Application Recommendations REF 542plus · Q12 - bus riser. A typical ... protocol uses a 1 Mb/s...

20
Application Recommendations REF 542plus Application and Setting Guide

Transcript of Application Recommendations REF 542plus · Q12 - bus riser. A typical ... protocol uses a 1 Mb/s...

Application Recommendations REF 542plus

Application and Setting Guide

Application Recommendations

Application and Setting Guide

REF 542plusIssued: 31.08.2007Version: B/29.08.2008

1MRS756405

CopyrightsThe information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.

In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document.

This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

Copyright © 2008 ABB Oy

All rights reserved.

3

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

Q01

Q05Q03

Q07 Q09 Q11

Q02

Q10Q12 Q04

Q08 Q06

Standard indoor switchgear: 2 sections, 10 cubicles per section.

070790

Q01, Q02 - incoming cubicles

Q03, Q04 - voltage transformer cubicles

Q05 - Q10 - outgoing feeders

Q11 - bus coupler

Q12 - bus riser

A typical application of REF542plus:

1. Define the auxiliary power supply:• 110 VDC• 220 VDC• range 48-220 VDC

2. Define if 4…20 mA signals need to be used in the switchgear to convert some signals or to transfer information signals (current, voltage, frequency, power) to the NCC. All these signals can also be sent via the communication board.

3. Select the right analog input board. The analog input board is used to get analog signals from the current transformers or voltage transformers (neutral current and voltage as well). The board has eight analog measurement inputs in different combinations: current inputs (1/5 A), voltage inputs (100-150 V), current inputs for connection to the sensitive earth-fault protection (0.2 A). The following board is the most frequently used:

Three current inputs for phase currents, three voltage inputs for voltages (you can use phase-to-phase or phase-to-earth voltage), one current input for sensitive earth-fault protection (from neutral current transformer), and one for the open delta voltage signal.

4

1MRS756405 Application Recommendations

Application and Setting Guide

REF 542plus

d2BI1

BI15

BI2

BI16

BI3

BI17

BI4

BI18

BI5

BI19

BI6

BI20

BI7

BI21

BI8

BI22

BI9

BI23

BI10

BI24

BI11

BI25

BI12

BI26

BI13

BI27

BI14

BI28

d2S1

S15

S2

S16

S3

S17

S4

S18 S20 S22 S24 S26 S28

S5

S19

S21 S23 S25 S27

S6

S7

S8 S9

S10

S11

S12 S13 S14

d10

d10

d12

d12

d18

d18

d20

d20

d22

d22

d24

d24

d26

d26

d28

d28

X20

X30

d4d4

d5d5

d8d8

d14

d14

d16

d16

Z2z2

z10

z10

z12

z12

z18

z18

z20

z20

z22

z22

z24

z24

z26

z26

z28

z28

z4z4

z5z5

z8z8

z14

z14

z16

z16

++

++

++

++

++

++

++

++

++

++

++

++

++

++

__

__

__

__

__

__

__

__

__

__

__

__

__

__

BO1

BO3

BO4

BO5

BO6

BO7

BO8

WD1

BO2

X21 d2 d6 z8 d10

d14

z10

z14

d20

z20

z26

d28

z32

z4d4 d8 z6 d12

d16

d18

z18

d24

z28

d30

z12

z16

d22

z22

z24

d26

z30

z2

4. Select the binary input-output board. You can select the board for 110 VDC or 220 VDC and verify whether is it necessary to use a static channel for the impulse signals.

The most often used boards are the one for 220 VDC and the following board:

Binary I/O3 - 80…250 V/143 V Standard. It has 14 binary inputs and 8 output relays. One output has an internal pulse generator to monitor the connected circuit (usually used for Trip Coil Supervision, TCS). The voltage input threshold is 143 V (according to GOST).

For incomings and bus couplers, it is recommended to use 3 I/O boards to have an option for designing a complex logical scheme. For the outgoings, it is recommended to use two boards.

5. Define the communication board (if needed). REF 542plus has an embedded WEB server. In addition, the MODBUS TCP communication protocol can be used via the Ethernet RJ 45 interface. An additional multi-communication system can be built using the following protocols:

• MODBUS RTU RS485 (used for SPA as well)• MODBUS RTU Fiber Optic with ST connectors (used for SPA as well)• SPA Plastic Fiber version snap-in connectors• SPA Glass Fiber with SMA connectors• SPA Glass Fiber with ST connectors• COM-L (LON - LAG 1.4)

5

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

• COM-I (IEC 60870-5-103)• Ethernet module for IEC 61850

The difference between the communication systems is the topology, the amount of devices, and the SCADA system of the NCC.

The most common protocol is the standard MODBUS RTU (baud rate 19.2-76.8 kb/s). Connetion to a third party communication system is therefore possible. This protocol has two interfaces: optical (ST connector) and electrical (RS485).

SPA is an ABB proprietary protocol, and it is also used to build communication systems. The baud rate is specified to 9600 kbit/sec. SPA has a lower baud rate but it is more flexible because of different types of converters or concentrators available. The network topology can be star of loops, loop of stars, or just loop or star. The info flow speed depends on the topology and it is not strictly defined. Usually, devices are split up by sections or other primary features.

In the figure below, an example of a ring topology, where the IEDs are connected in a loop.

The number of IEDs is limited when using SPA in a ring topology. The more IEDs you connect to the ring, the slower is the information flow. A larger number of devices can be used, but in this case, it is recommended to make several loops and to use a concentrator before the connection to SCADA. Do not connect more than 8-12 devices to the loop, otherwise the communication slows. If more devices are required, it is recommended to use the start topology. The maximum length of the pilot wire (RS485) is 1200 m (no more than 800 recommended). An optical connection can be used as well.

The ABB LON per LAG 1.4 (LON Application Guide) protocol is an ABB proprietary protocol too, and it is based on the IEC 60870-5-101 standard. This protocol uses a 1 Mb/s communication bus and enables horizontal interbay communication. This means, that a station wide interlocking is possible with this communication protocol. The engineering of the communication system shall be carried out according to the related application guide LAG 1.4.

IEC 60870-5-103 with the extension for sending commands is the first open protocol for microprocessor based protection in substations. In 1998, the standard was extended by the association of German utilities to apply to an IED (Intelligent Electronic Device) integrating protection and control in one device. Third party communication system can be connected without problems.

6

1MRS756405 Application Recommendations

Application and Setting Guide

REF 542plus

The IEC 61850 protocol is the most up-to-date communication standard. It can be connected to 10 or 100 Mb network. It is the fastest protocol used today. It has two RJ45 ports for normal LAN cables. A fiber-optic connection with LC connectors can also be used. Due to the engineering tool provided, it is easy to design the connection to the communication system. Only the star topology shall be used. In this case, it is necessary to use an industrial switch with IEC61850 and support. The recommended switch type is Ruggedcom. On the switch level, additionally a ring can be defined, if required.

6. Select the required housing. The two available types are: wide and normal.

7

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

ca. 70 261,5

M4

106,3

140 1233

185

106,3

244,8

10 18233,5

M4

75,5

75,5

? 0,1

? 0,1?0,1

?0,1

?0,1

?0,1

Standard housing• One power supply• One mainboard module• One analog input module• Two binary input and output modules at the maximum• As an option, a communication module or a 4/0...20 mA analog output

8

1MRS756405 Application Recommendations

Application and Setting Guide

REF 542plus

M4

106,3

184 1233

229

106,3

244,8

ca. 70 261,5

97,5

97,5

10 233,5 18

M4

? 0,1

? 0,1

?0,1

?0,1

?0,1

?0,1

Wide housing• One power supply• One mainboard module• One analog input module• Three binary input and output modules at the maximum• As an option, a communication module• As an option, a 4...20 mA analog input module or a 4/0...20 mA analog output

module

7. Select an HMI for the protection. Select the voltage level for the power supply: 48…110 VDC or 110…220 VDC, and select if a protection cover is needed for the LCD. A typical choice is HMI V5 110…220 VDC without a cover.

8. Selection of functionality level:

Table 1.1 Functionality levels of REF 542plus

ANSI CODE

Protection functions for REF542plus

Basic Low Basic Multi Low Multi Differential Distance Hsts

68 Prot Inrush current blocking

x x x x x x x

68 Prot Inrush harmonic x x x x x x x51 Prot Non-directional

overcurrent IDMTx x x x x x x

51 Prot Non-directional overcurrent low

x x x x x x x

51 Prot Non-directional overcurrent high

x x x x x x x

9

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

50 Prot Non-directional overcurrent instantaneous

x x x x x x x

67 Prot Directional overcurrent low

not available x x x not to be used x x

67 Prot Directional overcurrent high

not available x x x not to be used x x

51N Prot Non-directional earth-fault IDMT

x x x x x x x

51N Prot Non-directional earth-fault low

x x x x x x x

51N Prot Non-directional earth-fault high

x x x x x x x

67N Prot Directional earth-fault sensitive

not available x x x x x x

67N Prot Directional earth-fault low

not available x x x x x

67N Prot Directional earth-fault high

not available x x x x x x

67N Prot Directional earth-fault sector (stage 1)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 2)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 3)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 4)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 5)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 6)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 7)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 8)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 9)

not available x x x x x x

67N Prot Directional earth-fault sector (stage 10)

not available x x x x x x

59 Prot Overvoltage low not available not available x x not to be used x x59 Prot Overvoltage high not available not available x x not to be used x x59 Prot Overvoltage

instantaneousnot available not available x x not to be used x x

27 Prot Undervoltage low not available not available x x not to be used x x27 Prot Undervoltage high not available not available x x not to be used x x27 Prot Undervoltage

instantaneousnot available not available x x not to be used x x

59N Prot Residual overvoltage low

not available x x x x x x

59N Prot Residual overvoltage high

not available x x x x x x

49 Prot Thermal overload not available not available not available x x x x51 Prot Motor start-up not available not available not available x x x x51LR Prot Blocking rotor not available not available not available x x x x

Table 1.1 Functionality levels of REF 542plus (Continued)

ANSI CODE

Protection functions for REF542plus

Basic Low Basic Multi Low Multi Differential Distance Hsts

10

1MRS756405 Application Recommendations

Application and Setting Guide

REF 542plus

66 Prot Number of starts not available not available not available x x x x21+79 Prot Distance not available not available not available not available not to be used x x87 Prot Transformer

differentialnot available not available not available not available x not to be

usednot to be used

87N Prot Restricted Earth-Fault (low impedance)

not available not available not available not available x x x

46 Prot (CNeg-PhaseSe-quence)

Unbalanced load not available not available x x x x x

32 Prot Directional power not available not available not available x not to be used x x37 Prot Low load not available not available not available x x x81 Prot Frequency

supervisionnot available not available not available x not to be used x x

81 Prot Frequency protection (stage 1, network 1)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 2, network 1)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 3, network 1)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 4, network 1)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 5, network 1)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 6, network 1)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 1, network 2)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 2, network 2)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 3, network 2)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 4, network 2)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 5, network 2)

not available not available not available x not to be used x x

81 Prot Frequency protection (stage 6, network 2)

not available not available not available x not to be used x x

25 Prot Synchronism check x x x x not to be used x x79 Primi Autorecloser x x x x not to be used x

Primi Power factor controller not available not available not available x not to be used x xProt Switching resonance

protectionnot available not available not available x not to be used x x

Primi High harmonic protection

not available not available not available x x x

Primi Fault recorder x x x x x x x

Table 1.1 Functionality levels of REF 542plus (Continued)

ANSI CODE

Protection functions for REF542plus

Basic Low Basic Multi Low Multi Differential Distance Hsts

11

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

Typical protections for the following switchgear:

Incomings:Overcurrent (low and high stages), residual voltage (low and high stages), minimum voltage (low and high stage), earth-fault current protection (low and high stage).

Bus coupler:Overcurrent (low and high stages), residual voltage (low and high stages), minimum voltage (low and high stage), earth-fault current protection (low and high stage), synchrocheck.

Outgoings:Overcurrent (low and high stages), earth-fault current protection (low and high stage), sometimes minimum voltage and residual voltage protections.

VT cubicle:Protection functions are not needed in this kind of cubicles, because voltage wires can be connected to other REF 542 plus IEDs and the protections can be used separately.

Usually, the bus coupler and incoming feeder are the same type of REF542plus. It should have as many binary inputs and outputs as possible to have additional functionality and ability to extend the switchgear in the future.

Let's assume, the power supply is 220 VDC.

REF 542plus code for panels: Q01, Q02, Q11: 76B2NFFF301WB26

REF542plus [76], Mainboard - basic version [B], Power supply - rated voltage 220 VDC [2], No analog I/O [N], Binary I/O3 - 80…250 V/143V Standard [F], Binary I/O3 - 80…250 V/143V Standard [F], Binary I/O3 - 80…250 V/143V Standard [F], Analog input 3CT+3VT+1CT0.2A+1VT [30], Modbus RTU/SPAbus RS485 communication board [1], Housing - Wide [W], HMI V5 - IEC [B] auxiliary voltage 110-220 VDC, HMI cable 2.5 m [2], Software Multi License [6].

As for outgoing, the difference is usually only the number of I/O boards:

REF 542plus code for panels Q05-Q10: 76B2NFFN301WB26

REF542plus [76], Mainboard - basic version [B], Power supply - rated voltage 220 VDC [2], No analog I/O [N], Binary I/O3 - 80…250 V/143V Standard [F], Binary I/O3 - 80…250 V/143V Standard [F], Binary I/O slot 3 - empty slot [N],

12

1MRS756405 Application Recommendations

Application and Setting Guide

REF 542plus

Analog input 3CT+3VT+1CT0.2A+1VT [30], Modbus RTU/SPAbus RS485 communication board [1], Housing - Wide [W], HMI V5 - IEC [B] auxiliary voltage 110-220 VDC, HMI cable 2.5 m [2], Software Multi License [6].

Table 1.2 Code definition table

REF 542plus 7| | | | | | | | | | | | |

Operations field | | | | | | | | | | | | |Standard 6 | | | | | | | | | | | |

| | | | | | | | | | | |Mainboard | | | | | | | | | | | |Basic B | | | | | | | | | | |Standard S | | | | | | | | | | |Full F | | | | | | | | | | |

| | | | | | | | | | |Power supply | | | | | | | | | | |Rated voltage 110 VDC 1 | | | | | | | | | |Rated voltage 220 VDC 2 | | | | | | | | | |Wide range Voltage 48 to 220 VDC 3 | | | | | | | | | |

| | | | | | | | | |Analog - Input or Out | | | | | | | | | |No Analog I/O N | | | | | | | | |Analog Input board 4..20 mA A | | | | | | | | |Analog Output board 4..20mA B | | | | | | | | |

| | | | | | | | |Binary IO Slot 1 | | | | | | | | |Binary I/O3 - 80..250 V/59V - Standard 9 | | | | | | | |Binary I/O3 - 80..250 V/59V - with Static Channel A | | | | | | | |Binary I/O3 - 80..250 V/143V - Standard F | | | | | | | |Binary I/O3 - 80..250 V/143V - with Static Channel G | | | | | | | |

| | | | | | | | |Binary IO Slot 2 | | | | | | | | |None NBinary I/O3 - 80..250 V/59V - Standard 9 | | | | | | |Binary I/O3 - 80..250 V/59V - with Static Channel F | | | | | | |Binary I/O3 - 80..250 V/143V - Standard A | | | | | | |Binary I/O3 - 80..250 V/143V - with Static Channel G | | | | | | |

| | | | | | |Binary IO Slot 3 N | | | | | |Binary I/O3 - 80..250 V/59V - Standard 9 | | | | | |Binary I/O3 - 80..250 V/59V - with Static Channel A | | | | | |Binary I/O3 - 80..250 V/143V - Standard F | | | | | |Binary I/O3 - 80..250 V/143V - with Static Channel G | | | | | |

| | | | | |Analog Input XX: | | | | | |3 CT + 3 VT + 1 CT 0.2A + 1 VT 30 | | | | |3 VT + 3 VT + 1 CT 0.2A + 1 CT 0.2A 31 | | | | |3 CT + 3 CT + 1 CT 0.2A + 1 VT 33 | | | | |3 CT + 3 VY + 1 CT + 1 VT 36 | | | | |3 CT + 3 VT + 1 CT 0.2A + 1 CT 0.2A 39 | | | | |

13

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

Recommendations for wiring:

When selecting miniature circuit breakers for powering REF542plus, it is recommended to have separate circuits for the main unit and the HMI supply:

Table 1.3 Main unit supply

Voltage level Inom of MCB Ratio MCB recom. type

110 VDC 6 8-10 S202-K6220 VDC 4 8-10 S282-UC-K4

3 CT + 3 VT + 1 VT + 1 VT 40 | | | | |3 CT + 3 CT + 1 CT + 1 CT 41 | | | | |3 CT + 3 CT + 1 CT + 1 VT 42 | | | | |3 CT + 3 VT + 1 CT + 1 CT 43 | | | | |

| | | | |Communication - X (DNV) | | | | |None N | | | |MOD-BUS RTU / SPAbus RS485 1 | | | |MOD-BUS RTU / SPAbus Fiber Optic 2 | | | |SPABUS Plastic Fiber version 3 | | | |SPABUS Glass Fiber with SMA connectors 4 | | | |SPABUS Glass Fiber with ST connectors 5 | | | |

| | | |Housing | | | |Normal S | | |Wide W | | |

| | |RHMI - X (ANSI / IEC) | | |HMI V5 - IEC, auxiliary voltage (48...110V) A | |HMI V5 - IEC, auxiliary voltage (110...220V) B | |No HMI N | |

| |Cable | |No cable N |HMI cable - 1.8 m 1 |HMI cable - 2.5 m 2 |HMI cable - 3.5 m 3 |HMI cable - 4.5 m 4 |

|SwLicence |Basic Low 3Basic 4Multi Low 5Multi 6Differential 7Distance 8

Table 1.2 Code definition table (Continued)

REF 542plus 7

14

1MRS756405 Application Recommendations

Application and Setting Guide

REF 542plus

Table 1.4 Power supply range and power unit characteristicsRated voltage 110 VDC (-30%, +10%)

220 VDC (-30%, +10%) or48 to 220 VDC (-15%, +10%)

Power consumption 20 W (Typical, 2 BIOSs) Inrush current Module 759 168: 10 A, 1 ms; 35 A, 100 ms

Module 750 126: 8.3 A, 4 ms; 21 A 100 msAdmissible ripple Less than 10%

15

1MRS756405Application Recommendations

Application and Setting Guide

REF 542plus

10 14 18

multiples of rated current

Seco

nds

Min

utes

1 1.5 2 3 4 5 6 8 10 15 20 30

0.01

0.02

0.040.06

0.1

0.2

0.40.6

1

2

46

10

20

401

2

46

10

20

4060

120

1.05

1.2

Z K

Table 1.5 HMIRated voltage 48 ... 110 VDC (-15%, +10%)

110 ... 220 VDC (-15%, +10%)Power consumption 6 WAdmissible ripple Less than 10%

The HMI is recommended to be powered from the signaling circuits of the switchgear.

Separate galvanic binary input and output circuits from the signaling circuits and the power supply.

16

ADP.FFTeFw

1MR

S75

6405

EN

08.

2008

BB Oyistribution Automation O. Box 699 I-65101 Vaasa INLANDl. +358 10 22 11

ax. +358 10 224 1094ww.abb.com/substationautomation