APC Unit 1

download APC Unit 1

of 24

Transcript of APC Unit 1

  • 8/13/2019 APC Unit 1

    1/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 1

    SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL 637 003DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

    Analysis of Power ConverterUNITI Single Phase AC - DC Converter

    Introduction;

    It has been said that people do not use electricity, but rather they use communication, light,

    mechanical work, entertainment, and all the tangible benefits of both energy and electronics. In this sense,

    electrical engineering as a discipline is much involved in energy conversion and information. In the general

    world of electronics engineering, the circuits engineers design and use are intended to convert information.

    This is true of both analog and digital circuit design. In radio frequency applications, energy and information

    are sometimes on more equal footing, but the main function of any circuit is information transfer. What about

    the conversion and control of electrical energy itself? Energy is a critical need in every human endeavor. The

    capabilities and flexibility of modern electronics must be brought to bear to meet the challenges of reliable,

    efficient energy. It is essential to consider how electronic circuits and systems can be applied to the

    challenges of energy conversion and management. This is the framework of power electronics, a discipline

    defined in terms of electrical energy conversion, applications, and electronic devices. More specifically,

    DEFINITION: Power electronics involves the study of electronic circuits intended to control the flow of

    electrical energy. These circuits handle power flow at levels much higher than the individual device ratings.

    1. Static Characteristics of Power Diode

  • 8/13/2019 APC Unit 1

    2/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 2

    Forward recovery time, tFRis the time required for thediode voltage to drop to a particular value after

    the forward current starts to flow.

    Reverse recovery time trr is the time interval between the application of reverse voltage and the

    reverse cur-rent dropped to a particular value as shown in Fig.

    Parameter ta is the interval between the zero crossing of the diode current to when it becomes IRR.

    On the other hand, tb is the time interval from the maximum reverse recovery current to

    approximately 0.25 of IRR. The ratio of the two parameters ta and tb is known as the softness factor

    (SF).

    Diodes with abrupt recovery characteristics are used for high frequency switching. In practice, a

    design engineer frequently needs to calculate the reverse recovery time.

    This is in order to evaluate the pos-sibility of high frequency switching. As a thumb rule, the lower

    tRR the faster the diode can be switched.

  • 8/13/2019 APC Unit 1

    3/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 3

    2. Static Characteristics of SCR

    Aplot of the anode current (iA) as a function of anodecathode voltage (vAK) is shown in Fig.

    The forward-blocking mode is shown as the low-current portion of the graph (solid curve around

    operating point 1).

    With zero gate current and posi-tivev AK, the forward characteristic in the off- or blocking-state is

    determined by the center junction J2, which is reverse biased. At operating point 1 very little

    current flows (Ico only) through the device.

    However, if the applied voltage exceeds the forward-blocking voltage, the thyristor switches to its

    on-or conducting-state (shown as operating point 2) because ofcarrier multiplication.

    The effect of gate cur-rent is to lower the blocking voltage at which switching takes place. The

    thyristor moves rapidly along the negatively-sloped portion of the curve until it reaches a stable

    operating point determined by the external circuit (point 2).

    The portion of the graph indicating forward-conduction shows the large values ofiAthat may be

    conducted at relatively low values of vAK, similar to a power diode.

    As the thyristor moves from forward-blocking to forward-conduction, the external circuit must allow

    sufficient anode current to flow to keep the device latched.

  • 8/13/2019 APC Unit 1

    4/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 4

    The minimum anode current that will cause the device to remain in forward-conduction as it switches

    from forward-blocking is called the latching current IL.

    If the thyristor is already in forward-conduction and the anode current is reduced, the device can

    move its operating mode from forward-conduction back to forward-blocking.

    The minimum value of anode current nec-essary to keep the device in forward-conduction after it has

    been operating at a high anode current value is called the holding currentIH.

    The holding current value is lower than the latching current value as indicated in Fig. The reverse

    thyristor characteristic, quadrant III of Fig. is determined by the outer two junctions (J1 and J3),

    which are reverse biased in this operating mode (appliedvAKis neg-ative).

    Symmetric thyristors are designed so that J1will reach reverse breakdown due to carrier

    multiplication at an applied reverse potential near the forward breakdown value (operating point 3

    in Fig.

    The forward- and reverse-blocking junc-tions are usually fabricated at the same time with a very long

    diffusion process (1050h) at high temperatures (>1200C). This process produces symmetric

    blocking properties.

    Wafer edge termination processing causes the forward-blocking capability to be reduced to about

    90% of the reverse-blocking capability. Edge termination is discussed below.

    Asymmetric devices are made to optimize forward-conduction and turn-off properties, and as such

    reach reverse breakdown at a lower voltage than that applied in the forward direction.This is accomplished by designing the asymmetric thyristor with a much thinnern-base than is used in

    symmetric structures. The thin n-base leads to improved properties such as lower for-ward drop and

    shorter switching times.

    Asymmetric devices are generally used in applications when only forward volt-ages (positive,vAK)

    are to be applied (including many inverter designs).

  • 8/13/2019 APC Unit 1

    5/24

  • 8/13/2019 APC Unit 1

    6/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 6

    whereV0 =voltage intercept, models the voltage across the cathode and anode forward biased

    junctions andR0=on state resistance.

    When average and RMS values of on-state current (ITAV, ITRMS) are known, then the on-state

    power dissipation PON can be determined usingV0andR0. That is,

    Off State Characteristics

    Unlike the standard thyristor, the GTO does not include cathode emitter shorts to prevent

    non-gated turn-on effects due todv/dtinduced forward biased leakage current.

    In the off-state of the GTO, steps should, therefore, be taken to prevent such potentially

    dangerous triggering. This can be accomplished by either connecting the recommended value

    of resistance between the gate and the cathode (RGK) or by main-taining a small reverse bias

    on the gate contact (VRG=2V).

    This will prevent the cathode emitter becoming forward biased and therefore sustain the GTO

    thyristor in the off state.

    The peak off-state voltage is a function of resistanceRGK. This is shown in Fig. Under

    ordinary operating con-ditions, GTOs are biased with a negative gate voltage of around15V

    supplied from the gate drive unit during the off-state interval.

    Nevertheless, provision ofRGKmay be desir-able design practice in the event of the gate-

    drive failure for any reason (RGK

  • 8/13/2019 APC Unit 1

    7/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 7

    Single phase fully controlled half wave rectifier with R load

    This is the simplest and probably the most widely used rectifier circuit albeit at relatively small

    power levels.

    The output voltage and current of this rectifier are strongly influenced by the type of the load. In

    this section, operation of this rectifier with resistive, inductive and capacitive loads will be

    discussed.

    Fig shows the circuit diagram and the waveforms of a single phase

    uncontrolled half wave rectifier. If the switch S is closed at at t = 0, the diode

    D becomes forward biased in the the interval 0 < t . If the diode is

    assumed to be ideal then

    With a resistive load ripple factor of i0 will also be same.

    Because of such high ripple content in the output voltage and current this

    rectifier is seldom used with a pure resistive load.

  • 8/13/2019 APC Unit 1

    8/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 8

    The ripple factor of output current can be reduced to same extent by

    connecting an inductor in series with the load resistance as shown in Fig 2.3 (a).

    As in the previous case, the diode D is forward biased when the switch S is

    turned on. at t= 0.

    However, due to the load inductance i0 increases more slowly. Eventually at t

    = ,v0 becomes zero again. However, i0 is still positive at this point. Therefore,

    D continues to conduct beyond t = while the negative supply voltage is

    supported by the inductor till its current becomes zero at t= .

    Beyond this point, D becomes reverse biased. Both v0 and i0 remains zero till the

    beginning of the next cycle where upon the same process repeat

  • 8/13/2019 APC Unit 1

    9/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 9

  • 8/13/2019 APC Unit 1

    10/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 10

    Single phase fully controlled half wave rectifier with RL load

    Fig. shows the circuit diagram of a single phase fully controlled halfwave rectifier

    supplying a purely resistive load.

    At t = 0 when the input supply voltage becomes positive the thyristor T becomes

    forward biased. However, unlike a diode, it does not turn ON till a gate pulse is

    applied at t= .

    During the period 0 < t ,the thyristor blocks the supply voltage and the load voltage

    remains zero as shown in fig 10.1(b). Consequently, no load current flows during this

    interval.

    As soon as a gate pulse is applied to the thyristor at t= it turns ON. The voltage across

    the thyristor collapses to almost zero and the full supply voltage appears across the load.

    From this point onwards the load voltage follows the supply voltage.

    The load being purely resistive the load current io is proportional to the load voltage. At

    t = as the supply voltage passes through the negative going zero crossing the load

    voltage and hence the load current becomes zero and tries to reverse direction.

    In the process the thyristor undergoes reverse recovery and starts blocking the negative

  • 8/13/2019 APC Unit 1

    11/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 11

    supply voltage. Therefore, the load voltage and the load current remains clamped at zero

    till the thyristor is fired again at t= 2+ .

  • 8/13/2019 APC Unit 1

    12/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 12

    Single phase fully controlled bridge converter RLE Load

  • 8/13/2019 APC Unit 1

    13/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 13

    Fig shows the circuit diagram of a single phase fully controlled bridge converter.

    It is one of the most popular converter circuits and is widely used in the speed

    control of separately excited dc machines. Indeed, the RLE load shown in this figure may represent the electrical

    equivalent circuit of a separately excited dc motor. The single phase fully controlled

    bridge converter is obtained by replacing all the diode of the corresponding

    uncontrolled converter by thyristors.

    Thyristors T1 and T2 are fired together while T3 and T4 are fired 180 after T1 and

    T2. From the circuit diagram of Fig 10.3(a) it is clear that for any load current to

    flow at least one thyristor from the top group (T1, T3) and one thyristor from the

    bottom group (T2, T4) must conduct.

    It can also be argued that neither T1T3 nor T2T4 can conduct simultaneously For

    example whenever T3 and T4 are in the forward blocking state and a gate pulse is

    applied to them, they turn ON and at the same time a negative voltage is applied

    across T1 and T2 commutating them immediately.

    Similar argument holds for T1 and T2. For the same reason T1T4 or T2T3 can not

    conduct simultaneously.

    Therefore, the only possible conduction modes when the current i0 can flow are

    T1T2 and T3T4. Of course it is possible that at a given moment none of the

    thyristors conduct.

    This situation will typically occur when the load current becomes zero in between

    the firings of T1T2 and T3T4. Once the load current becomes zero all thyristors

    remain off.

    In this mode the load current remains zero. Consequently the converter is said to be

    operating in the discontinuous conduction mode. Fig shows the voltage across

    different devices and the dc output voltage during each of these conduction modes.

    It is to be noted that whenever T1 and T2 conducts, the voltage across T3 and T4

    becomesvi. Therefore T3 and T4 can be fired only when vi is negative i.e, over the

    negative half cycle of the input supply voltage.

    Similarly T1 and T2 can be fired only over the positive half cycle of the input

  • 8/13/2019 APC Unit 1

    14/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 14

    supply. The voltage across the devices when none of the thyristors conduct

    depends on the off state impedance of each device.

    The values listed in Fig assume identical devices. Under normal operating

    condition of the converter the load current may or may not remain zero over

    some interval of the input voltage cycle.

    If i0 is always greater than zero then the converter is said to be operating in the

    continuous conduction mode. In this mode of operation of the converter T1T2 and

    T3T4 conducts for alternate half cycle of the input supply.

    Continuous Conduction Mode:

    As has been explained earlier in the continuous conduction mode of operation i0never

    becomes zero, therefore, either T1

    T2

    or T3

    T4

    conducts. Fig. shows the waveforms of

    different variables in the steady state. The firing angle of the converter is . The angle

    is given by

    It is assumed that at t = 0-

    T3T

    4was conducting. As T

    1T

    2are fired at t = they turn on

    commutating T3

    T4

    immediately. T3

    T4

    are again fired at t = + . Till this point T1

    T2

    conducts. The period of conduction of different thyristors are pictorially depicted in the

    second waveform (also called the conduction diagram)

  • 8/13/2019 APC Unit 1

    15/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 15

  • 8/13/2019 APC Unit 1

    16/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 16

    The dc link voltage waveform shown next follows from this conduction diagram and the

    conduction table shown in Fig (b). It is observed that the emf source E is greater than the dc

    link voltage till t = . Therefore, the load current i0continues to fall till this point.

    However, as T1T

    2are fired at this point v

    0becomes greater than E and i

    0starts increasing

    through R-L and E. At t = v0

    again equals E. Depending upon the load circuit

    parameters io

    reaches its maximum at around this point and starts falling afterwards.

    Continuous conduction mode will be possible only if i0

    remains greater than zero till T3T

    4are

    fired at t = + where upon the same process repeats.

    The resulting i0

    waveform is shown below v0. The input ac current waveform i

    iis obtained

    from i0by noting that whenever T

    1T

    2conducts i

    i= i

    0and i

    i= - i

    0whenever T

    3T

    4conducts. The

    last waveform shows the typical voltage waveform across the thyristor T1.

    It is to be noted that when the thyristor turns off at t = + a negative voltage is applied

    across it for a duration of . The thyristor must turn off during this interval for successful

    operation of the converter.

    It is noted that the dc voltage waveform is periodic over half the input cycle. Therefore, it

    can be expressed in a Fourier series as follows.

  • 8/13/2019 APC Unit 1

    17/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 17

    Fourier series expression of v0is important because it provides a simple method of estimating

    individual and total RMS harmonic current injected into the load as follows:

    The impedance offered by the load at nth harmonic frequency is given by

    it can be argued that in an inductive circuit IonRMS

    0 as fast as 1/n2

    . So in practice it will be

    sufficient to consider only first few harmonics to obtain a reasonably accurate estimate of

    IOHRMS

    form equation This method will be useful, for example, while calculating the required

    current derating of a dc motor to be used with such a converter.

  • 8/13/2019 APC Unit 1

    18/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 18

    However to obtain the current rating of the device to be used it is necessary to find out a

    closed form expression of i0. This will also help to establish the condition under which the

    converter will operate in the continuous conduction mode.

    To begin with we observe that the voltage waveform and hence the current waveform is

    periodic over an interval . Therefore, finding out an expression for i0

    over any interval of

    length will be sufficient. We choose the interval t + .

    Now at steady state 00t=t=+i=i since i0is periodic over the chosen interval. Using this

    boundary condition we obtain

  • 8/13/2019 APC Unit 1

    19/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 19

    Dis Continuous Conduction Mode:

    So far we have assumed that the converter operates in continuous conduction mode without

    paying attention to the load condition required for it. In figure 10.4 the voltage across the R

    and L component of the load is negative in the region - t + .

    Therefore i0continues to decrease till a new pair of thyristor is fired at t = + . Now if the

    value of R, L and E are such that i0becomes zero before t = + the conduction becomes

    discontinuous.

    Obviously then, at the boundary between continuous and discontinuous conduction the

    minimum value of i0

    which occurs at t = and t = + will be zero. Pu tting this

    condition in we obtain the condition for continuous conduction as.

  • 8/13/2019 APC Unit 1

    20/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 20

    Fig shows waveforms of different variables on the boundary between continuous and

    discontinuous conduction modes and in the discontinuous conduction mode.

    It should be stressed that on the boundary between continuous and discontinuous conductionmodes the load current is still continuous.

    Therefore, all the analysis of continuous conduction mode applies to this case as well. However

    in the discontinuous conduction mode i0

    remains zero for certain interval. During this interval

    none of the thyristors conduct.

    These intervals are shown by hatched lines in the conduction diagram of Fig 10.6(b). In this

    conduction mode i0

    starts rising from zero as T1T

    2are fired at t = . The load current continues

    to increase till t = . After this, the output voltage v0falls below the emf E and i

    0decreases

    till t = when it becomes zero.

    Since the thyristors cannot conduct current in the reverse direction i0

    remains at zero till t = +

    when T3and T

    4are fired. During the period t + none of the thyristors conduct.

  • 8/13/2019 APC Unit 1

    21/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 21

    During this period v0

    attains the value E. Performance of the rectifier such as VOAV

    , VORMS

    ,

    IOAV

    , IORMS

    etc can be found in terms of , and . For example

    It is observed that the performance of the converter is strongly affected by the value of . The

    value of in terms of the load parameters (i.e, , and Z) and can be found as follows.

  • 8/13/2019 APC Unit 1

    22/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 22

    Inverter mode of operation:

    The expression for average dc voltage from a single phase fully controlled converter in

    continuous conduction mode was

    For < /2, Vd

    > 0. Since the thyristors conducts current only in one direction I0

    > 0 always.

    Therefore power flowing to the dc side P = V0I0

    > 0 for < /2. However for > /2, V0

    < 0.

    Hence P < 0. This may be interpreted as the load side giving power back to the ac side and the

    converter in this case operate as a line commutated current source inverter.

    So it may be tempting to conclude that the same converter circuit may be operated as an

    inverter by just increasing beyond /2. This might have been true had it been possible to

    maintain continuous conduction for < /2 without making any modification to the converter

    or load connection.

    To supply power, the load EMF source can be utilized. However the connection of this source

    in Fig 10.3 is such that it can only absorb power but can not supply it. In fact, if an attempt is

    made to supply power to the ac side (by making > /2) the energy stored in the load inductor

    will be exhausted and the current will become discontinuous as shown in Fig.

  • 8/13/2019 APC Unit 1

    23/24

    APC UNIT I

    Prepared By Mr.M.RAVICHANDRAN AP / EEE Page 23

    Therefore for sustained inverter mode of operation the connection of E must be reversed as

    shown in Fig (b). Fig (a) and (b) below shows the waveforms of the inverter operating in

    continuous conduction mode and discontinuous conduction mode respectively. Analysis of

    the converter remains unaltered from the rectifier mode of operation provided is defined as

    shown below

  • 8/13/2019 APC Unit 1

    24/24

    APC UNIT I

    Prepared By Mr M RAVICHANDRAN AP / EEE Page 24

    Prepared By Approved By

    M.Ravichandran Prof.P.Manimekalai

    AP / EEE HOD / EEE