AquaRite® - INYOpools.comimages.inyopools.com/cloud/documents/aquarite-tsg-aqr159d.pdffor the relay...
Transcript of AquaRite® - INYOpools.comimages.inyopools.com/cloud/documents/aquarite-tsg-aqr159d.pdffor the relay...
AquaRite®
Troubleshooting Guide Residential
TSG-AQR159d Copyright 2017 Hayward Industries Inc.
Safety Precautions
! Warning
2
High Voltage Electrocution Hazard
Hazardous voltage can shock, burn, cause serious injury and or death. To reduce the risk of electrocution and or
electric shock hazards:
• Only qualified technicians should remove the panel • Replace damaged wiring immediately • Insure panel is properly grounded and bonded
Table of Contents
How AquaRite® Works, Main PCB Layout, Chemistry Requirements Pg. 4-6 How To: Pg. 7-15
Change Metric to Standard & Change Default Reading 8-9 Set TurboCell® Type & Reset Average Salt 10-11 Adjust Chlorine Output & Clean TurboCell 12-15
Troubleshooting: Pg. 16-38 1. Check Salt & Inspect Cell: flashing or ON 17-20 2. High Salt: LED ON 21-25 3. No Flow: LED flashing or ON 26-30 4. Display ONLY, Lights ONLY, or Neither 31-36 5. LCD: Displaying “HOT” or “COLD” 37-38
Additional Information: Pg. 39-44 Cell Compatibility Chart & Salt Addition Table 40-41 Chlorine Output & Salt Levels 42-43 Reading Serial Numbers 44
3
AquaRite: How It Works
• The AquaRite Salt Chlorine Generator is designed to convert 99% pure salt into chlorine gas (HOCl).
• The conversion occurs in the Electrolytic Cell, also known as the TurboCell® (used throughout this guide).
• Power is sent from the AquaRite Control Center to the TurboCell, when chlorine production is scheduled (based on time percentage).
• When power is applied to the TurboCell, conductive plates produce a field; which in-turn establishes an electrochemical reaction between Chloride ions & the water to create Hypochlorous Acid.
4
AquaRite: Main PCB Layout
5
A PCB Input Power (120/240VAC)
B Transformer Input (120VAC & 120VAC)
C External Control Jumper
D Display Output (5-10VDC)
E Rectifier Output (18-33VDC)
F Comm Block – External Control (5-10VDC)
G Transformer Output (12 VAC)
H Chlorinator Fuse (20A – ATO style)
I Rectifier Input (12 VAC)
J Cell Input/Output
K Flow Switch Input/Output
F
B
C
E
A
D
G
I
H
K J
6
AquaRite: Chemistry Requirements
AquaRite®
How To:
How To: Switch from Metric to US Standard
8
If the first reading (average salt) is displayed in decimal form instead of a number represented in thousands, then the unit has been set to ‘Metric Mode’.
Step 3 Step 4
Step 1
3.20
To change the unit from Metric Mode to US Standard, start by pressing the ‘Diagnostics’ button one time.
Immediately the temperature reading should change to reflect a Fahrenheit value. If it does not repeat step 2.
After 30 seconds the unit should settle back to the default reading. The reading should now reflect a number in thousands.
Once showing the temperature in Celsius, move the switch up to ‘Super Chlorinate’ then back to ‘Auto’.
30
86 3200
Step 2
NOTE: The process is the same to go from US Standard to Metric.
How To: Change the Default Display
9
If the first reading represents a number followed by the letter ‘P’, then the default reading has been changed to express the ‘Desired Output %’.
Step 2
To change the default reading back to the average salt, start by pressing the ‘Diagnostics’ button two times.
Continue moving the switch up to ‘Super Chlorinate’ and back to ‘Auto’ until the display reads ‘AL-0’.
It takes about 30 seconds for the unit to settle back on the default reading. It should now reflect the average salt level.
When the unit reads ‘AL-4’ move the switch up to ‘Super Chlorinate’ and back to ‘Auto’.
77P AL-4
AL-0 3200
Step 1
Step 3 Step 4
How To: Set TurboCell Type
10
Before operation, the AquaRite must be configured to the correct TurboCell installed. “t-15” is the factory default. If the incorrect cell is chosen the salt level will be
inaccurate and the system will likely suspend chlorination as a result.
Start with the main toggle switch in the ‘Auto’ position.
To change cell type, cycle slide switch up to ‘Super Chlorinate’. Return switch to ‘AUTO’. Repeat until display shows correct cell.
Push the diagnostics button until ‘t - 15, t - 9, t -5 , t - 3’ appears.
3200 t -15
t -3 t -9
Step 2 Step 1
Step 3 Step 4
How to: Reset Average Salt Level
11
The Average Salt level needs to be reset after initial start up, after a board replacement, following major pool chemistry adjustments, and when a cell is replaced.
Step 3 Step 4
To reset, move the switch to ‘Off’ and then back to ‘Auto’. Wait for the relay to click (5 to 10 seconds).
When the instant salt level is stable (and the negative sign still present), slide switch to ‘Super Chlorinate’ and back to ‘Auto’.
It takes about 30 seconds for the unit to settle back on the default reading. It should now reflect the new average salt level.
Press Diagnostics button 5 times to display the Instant Salt level. Wait for the number to stabilize.
1600 -3200
-3200 3200
Step 2 Step 1
NOTE: Repeat this process once more to ensure both polarities are reading within 500ppm of each other.
NOTE: If the chlorine level does not increase within 24 hours after increasing output, test water using an independent test kit to determine the current salt, stabilizer, phosphate, and nitrate levels. More
information related to chlorine production on Pages 41-42). NOTE: Output is scaled back to 20% or lower (depending on where the dial is set) at 60°F and chlorine
production stops altogether at 50°F.
How To: Adjust Chlorine Output
12
The ‘Desired Output %’ dial, sets the level of cell operation in % of operating time, in 3 hour increments. Example: 50% (factory default) implies the cell is producing chlorine half the total pump/filter operating time; so the cell should produce
chlorine for the first 90 minutes of 3 hours before repeating.
Rotate dial to the left to lower chlorine
production.
Rotate dial to the right to raise chlorine
production.
How To: Clean the TurboCell
13
Cell cleaning frequency is dependent on several factors; pH & calcium levels have the greatest effect on how often cells requires cleaning. In pH environments between (7.2 -
7.8) cells typically require cleaning 3-4 times a year (with moderate calcium levels).
Holding the cell up to a light source, inspect for calcium deposits. Even if a TurboCell appears clean, it may still require cleaning if salt accuracy is off AND/OR chlorine
production has diminished.
Wear Protective Equipment
If the cell requires cleaning, please wear protective equipment. It is highly recommended to use a
Hayward Cell Cleaning Stand as shown on the right (GLX-CELLSTAND)
Turn Pump Off & Remove Cell Step 1
Clean Cell Calcified Cell
Step 2
NOTE: ALWAYS WEAR PROPER EYE PROTECTION AND PROTECTIVE GLOVES. MIX SOLUTION AND CLEAN CELL ONLY IN A WELL VENTILATED AREA.
MURIATIC AND OTHER ACIDS CAN CAUSE SEVERE INJURY, BURNS AND RESPIRATORY PROBLEMS IF NOT HANDLED PROPERLY. REFER TO THE MANUFACTURER’S DIRECTIONS FOR SAFE HANDLING.
14
The TurboCell draws amperage when power is applied, during chlorination. The amperage draw will be impaired when calcium and other debris exist within the cell’s
electrolytic grid; this in turn effects the salt reading and chlorination efficiency.
Mix a solution comprised of 4 parts water to 1 part Muriatic Acid. Always Add Acid to Water. Once mixed turn the turbo up vertically either in a bucket or using
the recommended cell cleaning stand.
Carefully pour the solution into the cell until it reaches the top. The solution should remain in the cell for 15
minute intervals until the reaction is complete. Carefully, pour solution back into approved container.
Mix: 4 Parts H2O / 1 Part Muriatic Acid Step 3 Step 4
NOTE: ALWAYS ADD ACID TO WATER! NEVER ADD WATER TO ACID. The cell cleaning solution may be reused a few times.
ALWAYS: STORE MIXED SOLUTIONS IN A SAFE AREA, OUT OF HARMS WAY. When the solution is depleted, follow the manufacturer’s instructions for proper disposal.
1 Part: Muriatic Acid
4 Parts: Water
Carefully Pour Solution into Cell
Cleaning Tip: For best results, stand the cell vertically with cord-side down
How To: Clean the TurboCell (Cont.)
15
The Inspect Cell LED, when flashing alone, indicates that the system is recommending the TurboCell should be inspected and cleaned (if necessary). The LED will flash alone
every 500 operational hours as a reminder to inspect and/or clean the TurboCell.
After the solution has been safely removed, thoroughly rinse the TurboCell before returning it to its place in the plumbing. Once returned turn the pump back ON and
proceed to the step 6.
IF the “Inspect Cell” LED was flashing alone, press and hold the diagnostics button for 5 seconds OR until the Inspect Cell LED goes out. This will reset the inspect
cell timer for another 500 operational hours.
Thoroughly Rinse Cell & Return Step 5 Step 6
NOTE: If the cell was reading a low salt level prior to cleaning, the average salt may need to be reset. To reset the average salt level, follow the steps outlined on pg.11 or wait 24 hours for the
system to acclimate to the recent changes.
Reset: Inspect Cell (if applicable)
How To: Clean the TurboCell (Cont.)
AquaRite®
Troubleshooting
17
Check Salt & Inspect Cell
Cell is Clean?
NO
YES YES
NO
Clean the Cell
Cell model matches display
reading?
NO
Program correct cell type
Add salt
Problem solved
YES
Reset Ave. Salt
Are both readings within 500ppm of
each other?
NO
Jump to Section B
Section B
YES Did LED Clear?
Replace the TurboCell
YES
NO
Contact Support (908) 355.7995
1. Check Salt & Inspect Cell: flashing or ON
Salt level is >3200?
Clean Cell Calcified Cell
18
When these lights flash, the cell reports salt levels between 2400-2700ppm; this does not affect chlorine production. When these LEDs are ON solid, the cell reports
2300ppm or less and chlorine production is suspended.
Test the salt concentration of the water using an independent test, with a calibrated salt meter. IF the
salt level is below 3200, raise the salt level (referring to salt addition table pg. 41). IF fine, go to 1B.
The TurboCell must be clean in order to report accurate salt readings. IF the cell looks like the image on the left, clean the cell (pg.13-15). IF cell is clean, proceed to step
1C.
Test the Salt Level Step 1A Step 1B
The system should be reading salt within 500ppm of an independent test. The cleanliness of the TurboCell plays a major role in the AquaRite’s ability to report salt levels accurately.
Inspect the TurboCell
Desired Salt Concentration:
3200PPM
1. Check Salt & Inspect Cell: flashing or ON
-3200
19
The AquaRite control center may be programmable to interact with different cell models (“t-15” is the factory default). Verify the TurboCell model (located on the label
the wraps around the body) then compare it to what is programmed in the system.
Verify the cell model programmed into the control center, matches the model listed on the cell. IF it does
not match, change programmed cell (refer to pg. 10). IF correct, go to step 1D.
Reset the average salt level, twice, following the steps on pg. 10. Are the two instant salt level readings within 500ppm of each other? IF not go to step 1E. IF they are
go to step 1F.
Correct Cell Programmed? Step 1C Step 1D
There are two polarities within a TurboCell which is why it is recommended to reset twice. Although there may be some variance between these two polarities, clean cell should NEVER show more than
a 500ppm variance between polarities.
Reset the Average Salt Level
1. Check Salt & Inspect Cell: flashing or ON (cont.)
-3100
Side A
Side B
1. Check Salt & Inspect Cell: flashing or ON (cont.)
20
If the cell requires replacement, check the model number and verify whether or not the cell is under warranty. To verify warranty, please refer to pg. 44.
The cell needs to be replaced in order for the AquaRite control center to read the salt level accurately. Replace
the cell with the same model as it had prior and then reset the average salt level (instructions on pg. 11).
IF the “Check Salt” & “Inspect Cell” LEDs cleared, then the problem is solved. IF not please contact technical
support directly by dialing: 908.355.7995 or email support via Hayward.com’s support page.
Replace the TurboCell Step 1E Step 1F
Did the LEDs clear?
Part Numbers: *T-Cell-15 OR GLX-CELL-15-W *T-CELL-9 OR GLX-CELL-9-W *T-CELL-3 OR GLX-CELL-3-W
*NOTE: When replacing the TurboCell, use the GLX-CELL-xx-W when the cell is under warranty, otherwise use the T-CELL-xx part number.
21
Cell is Clean?
NO
YES
NO
Clean the Cell
Cell model matches display
reading?
NO
Program correct cell type
Dilute salt concentration
YES
Reset Ave. Salt
Are both readings within 500ppm of
each other?
NO
YES
Section B
YES
Replace the TurboCell
2. High Salt: LED ON
Section B
Salt level is under 3400?
Problem solved
Did LED Clear?
YES
NO
Contact Support (908) 355.7995
High Salt LED ON
2. High Salt: LED ON
22
The High Salt LED will appear ON solid when the maximum allowable cell amperage has been reached. The AquaRite control center will shutdown all chlorine production
until the problem is solved and the LED light clears.
Test salt concentration of the water using an independent test, with a calibrated salt meter. IF salt is above 3400, go directly to 2G. IF the salt level is correct,
proceed to step 2B.
Verify the cell model programmed into the control center, matches the model listed on the cell. IF it does
not match, change programmed cell (refer to pg. 10). IF correct, go to step 2C.
Step 2A Step 2B
Correct Cell Programmed?
Desired Salt Concentration:
3200PPM
NOTE: High water temperatures (typically found in smaller bodies of water, such as spas) can cause the High Salt LED to trigger when the salt concentration favors the high end of the range. If the water temperature is high, then consider diluting the salt level down between 2700-3200ppm.
Test the Salt Level
Clean Cell Dirty Cell
2. High Salt: LED ON (cont.)
23
Although debris such as calcium typically cause low salt reading and not high ones, it is still recommended to clean out the cell. Conductive debris may cause an unwanted
variance.
The TurboCell must be clean to report accurate salt readings. IF the cell looks like the image on the left,
then clean the cell (pg.13-15). IF cell is clean, proceed to step 2D.
Step 2C Step 2D
Inspect TurboCell
-3200
Reset the average salt level, twice, following the steps on pg. 11. Are the two instant salt level readings within 500ppm of each other? IF not go to step 2E. IF they are
go to step 2F.
Reset the Average Salt Level
-3100
Side A
Side B
2. High Salt: LED ON (cont.)
24
If the cell requires replacement, check the model number and verify whether or not the cell is under warranty. To verify warranty, please refer to pg. 44.
The cell needs to be replaced in order for the AquaRite control center to read the salt level accurately. Replace
the cell with the same model as it had prior and then reset the average salt level (instructions on pg. 11).
IF the “High Salt” LED cleared, then the problem is solved. IF not please contact technical support directly by dialing: 908.355.7995 or email via Hayward.com’s
support page.
Replace the TurboCell Step 2E Step 2F
Did the High Salt LED clear?
Part Numbers: *T-Cell-15 OR GLX-CELL-15-W *T-CELL-9 OR GLX-CELL-9-W *T-CELL-3 OR GLX-CELL-3-W
*NOTE: When replacing the TurboCell, use the GLX-CELL-xx-W when the cell is under warranty, otherwise use the T-CELL-xx part number.
To calculate how much water will need to be removed from a pool, with too much salt, follow the formula provided below (Proportional Method):
2. High Salt: LED ON (cont.)
25
Part I
(Ave. Pool Depth” X 3200) Actual Salt level in Pool
Part 1: Take the average depth of the pool in inches and multiply that by 3200. Then divide that number by the actual salt level in the pool
(based on the independent test).
Part 2: Subtract the Ave. Pool Depth by the answer from part 1. This will give you the total number of inches to drain and replenish with
fresh water to achieve a salt level of 3200.
Part II
Ave. Pool Depth - Answer from Part 1 = Amount of Water to Drain
Example: a pool has an ave. depth of 54” and the salt level is 4500ppm
54 X 3200 = 172800 4500 38.4
Example: Part I
54 – 38.4 = 15.6”
Example: Part II
Step 2G
Note: It is recommended to reduce the water level no more than six inches at a time before replenishing with fresh water. Failure to due so may result in damage to the pool structure or
surface.
No Flow LED ON/Flashing
Flow switch orientation is
correct?
NO
YES
NO Turn pump
OFF & rotate switch
Switch is preceded by 12” straight
pipe?
NO
Consider moving switch
Turn pump ON & correct
valves.
YES
With Pump ON, did LED clear?
YES
3. No Flow: LED flashing or ON
Pump ON & valves are correct?
Problem solved
YES
NO Replace flow switch (GLX-
FLO-RP)
NO
Inspect wire, is it free of damage?
Remove connector, is it
free of damage?
NO
NO
YES
Go to Section B
YES
NO
Clean Pump basket & Filter
Pump & Filter free of Debris?
No Flow LED still ON?
Section B YES
Problem solved
NO
Install new switch &
manually close
YES
No Flow LED still ON?
Install this new switch
NO
YES
Replace Main PCB (GLX-PCB-
RITE)
Replace flow switch (GLX-
FLO-RP)
26
3. No Flow: LED flashing or ON
27
The “No Flow” LED indicates that the flow switch is not reporting consistent flow. When the pump initially turns on, this LED should flash for 10-60 seconds while the
system verifies consistent flow.
Verify the pump is running & valves are positioned so the flow switch is receiving water. IF the pump is not
ON or the valve are not correctly set, resolve that first, then recheck. IF correct go to step 3B.
It is recommended for the flow switch to have 12” of straight pipe preceding it (the TurboCell counts as
straight pipe). IF not, consider moving the flow switch. IF correct go to step 3C.
Pump Running & Valves are Set? Step 3A Step 3B
Verify 12” of Straight Pipe
NOTE: The flow switch requires a minimum flow rate of 11GPM in order to properly engage. If using a variable speed pump and the No Flow LED appears, try increasing the pump run speed to ensure
the flow rate is not causing the problem.
3. No Flow: LED flashing or ON (cont.)
28
The flow switch only works in one orientation. An arrow (molded into the top of the flow switch) indicates the direction water should be flowing through the switch.
Verify the arrows (located on switch top) are pointing in the same direction water is flowing. IF incorrect,
rotate the switch until it matches the direction of water flow (DO NOT OVERTIGHTEN). IF correct go to 3D.
Unplug the flow switch connector & inspect. Plug the connector back in, waiting 60 seconds. IF connector is
damaged, replace flow switch (GLX-FLO-RP). IF connector is not damaged, proceed to step 3E.
Verify Flow Switch Orientation Step 3C Step 3D
Unplug Connector & Inspect
The flow switch communicates through a connection similar to an RJ-11. Inspect the pins for damage or corrosion. If damaged replace the flow switch (GLX-FLO-RP) DO NOT attempt to repair.
3. No Flow: LED flashing or ON (cont.)
29
The flow switch wire carries the signal between the AquaRite and the flow switch. If damaged, the switch reports as an open circuit, which will suspend chlorination.
IF the flow switch wire is damaged, the signal will be interrupted so replace the flow switch (GLX-FLO-RP). IF
the wire is not damaged, proceed to step 3F.
Check Filter pressure & pump basket for debris. Remove debris, backwash / clean filter. Turn pump ON
& wait 60 seconds. IF LED is still ON go to 3G.
Inspect Flow Switch Wire Step 3E Step 3F
Inspect Filter & all Baskets
The Flow Switch is a safety switch. DO NOT attempt to repair the wire or the switch in any way. If compromised replace the switch (GLX-FLO-RP).
3. No Flow: LED flashing or ON (cont.)
30
TIP: Carry a working flow switch, because it is a great tool to have available. It will help when trying to determine whether an existing switch is failing or the main board
is not sending or receiving the signal.
Plug a confirmed (working) Flow Switch into the control center and hold it closed, manually, for 60 seconds.
Monitor the “No Flow” LED. IF LED goes out, install this new switch. IF LED remains on go to step 3G.
Replace the main circuit board (GLX-PCB-RITE). Then, turn pump ON & monitor the “No Flow” LED. IF the LED goes out, the problem is solved. IF the LED remains on
contact technical support (908.355.7995).
Test with New Switch Step 3G Step 3H
Replace Main PCB
Lights ONLY, Display ONLY,
or Neither
18-33VDC between red &
black wires?
NO
YES
NO
Reseat display, 5-10VDC between
pins 2-4?
Jumpers match source power?
NO
Power OFF & correct jumpers
YES
Inspect rectifier wiring
4. Display ONLY, Lights ONLY, or Neither
120/240VAC present?
Input power
YES
NO
120VAC between blue &white, violet & grey?
24VAC between two yellow wires?
Wired correctly?
NO
YES
Go to Section B
YES
NO
Test rectifier Input
Fuse blown?
12VAC between orange & ground?
Section B
NO
Replace Fuse
Correct Wiring
Resolve source power issue
YES
YES
Replace Display (GLX-PCB-DSP)
NO
Replace Main PCB (GLX-PCB-RITE)
Replace Main PCB (GLX-PCB-RITE)
YES Replace Transformer (GLX-XFMR)
YES
Replace Rectifiers
(GLX-DRK)
Replace Main PCB (GLX-PCB-RITE)
NO
31
4. Display ONLY, Lights ONLY, or Neither
32
If the power center, displays LEDs ONLY, a Display reading ONLY, or Neither, then the system is exhibiting a power related symptom. First verify the incoming power. It should be either 120 or 240VAC +/- 15%. Then match the jumper configuration.
Test incoming power for 120/240VAC (+/- 15%). IF no/low voltage, then the problem resides in the power source and NOT the AquaRite control center. IF power
is correct, go to step 4B.
Verify jumper configuration matches incoming power. FOR 240, jumpers should be stacked between terminals 2&3 (shown on left). FOR 120VAC, jumpers span 1&2. IF incorrect , power off and change. IF correct go to 4C.
Test Incoming Power Step 4A Step 4B
Match Jumpers & Incoming Power
240VAC 120VAC 238 HV
New boards come factory preset with jumpers in the 240VAC position. ALWAYS double check power before changing jumpers. The board may be damaged if the supplied power and jumper
configuration do not match.
4. Display ONLY, Lights ONLY, or Neither (cont.)
33
The display requires a minimum of 5VDC to function correctly. The rectifier output should provide 18-33VDC.
Test for 18-33VDC between the red and black wires (located in the top right hand corner of the main PCB board). IF power is correct go to step 4D. IF no/low
voltage, proceed to step 4E.
Carefully remove display from main PCB board & reseat. Test power between pins 2 & 4 (left to right),
for 5-10VDC. IF no/low voltage, replace main PCB (GLX-PCB-RITE). IF correct, replace display (GLX-PCB-DSP).
Test Rectifier Output Step 4C Step 4D
Reseat & Test Display Power
The power off the rectifiers not only provides the cell power during chlorination cycles, it also serves to power other board related functions (such as the display function).
4. Display ONLY, Lights ONLY, or Neither (cont.)
34
The rectifiers take AC voltage from the transformer and convert it to DC voltage for both main board and chlorination functions.
Make sure the rectifiers are wired as shown above. IF the rectifiers are incorrectly wired, correct the wiring
and retest. IF the rectifiers are wired, as shown above, proceed to step 4F.
Verify 24VAC between the two yellow wires (this represents the secondary side of the transformer). IF
no/low voltage go to step 4G. IF voltage is correct, jump to step 4H.
Inspect Rectifier Wiring Step 4E Step 4F
Test Transformer Output
*Cutoff Corner: (Bottom Right)
*
*
4. Display ONLY, Lights ONLY, or Neither (cont.)
35
The transformer input is split into four wires. The blue and the white carry 120VAC from the main PCB to the transformer, as do the grey and violet.
Disconnect the transformer input wires (blue, white, violet & grey). Test the board, first between the blue & white posts for 120VAC, then violet & grey for 120VAC.
IF low/no, replace main board (GLX-PCB-RITE). IF voltage is correct, replace the transformer (GLX-XFMR).
When voltage shows up on the transformer output, the transformer, and everything before it, is in good health.
Test the 20A fuse (located on the right side of the board) for continuity. IF the fuse is bad, replace it (GLX-
F20A-10PK). IF okay, go to step 4I.
Test Transformer Input Step 4G Step 4H
Test the 20A Fuse
NOTE: It is also important to visually inspect the fuse for damage. In rare cases, continuity may be measured in spite of a compromised fuse.
4. Display ONLY, Lights ONLY, or Neither (cont.)
36
The orange wire carries 12VAC of the rectifier voltage, from the main PCB to the top rectifier. Verify all connections before proceeding.
Disconnect the orange wire and test for 12VAC on the board against ground (where the orange wire plugs in). IF no/low voltage, replace
the main board (GLX-PCB-RITE). IF voltage is okay, replace the rectifiers (GLX-DRK).
Test Rectifier Input Step 4I
12 VAC
LCD Displays HOT or COLD
Check water temperature
YES
5. LCD: Displaying “HOT” or “COLD”
Did error clear?
Is water temp above 139 or
below 51?
Clean the Cell
Raise or lower water temp to clear message
NO
YES Problem solved
NO
Is the cell downstream of a
running heater/chiller?
NO Replace the
TurboCell
YES Move Cell or bypass
heater/chiller
37
5. LCD: Displaying “HOT” or “COLD”
38
The LCD display will read “COLD” when the cell is reading water temps below 50° F. The LCD display will read “HOT” when the cell is reading water temps above 140 ° F.
Inspect the cell for calcification. Clean the cell & reset the average salt reading (pg. 11). IF the message still
appears AND the water temperature is not greater than 139F or lower than 51F, then go to 5B.
Verify the cell is not directly downstream of a running chiller or heater. If directly downstream, this could
cause false temperature readings, otherwise replace the TurboCell.
Inspect Cell Upstream Equipment
To override a “COLD” message for 24 hrs., move the toggle switch from OFF, up to Super Chlorinate (without stopping on Auto). This will override the message for 24hours. If the system reads “HOT”
it is possible the temperature sensor (within the cell) has failed and the cell will require replacement.
“HOT” = > 140°F “COLD” = < 50°F
Step 5B
Clean Cell Calcified Cell
Step 5A
AquaRite®
Additional Information
Software Revision: Cell Compatibility Chart
40
AquaRite AquaRite XL AquaTrolSwimpure
PlusH40
SmartPure
Sanitizer
SmartPure
Sanitizer IISP40 Guardian Nature Soft
T-CELL-3 &
GLX-CELL-3-W
For residental
pools up to
15,000 gallons
1.50 or later X X 1.50 or later X X X X X X
T-CELL-5 &
GLX-CELL-5-W
For residental
pools up to
18,000 gallons
1.50 or later XAll
revisions1.50 or later X
All
revisionsX X X X
T-CELL-9 &
GLX-CELL-9-W
For residental
pools up to
25,000 gallons
1.50 or later X X 1.50 or later X X X X X X
T-CELL-15 &
GLX-CELL-15-W
For residental
pools up to
40,000 gallons
All
revisions
All
revisionsX
All
revisions
All
revisionsX
All
revisions
All
revisions
All
revisionsAll revisions
Cell Type
Control Center Model
Cell Compatibility Chart
Salt Addition Chart: lbs. required for 3200ppm
41
8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000
0 213 267 320 373 427 480 533 587 640 693 747 800 853 907 960 1013 1067
200 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
400 187 233 280 327 373 420 467 513 560 607 653 700 747 793 840 887 933
600 173 217 260 303 347 390 433 477 520 563 607 650 693 737 780 823 867
800 160 200 240 280 320 360 400 440 480 520 560 600 640 680 720 760 800
1000 147 183 220 257 293 330 367 403 440 477 513 550 587 623 660 697 733
1200 133 167 200 233 267 300 333 367 400 433 467 500 533 567 600 633 667
1400 120 150 180 210 240 270 300 330 360 390 420 450 480 510 540 570 600
1600 107 133 160 187 213 240 267 293 320 347 373 400 427 453 480 507 533
1800 93 117 140 163 187 210 233 257 280 303 327 350 393 397 420 443 467
2000 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400
2200 67 83 100 117 133 150 167 183 200 217 233 250 267 283 300 317 333
2400 53 67 80 93 107 120 133 147 160 173 187 200 213 227 240 253 267
2600 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
2800 27 33 40 47 53 60 67 73 80 87 93 100 107 113 120 127 133
3000 13 17 20 23 27 30 33 37 40 43 47 50 53 57 60 63 67
3200 Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal Ideal
3400 OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK
3600+ Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute Dilute
Current
Salt Level
Pool Size - Gallons
Note: Prior to adding salt, always test water with independent tests to determine current salt and stabilizer levels.
How to add salt Brushing the salt around will speed up the dissolving process. DO NOT allow the salt to sit in a pile at
the bottom of the pool. Salt water is heavier than fresh water, so the salt water will tend to accumulate at the deepest part of the pool. Run the filter system with the suction coming from the main drain for
24 hours to evenly distribute the salt throughout the pool
Note: Refer to the Plasters recommendations for cure time before adding salt.
Chlorine Output & Salt Levels
42
1. With Firmware Revision 1.55 (5/8/2009) the cycle time (reversal of polarity) changed from 120 minutes (2 hrs) to 180 minutes (3 hrs). When you set the ‘Desired Output %’ dial on the main panel this sets the level of salt cell operation as a percent of the operating time of each cycle. 50% is the factory default. Below are simple examples for 2 and 3 hr cycle times.
• 2 hr cycle: If the output is set at 50% and the total time for operation is 8 hrs, the salt cell will operate (and produce chlorine) for 50% (1 hr) of each 2hr cycle for a total of 4 hrs. • 3 hr cycle: If the output is set at 50% and the total time for operation is 9 hrs, the salt cell will operate (and produce chlorine) for 50% (1.5 hrs) of each 3 hrs cycle for a total of 4.5 hrs
2. Super-chlorinate is an additional option to use in order to ‘catch up’ in chlorine production when making adjustments to the desired output level. Move the switch to ‘Super Chlorinate’ to enable. This will cause the system to produce chlorine at 100% output for 24 hours assuming the pump remains on constant for 24hours. Once 24 hours expires, the chlorine output dial will once again drive the chlorine output percentage.
Chlorine Output & Salt Levels (cont.)
43
3. It is possible that the displayed salt level can be significantly different from the actual salt level (when measured through an independent test). This can happen as a result of a dirty cell or from a cell that is experiencing the aging process. Low salt readings should ALWAYS be followed by a cell cleaning first and then an actual meter measurement of the salt level in the water. If the cell is clean and the level of salt measured in the water is correct, then the cell has started to age, which results in a lower calculated salt level. This is an acceptable situation, assuming the level of free chlorine in the pool is appropriate. NEVER add additional salt in this circumstance.
4. If the free chlorine is not appropriate and the steps in item 2 have been followed and addressed as needed, then the ‘Desired Output %’ needs to be increased in a 25% increment (for example from 50% to 75%) to allow for the TurboCell to operate for a longer period (% of total operating time)in order to produce a sufficient amount of chlorine as the cell begins to age. Allow 24 hours and re-test free chlorine. Increase in increments of +10% if required. Keep in mind this is assuming the chemistry parameters are correct in the pool and there is nothing that is creating a significant chlorine demand. Also, it is common to have to increase the chlorine output % when the heat of the season, when a-typical temperatures are recorded.
Reading Serial Numbers
44
3A0112 = Standard Warranty Term
3A0112 = Product Family
3A0112 = Year of Manufacture
3A0112 = Month of Manufacture
123456 = Manufacturing ID
3A0112- 123456
3A11284- 123456
Beginning 08-05-2011
Beginning 11-01-2001
3A11284 = Standard Warranty Term
3A11284 = Product Family
3A11284 = Year of Manufacture
3A11284 = Day of Manufacture
123456 = Manufacturing ID