APICE Srl
Pag. 1 MA5600 Datasheet
Fig. 1 - MA5600
MA5600 Room Management System
Product descriptionProduct descriptionProduct descriptionProduct description
MA5600 is an intelligent solution based on LONWORKS technology for room control (for hotels, offices,
schools, hospitals, barracks, etc.). A single device which, openly and interoperably, resolves control problems
such as access control, security, thermo-regulation and illumination.
Highly miniaturized as standard module DIN rail box (6 standard modules: 105 mm total).
Main Applications:
• Office Automation
• Hotel Room Automation
• Residential Areas
Main Functionalities:
Security: 3 double balanced outputs
Lighting: 1 “0-10V”output,
1 luminosity sensor input,
1 push-button input.
HVAC: Environment probe with setpoint regulation, 0-10V output used to drive 3 veloci-
ties + valve using the accessory FN010 or FN020.
Access Control: Magnetic or proximity card reader management and electric-lock output.
Fire: 1 input for smoke sensor, directly managed or with auxiliary output of the sensor
Power Load
Management:
2 available power outputs
Utility Call push-button, busy room/don’t disturb information
![Page 2: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/2.jpg)
APICE Srl
Pag. 2 MA5600 Datasheet
Flexibility
The management through LONMARKobjects allows free use of hardware resources of the device:
• 3 configurable inputs: digital, balanced, double balanced
• 1 digital input
• 3 outputs with power relais
• 1 output with 2A relais
• 1 input for temperature probe
• 1 input for setpoint adjustment
• 1 input for smoke sensors
• 1 input for luminosity sensor
• 1 input for card reader: magnetic or proximity Clock+Data
• 2 analog outputs 0-10 V
• 4 Auxiliary outputs for LED or Buzzer
• 2 Digital auxiliary inputs
Installation instructionsInstallation instructionsInstallation instructionsInstallation instructions
Location
MA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible
sources of interference (contactors, switching power).
Power Supply
Devices with different supply voltage are available: 12 VDC or extended (15-36 VDC or 12-24 VAC).
In case of extended power supply 15-36 VDC, it is recommended 24 VDC.
In case of AC power, before powering the device, verify that the output voltage from the transformer does
not exceed 26 V.
Each MA5600 absorbs 500 mA.
The cable section must be calculated based on the number of MA5600 to be powered and the distance from
the power unit.
The power supply for the electric-locks must be separated from the power supply of the terminals, the BUS
cable and the badge reader cable.
![Page 3: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/3.jpg)
APICE Srl
Pag. 3 MA5600 Datasheet
Hotel Room ApplicationHotel Room ApplicationHotel Room ApplicationHotel Room Application
Fig. 2 - An application for Hotel functionalities managed by MA5600 Equipment
![Page 4: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/4.jpg)
APICE Srl
Pag. 4 MA5600 Datasheet
Office Room ApplicationOffice Room ApplicationOffice Room ApplicationOffice Room Application
Fig. 3 - An application for Office functionalities managed by MA5600 Equipment
![Page 5: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/5.jpg)
APICE Srl
Pag. 5 MA5600 Datasheet
General WiringGeneral WiringGeneral WiringGeneral Wiring
Fig. 4 - General Wiring
![Page 6: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/6.jpg)
APICE Srl
Pag. 6 MA5600 Datasheet
InteroperabilityInteroperabilityInteroperabilityInteroperability
The Company Apice, LONMARK member and active in the security task group, paied always
attention to the interoperability. The high quantity of the HW resources did not gone against
the structure organized by LONMARKobjects. MA5600, in the two main applications, has in
total 18 and 23 objects.
The below table shows the list of the objects present in the two main applications. The Room app. is dedi-
cated to the management of generic room as an office or a residential area, the Hotel app. is for a Hotel
room.
OBJ HW Resource Type N. NV Room app Hotel app.
0 OBJ0 4 √ √ 1 IN 1 Open/Close loop sensor 2 √ √ 2 IN 2 Open/Close loop sensor 2 √ √ 3 IN 3 Open/Close loop sensor 2 √ √ 4 IN 4 Open/Close loop sensor 2 √ √ 5 IN FIRE Fire Controller 2 √ √ 6 IN TEMP. SETUP Open loop sensor 1 √ √ 7 IN LUX Open loop sensor 1 √ √ 8 IN READER Open loop sensor 1 √ √ 9 OUT 1 Open/Close loop actuator 2 √ √
10 OUT 2 Open/Close loop actuator 2 √ √ 11 OUT 3 Open/Close loop actuator 2 √ √ 12 OUT 4 Open/Close loop actuator 2 √ √ 13 ANALOG OUT 1 Open/Close loop actuator 2 √ √ 14 ANALOG OUT 2 Open/Close loop actuator 2 √ √
15 CALL PUSHBOTTON Open/Close loop sensor
2 √
16 DON’T DISTURB P.BOTTON
Open/Close loop sensor 2 √
17 BUZZER Open/Close loop actuator 2 √
18 DON’T DISTURB LED Open/Close loop actuator
2 √
19 FCU CONTROLLER 11 √ √
20 CONSTANT LIGHT CONTROLLER
4 √ √
21 ROOM CONTROLLER 17 √ 22 OCCUPANCY CONVERTER 2 √
23 OCCUPANCY CONTROLLER 6 √
24 DOOR CONTROLLER 2 √
![Page 7: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/7.jpg)
APICE Srl
Pag. 7 MA5600 Datasheet
Hardware resourcesHardware resourcesHardware resourcesHardware resources Balanced Inputs:
IN1, IN2 and IN3 inputs are qualified to link NC and
NO contacts, with balanced or double balanced line.
The configuration of the input type is selectable via
SW.
• Digital configuration NO:
• Digital configuration NC:
• Balanced line configuration:
• Double balanced line configuration:
Note for the manual configuration:
When the node has not been configured yet
(service LED flashes), pushing for more 3 sec. the
push-button, with the inputs in st.by. The input type
configuration will happen automatically, so it is pos-
sible for the technician to test immediately the cor-
rect wiring. This configuration will be saved on the
node until the technician will procede to install the
SW of the node.
![Page 8: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/8.jpg)
APICE Srl
Pag. 8 MA5600 Datasheet
On/off input:
The input 4 of the device enables to interface an
ON/OFF contact.
Smoke sensor input:
There are two different models of the equipment
according with the managing of the smoke sensor.
There is the direct management and the manage-
ment by means the auxiliary output of the sensor
LED.
Direct management of the smoke sensors:
The direct management can be made when anti-
fire certifications are not required. It allows to drive
directly up to six smoke sensors with Voltage = 12 V.
When there is an alarm, the sensor remains in alarm
until there is a reset command that takes off power
supply to the sensors. The disconnection of a sensor
will become an alarm.
Sensors management by means the LED output:
Collecting the LED auxiliary output from smoke sen-
sors of anti-fire existing system, it is possible to have
the punctual supervision of the sensors.
In this case the smoke sensor input is completely
isolated from the rest of electronic system and it
doesn’t interfere with anti-fire system. The input is
seen by the sensor as a normal LED with a limitation
resistor, as in the below picture.
Lux input:
This input directly interfaces a light sensor
(photodiode BPW21).
Light, Power and Aux outputs:
These three NO outputs include a power 16 A relais
(100 A peak) suitable even to drive directly fluores-
cent lamps. On the front of the device a LED indi-
cates the output status and a push-button allows a
manual test of each relais.
Door output:
This output includes a second relais and it is nor-
mally used to drive an electric lock or an automatic
system. The max. working voltage is 48 VDC. Also in
this case, on the front panel a LED indicates the
relais status and a push-button allows a manual
test.
![Page 9: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/9.jpg)
APICE Srl
Pag. 9 MA5600 Datasheet
Fan output:
This is a 0-10 VDC analog output that allows to
drive directly a valve or a device to control the
warm.
By means a suitable interface it is possible to
change this output in a command for three veloci-
ties or three velocities command + Valve.
Dimmer output:
This is a 0-10 VDC analog output that allows to
drive a dimmer for lighting regulation.
Reader connector:
This connector interfaces a magnetic or proximity
ISO Clock+Data card reader, a LED to indicate the
status that the card has been read, a LED tipically
used to give information as DON’T DISTURB/BUSY
and an input to be used as call pushbutton.
Using a reader PX05-BA, it is possible to have a di-
rect connection.
To use another type of reader, we suggest to use
the front end board PL8M that allows to collect the
8 contacts.
Temperature connector:
This connector interfaces a module for the tem-
perature measurement and setpoint regulation. It
includes a LED to indicate the status of the air-
conditioning system and a buzzer to repeat the call
signal or an alarm signalling. An input and an auxil-
iary output can be used for the status DON’T DIS-
TURB/BUSY.
LON connector:
This is the connector to connect the LonWorks FTT-
10 network. The line has not polarity. For more infor-
mation, please refer to Echelon specs.
![Page 10: APICE Srl · PDF fileMA5600 occupies 6 DIN modules (105 mm), must be installed in a dedicated panel, away from possible sources of interference (contactors, switching power)](https://reader031.fdocuments.us/reader031/viewer/2022030420/5aa724bb7f8b9ab8228bdbee/html5/thumbnails/10.jpg)
APICE Srl
Pag. 10 MA5600 Datasheet
Order informationOrder informationOrder informationOrder information
Item Description
110-003 MA5600, power supply 12 VDC, aux fire input 12 VDC
110-004 MA5600, power supply 15..36 VDC or 12-24 VAC, aux fire input 12 VDC
110-005 MA5600, power supply 12VDC, fire input for smoke detector
110-006 MA5600, power supply 15..36 VDC or 12-24 VAC, fire input for smoke detector