Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van...

65
Applying Advanced Leakage Control and Pressure Management

Transcript of Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van...

Page 1: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Applying Advanced Leakage Control and Pressure

Management

Page 2: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Reinhard SturmCEO – Water Systems Optimization

Julian ThorntonThornton International

Reid CampbellDirector Water Services – Halifax Water

Learning Module Instructors

Page 3: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Pressure Leakage Relationship

• Pressure Management Benefits – Failure Frequency Reduction, Lifespan Extension and Leakage Reduction

• Tools for Pressure Management

• Advanced Pressure Management Zones in Halifax

• Pressure Management Debate

Learning Module Agenda

Page 4: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure and Leakage – There IS a Link

Page 5: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

0

10

20

30

40

50

60

Se

p-0

2

Oct-

02

No

v-0

2

De

c-0

2

Ja

n-0

3

Fe

b-0

3

Ma

r-0

3

Ap

r-0

3

Ma

y-0

3

Ju

n-0

3

Ju

l-0

3

Au

g-0

3

Se

p-0

3

Oct-

03

No

v-0

3

De

c-0

3

Ja

n-0

4

Fe

b-0

4

No

. B

reaks

Main Breaks

Service Breaks Pre-TrialFixed

PRV

Flow Mod

PRV

1st

Adju

stm

ent

2nd

Adju

stm

ent

3rd

Adju

stm

ent

Pressure and Leakage – There IS a Link

Page 6: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Fluctuations and Transients

Page 7: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Predicting Relationship BetweenPressure and Leakage

Fixed Area and Variable Area Discharges (FAVAD)

Fixed Area

Leakage rate L varies with Pressure P N1

where N1 may vary between 0.5 and 2.5

Variable Area

Page 8: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Thousands of pressure control schemes installed internationally since 1995 to reduce leakage; justified economically due to:• better methods to predict reductions in leak flow rates

(FAVAD, simplified to N1 Power Law)• advanced pressure control with flow modulation • methods to predict reductions in new burst frequency on

mains, and services, and extend infrastructure life

• As a consequence many systems now are operating at lower and more variable pressures

• It has now became necessary to review concepts used for calculations – moving from N1 to use FAVAD concept where necessary

Pressure Control Expands After 1995

Page 9: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Leakage Numbers for lab tests on pipe samples: • Leak Area vs pressure relationships • Influence of low/negative pressure on leak flow rates

• Open Access paper on hydraulic analysis by van Zyl, Lambert and Collins ASCE Journal of Hydraulic Engineering / Vol 143 Issue 9 - Sept 2017 ( 1000+ downloads)

• summarised in Presentation 2017S on LEAKSSuite

• Allan Lambert has now applied FAVAD concepts to N1 tests, to get fast-track methods for practitioners to use• See http://www.leakssuite.com/favad-and-n1update/

Recent Collaborative Research on FAVAD

Page 10: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Use Fast-track FAVAD calculations, customised for practitioners, for improved leakage calculations

• WLR&A’s ‘Leakage Practitioner’ fast-track approach for Utilities using FAVAD in 6 steps:

1. Calculate N1 from an N1 test, or assume N1, at a specified Average Zone Pressure

2. Identify % split of Fixed and Variable Area leaks from N1

3. Then calculate N1 vs Average Zone Pressure equation

4. Use N1 test to define Leak Flow Rate vs AZP equation

5. Predict zonal leakage from AZP pressures in real time

6. Improve reliability of assessment of Night-Day Factors

Fast Track Approaches for Practitioners

Page 11: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Step 3:Derive

N1 vs AZP equation

and graphs

from N1 test data

Step 4Derive

L vs AZP equation

and graphs

from N1 test data

Step 5Use AZP

and L vs AZP equation to track

leak flow rates in

real time

Step 6Use

AZPaveAZPmnf

and N1 at AZPave to calculate Night-DayFactor NDF http://www.leakssuite.com/favad-and-n1update/http://www.leakssuite.com/night-day-factor-update/

Fast Track Approaches for Practitioners

Page 12: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Leakage Relationship

• Large leaks from metal pipes – N1 ~ 0.5

• Background Leakage – N1 ~ 1.5

• Entire Systems with mixed pipe – N1 ~ 1

Page 13: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

0 .00

0 .20

0 .40

0 .60

0 .80

1 .00

1 .20

1 .40

0 .00 0 .10 0.20 0 .30 0 .40 0.50 0 .60 0 .70 0.80 0 .90 1 .00 1 .10 1.20

R a tio o f P re s s u re s P 1 /P o

Ra

tio

of

Le

ak

ag

e R

ate

s L

1/L

o

N 1 = 0 .50

N 1 = 1 .00

N 1 = 1 .15

N 1 = 1 .50

N 1 = 2 .50

Pressure Leakage Relationship

Page 14: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• At pressure Po (= 71psi), the leakage rate Lo = 10.0 gpm

• What is the predicted leakage rate at pressure P1 = 50 psi, for various N1 values?

Use the equation L1 = Lo x (P1/Po)N1

• If N1 = 0.5, L1 = 10 x (50/71)0.5 = 8.4 Gpm

• If N1 = 1.0, L1 = 10 x (50/71)1.0 = 7.0 Gpm

• If N1 = 1.5, L1 = 10 x (50/71)1.5 = 5.9 Gpm

• If N1 = 2.5, L1 = 10 x (50/71)2.5 = 4.1 Gpm

Pressure Leakage Relationship

Page 15: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Leakage Relationship

Page 16: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Management Benefits

Pressure Management: Reduction of Excess Average and Maximum Pressures

Conservation Benefits Water Utility Benefits Customer Benefits

Reduced Flow-rates Reduced Frequency of Burst and Leaks

Reduced Consum-

ption

Reduced Flow Rates

of Leaks and Bursts

Reduced Repair Costs,

Mains & Services

Deferred Renewals

and Extended Asset Life

Reduced Cost of Active

Leakage Control

Fewer Customer

Complaints

Fewer Problems

on Customer Plumbing

& Appliances

Source: A Lambert 2010

Page 17: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Management Benefits

Page 18: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Failure Frequency Reduction And Lifespan Extension

Page 19: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure: Breaks Relationship

• This approach links the ‘straw that breaks the camel’s back’ concept to the ‘Slope S’ predictions• and explains why Slope S in PMZs varies between 0 and around 3.0

Burs

t fr

equency B

F

Maximum AZP Pressure Pmax

Burs

t F

requency B

F

Maximum AZP Pressure Pmax

Burst frequency component that is

assumed to be independent of changes in

pressure, but which may vary from year to

year with climatic and other influences

Burst

frequency

component

that varies

wholly or

partly with

pressure

% change in burst

frequency

% change in burst

frequency

% change in

burst frequency

% change in Pmax

% change in Pmax

% change in Pmax

S = 2.8

S = 1.4

S = 0.7

Change

in Pmax.

Reduction in

pressure-

dependent

burst

frequency

Burst frequency component that is assumed to be

independent of changes in pressure, but which may

vary from year to year with climatic and other

influences

Assumed equation: BF = BFnpd + A x PmaxN2

BFnpd

Predicting Reduction in Breaks by Reducing Pmax

Strip out

BFnpd

Page 20: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

FAILURERATE

PRESSURE

NEW PIPES,

GRAVITY SYSTEM

Consider the situation when new mains and services are laid, they are designed to withstand existing system pressures

with a large factor of safety, so failure rate is low

Operating range

TIME

Pressure: Breaks RelationshipHow Does Pressure Management Reduce Pipe Failure Rates? (2006 Version)

Page 21: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

FAILURERATE

PRESSURE

NEW PIPES,

SYSTEM WITH

PRESSURE TRANSIENTS

If the new pipe system experiences pressure transients or variations the factor of safety is reduced, but the failure rate may remain quite low.

Operating range

Pressure: Breaks RelationshipHow Does Pressure Management Reduce Pipe Failure Rates? (2006 Version)

Page 22: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

COMBINATION OF FACTORS

CAUSES INCREASED

FAILURE RATE

FAILURERATE

PRESSURE

BOOM !!!

Pipes deteriorate through age and corrosion, and other local and seasonal factors reduce the ‘failure’ pressure until eventually burst frequency starts to increase significantly, often on a seasonal basis

Operating range

TIME

Pressure: Breaks RelationshipHow Does Pressure Management Reduce Pipe Failure Rates? (2006 Version)

Page 23: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

STEP 1: REDUCE TRANSIENTSFAILURE

RATE

PRESSURE

The first step in pressure management is to check for the presence of pressure transients or variations; if they exist, reduce the range and frequency of both

Pressure: Breaks RelationshipReduce Transients and Variations (2006 Version)

Page 24: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

FAILURERATE

PRESSURE

STEP 2: REDUCE EXCESS PRESSURE

Next, identify if the stabilized pressures at the critical point are higher than necessary; if so, reduce the excess

to avoid operating system at it’s ‘failure’ pressure

Operating range

TIME

Pressure: Breaks RelationshipReduce Excess Pressure (2006 Version)

Page 25: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

FAILURERATE

PRESSURE

Over time the age and corrosion factors grow and reduce the safety factor throughout the year. Infrastructure replacement has to take place eventually,

however in many cases significant benefits have been gained by deferring the investment through management of previously excess pressures

Minimum operating range

TIME

Pressure: Breaks RelationshipWhat Happens Next…

Page 26: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

FAILURE

RATE

PRESSURE

If the current failure rate is comparatively high (red circle), then quite a small % reduction in pressure (to the blue circle) may produce a large

reduction in failure frequency. But if the failure frequency is already quite low (blue circle), further pressure reductions may not greatly reduce

the current failure frequency, but could extend infrastructure life

Pressure: Breaks RelationshipWhat to Expect? – Initial Conditions

Page 27: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Reduction of excess pressure reduced the average mains failure frequency AND the large range of seasonal failure frequencies, so that even peak seasonal

failures were within acceptable limits, giving many years extra life. The improved 2011 visual explanation (next slide) shows why!

Pressure: Breaks RelationshipWhat Happened Next… in Durban CBD Mains

Page 28: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Average annual failure frequency consists of non-pressure dependent failures (BFnpd) plus failures triggered by excess pressure when added to other seasonally varying environmental factors

0

10

20

30

40

50

60

70

80

90

0 20 40 60 80 100

Failu

re F

req

ue

ncy

pe

r 1

00

km

/ye

ar

Maximum Pressure at Average Zone Point (metres)

Variation of Failure Frequency with Seasonal Environmental Factors

High

Average

Low

BFnpd

Pressure: Breaks RelationshipManaging Pressure to Reduce Seasonal Pipe Failure Rates and Add Extra Life to Your Older Pipes (2011)

Page 29: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

A North American city main break/leak seasonal trendchanges when finished water temperature changes abruptly

Example BFnpd – Seasonal Failures?

Page 30: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Example BFnpd – Ground Movement

Page 31: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Example BFnpd Third Party Hits

Page 32: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Example BFpd Tank Overflows

Page 33: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Example BFpd Pipe Leakage

Page 34: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Source: Gold Coast Australia

What to Expect?

Page 35: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Management and Infrastructure Life Span

Page 36: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

One bucket full

obviously has to go!

One is OK – not sure

about the other…

perhaps pressure

management can

extend the life

Pressure: Breaks RelationshipPM Extends Infrastructure Life

Page 37: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Factors• Soil Load• Live Load• Thermal Stress• Risk• Ground Movement• 3rd Party Digging• Degradation Rate• Operating Pressure• Surge Pressure

Control measures• Remove soil cover

• Divert traffic

• Manage water / ground temperature

• Move pipe

• Better trenches

• Call before you dig program

• Corrosion control

• Pressure Management

• Pressure Management

Factors Contributing to Asset Life and Control Measures

Page 38: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Average life of AC pipes before failure by lateral splits increases as maximum pressure decreases

40 50 60 70

100/CD 55 54 52 51

150/C 60 58 55 53

200/C 72 69 66 63

250/C 82 78 75 71

300/C 95 91 86 82

AC Pipe

DN/Class

Maximum Pressure (metres)

Average life of AC pipes, New Zealand

• Reductions in maximum pressure can add several years to average life of AC mains– depending upon the reduction in maximum pressure, and the pipe

diameter, Class and wall thickness

• Zones with large amounts of AC mains having low residual life can be targeted for pressure management– and financial benefit of deferred replacement calculated

Source: John R Black

Pressure: Breaks RelationshipAssessing Extension of Asset Life by Pressure Management (AC Pipes)

Page 39: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

How could PM influence your infrastructure life?

Each utility should:• Verify surge pressures• Smooth where possible• Verify operating pressures• Look for opportunities to manage pressure• Reduce OPEX to an efficient level• Identify pipe nearing end of useful life• Increase the useful life of the pipe if possible• Focus CAPEX on unavoidable replacements

On the Road to Improved Efficiency…

Page 40: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Tools ForPressure Management

Page 41: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Altitude Control

Page 42: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure Reduction

Page 43: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Remote Node Modulation

Flow Modulated Control

Page 44: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Remote Note Modulated Control

Page 45: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Transient Control

Page 46: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pump Control

Page 47: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Halifax Water’s Experience With Pressure Management

Page 48: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Adopted IWA/AWWA Methodology in 2000.

• Reduced ILI from 9.0 to 2.4

• System Inputs reduced from 168 to 130 MLD.

• 45 pressure zones, 75 DMA’s, 1 PMA

Water Loss Control at Halifax Water

Page 49: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

www.hrwc.ca Slide 49

Dartmouth Central

Page 50: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Flow modulated pressure control

• Controller reduces system pressure as demands decrease

Pressure Flow

Dartmouth Central PMA

Page 51: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Avg Annual 2002/03 – 2004/05

Main Leaks = 23

Pub. Service Leaks = 4

Priv. Service Leaks = 5

2005/2006

Main Leaks = 12

Pub. Service Leaks = 2

Priv. Service Leaks = 3

Since 2005/2006: 16 /year

UARL

Potentially Recoverable Annual

Volume of Real Losses

PressureManagement

Dartmouth Central PMA:Before and After

Page 52: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Based on several years of flow modulated pressure control:• Breaks are measurably reduced• Dependent on system characteristics

• At the time thought that it had important but limited application across the utility

• Dartmouth Central PMA/DMA has operated since 2005-06.• Changed to solenoid control in 2013-14

• Based on recent data analysis opportunity for pressure management is much greater

Pressure Management at Halifax Water

Page 53: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Collins Park is a small system owned by Halifax Water:• Commissioned 1988• Average system pressure: 70 psi• 75 residential customers• Ductile iron distribution system (2 km’s)• Direct pressure provided by pumps at the WTP• No specific break/leak history

• In response to new Provincial Water Treatment standards, a new treatment plant was constructed• Commissioned in June 2010

Case Study: Collins Park System

Page 54: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• 5 breaks in two months after commissioning:• Pressure increased by 15 psi

• Pressure surges detected by logging

• Quality of repairs

Collins Park System

Page 55: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Pressure reduced slightly in some zones• 6 zones with

reduced pressure

• 2-5 psi reduction

Leaks and Breaks2005-06 to 2014-15

Proactive Pressure Reduction

Page 56: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• In 2012 we did a statistical analysis of all watermain breaks

• Key findings:• 60% of all breaks happen between midnight and

6 am• Similar occurrence for all break types• Break clusters

New Finding

Page 57: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Where Are We Going Next? Breaks vs Time of Day

Page 58: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Pressure spikes in the

distribution system

captured on SCADA as

reservoir altitude valve

closes too quickly

Main failure

correlates to

pressure spikes

New Strategies Failure Analysis

Page 59: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• Night time pressure creep in PRV fed zones• PRV’s less precise in low end of flow range

• Due to water loss control:• PRV’s night time operation in lower end of design range• Less leakage to provide base line flow through prv• Less leakage to dampen HGL

• Need for improved maintenance

• Analysis of individual breaks will identify high priority prv’s for maintenance or re-configuration

New Strategies

Page 60: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

During low night flows,

system pressure creeps

up 60 kpa as a result of

a malfunctioning PRV.

New StrategiesCreeping PRV

Page 61: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

• On August 20, 2015, we had 6 breaks in a single zone over a 6 hour period

August 20, 2015

Page 62: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

BE

DFO

RD

BY

PS

WIN

DM

ILL RD

RO

CKY L

AKE D

R

LARRY U

TECK B

LVD

HAMMONDS PLAINS RD

BEDFORD HW

Y

CO

PP

ER

RD

BASINVIEW DR

BL

UE

WA

TE

R R

D

HIG

H S

T

SHO

RE D

R

UN

ION

ST

DU

KE

ST

MOIRS MILL RD

JETTY RD

LE

WIS

DR

OCEANVIE

W D

R

BRO

AD S

T

SO

UT

HG

AT

E D

R

KEARNEY LAKE RD

CO

LIN

S R

D

GA

RY

MA

RT

IN D

R

PE

WTE

R L

AN

E

SU

LPH

UR

RD

CA

RB

ON

RD

RUTLE

DG

E S

T

VERDI D

R

NORTH STS

MIT

HS

RD

RID

GEVA

LE D

R

STARBOARD DR

ARSENAL DR

LEAD RD

RIV

ER

LA

NE

FIR

ST

AV

E

MA

DIS

ON

DR

MA

PL

E S

T

ROY CRES

PERTH

ST

BEDFORD BYPS

Peakview PRV

Bedford South Booster

Location of Breaks

Page 63: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students
Page 64: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Questions or Comments?

Page 65: Applying Advanced Leakage Control and Pressure Management · 2017-12-19 · •By Prof. Kobus van Zyl, Allan Lambert, Dr Richard Collins and post-grad University of Cape Town students

Lets talk about it

Pressure Management Debate