Anti-islanding
-
Upload
nit-meghalaya -
Category
Engineering
-
view
209 -
download
0
Transcript of Anti-islanding
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
Satabdy Jena, Gayadhar Panda and Rangababu Peesapati
Presented by:
Dr. Rangababu Peesapati
Assistant Professor
National Institute of Technology Meghalaya
India.
Outline
Introduction
Topology of the system
DG Inverter Control
DG Islanding & Anti-islanding protection schemes for grid connected inverter system
Simulation Study
HIL co-simulation of grid-connected inverter system
Conclusion
Future Scope
References211/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
Introduction
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 3
• Conventional resources are under immense pressure due to increasing population
and increasing demand.
• Renewable energy resources have emerged as the most promising alternative.
• Grid Interfaced Distributed Generation (DG) possess the potential to meet local
demand of power as well as feed the excess power to the grid.
• Safety of critical loads, devices and personnel: Reliable tripping is required.
• Anti-islanding detection.
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 4
Fig.1. Topology of system
MPPT PWMSPWM MAF-
PLL
Modulating
Signal
Generation
DC-
LINK
PI
PV
+-
V*dc
vdc
3-ф
Inverter
Filter
Inductance
Isolation
Transformer
ia,b,c
ua,b,c
iq*
id*
iq
uq
Grid
abc
dq
ud* uq*
DC/DC
Boost
Converter
LfRf
Cf LtRt
ϴ ϴ
Reference
Signal
Generation
md
q
Xilinx System Generator
ipv
vpv LOAD
Anti-islanding
Protection
B2B1
TripTrip
Trip
f
PCC
id
iq
+
+
-
-
PI
PI
id
ud
ωL
+
+
+
++
-
ωL
Decoupling
Technique
MATLAB/Simulink
FPGA ML605
Evaluation platform
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 5
Moving Average Filter (MAF) : linear-phase finite impulse response filter
• Easy to realize in practice
• Effective in terms of computational burden
• 𝐺𝑀𝐴𝐹 =1
𝑁
1−𝑧−𝑁
1−𝑧−1
* *u * K (i i ) K (i i )dt ωLi uq p q q i q q d q
* *u * K (i i ) K (i i )dt ωLi ud p d d i d d q d
Decoupling Control : Control of d-q axes currents
DG Inverter Control
ωf
PI + ʃ
0
ω'θ
-+abc
dq
uq++
Z-1 Z-N
1
N+-
MAF
Kf
ua,b,c
Fig.2. MAF-Phase Locked Loop
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 6
DG Islanding
Islanding: DG continues to supply power to a location even though the electric utility is not present.
Types-
• Intentional
• Unintentional
Problems-
• Safety concerns
• End-user equipment damage
• Degradation of electrical components
• Out of phase reclosing of DG
11/13/2016 7
Remote Protection Schemes: Active and Passive.
Employed Schemes-
DC-Link protection
Over and Under frequency protection
Rate of change of frequency
The FPGA implementation enables for the automation of
the grid.
>
>
>
OR
OR
+-
(a)
(b)
(c)
˂
˂
z-1
d
dt β
vdc
vdc,high
vdc,low
flow
fhigh
f
f
Trip
Trip
Trip
Fig.3. AI Protection Schemes
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
Anti islanding Protection Schemes
The following cases were investigated :
• Loads less than the PV generation
• Resistive (P = 50 kW)
• Inductive (P = 50 kW, Q = 10 kVAr)
• Capacitive (P = 50 kW, Q = 10 kVAr)
• Loads greater than the PV generation
• Resistive (P = 110 kW)
• Inductive (P = 110 kW, Q = 50 kVAr)
• Capacitive (P = 110 kW, Q = 50 kVAr)
• Loads equal to PV generation
• Resistive (P = 80 kW)
• Inductive (P = 80 kW, Q = 50 kVAr)
• Capacitive (P = 80 kW, Q = 50 kVAr)
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 8
Simulation Study
System parameters Value System parameters Value
Series connected modules 7 DC Link voltage 750 V
Parallel connected
modules
40 Filter inductance and resistance 1 mH, 3 mΩ
MPP Voltage 54.7 V Grid inductance and resistance 16 mH, 0.8929 Ω
MPP Current 5.58 A Transformer inductance and
resistance
0.06 mH, 0.002 mΩ
Open-circuit voltage 64.2 V Inverter switching frequency 5 .5 kHz
Short-circuit current 5.96 A Boost switching frequency 5 kHz
Maximum PV power
(STC, S = 1000 W/m2)
85 kW Grid voltage 400 V
DC Link capacitor 5000 μF Grid frequency 50 Hz
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 9
Table 1. System parameters
11/13/2016 10
Local loads less than PV generation: (a) Resistive load (P=50 kW)
(b) Inductive load (P=50 kW, Q=10 kVAr)Fig.4. Power exchange Fig.5. Relay response
Fig.6. Power exchange Fig.7. Relay response
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 11
(c) Capacitive load (P=50 kW, Q=10 kVAr)
Fig.9. Relay responseFig.8. Power Exchange
Fig.10. Frequency deviation Fig.11. Voltage deviation
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 12
Local loads greater than PV generation: (a) Resistive load (P=110 kW)
(b) Inductive load (P=110 kW, Q=50 kVAr)
Fig.12. Power Exchange Fig.13. Relay response
Fig.15. Relay responseFig.14. Power Exchange
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 13
(c) Capacitive load (P=110 kW, Q=50 kVAr)
Fig.16. Power Exchange Fig.17. Relay Response
Fig.18. Frequency deviationFig.19. Voltage deviation
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 14
Local loads equal to PV generation: (a) Active load (P=80 kW)
(b) Inductive load (P=80 kW, Q=50 kVAr)
Fig.20. Power Exchange Fig.21. Relay Response
Fig.22. Power Exchange Fig.23. Relay Response
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 15
(c) Capacitive load (P=80 kW, Q=50 kVAr)
Fig.25. Relay ResponseFig.24. Power Exchange
Fig.26. Frequency deviationFig.27. Voltage deviation
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 16
Table 2. Comparison of Relay Response
Gen-load
Relay
Load less than PV power Load more than PV power Load equals PV power
Resistive
(Relay
Time (s))
Inductive
(Relay
Time (s))
Capacitive
(Relay
Time (s))
Resistive
(Relay
Time (s))
Inductive
(Relay
Time (s))
Capacitive
(Relay
Time (s))
Resistive
(Relay
Time (s))
Inductive
(Relay
Time (s))
Capacitive
(Relay Time
(s))
Over-
Frequency
No
Trip
0.0792 No
Trip
0.1107 0.0732 0.0438 0.0764 0.0735 No
Trip
Under-
Frequency
0.3407 No
Trip
0.177 0.3417 No
Trip
No
Trip
0.3774 No
Trip
0.1077
ROCOF 0.0121 0.0864 0.0293 0.0296 0.0315 0.0293 0.0429 0.0486 0.0084
DC-Link 0.07123 0.0132 0.0295 0.0297 0.0317 0.0295 0.0431 0.0487 0.0085
Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 17
Simulink as FPGA design tool is easy to use as there is no need of learning HDL.
Hardware co-simulation is achieved by Xilinx System Generator which puts hardware into Simulink
design.
It enables automatic data exchange.
It supports FPGA chips with JTAG programming.
HIL Co-simulation study
Fig.28. FPGA building blocks Fig.29. Configuration of each logic block
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 18
HIL Implementation
Fig.30. Ani-islanding protection schemes in XSG
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 19
Fig.31. PLL, Reference Signal generation and Voltage controller in XSG
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 20
Fig.32. Behavioral simulation for (a) PLL (b) Current Controller (c) SPWM
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 21
Design Slice
Registers
(301440)
Slice
LUTs
(150720)
LUT FF
Pairs
Slices
(37680)
IOBS
(600)
Memory
(58,400)
Critical Path delay
ns
( Maximum Freq
MHz)
PLL 139(1%) 962(1%) 123(12%) 283(1%) 59(10%) 33 (1%) 1.695
SPWM 0(0%) 57(1%) 0(0%) 20(1%) 92(15%) 0(0%) 3.220
Current
Controller
96(1%) 6410(4%) 62(1%) 1947(5%) 257(42%) 0(0%) 0.559
Voltage
Controller
48(1%) 1905(1%) 31(1%) 568(1%) 65(10%) 0(0%) 0.552
PWM 0 8(1%) 0(0%) 3(1%) 33(5%) 0(0%) 2.209
Reference
Signal
Generation
2306 (1%) 4765 (3%) 2250 (46%) 1374 (3%) 307 (51%) 25 (0%) 9.484
Table 3. Resource Utilization by the blocks
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 22
Fig.34. Experimental Testbed
• ML605• XILINX 14.2• Matlab 2012a
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 23
Fig.35. Relay response for load demand more than PV generation (a) Resistive (b) Inductive load
Fig.36. Relay response for load demand less than PV generation (a) Resistive (b) Inductive load
(a)
(a) (b)
(b)
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 24
Fig.37. Relay response for load demand equal to PV generation (a) Resistive (b) Capacitive load
(a) (b)
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 25
Gen-load
Relay
Load less than PV power Load more than PV power Load equals PV power
Resistive
(Relay
Time (s))
Inductive
(Relay
Time (s))
Capacitive
(Relay
Time (s))
Resistive
(Relay
Time
(s))
Inductive
(Relay
Time (s))
Capacitive
(Relay
Time (s))
Resistive
(Relay
Time (s))
Inductive
(Relay
Time (s))
Capacitive
(Relay
Time (s))
Over-
Frequency
No
Trip
0.3448 No
Trip
0.1107 0.0655 0.077 0.0942 0.0977 No
Trip
Under-
Frequency
0.381 0.069 0.0718 0.3417 0.381 No
Trip
No
Trip
0.4963 0.1086
ROCOF 0.0256 0.03 0.0293 0.02 0.0267 0.02 0.02 0.03 0.003
DC-Link 0.0655 0.0224 0.0295 0.0401 0.03 0.06 0.0401 0.0501 0.0501
Table 4. Comparison of Relay Response in HIL
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 26
The synchronization of DG inverter with the grid was made possible by the help
of Decoupling Control and MAF-PLL.
The performance of the DG inverter control and the anti-islanding detection
schemes was studied under various conditions in time-domain simulation using
Matlab/Simulink.
The effectiveness of the proposed controllers and islanding detection schemes was
validated by developing a hardware-in-loop simulation using XSG.
The HIL response of the employed schemes were found to conform to its
simulation counterpart.
Conclusion
Application of signal processing techniques for detection of islanding.
Real time implementation of the proposed system.
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 27
Future Scope
References
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 28
[1] Craig Abbey, Yves Brissette, and Philippe Venne, “An autoground system for anti-islanding protection of distributed
generation,” IEEE Transactions on Power & Energy Systems, vol. 29,no. 2, pp. 873-880,2014.
[2] Soummya Kar and Subhransu R Samantaray,“Data-mining-based intelligent anti-islanding protection relay for
distributed generations,” IET Generation, Transmission & Distribution,vol.8, no.4, pp.629-639,2014.
[3] Antonis G Tsikalakis and Nikos D Hatziargyriou, ,“Operation of microgrids with demand side bidding and
continuity of supply for critical loads,” European Transactions on Electrical Power, vol.21.,No.2, PP.1238-1254, 2011.
[4] J A Pecas Lopes, N Hatziargyriou, J Mutale, P Djapic, and N Jenkins,“Integrating distributed generation into electric
power systems: A review of drivers, challenges and opportunities,” Electric power systems
research, vol.77,no.9,pp.1189-1203,2007.
[5] Morris Brenna, Federica Foiadelli, Paola Petroni, Gianluca Sapienza,and Dario Zaninelli,“Distributed Generation
Regulation for Intentional Islanding in Smart Grids,” Proceedings of Innovative Smart Grid Technologies,
IEEE PES,pp.1-6,2012.
[6] IEEE Std. 1547-2003, “IEEE Standard for Interconnecting Distributed Resources With the Electric Power System,”
[7] Mehrnoosh Vatani,Turaj Amraee, Ali Mohammad Ranjbar, and Babak Mozafari,“Relay logic for islanding detection
in active distribution systems,” IET Generation, Transmission & Distribution, vol. 9, no.12, pp.1254-1263,2015
[8] Nahla E Zakzouk,Mohamed A Elsaharty,Ahmed K Abdelsalam,Ahmed A Helal, and Barry W Williams, ,“Improved
performance low-cost incremental conductance PV MPPT technique,” IET Renewable Power Generation,2016.
[9] Dong Dong, Bo Wen, Dushan Boroyevich, Paolo Mattavelli, and Yaosuo Xue, ,“Analysis of phase-lockedloop low-frequency stability in three-phase grid-connected power converters considering impedanceinteractions,” IEEE Transactions on Industrial Electronics,vol.62 ,no.1,pp.310-321,2015
[10] S.J.Huang and F.S.Pai,“Design and operation of grid connected phototvoltaic system with power factorcontrol and active islanding detection,” IEEE Proceedings on Generation, Transmission,Distribution,vol.48,No.2,2001.
[11] Rajasekar Selvamuthukumaran and Rajesh Gupta, “Rapid prototyping of power electronics converters forphotovoltaic system application using Xilinx System Generator,” IET Power Electronics,vol.7,no.9,pp.22692278,2014, 2011.
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 29
Thank you
11/13/2016 Investigation on FPGA based Passive Anti-Islanding Protection Schemes for Grid Interfaced Distributed Generation System 30