APPENDIX A – ROOM DATA SHEETS - USM...APPENDIX A – ROOM DATA SHEETS Armed Forces Retirement Home...
Transcript of APPENDIX A – ROOM DATA SHEETS - USM...APPENDIX A – ROOM DATA SHEETS Armed Forces Retirement Home...
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
APPENDIX A – ROOM DATA SHEETS
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
BASE CONTRACT
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 101
Room Name Entry
Net Area 100
Quantity 1
Adjacency Locate along public corridor.Adjacent to Secretary.Shared with Business Office.
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Includes Seating Area for 4.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 102
Room Name Secretary
Net Area 100
Quantity 1
Adjacency Entry, Director's Office, Marketing Public Affairs Office, Director's Meeting Room, and Work/Copy Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation with 2 visitor chairs.Provide observation window.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 103
Room Name Director's Office
Net Area 224
Quantity 1
Adjacency Secretary, Director's Meeting Room
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Executive desk and credenza with 2 visitor chairs.Conference table for 4 with storage unit.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 104
Room Name Deputy Director's Office
Net Area 168
Quantity 1
Adjacency Director's Office, Director's Meeting Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference table for 2 and storage unit.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 105
Room Name Director's Meeting Room / EOC
Net Area 600
Quantity 1
Adjacency Director's Office, Secretary, Entry,Work / Copy Room
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Wood
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework Wood Base & SOlid Surface Top
Equipment AV System.Include ceiling-mounted projector, motorized projection screen, and wall-mounted whiteboard.
Arch Notes Conference room also serves as Emergency Operations Center (EOC).Include board table and seating for 12.Room shall have direct access from corridor and Director's office.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include teleconferencing capacity.Provide multiple telephone and data outlets for use as EOC, including CCTV monitoring station.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide standby power to allow space to be used as Emergency Operations Center.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 106
Room Name Marketing Public Affairs Off.
Net Area 200
Quantity 1
Adjacency Secretary, Director's Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs, andconference table.Room for "fireside chats."
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include channel 99 equipment (approximately 3' square - flat screen TV)
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 107
Room Name Agency / Multi-Use Office
Net Area 120
Quantity 1
Adjacency Secretary, Entry.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 108
Room Name Staff Break Area / Work / Copy Room
Net Area 225
Quantity 1
Adjacency Locate on Internal corridor adjacent to Director's Meeting Room, Secretary.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Copiers, fax machines, and printers.Full-size refrigerator.
Arch Notes Storage cabinets and work counters.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Provide additional voice / data lines (copiers, fax machines).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 109
Room Name Safety Officer
Net Area 120
Quantity 1
Adjacency Administrative Officer and Deputy Director's Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Executive Desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 110
Room Name Administrative Officer
Net Area 120
Quantity 1
Adjacency Safety Officer and Deputy Director's Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 111
Room Name Master Chief / Ombudsman
Net Area 120
Quantity 1
Adjacency Director's Office, Secretary
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 112
Room Name Staff Men's Toilet
Net Area 70
Quantity 1
Adjacency Entry and Secretary.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide one ADA accessible sink and toilet in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 113
Room Name Staff Women's Toilet
Net Area 70
Quantity 1
Adjacency Entry and Secretary.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide one ADA accessible sink and toilet in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 114
Room Name IT Employee / Contractor Office
Net Area 240
Quantity 1
Adjacency Locate on public corridor.Adjacent to IT Training Room and IT Server Room.Locate near Business Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes 2 workstation cubicles and 1 workbench.Contain one employee, one contractor, and one open workstation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 115
Room Name IT Training Room
Net Area 400
Quantity 1
Adjacency Locate along public corridor.Adjacent to IT Office, IT Secure Storage, and IT Server Room.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment AV System.Include ceiling-mounted projector, motorized projection screen, and wall-mounted whiteboard.
Arch Notes Tables and seating for 12 students and 1 instructor with storage unit.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 116
Room Name IT Secure Storage
Net Area 100
Quantity 1
Adjacency IT Training Room
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 117
Room Name IT Server Room
Net Area 300
Quantity 1
Adjacency IT Employee / Contractor Office and IT Training Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Computer Servers and related equipment.PBX and main telephone switch.
Arch Notes Raised flooring throughout.Dedicated HVAC service.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 72 Deg (F)
% R Humidity (Winter) 45%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
LAN Fiber / CAT MDF.Provide additional voice and data capacity.
Sprinkler FM 200
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide UPS System with 4-hour battery backup to support IT equipment.Provide standby power for 4-hour IT equipment.Provide standby power for HVAC service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 118
Room Name IT Distribution Closets
Net Area 25
Quantity 19
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Protect in cabinet Data Switch.
Arch Notes Lockable cabinets for telephone, data, and cable TV.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 119
Room Name Business Office Chief
Net Area 120
Quantity 1
Adjacency Director Gulfport Entry
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 120
Room Name Business Offices
Net Area 100
Quantity 3
Adjacency Business Office Chief
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 201
Room Name Chief of Campus Operations
Net Area 200
Quantity 1
Adjacency Campus Operations Office Assistant.Contract Surv. Specialists.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference table for 4 with storage unit.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 202
Room Name Campus Operations Office Assistant
Net Area 80
Quantity 1
Adjacency Locate along public corridor.Adjacent to Chief of Campus Operations.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Functions as Chief of Campus Operations' Reception
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 203
Room Name Facilities Maintenance Supervisor
Net Area 120
Quantity 1
Adjacency FM Contractor Shop and Chief of Campus Operations
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 204
Room Name Engineering Technician
Net Area 100
Quantity 1
Adjacency Chief of Campus Ops.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard Desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 205
Room Name Contract Surv. Specialists
Net Area 80
Quantity 3
Adjacency FM Supervisor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstations.Locate in same room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 206
Room Name Contractor Supervisor
Net Area 120
Quantity 1
Adjacency FM Contractor Shop
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 207
Room Name Service Desk
Net Area 80
Quantity 1
Adjacency Locate along public corridor.Adjacent to Contractor Supervisor and FM Contractor Shop.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Reception Desk
Equipment
Arch Notes Secretarial workstation with 2 visitor chairs.Function as reception for FM Contractor Shop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 208
Room Name FM Contractor Shop
Net Area 4000
Quantity 1
Adjacency Locate along public corridor.Adjacent to Service Desk.Easy access to Loading Dock & Service Elevators.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Equipment and casework provided by contractor.
Arch Notes Includes room for 8 workstations, and a separate shop area with "attic stock" storage.Similar to NAVFAC P-80 Standard.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Utility sink (wall-mounted).
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Provide additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 209
Room Name Maintenance Work Area
Net Area 2000
Quantity 1
Adjacency FM Contractor Shop
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes Maintenance area for long-term projects.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 210
Room Name Building Supply
Net Area 400
Quantity 1
Adjacency Maintenance Work Area
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes Includes space for storage of building materials.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 211
Room Name Active Repair
Net Area 500
Quantity 1
Adjacency Maintenance Work Area
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Equipment and casework provided by contractor.
Arch Notes Repair equipment.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 212
Room Name HVAC Crew
Net Area 500
Quantity 1
Adjacency Maintenance Work Station
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Equipment and casework provided by contractor.
Arch Notes Fume hood for welding / soldering.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 213
Room Name Logistics Supervisor
Net Area 120
Quantity 1
Adjacency Near Chief of Campus Operations.Easy access to Loading Dock.Adjacent to Transportation Specialist and close to Supply Area.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 214
Room Name Transportation Specialist
Net Area 80
Quantity 1
Adjacency Near Chief of Campus Operations and Close to Logistics Supervisor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Locate in same room as Supply Workstation.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 215
Room Name Supply Workstation
Net Area 80
Quantity 1
Adjacency Locate along public corridor.Adjacent to Resident Bulk StorageEasy access to Logistics Supervisor and Housekeeping.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Locate in same room as Transportation Specialist.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 216
Room Name Resident Bulk Storage
Net Area 6300
Quantity 1
Adjacency Locate along public corridor.Adjacent to other storage rooms.Easy access to Loading Dock andService Elevators.Near Supply Workstation.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Wire cage partition with lockable doors - 2 layers. Allow 12 SF per resident.
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 217
Room Name COOP Storage
Net Area 1600
Quantity 1
Adjacency Resident Bulk Storage
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment "Continuity of Operations" Storage for Emergency Response.
Arch Notes If combined with Resident Bulk Storage, provide wire cage partitions with lockable door.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 218
Room Name Furniture Storage
Net Area 400
Quantity 1
Adjacency Resident Bulk Storage
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes If combined with Resident Bulk Storage, provide wire cage partitions with lockable door.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 219
Room Name Mattress Storage
Net Area 400
Quantity 1
Adjacency Resident Bulk Storage
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes If combined with Resident Bulk Storage, provide wire cage partitions with lockable door.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 220
Room Name E-Tank Storage Room
Net Area 120
Quantity 1
Adjacency Resident Bulk Storage
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes If combined with Resident Bulk Storage, provide wire cage partitions with lockable door.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 221
Room Name Medical Records Storage
Net Area 500
Quantity 1
Adjacency Resident Bulk Storage
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes If combined with Resident Bulk Storage, provide wire cage partitions with lockable door.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 222
Room Name Laundry Distribution Room
Net Area 120
Quantity 1
Adjacency Locate along a public corridor.Adjacent to Laundry Clean Room and Laundry Dirty Room.Easy Access to Loading Dock.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Include a hand sanitation station.
Arch Notes Pass-through window from Distribution Room to public corridor.Provide a door to Clean / Dirty Rooms.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 223
Room Name Laundry Dirty Room
Net Area 400
Quantity 1
Adjacency Laundry Clean Room and Laundry Distribution Room.Easy Access to Loading Dock andService Elevators.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Storage containers provided by contractor.
Arch Notes Pass-through window from Dirty Room to Distribution Room.Provide a convenient door to Loading Dock.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 224
Room Name Laundry Clean Room
Net Area 600
Quantity 1
Adjacency Laundry Distribution Room and Laundry Dirty Room.Easy access to Loading Dock andService Elevators.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Shelving for clean laundry provided by contractor.
Arch Notes Provide door from Clean Room to Distribution Room.Provide 2 convenient doors to Loading Dock.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 225
Room Name Decedent Storage
Net Area 500
Quantity 1
Adjacency Resident Bulk Storage
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes If combined with Resident Bulk Storage, provide wire cage partitions with lockable door.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 226
Room Name Main Trash Rooms (1 per 150 units)
Net Area 300
Quantity 3
Adjacency Trash Chutes (from above).Easy access to Loading Dock.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Trash compactor and trash chute with fire-rated doorsat each level.Include smoke detectors in chute.
Arch Notes 1 Trash Room per 150 Units.The DBC shall describe how trash removal is addressed.May be located at First Floor or Wash-Out Level.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Self-cleaning trash chute will require water supply and drain.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 227
Room Name Trash Room (Includes all Living Units)
Net Area 50
Quantity 19
Adjacency Elevators, Janitor Closet, and Laundry Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Self-cleaning trash chute with fire-rated doors.Recycling bins provided by Housekeeping Contractor.
Arch Notes 1 trash room per 24 residents ( Independent Living).1 trash room per 30 residents (Assisted Living).1 trash room per 12 residents (Memory Support and Long Term Care).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 228
Room Name Main Recycling Room
Net Area 250
Quantity 1
Adjacency Easy Access to Loading Dock.Adjacent to Trash Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Recycling containers provided by contractor.
Arch Notes Once-a-week service.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 229
Room Name Medical Waste Holding Room
Net Area 100
Quantity 1
Adjacency Easy Access to Loading Dock.Adjacent to Trash Room and Main Recycling Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Secure containers provided by contractor.
Arch Notes 90-day storage facility.For medical waste disposal.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 230
Room Name Loading Area
Net Area 0
Quantity
Adjacency Locate along service corridor.Adjacent to Kitchen, Trash Room(s), and other service and storage areas.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type OHD
Wall Construction CMU
Casework
Equipment Trash compactor in one dedicated loading space.Dock levelers at other loading spaces.Include space for 30 cubic yard dumpster, screened from view, separated from loading dock (could be in
Arch Notes 4 spaces including trash compactor, food delivery, recycling, and typical deliveries.Prefer recessed location, not enclosed, at Main Floor Level.Provide direct connection from Loading Dock to Kitchen (separate from other delivery paths).
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include motion detectors.
Sprinkler Dry Pipe System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 231
Room Name Building Engineer's Office
Net Area 120
Quantity 1
Adjacency Mechanical / Electrical Room
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Metal SGL w/Side Lite
Wall Construction CMU w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Include observation window.Provide acoustical treatment. Provide one door to corridor and one door for Mechanical / Electrical room
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 232
Room Name Engineer's Toilet
Net Area 70
Quantity 1
Adjacency Building Engineer's Office
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 233
Room Name Mechanical / Electrical Room
Net Area 5000
Quantity 1
Adjacency Locate as required.Provide exterior access for maintenance.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Mechanical and Electrical equipment (see separate description).Emergency Generator with 7-day fuel supply (safety items and emergency items).
Arch Notes 7-day survivability is required.Category 5 Hurricane requirements will influence location and layout of mech/elec equipment.2 independent electrical feeders shall be provided for redundant power.Emergency Generators are required.
Temp F (Winter) 50 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide access to building exterior for removal and replacement of major equipment components.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide multiple floor drains.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 301
Room Name Resident Services Chief
Net Area 224
Quantity 1
Adjacency Director's Office Entry and Admissions Officer.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference table for 4 with storage unit.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 302
Room Name Main Lobby / Seating
Net Area 500
Quantity 1
Adjacency Located within Hall of Honor.
Floor Finish Stone
Wall Finish Paint & FWC
Base Stone
Ceiling Finish Painted GWB
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Includes Seating Area for approximately 20 people.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Multiple room uses.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 303
Room Name Reception Room
Net Area 800
Quantity 1
Adjacency Hall of Honor, Security Services, Main Entrance, and Concierge.
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Memorabilia display area (floor and wall units).
Arch Notes Formal Parlor, always ready for formal events.Contains seating groups for 20 people and a grand piano.Provide separate entrance from exterior.Memorabilia displays included items from past, present, and future conflicts and AFRH history.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide lighting for multiple room uses.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 304
Room Name Concierge
Net Area 144
Quantity 1
Adjacency Locate in Main Lobby / Seating Area.
Floor Finish Stone
Wall Finish Paint & FWC
Base Stone
Ceiling Finish Painted GWB
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Home-Style desk manned by volunteers with 2 visitor chairs with lockable storage.Assembly point for transportation scheduling.Collect flowers, dry cleaning deliveries, etc.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 305
Room Name News & Vending
Net Area 150
Quantity 1
Adjacency Hall of Honor and Main Entrance.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment Vending machines and news paper boxes.Provide by outside vendor microwave and ice machine.
Arch Notes Provide countertop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Drain, water, and power required for vending machines.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 306
Room Name Hall of Honor
Net Area 2500
Quantity 1
Adjacency Main Entrance, Reception Room, Concierge, News & Vending, and Main Street.
Floor Finish TBD
Wall Finish TBD
Base TBD
Ceiling Finish TBD
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment Memorabilia display area (floor and wall units).Provide shelf space.Refer to Allowance 3.
Arch Notes Two-story exhibit space with overlook from above.Seating for 20 people.Recessed display cases and wall exhibits (TBD).Intended to display military memorabilia, including flags, uniforms, plaques, medals, photos, and other display materials.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide dedicated panel, and sufficient electrical lighting.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide special lighting for museum-quality display. Provide display lighting for wall-mounted exhibits. Consider UV effects on exhibits.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 307
Room Name Admissions Officer
Net Area 200
Quantity 1
Adjacency Adjacent to Move-In / Admissions Assistant and Resident Services Chief.Easy access to Director's MeetingRoom.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference table with 4 chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 308
Room Name Move-In / Admissions Assistant
Net Area 120
Quantity 1
Adjacency Locate along public corridor.Adjacent to Director of Admissions and Resident Records / Information Receptionist.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 309
Room Name Resident Records / Information Receptionist
Net Area 300
Quantity 1
Adjacency Move-In Admissions Assistant
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment "LEKTRIEVER" system.
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 310
Room Name Admissions Social Worker
Net Area 120
Quantity 1
Adjacency Move-In / Admissions Assistant
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 311
Room Name Admissions Itinerant Office
Net Area 120
Quantity 2
Adjacency Move-In / Admissions Assistant and Resident Records / Information Receptionist.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Work table with lockable storage and 4 chairs.Moving in residents' families.Receiving people.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 312
Room Name Admissions Work / Copy Alcove
Net Area 80
Quantity 1
Adjacency Resident Records / Information Receptionist
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard workstation with files.Locate in open area
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 313
Room Name Shared Work / Copy Room
Net Area 160
Quantity 1
Adjacency Locate along public corridor.Adjacent to Post Office and Bank.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment "All-in-one" copy-fax machines (networked).Lockable storage units.
Arch Notes Shared among staff and residents.24-hour access for Residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide additional telephone and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 314
Room Name Mail Room / Post Office
Net Area 950
Quantity 1
Adjacency Along public corridor.Adjacent to Shared Work / Copy Room and Bank.Easy access to Loading Dock.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Equipment ADA accessible and casework for full postal operations, including mailboxes.Follow USPS standards.
Arch Notes Manned by Contractor.Include area for USPS vending machines.24-hour access to post office boxes and vending.Include counter with roll-up door for USPS operator.Package drawer below with key."Knees-to-eyebrows" for mailboxes.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide special access control per USPS requirements.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 315
Room Name Bank
Net Area 400
Quantity 1
Adjacency Locate along public corridor.Adjacent to Shared Work / Copy Room and Post Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Equipment and casework provided by Bank Tenant.
Arch Notes Manned by Bank Tenant.2 tellers plus office.ATM located outside the bank. Accessible after hours.The DBC will coordinate installation with Bank Tenant
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Run empty conduit from main telephone room for independent voice and data access.CCTV camera to be located for view of door to Bank.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 316
Room Name Security Counter / Eqpt. Room
Net Area 285
Quantity 1
Adjacency Locate at Main Entrance.Adjacent to Security Office and Interview Room.
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Security Desk
Equipment Monitors, panels, and CCTV equipment.Include Resident Monitoring System.
Arch Notes Subdivide into 2 rooms with glass partitions.Dedicated HVAC service with UPS system.Work station for 2 behind counter.Include recessed emergency medical cabinet (wired to security).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide additional voice and data capacity.Include Resident Monitoring System.Include AED (electronically monitored by security).
Sprinkler FM 200
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power system as required by users and to support security equipment.Provide UPS system with 4-hour battery backup to support security equipment.Provide standby power for HVAC service
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 317
Room Name Security Office
Net Area 170
Quantity 1
Adjacency Security Counter / Equipment Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Wall mounting monitor display system with Flat screens TVs, monitors, and recording devices.No drawers on the base of manning system.
Arch Notes Accommodate "L" shaped furniture arrangements. Standard workstation with 4 chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 318
Room Name Interview Room
Net Area 120
Quantity 1
Adjacency Security Office and Security Counter / Equipment Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Work table with lockable storage and 4 chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 319
Room Name Housekeeping Contractor's Office
Net Area 120
Quantity 1
Adjacency Supply and Contractor / EmployeeBreak Area.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 320
Room Name Janitor's Closet (On Main Level)
Net Area 30
Quantity 2
Adjacency Locate along public corridor.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction CMU
Casework
Equipment Mop sink and rack.
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Mop sink.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 321
Room Name Janitor's Cart Storage (On Main Level)
Net Area 100
Quantity 2
Adjacency Locate near Service Elevators.Adjacent to Janitor's Closet.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction CMU
Casework
Equipment 4 Carts 3' x 4' in each room.
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 322
Room Name Janitor's Closet (On Residential Units Levels)
Net Area 30
Quantity 19
Adjacency Trash Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction CMU
Casework Security Desk
Equipment Mop sink and rack.
Arch Notes Provide at least one Janitor's Closet per floor.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 323
Room Name Contractor / Employee Break Area
Net Area 500
Quantity 1
Adjacency Locate along public corridor.Adjacent to Housekeeping Contractor's Office
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Kitchenette equipment, including refrigerator.Employee lockers.
Arch Notes Provide separate Men's and Women's Locker Areas leading to Staff Toilets.Provide full kitchenette and tables with seating for 12.Provide half-height lockers for 24 in each locker area.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Do not locate CCTV cameras in Locker Areas.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 324
Room Name Contractor / Employee Toilets
Net Area 600
Quantity 1
Adjacency Contractor / Employee Break Room
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.Provide 3 water closets (or equivalent) and 2 lavatories in each room.
Arch Notes Provide Men's and Women's Toilet Rooms.Provide 2 accessible showers in each Toilet Room.Provide automatic door openers.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 325
Room Name Public Toilet Rooms (On Main Level)
Net Area 3200
Quantity 1
Adjacency Locate along public corridor near major program areas.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Provide complete stainless steel toilet accessories.Provide at least 32 accessible water closets and 16accessible lavatories.Provide automatic door openers at all Toilet Rooms
Arch Notes Provide Men's and Women's Toilet Rooms.Distribute throughout Mail Level , so that all entrances, exits, and gathering places are no more than 80 ft. from a public toilet room.Toilet rooms shall be ADA-UFAS compliant and accommodate BPV's.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 326
Room Name Ham Radio / Electronic Repair / Computer Shop
Net Area 400
Quantity 1
Adjacency Locate near Main Street.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Refer to Appendix C - Ham Radio Shop Information.Provide portable antennas and "Man-Pack" radios.
Arch Notes 4 computer workstations with seating and storage units.See Appendix C for more information about antenna requirements.Provide portable antennas and man pack radios to re-establish communication if fixed antennas fail.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to accommodate Ham Radios that can connect to theFederal communication system in an emergency.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide minimal lighting on standby power to allow room to be used in an emergency.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 327
Room Name Wood Shop
Net Area 1500
Quantity 1
Adjacency Locate near Main Street.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Woodworking benches with stools and storage units.Woodworking equipment to be determined.Include lighting for equipment.Flammable storage cabinet / locker.
Arch Notes Provide special ventilation and acoustical treatment.Include Service desk.Subdivide into small "Amateur " shop (300 - 400 SF with hand tools and benches) and larger "Power Tool"shop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide exhaust system for collection and removal of saw dust.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Address power equipment for woodworking equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 328
Room Name Wood Shop Storage
Net Area 300
Quantity 1
Adjacency Wood Shop
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 329
Room Name Wood Shop Office
Net Area 120
Quantity 1
Adjacency Wood Shop
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Provide observation window into Wood Shop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 330
Room Name Wood Shop Paint Room
Net Area 150
Quantity 1
Adjacency Wood Shop and Wood Shop Office.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Wood DBL
Wall Construction CMU
Casework
Equipment
Arch Notes Special ventilation requirements.Provide lockable closet for storage of flammable materials.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide dedicated, locally operated exhaust hood system.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 331
Room Name Vending
Net Area 150
Quantity 1
Adjacency Locate along public corridor.Adjacent to Shops and Fitness Center.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Vending machines provided by Contractor.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 332
Room Name Bike Shop
Net Area 225
Quantity 1
Adjacency Locate near Main Street.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Wood DBL w/Side Lite
Wall Construction CMU w/GWB
Casework
Equipment
Arch Notes Provide work benches and stools for 4 stations.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 333
Room Name Bike Storage
Net Area 540
Quantity 1
Adjacency Locate on "Wash-Out" Level.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes Provide blocking for wall-mounted racks.Include floor striping and numbering for 60 oversized 3-wheeled bikes.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 334
Room Name Fitness Equipment Area
Net Area 2500
Quantity 1
Adjacency Locate near Main Street and Vending.Adjacent to Exercise Classroom and Fitness Storage.
Floor Finish Anti Microbial Carpet
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Fitness equipment as required.Refer to Appendix C for a list of Recommended Equipment.Include recessed emergency medical cabinet (wired
Arch Notes Provide special ventilation and acoustical treatment.Rubber floor under major equipment.Provide wall mirrors and balanced bars.Refer to Appendix C for equipment list.Water fountain should be included.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Include drinking fountain.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Multiple TV outlets.Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide floor outlets for fitness equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 335
Room Name Fitness Center Office
Net Area 120
Quantity 1
Adjacency Fitness Center, Equipment Area, and Exercise Classroom, and Fitness Storage.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Include observation window.Standard desk and credenza with 2 visitors chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 336
Room Name M & W Shower / Locker Rooms
Net Area 230
Quantity 2
Adjacency Fitness Equipment Room.
Floor Finish Rubber
Wall Finish Sanitary Wainscot
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes No-wall shower (floor drain and rubber walls).Include 20 half-height lockers (no metal), benches, 4 showers (2 showers / gender), toilet, and sink. Showers and toilets should be separate from locker rooms. Showers to include a separate dressing area.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Emergency phone
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 337
Room Name Assisted Unisex Bathroom
Net Area 160
Quantity 1
Adjacency Fitness Center M & W Shower / Locker Room.
Floor Finish Seamless Vinyl
Wall Finish Sanitary Wainscot
Base Integral Coved Base
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Accessible bathroom with sink, toilet, and safety tub (similar to Bathease).
Arch Notes Discreet entrance for private access.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide toilet exhaust in accordance with Code.
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 338
Room Name Exercise Classroom
Net Area 2000
Quantity 1
Adjacency Fitness Equipment Area and Fitness Storage.Near Vending Area.
Floor Finish Sprung Wood
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Exercise Floors Mats.
Arch Notes Low-impact exercises are typical. Provide movable partition to sub-divide classroom.Provide special ventilation and acoustical treatment.Include wall mirrors and balance bars.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phones and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 339
Room Name Fitness / Recreation Storage
Net Area 500
Quantity 1
Adjacency Fitness Equipment and Exercise Classroom.Easy access to Loading Dock.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish No Ceiling
Door Type Wood DBL
Wall Construction CMU
Casework
Equipment Industrial metal shelving.
Arch Notes Exterior access preferred.Wire partitions multiple-compartment lockable storage.Include 60 - 80 SF alcohol storage -- locked with cardaccess Key (out of sight).
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 340
Room Name Multi-Purpose Activity Room
Net Area 3400
Quantity 1
Adjacency Located near Main Street.Adjacent to Dining Room.Near Prefunction, Outside Patio, and Exercise Classroom.
Floor Finish Marble Floor
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide moveable partition between Multi-Purp Activity Room and Dining Room for expansion during major events w/soundproofing.Provide storage for tables, chairs, etc.
Arch Notes Hi-ceiling, square shape, column-free space with flat floor.Provide movable partition to sub-divide room into 2 spaces.Provide special ventilation and acoustical treatment,Small raised stage with ramp.Provide dance floor (size TBD)
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include movie projection system and adequate microphone equipment.Include emergency phone and AED (electronically monitored by security).Include recessed emergency medical cabinet (wired to security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow room to be used in an emergency.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide lighting on standby power to allow room to be used in an emergency.Provide special theatrical lighting for stage area.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 341
Room Name Lounge
Net Area 1800
Quantity 1
Adjacency Locate along Main Street.Adjacent to Smokehouse / BBQ Equipment Storage , Outside Patio, Bowling, Multi-Purpose Activity Room and Dining Room.
Floor Finish Wood
Wall Finish Paint & FWC
Base Wood
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Bar equipment as required.Common kitchen and hood ventilation for grilling.Include recessed emergency medical cabinet (wired to security).
Arch Notes Provide bar tables and seating for 25 people.Provide special ventilation and acoustical treatment.Floor finish should be different at bar area.Include anti-fatigue mats behind bar.Include storage area as required.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Floor Drain and sink placed at bar service area.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 342
Room Name Smokehouse / BBQ Equipment Storage
Net Area 150
Quantity 1
Adjacency Locate near Lounge, Game Room and Bowling.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Include recessed emergency medical cabinet (wired to security).Provide pass-through window from the bar.Not directly attached to building.
Arch Notes Provide tables and seating for 12.Provide separate special ventilation and acoustical treatment.Available for staff and residents.Glass walls and ceiling fan (greenhouse type, outdoorfeeling).Provide fireplace.Exterior access desired.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide confinement ventilation system with 100% exhaust of space.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 343
Room Name Game Room
Net Area 1100
Quantity 1
Adjacency Locate near Main Street.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Pool table and card tables.Lockable storage units.Table-top shuffle board.
Arch Notes Provide tables and seating for 24.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 344
Room Name Meditation Room
Net Area 600
Quantity 1
Adjacency Locate in quiet area near Main Street.
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment 8 pews for 30 to 40 people.Lectern with microphone.
Arch Notes Provide special ventilation and acoustical treatment.Inter-faith services.Multi-purpose room for group settings.Quiet room.Provide "Open-Flame" vitrine.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 345
Room Name Recreation Activities Supervisor
Net Area 120
Quantity 1
Adjacency Locate near Main Street and recreational areas.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 346
Room Name Program Office
Net Area 100
Quantity 4
Adjacency Locate off public corridor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk with 2 visitor chairs.Function as reception for recreation spaces.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 347
Room Name Recreation Therapy Supervisor
Net Area 120
Quantity 1
Adjacency Near to Therapy offices.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitors chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 348
Room Name Recreation Therapy Workstations
Net Area 100
Quantity 2
Adjacency Therapeutic Recreational Supervisor, AL, MS, and L-TC Units.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Workstations
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 349
Room Name Indoor Shuffle Board / Bocce Ball Court
Net Area 2160
Quantity 1
Adjacency Located near Main Street.Optional location in "Wash-Out" Level.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL w/Side Lite
Wall Construction CMU w/GWB
Casework
Equipment Shuffle Board equipment as required.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 350
Room Name Resident Computer Lab
Net Area 600
Quantity 1
Adjacency Locate near Main Street.Adjacent to Electronic Repair Room, Listening Room / Multi-Functional, 24-Hour Resident Training Room, and Library.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment Computers.
Arch Notes Computer workstations and seating for 8.Teaching classroom.Alternate EOC location.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 351
Room Name 24 Hour Internet and Game Room
Net Area 720
Quantity 1
Adjacency Locate near Main Street.Adjacent to Resident Computer Lab and Electronic Repair Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Computer workstations and seating for 16.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 352
Room Name Listening / Multi-Function Room
Net Area 225
Quantity 1
Adjacency Resident Computer Lab and 24-Hour Resident Training Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment TV's, DVD's, and music equipment.
Arch Notes "Softest" room in building.Provide acoustical treatment.Should accommodate up to 6 people.Library-type storage.Piano - record music.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 353
Room Name Emergency Supply Alcove
Net Area 110
Quantity 1
Adjacency Locate near Multi-Purpose ActivityRoom and Dining Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Open storage area for crash cart.Cart with tanks.Mouth-to-Mouth resuscitation equipment.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 354
Room Name Bowling
Net Area 2750
Quantity 1
Adjacency Lounge, Smokehouse / BBQ Equipment Storage and Game Room.Near Vending.
Floor Finish Wood
Wall Finish Paint
Base Wood
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Bowling equipment as required.
Arch Notes 4 lanes.End lane should be accessible for mobility impaired.Fully automatic system and scoring.This space should be isolated for sound control.Special humidity control.Include unisex accessible toilet room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 355
Room Name Thrift Shop
Net Area 400
Quantity 1
Adjacency Locate on "Wash-Out" Level.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes Storage and display of resident items sold on a monthly basis ("garage sale").
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 356
Room Name Hair Care / Salon
Net Area 260
Quantity 1
Adjacency Locate along Main Street.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Hair Care Salon equipment provided by operator.Include 4 stations.
Arch Notes Space should be divided as follows: 240 SF for 4 stations and 20 SF for locked storage and shelving.Include handwashing station.Include hair washing station.Provide wall mirrors.Provide special ventilation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide sufficient power for hair dryers and equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 357
Room Name Library + DVD Room
Net Area 2000
Quantity 1
Adjacency Locate along Main Street.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Main Desk
Arch Notes Provide library shelving for books.Tables and seating for 20 to 30.Provide small storage room (lockable) with shelving (10' x 10').
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide additional lighting in reading areas.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 358
Room Name Exchange PX
Net Area 2000
Quantity 1
Adjacency Locate along Main Street.Easy access to Loading Dock.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Store fixtures to be provided by tenant (AAFES).
Arch Notes Small grocery store.Provide separate electric meter.Includes rear lockable storage room (size TBD).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide empty conduit from main switch room for independent voice and data access.CCTV camera to be located for view of door to Exchange PX.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Additional power for tenant equipment.Refrigerator on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 359
Room Name Multi-Function Media Room
Net Area 1000
Quantity 1
Adjacency Locate along Main Street and Lounge.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Projector, projection screen, and AV systems.
Arch Notes Provide offset theater-style seating for up to 100 people to watch movies, etc.Provide special ventilation and acoustical treatment.Wall treatment with wheelchair protection.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Floor drain and sink placed at bar service area.
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide additional power for AV equipment as required.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 360
Room Name Spiro's Canteen
Net Area 700
Quantity 1
Adjacency Locate along Main Street.
Floor Finish VCT
Wall Finish Sanitary Wainscott
Base Integral Coved Base"
Ceiling Finish 2 x 4 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Base & Solid Surface Top
Equipment Provided by vendor.
Arch Notes Provide 6 tables and seating for 20 to 25 people.Provide special ventilation and acoustical treatment.Self-service café.Open area.Late night operation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Handwashing sink placed on countertop.Drain and water supply to beverage dispensing equipment (approx. 4 machines).
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Provide additional power for beverage dispensing machines.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 361
Room Name Painting and Ceramics (Wet)
Net Area 600
Quantity 1
Adjacency Locate along Main Street.Adjacent to Crafts (Dry), Sewing Room, and Resident Art Display Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Arts equipment as required.Provide separate room for kilns. (100 SF). Locate with special exhaust ventilation.Include 2 - 3 stations with hoods for localized table-
Arch Notes Provide a door to open directly to Crafts (Dry).Shelving for storing items.Tables and seating for 12.Provide 2 service sinks and worktop.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide 2 sinks with sano-trap.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide additional power for electric kilns.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 362
Room Name Crafts (Dry)
Net Area 600
Quantity 1
Adjacency Locate along Main Street.Adjacent to Painting and Ceramics (Wet), Sewing Room, and Resident Art Display Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Crafts equipment as required.
Arch Notes Provide a door to open directly to Arts (Wet).Shelving for storing items.Tables and seating for 20.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 363
Room Name Sewing Room
Net Area 600
Quantity 1
Adjacency Locate along Main Street.Adjacent to Painting and Ceramics (Wet), Crafts (Dry), and Resident Art Display Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood DBL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Wood Base & Solid Surface Top
Equipment Sewing equipment as required.
Arch Notes Tables and seating for 12 with storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 364
Room Name Puzzle Room
Net Area 180
Quantity 1
Adjacency Assisted Living
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Tables and seating for 12 with storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 365
Room Name Resident Art Display Room
Net Area 500
Quantity 1
Adjacency Locate along Main Street.Adjacent to Painting and Ceramics (Wet), Crafts (Dry), and Sewing Room.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide floor and wall display cases (lockable and accessible).
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 366
Room Name Volunteer Coordinator Office
Net Area 120
Quantity 1
Adjacency Volunteer Home Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 367
Room Name Volunteer Home Room
Net Area 600
Quantity 1
Adjacency Locate along public corridor.Adjacent to Main Street functions.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Provide tables and seating for 12 with storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 368
Room Name Volunteer Storage
Net Area 400
Quantity 1
Adjacency Volunteer Home Room
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment
Arch Notes Hi-density pallet storage for Holiday decorations, etc.Manual operation "sliding doors."
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 369
Room Name Toilet Rooms
Net Area 400
Quantity 1
Adjacency Near to the Volunteer Home Room.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide Men's and Women's Toilet Rooms.Provide automatic door openers.Provide 3 water closets (or equivalent) and 2 lavatories in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 370
Room Name Contractor Services Representative / Janitorial Servi
Net Area 120
Quantity 1
Adjacency Housekeeping Contractor's Office
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 371
Room Name Dining Services Administrator
Net Area 120
Quantity 1
Adjacency Kitchen and Dining Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 372
Room Name Prefunction
Net Area 1000
Quantity 1
Adjacency Locate along public corridor.Adjacent to Service Line.Easy access to Public Toilets.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment Memorabilia display area (floor and wall units).
Arch Notes Provide seating for "people-watching".Open area.20 - 30 seats.Memorabilia displays included items from past, present, and future conflicts and AFRH history.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide lighting to allow for multiple room uses.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 373
Room Name Dining and Assisted Dining
Net Area 7700
Quantity 1
Adjacency Prefunction, Kitchen, Multi-Purpose Activity Room, Outside Patio, and Public Toilets.
Floor Finish VCT
Wall Finish Wainscott"
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Provide moveable partition between Dining Room and Multi-Purpose Activity Room for expansion during major events.Dining equipment as required.
Arch Notes Provide separate Assisted Dining Area with separate entrance and a separate service line.Estimated seating for 275 (28 SF / person). NO ROUND TABLES.Provide variety of seating (individuals, doubles, and groups of 6-12) with adjustable table heights.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).Include recessed emergency medical cabinet (wired to security).Provide AV System for major events.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide minimal receptacles on standby power to allow room to be used in an emergency.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Provide l lighting on standby power to allow room to be used in an emergency.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 374
Room Name Service Line
Net Area 2000
Quantity 1
Adjacency Kitchen and Dining.
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Integral Coved Base"
Ceiling Finish Painted GWB
Door Type
Wall Construction CMU w/GWB
Casework
Equipment Stainless steel service line equipment.
Arch Notes "Functionally accessible for older people."Secure sanitized areas from Dining Room for after-hours operation.ADA-Compliant.36-foot overall length (approx.).Half-height anti-fungal durable / washable hard surface.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power to allow for fully functional kitchen service.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 375
Room Name Assisted Dining Service Line
Net Area 300
Quantity 1
Adjacency Assisted Dining
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type
Wall Construction CMU w/GWB
Casework
Equipment Stainless steel service line equipment.
Arch Notes "Functionally accessible for older people."ADA compliant.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching:
Lighting Notes: Provide lighting on standby power to allow for fully functional kitchen service.
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 376
Room Name Kitchen
Net Area 8000
Quantity 1
Adjacency Service Lines and Loading Dock.Provide direct connection to MS Service Line (maybe dedicated elevator) for food delivery and scullery service.
Floor Finish Sheet Vinyl
Wall Finish Sanitary Wainscot
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Kitchen equipment as required - refer to Section K - Dining and Food Service.Refer to Appendix C - List of Existing Kitchen Equipment and Plan of Existing Kitchen.
Arch Notes Includes Offices, Cold Stores, Dry Stores, EmergencyStores, and Staff Lockers.Full-service common kitchen menus - refer to Appendix C for examples.Catering (10-300) up to 1 per week.7-10 day food storage.Serves 1,200 meals per day (3 servings).
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide dedicated kitchen make-up air and exhaust systems sized and configured in accordance with Code.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide hand washing and service sinks as required.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power to allow for fully functional kitchen service.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 377
Room Name Kitchen Staff Men's Toilet
Net Area 300
Quantity 1
Adjacency Kitchen
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide 3 water closets (or equivalent) and 2 lavatories in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 378
Room Name Kitchen Staff Women's Toilet
Net Area 300
Quantity 1
Adjacency Kitchen
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide 3 water closets (or equivalent) and 2 lavatories in each Toilet Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 379
Room Name Independent Living 1 Units
Net Area 450
Quantity 282
Adjacency See Adjacency Diagram for Typical Independent Living Level.
Floor Finish Anti Microbial Carpet
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Wall Base & Solid Surface Top
Equipment Full kitchenette with sink and area for "mini" refrigerator and microwave oven.Include "lock boxes" for valuables (6" x 12" - Type TBD).
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and 1 data connection with 2 data lines.Provide 1 emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide indirect lighting in living area.Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 380
Room Name IL1 Day Room / Lounge
Net Area 250
Quantity 12
Adjacency Elevator Lobby and Resident Corridor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment
Arch Notes 1 unit serves 24 residents.Provide TV, couches and chairs, and 2 card tables with 4 chairs each.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Dry Pipe System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 381
Room Name IL1 Laundry Room
Net Area 100
Quantity 12
Adjacency Elevators, Janitor Closet, and Trash Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stackable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 24 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special oversized floor drain with gooseneck faucet to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 382
Room Name IL1 Public Toilet Rooms (M & W)
Net Area 70
Quantity 24
Adjacency IL1 Day Room / Lounge and Independent Living Units.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Fully ADA accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 401
Room Name WC Reception / Check In
Net Area 140
Quantity 1
Adjacency Locate along public corridor on Main Level.Adjacent to Waiting Area and Medical Records.Direct access to emergency vehicle drop-off.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework Reception Desk
Equipment Provide standard hospital floor area wall bumpers with integral corner guards in waiting areas and corridors.Provide publication niche for magazine/brochure
Arch Notes Provide work surface with area to charge PDA's, etc.Accessible for Battery Powered Vehicles (BPV).NOTE: Internal corridors in wellness center are 8' wide typical.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 402
Room Name WC Waiting Area
Net Area 280
Quantity 1
Adjacency WC Reception / Check In and Exam Rooms.
Floor Finish Carpet 32 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Seating for 15 plus space for BPV (40 people max.)
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide A.E.D and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 403
Room Name Toilet / Specimen Room
Net Area 70
Quantity 2
Adjacency WC Waiting Area and Exam Rooms.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Provide one ADA accessible sink and toilet in each Toilet / Specimen Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 404
Room Name Clinical Supervisor
Net Area 200
Quantity 1
Adjacency Office Assistant, MD Office and Clinical Administrator.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Conference Table for 4 with storage unit.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Provide wireless conference phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 405
Room Name Office Assistant
Net Area 80
Quantity 1
Adjacency Clinical Supervisor
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Function as reception for Director of Health Services.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 406
Room Name Clinical Administrator
Net Area 120
Quantity 1
Adjacency Clinical Supervisor and MD Office.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 407
Room Name MD Office
Net Area 120
Quantity 1
Adjacency Exam Rooms and WC Staff Offices.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 408
Room Name Geriatric Nurse Practitioner
Net Area 120
Quantity 1
Adjacency Exam Rooms and WC Staff Offices.Easy access from internal corridor
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 409
Room Name Central Appointment Office
Net Area 120
Quantity 1
Adjacency WC Staff Offices
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 410
Room Name Exam Room
Net Area 120
Quantity 1
Adjacency WC Waiting Area
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment (TBD).See Appendix C for Exam Room information.
Arch Notes Provide handwashing station, locked storage units, plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Task lighting.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 411
Room Name Bariatric Exam Room
Net Area 120
Quantity 1
Adjacency Exam Room
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Bariatric Exam Room equipment (TBD).See Appendix C for Exam Room information.
Arch Notes Provide handwashing station, locked storage units, plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Task lighting.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 412
Room Name Triage / Exam Room
Net Area 120
Quantity 1
Adjacency Exam RoomsClose to Waiting Room.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment as (TBD).Ceiling-mounted exam light.
Arch Notes Provide handwashing station, locked storage units, plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 413
Room Name Phlebotomy / Exam Room
Net Area 120
Quantity 1
Adjacency WC Waiting Area
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment (TBD).Special medical-type casework for Phlebotomy equipment.
Arch Notes Includes handwashing station, lockable storage units,plus writing desk.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 414
Room Name Centrifuge Room
Net Area 70
Quantity 1
Adjacency Exam Room
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Undercounter refrigerator and handwashing sink.
Arch Notes Provide lockable door.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 415
Room Name Podiatry / Exam Room
Net Area 150
Quantity 1
Adjacency WC Waiting Area
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Mtl Base & Wall w/solid surface top
Equipment Exam Room equipment (TBD), including Podiatric sink.
Arch Notes Includes handwashing station, lockable storage units,plus writing desk.Additional casework near Podiatric sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Includes handwashing station and podiatric sink with floor drain.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 416
Room Name WC Medication Distribution
Net Area 120
Quantity 1
Adjacency WC ReceptionEasy access from public corridor.
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Full-size refrigerator.
Arch Notes Locked, secure room.Provide handwashing station and locked storage unitsSpecial locked cabinets for narcotics and drugs.Include drop-off window
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide standby power for refrigerators and freezers.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide standby power for lighting.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 417
Room Name Dental and Eye Clinic Waiting Area
Net Area 200
Quantity 1
Adjacency Reception, Dental Area, and Eye Clinic Area.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Seating for 8 plus space for BPV.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
P
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 418
Room Name Dental Reception
Net Area 100
Quantity 1
Adjacency Dental and Eye Clinic Waiting Area.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Reception Desk
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access ControlCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler
Fire Suppression Notes
Include on Emergency Power Genset
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: Avg Maintained Level (fc):
Fixture Types: Switching:
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 419
Room Name Dentist's Office
Net Area 120
Quantity 1
Adjacency Dental Reception, Dental Lab, and Dental Equipment.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 420
Room Name Dental Medical Files
Net Area 140
Quantity 1
Adjacency Dental Reception
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Filing cabinets.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 421
Room Name Dental Chairs
Net Area 200
Quantity 3
Adjacency Dentist's Office and Dental Reception.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Dental Cabinetry"
Equipment Fixed dental equipment as required.See Appendix C - List of Medical Equipment for Dental Area.
Arch Notes Extra Room for chair, doctor, and BPV.Provide lockable storage cabinets.Provide small handwashing sink with counter space and drawers.Lots of indirect, color corrected lighting.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 422
Room Name Sterilization Room
Net Area 120
Quantity 1
Adjacency Dental Lab and Dentist's Office.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Dental Cabinetry"
Equipment
Arch Notes Sink large enough to drain.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 423
Room Name X-Ray Station
Net Area 25
Quantity 1
Adjacency Dental Chair and Sterilization Room.
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment X-Ray machine.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 424
Room Name Supply Closet
Net Area 100
Quantity 1
Adjacency Dental Lab and Dental Chairs.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Shelving.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 425
Room Name Dental Lab
Net Area 100
Quantity 1
Adjacency Dentist's Office, Supply Closet, and Sterilization Room.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Dental Cabinetry"
Equipment Dental Lab equipment as required.
Arch Notes Provide counter space and drawers.Provide natural gas for denture making (left and right hand).Provide small handwashing sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 426
Room Name Dental Equipment
Net Area 25
Quantity 1
Adjacency Supply Closet.
Floor Finish Seamless Non Glare
Wall Finish Paint
Base Integral Coved Base
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Wood Dental Cabinetry"
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 427
Room Name Dental Break Room
Net Area 100
Quantity 1
Adjacency Supply Closet
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Ice machine and small refrigerator.
Arch Notes Coat closet.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Small handwashing sink with counter space and drawers.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 428
Room Name Eye Clinic / Fitting Room
Net Area 200
Quantity 1
Adjacency Dental and Eye Clinic Waiting Room and Optometrist Office.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Optometric equipment as required.Refer to Appendix C - List of Medical Equipment for the Eye Clinic.
Arch Notes Provide enough space for cabinets and BPV's turning radius in room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 429
Room Name Eye Clinic Work Room
Net Area 80
Quantity 2
Adjacency Eye Clinic Fitting Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 430
Room Name Optometrist / Ophthalmologist Office
Net Area 200
Quantity 1
Adjacency Eye Clinic Fitting Room
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Optometric equipment as required.See Appendix C - List of Medical Equipment for the Eye Clinic.
Arch Notes Standard desk and credenza with 2 visitor's chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 431
Room Name WC Conference Room / Alt. EOC
Net Area 400
Quantity 1
Adjacency Exam Rooms and MD Office.
Floor Finish Carpet 32 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment Motorized projection screen (recessed automatic), and wall-mounted whiteboard (9' x 8').Provide emergency cabinet.
Arch Notes Large conference table and seating for 12.Space for social workers and group sessions.Provide acoustical treatment.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide wireless conference phone.Include additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes: Special lighting for projection purposes.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 432
Room Name Medical Records
Net Area 2000
Quantity 1
Adjacency WC Reception / Check-In
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment "LEKTRIEVER" system or similar.
Arch Notes Average length of record keeping: 10 years.Increase structural support for hi-density filing system60 filing cabinets.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 433
Room Name Medical Chart Alcove
Net Area 24
Quantity 1
Adjacency Medical Records
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Open storage area for medical charts.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 434
Room Name WC Mobility Alcove
Net Area 60
Quantity 1
Adjacency WC Waiting Area
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment
Arch Notes Open storage area for wheelchairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access ControlCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 435
Room Name WC Clean Linen
Net Area 120
Quantity 1
Adjacency Exam Rooms
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes Storage for "full" and "empty" containers, 8-12 "E" tanks.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 436
Room Name WC Soiled Linen / Trash Room
Net Area 120
Quantity 1
Adjacency Exam Rooms
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No air recirculation allowed.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Utility sink.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 437
Room Name WC Medical Supply Storage
Net Area 120
Quantity 1
Adjacency Close to WC Staff Locker Area, WC Clean Linen, and WC Soiled Linen / Trash Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 438
Room Name WC Oxygen Storage Room
Net Area 80
Quantity 1
Adjacency WC Medical Supply Storage
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 439
Room Name WC Staff Locker Area
Net Area 100
Quantity 1
Adjacency WC Soiled Linen / Trash Room, WC Clean Linen, and Staff Toilets.
Floor Finish VCT
Wall Finish Sanitary Wainscot
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Half Lockers for 24 people.Benches.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 440
Room Name WC Medical Waste
Net Area 24
Quantity 1
Adjacency Exam Rooms
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Medical Waste containers provided by Medical Waste
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No air recirculation allowed.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 441
Room Name Nourishment Center / Break Room
Net Area 400
Quantity 1
Adjacency WC Staff Offices
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator and microwave.
Arch Notes Tables and seating for 12.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power for refrigerator and kitchenette.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 442
Room Name Clinical Dietician
Net Area 120
Quantity 1
Adjacency WC Staff Offices
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 443
Room Name WC Social Worker
Net Area 120
Quantity 1
Adjacency WC Staff Offices
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 444
Room Name WC Staff Toilet
Net Area 70
Quantity 2
Adjacency WC Staff Offices
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide complete stainless steel toilet accessories.
Arch Notes ADA accessible water closet and sink.1 Men assigned.1 Women assigned.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 445
Room Name Rehabilitation Services
Net Area 3000
Quantity 1
Adjacency Locate along public corridor.Adjacent to Wellness Center.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment 1 treadmill, 2-3 stationary bikes, 1 parallel bars and steps. Hot pack station, 2 tables with massage mats1 small Jacuzzi (limbs), 1 Aquasizer, Paraffin hot wax, and fluido-therapy equipment.
Arch Notes Sub-divide into 2 Rehab Clinics (PT and OT). Provide one accessible unisex toilet room in each clinic.Provide ADL Bathroom with shower.Include 200 sf locked storage.Provide seating for 6-8.Ceiling lift-track system ("Voyager" style).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 446
Room Name Rehab Spa / Bathing
Net Area 230
Quantity 1
Adjacency Rehabilitation Services
Floor Finish Rubber
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 447
Room Name Rehab Storage
Net Area 200
Quantity 1
Adjacency Rehabilitation Services and Evaluation / Treatment Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Wood SGL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 448
Room Name Evaluation / Treatment Room
Net Area 200
Quantity 1
Adjacency Rehabilitation Services
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide observation window into Rehabilitation Services.
Arch Notes Work table with lockable storage and 4 chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 449
Room Name Director of Rehabilitation Services
Net Area 120
Quantity 1
Adjacency Rehabilitation Services
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide observation window into Rehab Activity Room
Arch Notes Standard desk and credenza with 2 visitor chairs.Used for private conversation.Provide acoustical treatment.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 450
Room Name Occupational Therapists
Net Area 160
Quantity 1
Adjacency Rehabilitation Services
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide observation window into Rehabilitation Services.
Arch Notes Provide 2 workstations in same room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 451
Room Name Physical Therapists
Net Area 160
Quantity 1
Adjacency Rehabilitation Services
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide observation window into Rehabilitation Services.
Arch Notes Provide 2 workstations in same room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
d
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 452
Room Name Nurse Educator
Net Area 120
Quantity 1
Adjacency Education Classroom
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 453
Room Name Education Classroom
Net Area 700
Quantity 1
Adjacency Locate along public corridor.Adjacent to Assisted Living offices
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Include filing cabinets.Provide motorized projection screen, whiteboard, and projector.
Arch Notes Work tables and chairs for 25 people and 1 instructorProvide lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 454
Room Name Classroom Storage
Net Area 100
Quantity 1
Adjacency Education Classroom
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 455
Room Name Reference Library
Net Area 200
Quantity 1
Adjacency Locate along public corridor.Adjacent to Education Classroom.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment
Arch Notes Library furniture and shelving.Include seating for 6-8 people.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 456
Room Name Healthcare Administrator
Net Area 200
Quantity 1
Adjacency Administrative Assistant and Director of Nursing.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 457
Room Name Administrative Assistant
Net Area 100
Quantity 1
Adjacency Healthcare Administrator, Director of Nursing, Conference Room, and Work / Copy Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Printers, fax machines, copiers, filing cabinets.
Arch Notes Locate in same room as Director of Nursing's Administrative Assistant.Secretarial workstation.Secured room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 458
Room Name Director of Nursing
Net Area 120
Quantity 1
Adjacency Administrative Assistant and Healthcare Administrator.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 459
Room Name Administrative Assistant
Net Area 100
Quantity 1
Adjacency Director of Nursing, Healthcare Administrator, Conference Room, and Work / Copy Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Printers, fax machines, copiers, filing cabinets.
Arch Notes Locate in same room as Director of Nursing's Administrative Assistant.Secretarial workstation.Secured room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 460
Room Name MDS Coordinator
Net Area 120
Quantity 1
Adjacency Healthcare Administrator, Director of Nursing, Performance Improvement Office, Conference Room, and Inventory Supply Specialist.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 461
Room Name Performance Improvement Office
Net Area 200
Quantity 1
Adjacency Healthcare Administrator, Director of Nursing, MDS Coordinator, Conference Room, and Inventory Supply Specialist.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.Provide space for additional filing storage.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 462
Room Name Conference Room
Net Area 240
Quantity 1
Adjacency Locate along public corridor.Adjacent to Administrative Assistants, Healthcare Administrator, Director of Nursing, and Work / Copy Room.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Wood
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Motorized projection screen (recessed automatic), and wall-mounted whiteboard (9' x 8').Provide emergency cabinet.
Arch Notes Large conference table and seating for 12.Space for social workers and group sessions.Provide acoustical treatment.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Provide wireless conference phone.Include additional voice and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Dimming
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 463
Room Name Central Medical Supply
Net Area 200
Quantity 1
Adjacency Locate along public corridor.Adjacent to Inventory Supply Specialist.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 464
Room Name Inventory Supply Specialist
Net Area 120
Quantity 1
Adjacency Central Medical Supply
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Copier machines, fax machines, and filing cabinets.
Arch Notes Secretarial workstation with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 465
Room Name Work / Copy Room
Net Area 160
Quantity 1
Adjacency Administrative Assistants and Conference Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Copiers, fax machines, and printers.
Arch Notes Storage cabinets and work counters.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide additional telephone and data capacity.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 466
Room Name Independent Living 2 Units
Net Area 450
Quantity 24
Adjacency
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Same as Independent Living 1 Units.
Arch Notes Same as Independent Living 1 Units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Same as Independent Living 1 Units.
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Same as Independent Living 1 Units.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Same as Independent Living 1 Units.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 467
Room Name IL2 Home Base
Net Area 270
Quantity 2
Adjacency IL2 Main Entrance
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Same as AL Home Base.
Arch Notes 1 unit serves 12 residents.Same as AL Home Base.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Same as AL Home Base.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Same as AL Home Base.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Same as AL Home Base.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 468
Room Name IL2 Work Space
Net Area 45
Quantity 4
Adjacency Resident Corridor
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Same as MS Work Space.
Arch Notes Same as MS Work Space.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 469
Room Name IL2 Activity Room
Net Area 1000
Quantity 1
Adjacency IL2 Home Base and Staff Work Area
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Same as MS Activity Room.
Arch Notes Same as MS Activity Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Same as MS Activity Room.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Same as MS Activity Room.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 470
Room Name IL2 Public Toilet Room
Net Area 70
Quantity 2
Adjacency
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Same as IL1 Public Toilet Rooms (M & W).
Arch Notes Same as IL1 Public Toilet Rooms (M & W).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 471
Room Name IL2 Medical Waste Storage
Net Area 24
Quantity 2
Adjacency IL2 Laundry Room
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Same as AL Medical Waste Storage.
Arch Notes Same as AL Medical Waste Storage.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No recirculation allowed.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 472
Room Name IL2 Laundry Room
Net Area 100
Quantity 2
Adjacency Elevators
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Same as IL1 Laundry Room.
Arch Notes Same as IL1 Laundry Room.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Same as IL1 Laundry Room.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Same as IL1 Laundry Room.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Same as IL1 Laundry Room.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 473
Room Name IL2 Staff Toilet
Net Area 70
Quantity 2
Adjacency Staff Area and IL2 Home Base
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Same as AL Staff Toilet.
Arch Notes Same as AL Staff Toilet.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 474
Room Name IL2 Nurse Practitioner
Net Area 120
Quantity 1
Adjacency IL2 Social Worker and IL2 Work Space.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Same as MS Nurse Practitioner.
Arch Notes Same as MS Nurse Practitioner.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 475
Room Name IL2 Social Worker
Net Area 120
Quantity 1
Adjacency IL2 Nurse Practitioner and IL2 Work Space.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Same as AL Social Worker.
Arch Notes Same as AL Social Worker.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 476
Room Name Assisted Living Units (AL)
Net Area 450
Quantity 60
Adjacency Refer to Assisted Living Unit Adjacency Diagram.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Full kitchenette with sink and area for "mini" refrigerator and microwave oven.Include "lock boxes" for valuables (6" x 12" - Type TBD).
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and one data connection with 2 data linesProvide one emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.Nurse Call System shall be on standby power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.Provide indirect lighting in living area.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 477
Room Name AL Home Base
Net Area 270
Quantity 2
Adjacency AL Main Entrance and Club Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Include copy machine, refrigerator, and Nurse Call System base unit."Home Free" system and other equipment as required by AFRH.
Arch Notes 1 unit serves 30 residents.Open nurses' station with lockable storage.Includes patient records storage in lateral files.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide handwashing sink.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide multiple outlets for monitoring equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 478
Room Name AL Club Room
Net Area 1080
Quantity 2
Adjacency AL Home Base
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Include recessed emergency medical cabinet (wired to security).
Arch Notes 1 Club Room per 30 residents.Provide lounge seating for 30 - 40 people.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include Nurse Call device, emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 479
Room Name AL Activity Room
Net Area 340
Quantity 1
Adjacency AL Club Room, AL Nourishment Center, and AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator.
Arch Notes 1 Activity Room per 60 residents.Movable wall.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 480
Room Name AL Nourishment Center
Net Area 100
Quantity 1
Adjacency Locate along internal corridor near AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator and microwave.
Arch Notes 1 Nourishment Center for 30 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 481
Room Name AL Spa / Bathing Room
Net Area 230
Quantity 2
Adjacency AL Home Base and Resident Corridor.
Floor Finish Rubber
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes 1 Spa / Bathing Rm per 30 residents.No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 482
Room Name AL Public Toilet Room
Net Area 70
Quantity 2
Adjacency AL Home Base and Resident Corridor.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes 1 Public Toilet Room per 30 residents.Provide accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 483
Room Name AL Clean Linen
Net Area 120
Quantity 2
Adjacency AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes 1 Clean Supply Room per 30 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 484
Room Name AL Soiled Linen / Trash Room
Net Area 120
Quantity 2
Adjacency Near AL Living Units
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment
Arch Notes 1 Soiled Linen / Trash Room per 15 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No air recirculation.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 485
Room Name AL Medical Storage
Net Area 150
Quantity 1
Adjacency AL Medication Room and AL Medical Waste Storage.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 486
Room Name AL Medical Supply Storage
Net Area 80
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 487
Room Name AL Medical Waste Storage
Net Area 24
Quantity 2
Adjacency AL Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Medical Waste containers provided by Housekeeping Contractor.
Arch Notes 1 Medical Waste Storage Room per 30 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No air recirculation.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 488
Room Name AL Medication Room
Net Area 120
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Full-size refrigerator.
Arch Notes 1 Medication Room per 30 residents.Includes handwashing station and lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator and minimal lighting only.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 489
Room Name AL Laundry Room
Net Area 100
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Commercial-grade Washer / Dryer and deep stackable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 30 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special floor drain to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 490
Room Name AL Staff Break Area
Net Area 150
Quantity 2
Adjacency AL Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Half-height lockers for 16 employees.Kitchenette with full-size refrigerator.
Arch Notes 1 Staff Break Area per 30 residents.Tables and chairs for 6.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 491
Room Name AL Staff Toilet
Net Area 70
Quantity 2
Adjacency AL Staff Break Area
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes ADA accessible water closet and sink.1 Men assigned.1 Women assigned.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 492
Room Name AL Clinical Supervisor
Net Area 200
Quantity 1
Adjacency AL Medical Provider, AL Medical Records Technician, AL Recreational Therapist, AL Dietician, and AL Social Worker.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 493
Room Name AL Medical Provider
Net Area 200
Quantity 1
Adjacency AL Clinical Supervisor, AL MedicalRecords Technician, AL Recreational Therapist, and AL Dietician.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Ptd Metal Base w/Solid Surface Top
Equipment
Arch Notes Seamless floor non-glare sheet, pre-finished for one step cleaning process.Conference table with 4 chairs.Serves as Exam Room.Exam Table and workstation.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Include handwashing station.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 494
Room Name AL Medical Records Technician
Net Area 120
Quantity 1
Adjacency Locate along public corridor.Adjacent to Assisted Living Unit Entrance.Close to AL Home Base (2)
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment Medical charts carousel (60 residents).
Arch Notes Secretarial workstation.Functions as reception area for Assisted Living Offices.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 495
Room Name AL Recreational Therapist
Net Area 120
Quantity 1
Adjacency Director of Health Services
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 496
Room Name AL Dietician
Net Area 120
Quantity 1
Adjacency AL Recreational Therapist
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 497
Room Name AL Social Worker
Net Area 120
Quantity 1
Adjacency AL Nurse Manager
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 498
Room Name Memory Support Units (MS)
Net Area 350
Quantity 24
Adjacency MS Home Base and Staff Work Areas.
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Include "lock boxes" for valuables (6" x 12" - Type TBD).Provide Nurse Call device in living area and CCTV in hallways.
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and one data connection with 2 data linesProvide one emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.Nurse Call System shall be on standby power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.Provide indirect lighting in living area.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 499
Room Name MS Day Club
Net Area 5600
Quantity 1
Adjacency Locate on common corridor.Adjacent to MS Dining Room and Country Kitchen.Shared with LTC.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Piano, TV, and games.Provide storage closets for games and supplies.Include recessed emergency medical cabinet (wired to security).
Arch Notes Provide walkable space for MS residents.Include controlled Outside Area on same floor.Tables and chairs for 35 - 40 people seating in groups.Provide unisex toilet room and storage cabinets.Provide "cubby" space for individual storage (24).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include Nurse Call device, emergency phone and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Electric locks to be conduited with emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 500
Room Name MS Secure Exterior Patio
Net Area 3500
Quantity 1
Adjacency MS Day Club
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Include enclosing fence and motion detection securityfeatures.Gazebo and / or trellis.
Arch Notes Provide level surfaces for group and individual activity with shade.Include edge details that reduce the potential to placea chair or climb the fence.May be used as an emergency exit into a safe area orefuge.Expect pet visitation to this area.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 60%
Special HVAC Requirements
No HVAC service required for this space.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Motion Detector.Include emergency phone and Home Free system.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching:
Lighting Notes:
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 501
Room Name MS Home Base
Net Area 270
Quantity 2
Adjacency MS Dining Room and Activity Room.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Include copy machine, refrigerator, and Nurse Call System base unit."Home Free" system and other equipment as required by AFRH.
Arch Notes 1 Home Base per 12 residents.Locate to maintain visual connection to all resident units.Included patient records storage in lateral files.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide multiple outlets for monitoring equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 502
Room Name MS Work Space
Net Area 45
Quantity 4
Adjacency Resident Corridor
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment
Arch Notes 1 Work Space per 6 residents.Locate on resident corridor (no door).Include patient record storage (stand alone and movable).Lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 503
Room Name MS Dining Room
Net Area 1080
Quantity 1
Adjacency MS Home Base and Activity Room
Floor Finish VCT
Wall Finish Wainscott"
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Movable partition between Dining and Activity.
Arch Notes 1 Dining Room per all MS residents.Estimated seating for 32 (28 SF / person). NO ROUND TABLES.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Include handwashing station.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 504
Room Name MS Servery
Net Area 300
Quantity 1
Adjacency MS Dining Room
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Stainless steel service line equipment.
Arch Notes "Functionally accessible for older people."ADA compliant.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power to allow for fully functional kitchen service.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 505
Room Name MS Activity Room
Net Area 1000
Quantity 1
Adjacency MS Home Base and Staff Work Area
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator.
Arch Notes 1 Activity Room per 24 residents.Movable wall.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator only.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Minimal lighting for access to refrigerator.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 506
Room Name MS Country Kitchen
Net Area 200
Quantity 1
Adjacency MS Activity Room
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood Pocket
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Kitchen equipment including sink, stove, and full-size refrigerator.
Arch Notes Open to MS Activity Room.Pass through countertop with 4 stools.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide kitchen make-up air and exhaust system in accordance with Code.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 507
Room Name MS Activity Alcove (one person)
Net Area 180
Quantity 2
Adjacency MS Home Base and Staff Work Area.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes 1 Activity Alcove per 12 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Nurse call.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 508
Room Name MS Spa / Bathing Room
Net Area 230
Quantity 2
Adjacency MS Home Base and Resident Corridor.
Floor Finish Rubber
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes 1 Spa / Bathing Rm per 12 residents.No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 509
Room Name MS Public Toilet Room
Net Area 70
Quantity 2
Adjacency MS Home Base and Resident Corridor.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes 1 Public Toilet Room per 12 residents.Provide accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 510
Room Name MS Clean Linen
Net Area 120
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes 1 Clean Linen Room per 12 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 511
Room Name MS Soiled Linen / Trash Room
Net Area 60
Quantity 4
Adjacency MS Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes 1 Soiled Room per 6 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No air recirculation.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 512
Room Name MS Medical Supply Storage
Net Area 80
Quantity 1
Adjacency MS Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide industrial-grade solid shelving.
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 513
Room Name MS Medical Waste Storage
Net Area 24
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Medical Waste containers provided by Housekeeping Contractor.
Arch Notes 1 Medical Waste Storage Room per 12 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No air recirculation allowed.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc): 10
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 514
Room Name MS Medication Room
Net Area 110
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Full-size refrigerator.
Arch Notes 1 Medication Room per 12 residents.Includes handwashing station and lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator for medications.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Minimal lighting for emergency access to refrigerator.
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 515
Room Name MS Laundry Room
Net Area 100
Quantity 2
Adjacency MS Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stackable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 12 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special floor drain to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 516
Room Name MS Staff Break Area
Net Area 150
Quantity 2
Adjacency MS Home Base
Floor Finish VCT
Wall Finish Sanitary Wainscot
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Half-height lockers for 16 employees.Kitchenette with full-size refrigerator.
Arch Notes 1 Staff Break Area per 30 residents.Tables and chairs for 6.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 517
Room Name MS Staff Toilet
Net Area 70
Quantity 2
Adjacency MS Home Base and MS Staff Break Area
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories
Arch Notes ADA accessible water closet and sink.1 Men assigned.1 Women assigned.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 518
Room Name MS Clinical Supervisor
Net Area 120
Quantity 1
Adjacency MS Staff Area
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 519
Room Name MS Medical Records Technician
Net Area 80
Quantity 1
Adjacency Locate along public corridor.Adjacent to Memory Support Unit Entrance, and MS Staff Area.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Functions as reception area for Memory Support Offices.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 520
Room Name MS Nurse Practitioner
Net Area 120
Quantity 1
Adjacency MS Staff Area
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 521
Room Name MS Dietician
Net Area 120
Quantity 1
Adjacency MS Staff Area
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 522
Room Name MS Social Worker
Net Area 120
Quantity 1
Adjacency MS Staff Area
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 601
Room Name Security Gate House
Net Area 150
Quantity 1
Adjacency Main Vehicular Site Entrance
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Metal SGL
Wall Construction CMU w/GWB
Casework Security Desk
Equipment Gates and retractable bollards at entrance roadways.Security equipment as required.
Arch Notes Includes accessible toilet room with toilet and sink.Provide glazing to control all security barriers.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 602
Room Name Exterior Recreational Terrace
Net Area 3000
Quantity 1
Adjacency Dining Room
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Grilles, serving line equipment, and work tables for outside events.
Arch Notes Moveable tables, chairs, benches, etc. to accommodate 100 to 350 people.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 60%
Special HVAC Requirements
No HVAC service required for this space.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide floor drains as required.
Voice ( x ) Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide emergency phone.Provide capacity for portable outdoor telephone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide power for portable outdoor electrical appliances and equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Base Bid
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
OPTION 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 226
Room Name Main Trash Rooms
Net Area 300
Quantity 1
Adjacency Trash Chutes (from above).Easy access to Loading Dock.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Trash compactor and trash chute with fire-rated doorsat each level.Include smoke detectors in chute.
Arch Notes 1 Trash Room per 150 Units.The DBC shall describe how trash removal is addressed.May be located at First Floor or Wash-Out Level.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Self-cleaning trash chute will require water supply and drain.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 227
Room Name Trash Room (Includes all Living Units)
Net Area 50
Quantity 9
Adjacency Elevators, Janitor Closet, and Laundry Room.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Self-cleaning trash chute with fire-rated doors.Recycling bins provided by Housekeeping Contractor.
Arch Notes 1 trash room per 24 residents ( Independent Living).1 trash room per 30 residents (Assisted Living).1 trash room per 12 residents (Memory Support and Long Term Care).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 322
Room Name Janitor's Closet (On Residential Units Levels)
Net Area 30
Quantity 9
Adjacency Trash Room.
Floor Finish
Wall Finish
Base
Ceiling Finish
Door Type
Wall Construction
Casework
Equipment Mop sink and rack.
Arch Notes Provide at least one Janitor's Closet per floor.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 379
Room Name IL1Independent Living Units
Net Area 450
Quantity 170
Adjacency See Adjacency Diagram for Typical Independent Living Level.
Floor Finish Anti Microbial Carpet
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Wood Wall Base & Solid Surface Top
Equipment Full kitchenette with sink and area for "mini" refrigerator and microwave oven.Include "lock boxes" for valuables (6" x 12" - Type TBD).
Arch Notes Includes full accessible bath with sink, toilet and shower.Provide rubber floor and "sanitary" walls in bathroom for wash down.Provide pull-down bars at toilet, and standard grab bars elsewhere as required.Provide connecting door for 10% of units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access W/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and 1 data connection with 2 data lines.Provide 1 emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide indirect lighting in living area.Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 380
Room Name IL1 Day Room / Lounge
Net Area 250
Quantity 7
Adjacency Elevator Lobby and Resident Corridor.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment
Arch Notes 1 unit serves 24 residents.Provide TV, couches and chairs, and 2 card tables with 4 chairs each.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phone and AED.
Sprinkler Dry Pipe System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 381
Room Name IL1 Laundry Room
Net Area 100
Quantity 7
Adjacency Elevators, Janitor Closet, and Trash Room.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stockable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 24 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide utility sink.Provide special oversized floor drain with gooseneck faucet to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 382
Room Name IL1 Public Toilet Rooms (M & W)
Net Area 70
Quantity 14
Adjacency Day Room / Lounge and Independent Living Units.
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes Fully ADA accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 523
Room Name Long-Term Care Units
Net Area 350
Quantity 24
Adjacency LTC Home Base and Staff Work Areas
Floor Finish Carpet 36 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Same as Memory Support Unit.Not Kitchenette.
Arch Notes Provide at least one Bariatric room with larger bed, ceiling lift track, and larger entry and bathroom doors.Provide connecting door between units for 10% of rooms.Ceiling structure in unit shall support ceiling lifts ("Voyage" style).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Medical gases are not required in the Long Term Units.Provide fully-waterproofed floor in bathroom.Provide separate floor drains in shower and bathroom floor.
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Provide 2 telephone outlets (on opposite walls) and one data connection with 2 data linesProvide one emergency device in bathroom and 2 devices in living area connected to the Resident Monitoring System (including Wellness Center Check-In Button).
Sprinkler Quick Response Heads
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide one duplex outlet in each room on standby power circuit.Provide circuit for personal battery powered vehicle charging.Nurse Call System shall be on standby power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide one permanently installed lighting fixture in the living unit and one permanently installed lighting fixture in the bathroom on standby power.Provide indirect lighting in living area.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 524
Room Name LTC Secure Exterior Patio
Net Area 3500
Quantity 1
Adjacency LTC Home Base and LTC Day / Visitor Room.
Floor Finish Stone
Wall Finish Paint
Base Stone
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Include enclosing fence and motion detection securityfeatures.Gazebo and / or trellis.
Arch Notes Provide level surfaces for group and individual activity with shade.Include edge details that reduce the potential to placea chair or climb the fence.May be used as an emergency exit into a safe area orefugeExpect pet visitation to this area.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 82 Deg (F)
% R Humidity (Winter) -
% R Humidity (Summer) 60%
Special HVAC Requirements
No HVAC service required for this space.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include motion detector.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 525
Room Name LTC Home Base
Net Area 270
Quantity 2
Adjacency MS Dining Room
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework Plam Wall Base & Top
Equipment Include copy machine, refrigerator, and Nurse Call System base unit."Home Free" system and other equipment as required by AFRH.
Arch Notes Locate to maintain visual connection to all resident units.1 Home Base per 12 residents.Included patient records storage in lateral files.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide multiple outlets for monitoring equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
PER IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 526
Room Name LTC Work Space
Net Area 45
Quantity 4
Adjacency Resident corridor and Long Term Care Units
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment
Arch Notes 1 Work Space per 6 residents.Locate on resident corridor (no door).Include patient record storage (stand alone and movable).
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 527
Room Name LTC Dining Room
Net Area 1080
Quantity 1
Adjacency LTC Servery
Floor Finish VCT
Wall Finish Wainscott"
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Glass DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment
Arch Notes 1 Dining Room per all LTC residents.Estimated seating for 30-35 (28 SF / person). NO ROUND TABLES.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Include handwashing station.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 528
Room Name LTC Servery
Net Area 300
Quantity 1
Adjacency LTC Dining Room
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Stainless steel service line equipment.
Arch Notes "Functionally accessible for older people."ADA compliant.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power to allow for fully functional kitchen service.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 529
Room Name LTC Activity Room
Net Area 1000
Quantity 1
Adjacency LTC Country Kithcen, LTC Day / Visitor Room, LTC Nourishment Center, and LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish ACT w/GWB Accents
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Kitchenette with full-size refrigerator.
Arch Notes 1 Activity Room per 24 residents.Movable wall.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 530
Room Name LTC Country Kitchen
Net Area 200
Quantity 1
Adjacency LTC Activity Room
Floor Finish Sheet Vinyl
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood Pocket
Wall Construction CMU w/GWB
Casework Plam Wall Base & Top
Equipment Kitchen equipment including sink, stove, and full-size refrigerator.
Arch Notes Open to LTC Activity Room.Pass through countertop with 4 stools.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide kitchen make-up air and exhaust system in accordance with Code.
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator on emergency power.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 531
Room Name LTC Activity Alcove (one person)
Net Area 180
Quantity 1
Adjacency
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes 1 LTC Activity Alcove per 24 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 532
Room Name LTC Spa / Bathing Room
Net Area 230
Quantity 2
Adjacency LTC Home Base and Resident Corridor.
Floor Finish Rubber
Wall Finish Ceramic Tile 1/2 Ht.
Base Ceramic
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment Ceiling lift-track system ("voyager" style).Podiatric sink.Recumbent, fast-fill tub, usable from ceiling or hydraulic lift.
Arch Notes 1 Spa / Bathing Rm per 12 residents.No-wall shower (floor drain and sanitary walls).Provide pull-down "Lalido" bars at toilet, and standard grab bars elsewhere as required.Provide exterior window and appropriate window treatment for natural light.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( x ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 533
Room Name LTC Nourishment Center
Net Area 100
Quantity 1
Adjacency LTC Home Base
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Kitchenette with full-size refrigerator, microwave, and ice machine.
Arch Notes Tables and seating for 4.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 76 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Provide receptacles on standby power for refrigerator and kitchenette.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Provide lighting on standby power.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 534
Room Name LTC Workstation
Net Area 80
Quantity 1
Adjacency Locate along public corridor near Long Term Care Unit Entrance.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Functions as reception area for Long Term Care Offices.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 534
Room Name LTC Public Toilet Room
Net Area 70
Quantity 2
Adjacency
Floor Finish Seamless Vinyl
Wall Finish Paint
Base Integral Coved Base"
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes 1 Public Toilet Room per 12 residents.Provide accessible water closet and sink.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Include Nurse Call device and emergency phone.
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 535
Room Name LTC Clean Linen
Net Area 120
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes 1 Clean Supply Room per 12 residents.Storage for "full" and "empty" containers, 8-12 "E" tanks.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 536
Room Name LTC Soiled Linen / Trash Room
Net Area 120
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes 1 Soiled Linen / Trash Room per 6 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No recirculation allowed.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 537
Room Name LTC Medical Supply Storage
Net Area 80
Quantity 2
Adjacency LTC Medical Waste Storage
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 4 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 538
Room Name LTC Medical Waste Storage
Net Area 24
Quantity 2
Adjacency
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes 1 Medical Waste Storage Room per 12 residents.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Provide 100% exhaust from space. No recirculation allowed.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 539
Room Name LTC Medication Room
Net Area 110
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Base & Top
Equipment Full-size refrigerator.
Arch Notes 1 Medication Room per 12 Residents.Includes handwashing station and lockable storage units.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes Refrigerator for medications.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Minimal lighting for emergency access to refrigerator.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 540
Room Name LTC Laundry Room
Net Area 100
Quantity 2
Adjacency LTC Home Base.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/Impact Res. GWB
Casework Plam Wall Base & Top
Equipment Commercial-grade Washer / Dryer and deep stockable front load. ADA-accessible sink.Provide Industrial-grade solid shelving.Warpool system for drying and "steaming" equipment
Arch Notes 1 Laundry Room per 24 residents.Include table for folding laundry, clothes rod, and 2 chairs.Provide special ventilation and acoustical treatment.Water temperature booster in laundry rooms for one of washer --controlled by staff.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Provide utility sink.Provide special floor drain to accommodate washer overflow.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( x )
Power Notes
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( x ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 541
Room Name LTC Lift Storage
Net Area 100
Quantity 1
Adjacency Internal corridor.
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood DBL
Wall Construction Metal Stud w/Impact Res. GWB
Casework
Equipment Provide Industrial-grade solid shelving.
Arch Notes Provide storage for five wheelchairs, two lifts (3' x 3'), and general storage for other equipment.
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 542
Room Name LTC Chart Room
Net Area 120
Quantity 1
Adjacency LTC Home Base
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment To be determined with AFRH staff.
Arch Notes
Temp F (Winter) 70 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 543
Room Name LTC Day / Visitor Room
Net Area 200
Quantity 1
Adjacency LTC Home Base
Floor Finish Carpet 36 oz
Wall Finish Paint & FWC
Base Vinyl
Ceiling Finish Painted GWB
Door Type Wood DBL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control NoneCCTV ( ) Cable TV ( x )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency room.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 544
Room Name LTC Staff Break Area
Net Area 150
Quantity 2
Adjacency LTC Staff Toilets
Floor Finish VCT
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment Half-height lockers for 16 employees.Kitchenette with full-size refrigerator.
Arch Notes 1 Staff Break Area per 24 residents.Tables and chairs for 6.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 545
Room Name LTC Staff Toilet
Net Area 70
Quantity 2
Adjacency LTC Home Base
Floor Finish Ceramic Tile
Wall Finish Ceramic Tile Wet Wall
Base Ceramic
Ceiling Finish Painted GWB
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework Plam Base & Top
Equipment Provide complete stainless steel toilet accessories.
Arch Notes ADA accessible watercloset and sink.1 Men assigned.1 Women assigned.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Privacy SetCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 546
Room Name LTC Clinical Supervisor
Net Area 120
Quantity 1
Adjacency LTC Scial Woorker
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 547
Room Name LTC Medical Records Technician
Net Area 80
Quantity 1
Adjacency Locate along public corridor.Adjacent to Long-Term Care Unit Entrance.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL w/Side Lite
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Secretarial workstation.Functions as reception area for Long-Term Care Offices.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 548
Room Name LTC Nurse Practitioner
Net Area 120
Quantity 1
Adjacency LTC Workstation and LTC Office Coordinator.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 549
Room Name LTC Dietician
Net Area 120
Quantity 1
Adjacency LTC Clinical Supervisor
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 550
Room Name LTC Social Worker
Net Area 120
Quantity 1
Adjacency LTC Clinical Supervisor and LTC Medical Records Technician.
Floor Finish Carpet 32 oz
Wall Finish Paint
Base Vinyl
Ceiling Finish 2 x 2 ACT
Door Type Wood SGL
Wall Construction Metal Stud w/GWB
Casework
Equipment
Arch Notes Standard desk and credenza with 2 visitor chairs.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 75 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 1
Armed Forces Retirement Home Design Build Services Request for Proposal Gulfport, Mississippi 21 May 2007
General Services Administration Public Buildings Service Southeast Sunbelt Region Real Estate Design and Construction
UNCLASSIFIED
OPTION 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 701
Room Name Pool(s) and Deck
Net Area
Quantity 1
Adjacency General Swimming Area.
Floor Finish TBD
Wall Finish
Base None
Ceiling Finish No Ceiling
Door Type
Wall Construction
Casework
Equipment Standard pool equipment including ladders, ropes, and life guard station.
Arch Notes Provide 25 meter lap pool with 8 lanes.Chaise lounges, tables, and chairs for 40-50 people.Provide "Cool Deck" finish surrounding pool.
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Provide emergency phone.
Sprinkler
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.Provide connections for food service equipment.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes: Underwater pool lighting and decorative fixtures for nighttime use.
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 702
Room Name Dressing Area
Net Area 750
Quantity 2
Adjacency Pool(s) and Deck
Floor Finish Rubber
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment
Arch Notes Provide Men's and Women's locker / toilet rooms.Provide 40 -50 half-height lockers (no metal) and benches.Include 2 showers, 3 water closets (or equivalent) and2 sinks in each room.Provide direct outside access to pool.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 60%
Special HVAC Requirements
Sink ( x ) Toilet ( x ) Shower ( x ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 703
Room Name Sunning Area / Outdoor Terrace
Net Area
Quantity 1
Adjacency Pool(s) and Deck
Floor Finish TBD
Wall Finish
Base TBD
Ceiling Finish
Door Type
Wall Construction
Casework
Equipment
Arch Notes Provide "Cool Deck" floor finish.Chaise lounges, tables, and chairs for 20-25 people.
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control NoneCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 704
Room Name Mechanical Room / Pool Eqpt.
Net Area 400
Quantity 1
Adjacency Swimming Pool.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment Pool Equipment
Arch Notes
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Venitlation only (per Code).
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide safety shower.
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Key OnlyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 705
Room Name Pool Office
Net Area 144
Quantity 1
Adjacency Swimming Pool.
Floor Finish Sealed Concrete
Wall Finish Paint
Base Vinyl
Ceiling Finish Painted GWB
Door Type Metal SGL
Wall Construction CMU
Casework
Equipment Include observation window facing pool.
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 60%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 706
Room Name Recreational Storage
Net Area 180
Quantity 1
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 60%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( x ) Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 707
Room Name Patio Cookout Storage
Net Area 100
Quantity 1
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Ventilation only.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 708
Room Name Chemical Storage
Net Area 200
Quantity 1
Adjacency Mechanical Room / Pool Eqpt.
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Ventilation only (per Code).
Sink ( x ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( x )
Spec Plumb Requirements
Provide safety shower.
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 709
Room Name Table Storage
Net Area 500
Quantity 1
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Ventilation only.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 710
Room Name Activity Storage Room
Net Area 400
Quantity 1
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Ventilation only.
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Not on emergency system.
Include on Emergency Power Genset ( )
Power Notes Provide dry pipe system if located in outbuilding.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 711
Room Name Open Exercise Room
Net Area 2000
Quantity 1
Adjacency
Floor Finish Sprung Wood
Wall Finish Paint
Base Wood
Ceiling Finish 2 x 4 ACT
Door Type Glass DBL
Wall Construction CMU w/GWB
Casework
Equipment Exercise floor mats.
Arch Notes Low-impact exercises typical.Provide special ventilation and acoustical treatments.Include wall mirrors and balance bars.
Temp F (Winter) 72 Deg (F)
Temp F (Summer) 78 Deg (F)
% R Humidity (Winter) 30%
% R Humidity (Summer) 50%
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( x ) Data ( x ) Audio-Video ( x ) Access Control Card Access w/KeyCCTV ( x ) Cable TV ( x )
Tele Data Special Requirements
Include emergency phones and AED (electronically monitored by security).
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2
Room Data Sheet Armed Forces Retirement Home
Gulfport, Mississippi
Room Number 712
Room Name Storage
Net Area 500
Quantity 1
Adjacency
Floor Finish Sealed Concrete
Wall Finish Paint
Base None
Ceiling Finish No Ceiling
Door Type Metal DBL
Wall Construction CMU
Casework
Equipment
Arch Notes
Temp F (Winter)
Temp F (Summer)
% R Humidity (Winter)
% R Humidity (Summer)
Special HVAC Requirements
Sink ( ) Toilet ( ) Shower ( ) Soak Tub ( ) Floor Drain ( )
Spec Plumb Requirements
Voice ( Data ( ) Audio-Video ( ) Access Control Card Access w/KeyCCTV ( ) Cable TV ( )
Tele Data Special Requirements
Sprinkler Std Wet System
Fire Suppression Notes
Provide dry pipe system if located in outbuilding.
Include on Emergency Power Genset ( )
Power Notes Not on emergency system.
SF
EA
Program Space
Architectural
Mechanical
Plumbing
Technology, Telecomunications Security
Fire Suppression System
Power
Lighting On Generator: ( ) Avg Maintained Level (fc):
Fixture Types: Switching: Standard
Lighting Notes:
Per IESNA
May 21, 2007AFRH Gulport RFP Option 2