIT AMPACITY MINIMUM CIRCUIT AMPACITY MISCMISCELLANEOUS MISCELLANEOUS N.I.C.NOT IN CONTRACT NOT IN CONTRACT NTSNOT TO SCALE NOT TO SCALE OAOUTSIDE AIR OUTSIDE AIR OALOUTSIDE AIR LOUVER OUTSIDE AIR LOUVER OCON CENTER ON CENTER PDPRESSURE DROP PRESSURE DROP PHPHASE PHASE PVCPOLYVINYLCHLORIDE POLYVINYLCHLORIDE RARETURN AIR RETURN AIR REFREFRIGERANT REFRIGERANT RGRETURN GRILLE RETURN GRILLE RLARUNNING LOAD AMPS RUNNING LOAD AMPS RTUROOFTOP A/C UNIT ROOFTOP A/C UNIT SASUPPLY AIR SUPPLY AIR SDSUPPLY DIFFUSER SUPPLY DIFFUSER SENSENSIBLE SENSIBLE SGSUPPLY GRILLE SUPPLY GRILLE UONUNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED VAVVARIABLE VOLUME VARIABLE VOLUME VFDVARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE WMSWIRE MESH SCREENWIRE MESH SCREEN
AutoCAD SHX TextAIR FLOW DIRECTION
AutoCAD SHX TextEXHAUST GRILLE
AutoCAD SHX TextREMOTE TEMPERATURE SENSOR
AutoCAD SHX TextBACKDRAFT DAMPER
AutoCAD SHX TextSMOKE DETECTOR
AutoCAD SHX TextMANUAL VOLUME DAMPER
AutoCAD SHX TextTHERMOSTAT
AutoCAD SHX TextFLEX DUCT
AutoCAD SHX TextDUCTWORK
AutoCAD SHX TextSUPPLY DIFFUSER
AutoCAD SHX TextRETURN GRILLE
AutoCAD SHX TextPOINT OF CONNECTION
AutoCAD SHX TextDROP IN ELEVATION
AutoCAD SHX TextRISE IN ELEVATION
AutoCAD SHX TextFIRE DAMPER
AutoCAD SHX TextSUPPLY DUCT DOWN
AutoCAD SHX TextRETURN DUCT DOWN
AutoCAD SHX TextEXHAUST DUCT DOWN
AutoCAD SHX TextAREA OF DEMOLITION
AutoCAD SHX TextBDD
AutoCAD SHX TextR
AutoCAD SHX TextD
AutoCAD SHX Text1" DOOR UNDERCUT
AutoCAD SHX TextM
AutoCAD SHX TextMOTORIZED DAMPER
AutoCAD SHX TextTS
AutoCAD SHX TextFD
AutoCAD SHX TextT
AutoCAD SHX TextSD
AutoCAD SHX TextSUMMER OUTSIDE-91/79 F -91/79 F 91/79 F WINTER OUTSIDE-35 F -35 F 35 F INSIDE TEMP/RH-75F/50%-75F/50%75F/50%
AutoCAD SHX Text1.PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, AND TOOLS TO PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, AND TOOLS TO PERFORM ALL WORK NECESSARY FOR THE COMPLETE EXECUTION OF THE HVAC WORK AS SHOWN ON THE DRAWINGS. PIPING SHALL ESSENTIALLY BE ROUTED AND LOCATED AS INDICATED ON THE DRAWINGS. HOWEVER, ACTUAL PLACEMENT SHALL BE VERIFIED BY CONFIRMING EXACT LOCATION OF STRUCTURES AND OTHER UTILITIES IN THE FIELD AND BY CAREFUL LAYOUT PRIOR TO EXECUTION OF THE WORK. HVAC PIPING LAYOUTS ARE GENERALLY DIAGRAMMATIC AND SHOULD NOT BE SCALED. 2.ALL DISCREPANCIES ON DRAWINGS SHALL BE BROUGHT TO ALL DISCREPANCIES ON DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN WRITING PRIOR TO SUBMISSION OF BIDS. SUBMISSION OF A BID CONSTITUTES ACCEPTANCE OF FIELD CONDITIONS. 3. SUPPORT DUCTS PER SMACNA FROM SUPPORT STRUCTURE. SUPPORT DUCTS PER SMACNA FROM SUPPORT STRUCTURE. 4.ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, 2014, SMACNA FGDCS & DCS, AND NFPA 90A. 5.ROUTE ALL DUCTWORK, PIPING, ACCESSORIES AS NECESSARY ROUTE ALL DUCTWORK, PIPING, ACCESSORIES AS NECESSARY TO AVOID BUILDING STRUCTURE, COMPONENTS AND LIGHTING. COORDINATE ANY TRANSITIONS MADE TO DUCTWORK WITH MAXIMUM FAN PRESSURE DROP REQUIREMENTS FROM MANUFACTURER'S RECOMMENDATIONS. 6.ALL DIMENSIONS ARE APPROXIMATE. DO NOT SCALE DRAWINGS ALL DIMENSIONS ARE APPROXIMATE. DO NOT SCALE DRAWINGS FOR CONSTRUCTION. 7.ALL FINISHED WORK SHALL BE FREE OF DEFECTS WITH ALL FINISHED WORK SHALL BE FREE OF DEFECTS WITH EXISTING SURFACES MAINTAINED IN THE SAME CONDITION AS ORIGINAL. 8.ALL DEBRIS SHALL BE PROPERLY DISPOSED OF OFF-SITE. ALL DEBRIS SHALL BE PROPERLY DISPOSED OF OFF-SITE. 9.CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING FIRE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING FIRE RATING AND WEATHERPROOFING INTEGRITY OF ALL PIPING AND PENETRATIONS. 10.CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY SUPPORTING DEVICES FOR ALL ACCESSORIES INCLUDED IN CONTRACT OR HEREIN SPECIFIED OR OTHERWISE. 11.MECHANICAL CONTRACTOR SHALL PROVIDE A SMOKE DETECTOR MECHANICAL CONTRACTOR SHALL PROVIDE A SMOKE DETECTOR IN THE RETURN DUCT PER FLORIDA BUILDING CODE (2014) AND IN THE SUPPLY DUCT PER NFPA-90A FOR ALL AIR HANDLING UNIT SYSTEMS > 2000 CFM OR AS APPLICABLE. ELECTRICAL CONTRACTOR TO WIRE SMOKE DETECTOR. PROVIDE A REMOTE INDICATING LIGHT AND AUDIBLE ALARM WITH A KEYED SWITCH IN THE GENERAL VICINITY OF THE SMOKE DETECTORS PER CODE REQUIREMENTS. COORDINATE WITH HVAC SCHEDULES, EXISTING DETECTORS AND EGRESS CORRIDORS.
AutoCAD SHX Text 0- 100 CFM- 6" - 100 CFM- 6" - 6" 105- 200 CFM- 8" - 200 CFM- 8" - 8" 205- 350 CFM- 10" - 350 CFM- 10" - 10" 355- 550 CFM- 12" - 550 CFM- 12" - 12" 555- 900 CFM- 14" - 900 CFM- 14" - 14" 905- 1100 CFM- 16" - 1100 CFM- 16" - 16"
AutoCAD SHX TextNOTE: BRANCH RUNOUT SIZE REFLECTS SUPPLY DIFFUSER NECK SIZE UNLESS OTHERWISE NOTED.
AutoCAD SHX TextIT IS THE RESPONSIBILITY OF ALL BIDDING CONTRACTORS TO ENSURE THAT EACH OF THEIR SUBCONTRACTORS RECEIVE THE NECESSARY DRAWINGS AND INFORMATION FOR BIDDING. MECHANICAL CONTRACTOR SHALL INDICATE TO ALL BIDDING VENDOR'S THAT EACH VENDOR SHALL REQUEST FROM THE BLUEPRINT COPY COMPANY FULL SIZE DRAWINGS PER MECHANICAL CONTRACTOR'S FOR WHICHEVER DRAWINGS HE/SHE DEEMS NECESSARY.
AutoCAD SHX Text24"x24" LOUVERED FACE RETURN GRILLE, WHITE FINISH, ALUMINUM CONSTRUCTION. BASIS OF DESIGN: PRICE MODEL 630.
AutoCAD SHX Text24"x24" OR 12"x12" 3-CONE ALUMINUM SUPPLY AIR DIFFUSER. 360 DEGREE FIXED PATTERN. LOUVERED FACE. SEE ARCH FOR CEILING TYPE. PROVIDE INSULATED BACK COVER. NECK TO MATCH FLEX SIZE. WHITE FINISH. CFM INDICATED ON PLANS. BASIS OF DESIGN: PRICE MODEL ASCD.
AutoCAD SHX TextSIDEWALL SUPPLY REGISTER, DOUBLE DEFLECTION, WHITE FINISH, ALUMINUM CONSTRUCTION. OPPOSED BLADE BALANCING DAMPER, ADJUSTABLE THROUGH FACE, BASIS OF DESIGN: PRICE MODEL 620.
AutoCAD SHX TextRG-1 XXXR
AutoCAD SHX Text 0- 250 CFM- 12x6 - 250 CFM- 12x6 - 12x6 255- 350 CFM- 12x8 - 350 CFM- 12x8 - 12x8 355- 475 CFM- 12x10 - 475 CFM- 12x10 - 12x10 480- 650 CFM- 12x12 - 650 CFM- 12x12 - 12x12 655- 850 CFM- 14x12 - 850 CFM- 14x12 - 14x12 855- 1000 CFM- 16x12 - 1000 CFM- 16x12 - 16x12 1005 - 1200 CFM - 18x12
AutoCAD SHX TextSD-1 XXX
AutoCAD SHX TextSR-1 XXX
AutoCAD SHX TextTAG AIRFLOW
AutoCAD SHX TextTAG AIRFLOW
AutoCAD SHX TextTAG AIRFLOW
AutoCAD SHX TextBRANCH DUCT SIZE:
AutoCAD SHX TextAPPROVED ALTERNATES: PRICE, TITUS, METALAIRE
AutoCAD SHX TextSYSTEM
AutoCAD SHX Text# OF OCCUPANTS
AutoCAD SHX TextRTU-7
AutoCAD SHX TextRTU-8
AutoCAD SHX TextCFM/SF
AutoCAD SHX TextAREA OA RATE (CFM)
AutoCAD SHX TextAREA (SF)
AutoCAD SHX TextCFM/ PERSON
AutoCAD SHX TextPEOPLE OA RATE CFM
AutoCAD SHX TextTOTAL OA RATE (CFM)
AutoCAD SHX TextOA RATE PROVIDED (CFM)
AutoCAD SHX TextAREA SERVED
AutoCAD SHX TextBACK OF HOUSE
AutoCAD SHX TextKITCHEN
AutoCAD SHX Text804
AutoCAD SHX Text0.12
AutoCAD SHX Text96
AutoCAD SHX Text21
AutoCAD SHX Text7.5
AutoCAD SHX Text158
AutoCAD SHX Text254
AutoCAD SHX Text240
AutoCAD SHX Text280
AutoCAD SHX Text0.12
AutoCAD SHX Text34
AutoCAD SHX Text5
AutoCAD SHX Text7.5
AutoCAD SHX Text38
AutoCAD SHX Text72
AutoCAD SHX Text320
AutoCAD SHX TextPER ASHRAE 62.1
AutoCAD SHX Text%%U-80 CFM
AutoCAD SHX Text6480
AutoCAD SHX TextTOTAL EXH. = 6400
AutoCAD SHX TextBUILDING PRESSURIZATION =
AutoCAD SHX TextC
AutoCAD SHX TextCOPYRIGHT STATEMENT
AutoCAD SHX TextTHESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF CONSTRUCTION ENGINEERING GROUP (CEG) AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT NOTED ON THESE DOCUMENTS. ANY REVISIONS, REPRODUCTIONS OR MODIFICATIONS OF THESE DOCUMENTS WITHOUT THE EXPRESS WRITTEN CONSENT OF CEG IS PROHIBITED BY LAW.
AutoCAD SHX TextNOMINAL TONS
AutoCAD SHX TextFILTER EFFICIENCY
AutoCAD SHX TextUNIT MCA/MOCP
AutoCAD SHX TextINDOOR FAN (HP)
AutoCAD SHX TextSUPPLY AIR (CFM)
AutoCAD SHX TextFILTER TYPE
AutoCAD SHX TextINDOOR FAN ESP (IN-H20)
AutoCAD SHX TextHEATER KW (@240V)/STEPS
AutoCAD SHX TextOUTSIDE AIR (CFM)
AutoCAD SHX TextUNIT SINGLE POINT V/PH
AutoCAD SHX TextMIN. EFFICIENCY - SEER
AutoCAD SHX TextMANUFACTURER/MODEL
AutoCAD SHX TextWEIGHT (LBS.)
AutoCAD SHX TextPROVIDE / INSTALL
AutoCAD SHX TextUNIT TAG
AutoCAD SHX TextDOWNFLOW
AutoCAD SHX TextTYPE
AutoCAD SHX Text13
AutoCAD SHX Text3.0
AutoCAD SHX Text0.80
AutoCAD SHX Text208/3
AutoCAD SHX TextMERV 8
AutoCAD SHX Text2" PLEATED
AutoCAD SHX TextTRANE TSC036
AutoCAD SHX Text1200
AutoCAD SHX Text240
AutoCAD SHX Text0.75
AutoCAD SHX Text721
AutoCAD SHX TextRTU-7
AutoCAD SHX Text37.5/40
AutoCAD SHX Text9/1
AutoCAD SHX Text1. PROVIDE 14" HIGH ROOF CURB. 2. PROVIDE PROGRAMMABLE THERMOSTAT WITH NIGHT SETBACK. 3. PROVIDE LOW AMBIENT COOLING TO 40°F.4. PROVIDE OUTSIDE AIR HOOD W/MOTORIZED DAMPERS AND COIL GUARDS. 5. PROVIDE (1) EXTRA SET OF FILTERS WHICH WILL BE REPLACED 2-WEEKS AFTER CERTIFICATE OF OCCUPANCY IS SUBMITTED. FILTER REPLACEMENT SHALL BE INCLUDED WITHIN THIS PROJECT'S BID. 6. PROVIDE THRU CURB ELECTRICAL. 7. PROVIDE BELT DRIVE SUPPLY FAN MOTOR. 8. ACCEPTABLE MFR'S: TRANE, JCI, CARRIER, DAIKIN.
AutoCAD SHX TextREMARKS:
AutoCAD SHX TextEXISTING
AutoCAD SHX TextDISCONNECTSDIV-26 DIV-26 THERMOSTATSDIV-23 DIV-23 HUMIDISTATNONE NONE CONTROL WIREDIV-23 DIV-23 EXTERNAL POWERDIV-26 DIV-26 SMOKE DETECTORSDIV-23* DIV-23* ROOF CURBSDIV-23DIV-23
AutoCAD SHX TextPROVIDED BY DIV. 23, WIRED BY DIV. 26.
AutoCAD SHX Text*
AutoCAD SHX TextRTU-8
AutoCAD SHX TextRTU-9
AutoCAD SHX TextRTU-10
AutoCAD SHX Text13
AutoCAD SHX TextDOWNFLOW
AutoCAD SHX Text4.0
AutoCAD SHX Text0.80
AutoCAD SHX Text208/3
AutoCAD SHX TextMERV 8
AutoCAD SHX Text2" PLEATED
AutoCAD SHX TextTRANE TSC048
AutoCAD SHX Text1600
AutoCAD SHX Text320
AutoCAD SHX Text37.5/40
AutoCAD SHX Text9/2
AutoCAD SHX Text1.0
AutoCAD SHX Text751
AutoCAD SHX TextEXISTING
AutoCAD SHX Text13
AutoCAD SHX TextDOWNFLOW
AutoCAD SHX Text4.0
AutoCAD SHX Text0.80
AutoCAD SHX Text208/3
AutoCAD SHX TextMERV 8
AutoCAD SHX Text2" PLEATED
AutoCAD SHX TextTRANE TSC048
AutoCAD SHX Text1600
AutoCAD SHX Text320
AutoCAD SHX Text37.5/40
AutoCAD SHX Text9/2
AutoCAD SHX Text1.0
AutoCAD SHX Text751
AutoCAD SHX TextEXISTING
AutoCAD SHX Text5.0
AutoCAD SHX Text0.80
AutoCAD SHX Text208/3
AutoCAD SHX TextMERV 8
AutoCAD SHX Text13
AutoCAD SHX TextTRANE TSC060
AutoCAD SHX Text2000
AutoCAD SHX Text400
AutoCAD SHX Text37.5/45
AutoCAD SHX Text9/2
AutoCAD SHX Text1.0
AutoCAD SHX Text801
AutoCAD SHX Text2" PLEATED
AutoCAD SHX TextDOWNFLOW
AutoCAD SHX TextEXISTING
AutoCAD SHX TextRTU-11
AutoCAD SHX Text5.0
AutoCAD SHX Text0.80
AutoCAD SHX Text208/3
AutoCAD SHX TextMERV 8
AutoCAD SHX Text13
AutoCAD SHX TextTRANE TSC060
AutoCAD SHX Text2000
AutoCAD SHX Text400
AutoCAD SHX Text37.5/45
AutoCAD SHX Text9/2
AutoCAD SHX Text1.0
AutoCAD SHX Text801
AutoCAD SHX Text2" PLEATED
AutoCAD SHX TextDOWNFLOW
AutoCAD SHX Text1,2,3,4,5,6,7,8,9
AutoCAD SHX TextRTU-9
AutoCAD SHX TextRTU-10
AutoCAD SHX TextREST RMS/BAR
AutoCAD SHX TextDINING
AutoCAD SHX Text798
AutoCAD SHX Text0.18
AutoCAD SHX Text144
AutoCAD SHX Text18
AutoCAD SHX Text7.5
AutoCAD SHX Text135
AutoCAD SHX Text279
AutoCAD SHX Text320
AutoCAD SHX Text749
AutoCAD SHX Text0.18
AutoCAD SHX Text135
AutoCAD SHX Text34
AutoCAD SHX Text7.5
AutoCAD SHX Text255
AutoCAD SHX Text390
AutoCAD SHX Text400
AutoCAD SHX TextRTU-11
AutoCAD SHX TextDINING
AutoCAD SHX Text400
AutoCAD SHX Text0.18
AutoCAD SHX Text72
AutoCAD SHX Text40
AutoCAD SHX Text7.5
AutoCAD SHX Text300
AutoCAD SHX Text372
AutoCAD SHX Text400
AutoCAD SHX TextMUA-1
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text-
AutoCAD SHX Text4800
AutoCAD SHX Text2 1/2" R
AutoCAD SHX Text4 1/2" R
AutoCAD SHX Text3 1/2"
AutoCAD SHX Text2 1/2"
AutoCAD SHX TextNUT & BOLT W/ WASHER, TYP. OF BOTH SIDES, TOP & BOTTOM
AutoCAD SHX TextDUCT
AutoCAD SHX Text2"x2"x1/4" ANGLE (AS REQUIRED BY SMACNA PER WIDTH & GAGE) IF PERMISSIBLE STRAP TO DUCT
AutoCAD SHX TextATTACH WITH 1/2" NUT & BOLT W/WASHER AT EVERY JOIST
AutoCAD SHX TextNTS
AutoCAD SHX TextNTS
AutoCAD SHX Text%%uTYPICAL SLOPED ROOF CAP
AutoCAD SHX Text%%uTYPICAL WALL CAP
AutoCAD SHX TextOFF
AutoCAD SHX TextLOW
AutoCAD SHX Text%%uSPEED CONTROL
AutoCAD SHX Text(SOLID STATE)
AutoCAD SHX TextNOTES: 1. PROVIDE BACKDRAFT DAMPER W/ SCREEN 2. PROVIDE INTERNAL ISOLATION AND SOUND INSULATION, AS NECESSARY 3. SUPPORT FAN FROM STRUCTURE
AutoCAD SHX Text%%uTYPICAL FLAT ROOF CAP
AutoCAD SHX TextVIBRATION HANGER SPRING TYPE W/ NEOPRENE ISOLATOR AS REQUIRED BY MANUFACTURER'S RECOMMENDATIONS
AutoCAD SHX TextMETAL DUCT, EITHER ROUND OR RECTANGULAR
AutoCAD SHX TextNTS
AutoCAD SHX TextLAY-IN TILE FIXTURE WHERE APPLICABLE
AutoCAD SHX TextPROVIDE 2" STAND-OFF THRU INSULATION FOR PROPER ACCESS AND OPERATION OF DAMPER
AutoCAD SHX TextINSULATE WITH 2" THICK INSULATION WITH VAPOR BARRIER LEAVING DAMPER OPERATOR ACCESSIBLE
AutoCAD SHX TextSQUARE-TO-ROUND 45° FITTING WITHVOLUME DAMPER
AutoCAD SHX TextFLEX DUCT CLAMP
AutoCAD SHX TextFLEXIBLE DUCT
AutoCAD SHX TextSUPPORT FROM STRUCTURE ABOVE
AutoCAD SHX TextWIRE SUPPORT SYSTEM
AutoCAD SHX TextINSULATE ABOVE DIFFUSER OR GRILLE
AutoCAD SHX TextMETAL GALVANIZED SADDLE
AutoCAD SHX TextCEILING
AutoCAD SHX TextNOTE: DAMPER ACTUATOR SHALL BE ACCESSIBLE AND PAINTED BRIGHT ORANGE BY DUCT INSTALLER
AutoCAD SHX TextNTS
AutoCAD SHX TextUNIT BASE RAIL
AutoCAD SHX TextDOWNFLOW CURB WITH FACTORY FITTED NAILER STRIP
AutoCAD SHX Text(2) #12-24-1" HWH TEX 5 SCREWS THROUGH CURB TO ATTACH STRAP TO CURB PRIOR TO SETTING RTU.
AutoCAD SHX TextLAP SEALANT
AutoCAD SHX TextRIGID INSULATION
AutoCAD SHX Text16 GA. G90 GALVANIZED STEEL 4" WIDE STRAP. INSTALL TWO PER SIDE
AutoCAD SHX TextBEND STRAP UP AFTER RTU IS SET AND ATTACH TO RAIL
AutoCAD SHX Text(2) #12-24 1-1/4" HWH TEX 5 SCREWS
AutoCAD SHX Text1/2" BOLTS, NUTSAND WASHERS @ 24" O.C. MIN. 3 PER UNIT SIDE. (GRADE 5 ZINC)
AutoCAD SHX TextUNIT BASE BOTTOM
AutoCAD SHX TextNOTE: ROOF CURB SET ON ROOF DECK, CUT DECK ONLY AROUND DUCT OPENINGS.
AutoCAD SHX TextNTS
AutoCAD SHX Text14 GA. PAINT GRIP GALV. CLOSER ANGLE
AutoCAD SHX TextAUXILIARY STEEL ANGLE FRAMING - SEE STRUCT. DWGS
AutoCAD SHX TextPIPE DRAIN FULL SIZE INTO DOWNSPOUT (WITHIN 1")
AutoCAD SHX TextWIRING SHALL BE THROUGH ROOF CURB
AutoCAD SHX TextRA
AutoCAD SHX TextSA
AutoCAD SHX Text%%URTU
AutoCAD SHX TextCONTINUOUS WOOD CURB CUT TO ROOF SLOPE TO "LEVEL" TOP
AutoCAD SHX TextH = 6 MIN. HEIGHT
AutoCAD SHX Text0R 150% OF UNIT S.P.
AutoCAD SHX Text1/2 H MIN
AutoCAD SHX Text ROOF
AutoCAD SHX TextROOF CURB
AutoCAD SHX TextNTS
AutoCAD SHX TextCURB
AutoCAD SHX TextPROVIDE 2" RIGID DUCTBOARD SEALED TO ROOF DECK AND CURB FOR SOUND TRAP.
AutoCAD SHX TextWHITE CEILING GRILLE
AutoCAD SHX Text1/4" ALL-THREAD RODS
AutoCAD SHX TextRTU
AutoCAD SHX TextCAP
AutoCAD SHX TextPROVIDE CONDENSATE DRAIN FROM EACH RTU DRAIN PAN FULL SIZE OF DRAIN PAN OUTLET ADJACENT TO UNIT SERVED.
AutoCAD SHX Text(PROVIDE TURNING VANES AT ALL 90° ELBOWS)
AutoCAD SHX TextVANED ELBOW
AutoCAD SHX TextTURNING VANE
AutoCAD SHX TextLOCKING LUG
AutoCAD SHX TextFRAME
AutoCAD SHX TextJOIST OR SLAB
AutoCAD SHX Text1/2" THREADED ROD
AutoCAD SHX Text(EQUAL TO MIRO INDUSTRIES)
AutoCAD SHX TextINSTALLATION: TO INSTALL THE PILLOW BLOCK PIPESTANDS, (1) CENTER THE PIPESTAND BENEATH THE PIPE SO THAT THE CRADLE ALLOWS THE PIPE TO BE SQUARELY OVER AND THROUGH THE CRADLE OF THE PIPESTAND. (2) SET THE PIPE IN THE PIPESTAND WITHOUT DROPPING OR CAUSING UNDUE IMPACT. AN ADDITIONAL SHEET OF ROOFING MATERIAL, A MIRO SUPPORT PAD, OR A MIRO DECK PLATE SHOULD BE INSTALLED BENEATH THE PIPESTAND. FOR BUILTUP ROOFS, ALL LOOSE AGGREGATE FROM AN AREA 10" SQUARE SHOULD BE REMOVED FROM THE AREA DIRECTLY BENEATH THE PIPESTAND AND THEN FOLLOW THE INSTALLATION DIRECTIONS SET FORTH ABOVE. CARE SHOULD BE TAKEN TO INSTALL EACH PIPESTAND SO IT SUPPORTS A PROPORTIONAL AND EQUAL AMOUNT OF WEIGHT WITH ALL OTHER PIPESTANDS. IN ADDITION, THE PIPE MAY BE SECURED TO THE PIPESTAND BY USING A MIRO PIPE STRAP AND #8 STAINLESS STEEL SCREWS IN THE GUIDE HOLES AT THE TOP OF EACH PIPESTAND. NOTE: ALLOW SUFFICIENT ROOM BETWEEN THE PIPE AND THE STRAP TO PROVIDE FOR FREE MOVEMENT OF THE PIPE WITHOUT BINDING.
AutoCAD SHX TextNTS
AutoCAD SHX TextROOF
AutoCAD SHX TextREMOVABLE HOUSING
AutoCAD SHX TextBASE
AutoCAD SHX TextGALVANIZED DUCT (SEE PLANS FOR CONTINUATION)
AutoCAD SHX TextRUN POWER LEADS INSIDE CORNER OF CURB
AutoCAD SHX Text14" HIGH INSULATED PRE-FAB CURB
AutoCAD SHX TextSECURE FAN TO CURB WITH S.S. SHEET METAL SCREWS 6" O.C. ALL AROUND
AutoCAD SHX TextNTS
AutoCAD SHX TextPROVIDE (2) 24GA. GALVANIZED STRAPS
AutoCAD SHX TextNTS
AutoCAD SHX TextROOF CONSTRUCTION
AutoCAD SHX TextWEATHERPROOF SEALING STRIP
AutoCAD SHX TextPREFABRICATED CURB BY UNIT MANUFACTURER
AutoCAD SHX TextWOOD CURB INSERT
AutoCAD SHX TextTAPERED WOOD OR GALV. SHT. METAL, SHIM TO MATCH PITCH OF ROOF
AutoCAD SHX TextEQUIPMENT
AutoCAD SHX Text24 GA. SHEET METAL COUNTER FLASHING
AutoCAD SHX TextCANT STRIP SEE ARCH. DWG.
AutoCAD SHX TextROOFING
AutoCAD SHX TextNOTE:THE DISTANCE FROM ROOF SURFACE TO BOTTOM OF THE THE DISTANCE FROM ROOF SURFACE TO BOTTOM OF THE EQUIPMENT MOUNTED ON CURB MUST BE A MINIMUM OF 14"
AutoCAD SHX Text CFM NECK SIZE CFM NECK SIZE NECK SIZE NECK SIZE 0-175 8x4 180-300 10x6 305-450 12x8 455-650 16x8
Renee EngelsKEATOR CONSTRUCTION - BID SET
2016-11-18T13:05:34-0500David E AlleyI attest to the accuracy and integrity of this document