![Page 1: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/1.jpg)
Building Systems and Performance: an
Introduction to Building Operator
Certification –
Lesson 10: Control Principles, Terms,
and Concepts
CUNY Institute for Urban Systems Building Performance Lab
![Page 2: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/2.jpg)
Lesson 9 Review
![Page 3: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/3.jpg)
Control Principles, Terms, and Concepts Agenda
• Control principles, terminology and concepts.
• Types of controls and control systems.• Sequences of operation.• Maintenance of Controls.
![Page 4: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/4.jpg)
What are Controls?• “Controls are simply devices
that try to duplicate the human thought process. With HVAC controls, the controls are designed to carry out the thoughts and desires of the HVAC system designer.”
• Definition by American Society of Heating, Refrigeration & Air Conditioning Engineers (ASHRAE)
4
![Page 5: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/5.jpg)
What are Controls?
• Controls are the brains of the HVAC system: they directly impact energy use, Indoor Air Quality (IAQ), facility safety and the environment.
• Not just temperature! What else do we control?• Energy• Relative Humidity/dew point• CO2/CO• Pressure• Velocity, Flow, Air Changes, and more
5
![Page 6: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/6.jpg)
Control Acronyms
• ATC – Automatic Temperature Control
• EMS – Energy Management System
• EMCS – Energy Management Control System
• BMS – Building Management System
• BAS – Building Automation System
• CSCS – Central Supervisory Control System
• DDC – Distributed Digital Control
6
![Page 7: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/7.jpg)
Control Concepts - TerminologyControlled Variable the temperature, humidity, pressure, velocity, or other condition
being controlled.Sensor the device that measures the condition of the controlled variable. In
an open system the measurement signal (pneumatic, electric, electronic) is sent to the controller.
Set point the desired value of the controlled variable.Controller the device that compares state of controlled variable from sensor
(temp, pressure, etc.) and signals the controlled device for corrective action if needed: a comparator.
Controlled device the hardware (valve, damper, variable speed drive (VSD), electric reheat, etc.) manipulated by the controller.
Control agent the medium (gas, chilled water, conditioned air) manipulated by the controlled device.
Control process the apparatus being controlled; steam heat, DX system, fan. The control process reacts to the control agent output and effects change in the controlled variable.
Control loops open or closed. Actuator manipulates the controlled device, e.g. motor on a hot water valve to
a heating coil.
7
![Page 8: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/8.jpg)
Control Concepts – More Terms• Control point is the actual value of the controlled variable such as the space temperature.
• Deadband occurs when there is neither heating nor cooling.
• Error is the difference between control point and desired set point
• Range and span refer to the variable points over which the sensors and controllers operate. Range
refers to the sensing elements. Span refers to the controller.
• Throttling range is the amount of change in the controlled variable that causes the controlled device to move from one extreme to the other, from full open to full closed.
• Authority refers to the priority ranking of two, or more, sensors.
• Calibration is the verification, and adjustment if necessary, of the accuracy of a sensor or controller.
Calibration should be done regularly.
• Analog and digital refer to the input/output signal type. Analog is a varying parameter such as temperature or pressure and can have many numbers. Digital is two state (0 or 1) and can represent
on/off or open/closed.
• A thermostat can be any sensor and controller combination.
• Time delay relays are used to deliberately provide time delays in a control action. For, example, time
delay relays are used in boiler systems to delay the firing of the burner until the boiler has completed the pre-purge cycle.
8
![Page 9: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/9.jpg)
Control Loops
sensor controller controlled variable
Open Loop Control • light sensor for outdoor lights• motion sensor for indoor lights• time-clock for on/off of any device
Closed Loop Control • Thermostat for room temperature• Boiler Pressure Control• Lighting Level Control with Dimming
sensor controller controlled variable
9
![Page 10: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/10.jpg)
Control Concepts
• Control action• Two position control
• On/Off or Open/Closed Control• Modulating Control (P, PI, PID)
• Proportional: controller output signal is in proportion to the error (deviation from set-point)
• Proportional-Integral: adds a mathematical value to adjust the control action in relation to the average error
• Proportional-Integral-Derivative: looks at the rate of change of the controlled variable
10
![Page 11: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/11.jpg)
2 Position Control
• Digital (Two position) Output
• Upper Limit and Lower Limit (for example, cooling on at 78 and off at 76)• Change of output based on analog input crossing limits (i.e.
temperature going above or below limits)
• Applications• Temperature control• Freeze stats• Moderate to slow responding control loops• Step Control: Multi speed motors, multi stage burners, multi
stage compressors
11
![Page 12: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/12.jpg)
Two Position ControlAn example of this type of control is an exhaust fan that comes on/off to maintain space temperature. Could come on at 90 and off at 85.
12
![Page 13: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/13.jpg)
Modulating Control• PID Terms / Mathematical Relationships
• V=output of controller• V= proportional control + integral control + derivative
control• V= Kp(e) + Ki (∫edt) + Kd (de/dt)• e=error• t=time• d=differential• ∫ = integral symbol• Kp=proportional gain• Ki=integral gain• Kd=derivative gain
13
![Page 14: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/14.jpg)
Proportional Only Control• Simple / Common
• “Happy with Offsets” which means once control loop settles out there will be a difference between desired value and set point
• @ set point, e=0
• Proportional gain is the amount of change in controller output signal for a given change in the difference between controlled variable and its set point (error)
• Kp=controller proportional gain• Large gain, small offset• Large gains can cause hunting• When tuning control loops this is the variable you are adjusting
14
![Page 15: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/15.jpg)
Proportional (P) ControlAn example of this type of control is a hot water control valve modulating to maintain a temperature set point. There is always offset. The controlled variable never stays at set point.
15
![Page 16: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/16.jpg)
Proportional plus Integral (PI) Control
An example of this type of control is a chilled water control valve maintaining 55 degree F air temperature on an air handling unit. There is no offset. The controlled variable gets to set point and stays there.
16
![Page 17: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/17.jpg)
Proportional + Integral + Derivative (PID) Control
• Applies the brakes to the integral term
• Very fast response
• Used in industrial processes and rocketry (in-space flight controls)
• Not common in hvac (except lab air flow tracking, etc.)
17
![Page 18: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/18.jpg)
Types of Controls and Control Systems
• Classified by Energy Sources:
• Pneumatic• Self Acting
• Electric
• Distributed Digital Control (DDC)
18
![Page 19: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/19.jpg)
Pneumatic Controls• Powered by compressed air
• Inherently modulating
• Simple
• Low cost
• Reliable
• Explosion proof
• Compressed air is an open protocol
• Obsolescence has been predicted since 1950’s (not installed in new buildings, many remain in existing buildings)
19
![Page 20: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/20.jpg)
Pneumatic System Diagram20
![Page 21: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/21.jpg)
Pneumatic Control - O&M
• What are things that need routine maintenance?
• Belt
• Pressure settings
• Compressor wear
• Oil
• Moisture
system leakage will increase compressor run-time
21
![Page 22: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/22.jpg)
Pneumatic Thermostat
• How do these work? They utilize springs, mechanical levers, valves/nozzles and bellows that are all energized by compressed air .
• Why are these devices hard to keep calibrated? Parts wear out.
• Why might there be air leakage? Fixable? Sometimes it is fixable. Some are designed to leak air (bleed type)
22
![Page 23: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/23.jpg)
Example of Pneumatic Action• Direct Acting / Normally Open (DA/NO)
• Direct-acting: increase in the level of the sensor signal results in an increase level of controller output (outlet air pressure to actuator)
• Stem down closes valve• Normally retracted valve stem• Air pressure pushes diaphragm/stem down
• Reverse Acting / Normally Closed (RA/NC)• Reverse-acting: increase in level of sensor signal results in
decreased controller output• Stem down opens valve• Normally extended stem• Air pressure pushes diaphragm/stem up
23
![Page 24: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/24.jpg)
Pneumatic Thermostat Action
Air pressure is fallingTemperature is falling Direct acting
Air pressure is risingTemperature is rising Direct acting
Air pressure is fallingTemperature is rising Reverse acting
Air pressure is risingTemperature is falling Reverse acting
24
![Page 25: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/25.jpg)
Pneumatic Thermostats• Day/Night Set Points
• Heat/Cool Set Points
• Different manufacturers use different pressures:Mfr Day (psi) Night
(psi)Honeywell 13 18Johnson 15 20Siemens 18 25Barber Coleman
15 20
Robertshaw 16 25
25
![Page 26: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/26.jpg)
Pneumatic Actuators• Metal cylinder, piston, flexible diaphragm and a
spring
• Normal position versus actuated position• What does “Normal” mean in controls?
• The de-energized position. The failed position.
26
![Page 27: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/27.jpg)
Pneumatic ActuatorsRequired air pressure is determined via spring range.
• Honeywell book pages 74 and 75: Figures 26 & 27:
• http://customer.honeywell.com/techlit/pdf/77-0000s/77-E1100.pdf
27
![Page 28: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/28.jpg)
Pneumatic Control Valves
Diaphragm
DIAPHRAGM
28
![Page 29: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/29.jpg)
Pneumatic Valve Actuators•NO (normally open)
• Spring opens valve• Valve fails open• Valve and actuator have same
action • DA actuator with DA valve• RA actuator with RA valve
•NC (normally closed)• Spring closes valve• Valve fails closed• Valve and actuator have
opposite action • RA actuator with DA valve• DA actuator with RA valve
Fig. 6.6.5 Net effect of various combinations for two port valves (Arrangement of spring/diaphragm/port/valve seat dictates RA or DA action):
http://www.spiraxsarco.com/resources/steam-engineering-tutorials/control-hardware-el-pn-actuation/control-valve-actuators-and-positioners.asp
29
![Page 30: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/30.jpg)
Pneumatic Valve Actuators
• Positive Pilot Positioners• Actual position of controlled device might not
correspond to signal expectations• Friction, binding, aging, corrosion, spring range
drift, etc.• Amplifier/relay that corrects for the above• Moves valve to desired position if valve position
does not match signal
30
![Page 31: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/31.jpg)
Pneumatic Damper Actuators
• Functions:• Open/close• Vary flow• Hold position• Meet sequences• Provide min/max range• Provide feedback
• NO/NC is dependent on push rod linkage arrangement (linkage that connects damper to actuator)
31
![Page 32: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/32.jpg)
E/P Switch
Interface the old pneumatics to the new electrical controls
Early steps towards Direct Digital Control Systems (DDC)
Pneumatic to Electric - ConverterP/E Switch
32
![Page 33: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/33.jpg)
Self Acting Controls
• Self powered
• Two types• Liquid
• Liquid expands when heated and contracts when cooled• This expansion/contraction force can move a valve or
damper• Liquid/Vapor
• Liquid boils to vapor when heated. Vapor condenses to liquid when cooled
• Pressure difference when liquid or vapor causes force to act on valve or damper
33
![Page 34: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/34.jpg)
Electric Controls
• Usually 24 volts AC
• Use contact closures and resistance for control logic
• Usually 2 position with the controlled variable sensed and compared to set point• Contact opened or closed accordingly
34
![Page 35: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/35.jpg)
2 Position Electric Controls
• ~<1hp, line thermostat used
• ~>1hp, motor starter with overload protection used
• Traditional packaged HVAC systems used electric controls• Newer systems include analog/digital
controls
35
![Page 36: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/36.jpg)
Packaged HVAC Electric Controls: “Residential” Thermostat Wiring
• Residential style Thermostats• Anyone know wires / colors / what they
represent?
36
![Page 37: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/37.jpg)
Packaged HVAC Electric Controls: “Residential” Thermostat Wiring
5 wire cable Color Terminal Code
Notes
1 24 VAC Red R Power
2 Heat White W or W1 Shorting (connecting) red/white = heat
3 Fan Green G Shorting (connecting) red/green = fan
4 Cool Yellow Y or Y1 Shorting (connecting) red/yellow = cool
5 Common Blue C Used in newer systems to power tstat (backlight , etc.)
>5 wires multistage Color Terminal Code
Notes
6 2nd stage Cool Light Blue Y2
7 2nd stage Heat Brown R2
Potential activity and video: http://www.prothermostats.com/find_thermostat.php
37
![Page 38: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/38.jpg)
Packaged HVAC Electric Controls• Wire coming to the RH, RC, or R terminal - usually red - The
red wire is the source hot wire from the transformer on the heating/cooling equipment.
• Wire coming to the G terminal - usually Green. This is the fan relay - when energized, it will turn on the system fan/blower.
• Wiring coming to the Y terminal - usually Yellow. This is the compressor relay for cooling. When energized, it will turn on the AC.
• Wire coming to the W terminal - usually White. This is the heating relay. When energized, the heating system will start up
• Wire coming to the C terminal - usually Blue. This is power to the thermostat to do things like lighting the display, closing switching relays, keeping the program. • Without 5th blue wire, you will need a battery powered thermostat.
38
![Page 39: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/39.jpg)
Electric Actuators
• Types• Solenoid – 2 position• Motor – 2 position or modulating control
• Linkage Configuration• Direct coupled – no linkages• Foot mounted – linkages
• Normal or Failed Configuration• Spring return or fail safe• Non spring return
• Motion• Rotary• Linear
39
![Page 40: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/40.jpg)
Maintenance of Controls• What kind of maintenance?
• Calibration of sensors
• Check and adjust actuators
• Check schedules and set-points
• Up-grades (usually programming) • Maintain documentation
40
![Page 41: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/41.jpg)
DDC• The automated control of a condition or process by a
digital device (computer)• Control energy costs with advanced programming and
scheduling of equipment• Fault detection and alarming• Programming / graphical interfaces• Less maintenance than pneumatics
• A DDC system cannot overcome design problems
41
![Page 42: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/42.jpg)
DDC Control System42
![Page 43: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/43.jpg)
DDC• Controls operated by a digital microcomputer
• 4 types of control points (I/O)• Digital Points are 2 state (on/off, open/closed)
• DI-Digital Inputs• DO-Digital Outputs
• Analog Points have more than 2 positions (are variable)• AI-Analog Inputs• AO-Analog Outputs
• A/D Converters – convert Analog values to Digital
43
![Page 44: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/44.jpg)
Distributed Digital Controls (DDC)
• Integrates controls
• Enables central station monitoring
• Enables more sophistical controls programming --“algorithmic”
• But still based on concept of Sequences of Operation!
44
![Page 45: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/45.jpg)
Ideas for DDC Controls Maintenance• Your controller company could perform the following types
of maintenance• Overrides• Failed Points• Alarms
• Respond to legitimate• Clean up nuisance• Set up remote notification
• Network diagnostics• Database/program back up
• Get training from controller company
45
![Page 46: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/46.jpg)
Ideas for DDC Controls Maintenance• Application Software upgrades• Operating System Upgrades• IT Maintenance: Security, etc.
• Panel firmware upgrades• Panel upgrades (hopefully backwards compatible,
meaning that new controller can use old controllers programming and other features)
• Remote access configuration
• Portable device access configuration• Maintain response times / refresh rates
46
![Page 47: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/47.jpg)
DDC Controls Maintenance – Network / Software Performance Benchmarks
Ensure system is not “slowing down”
Ways to define/track system speed (i.e. “why computer is so
slow?”)• Graphic Display: Display graphic with minimum 20 dynamic points with current data
within 10 seconds.
• Graphic Refresh: Update graphic with minimum 20 dynamic points with current data
within 8 seconds.
• Object Command: Reaction time of less than two seconds between operator
command of a binary object and device reaction.
• Object Scan: Transmit change of state and change of analog values to control units
or workstation within six seconds.
• Alarm Response Time: Annunciate alarm at workstation within 45 seconds.
• Multiple workstations: must receive alarms within five seconds of each other.
• Program Execution Frequency: Run capability of applications as often as five
seconds, but selected consistent with mechanical process under control.
• Performance: Programmable controllers shall execute DDC PID control loops, and
scan and update process values and outputs at least once per second.
47
![Page 48: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/48.jpg)
Sequences of Operation: Control Strategies
• A method for optimizing the control of building system equipment. The optimum outcome
• What is an optimum control strategy?• One that does the following:
• Fulfill sequence of operation• Minimize energy use• Minimize manual interaction• Minimize equipment wear and tear
48
![Page 49: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/49.jpg)
Examples of Control Strategies
• Set point control• Example - controlling room temperature to desired value (set
point) using a thermostat and reheat valve
• Lead / Lag control• Example – equalize run time by controlling which pump to
bring on (lead) and which is on standby (lag) based on run hours
49
![Page 50: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/50.jpg)
Control Logic
• Control logic is portion of controller that produces outputs based on inputs• Algorithm: sequence of instructions for producing the
optimal results to a problem• Control loop: continuous repetition of the control logic
decisions• Open
• No feedback• Closed
• Feedback
50
![Page 51: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/51.jpg)
Example SOP: Single Zone System
H
C
C
CNC
NO
RA
OA
OA MA
SPACEZT
EA NC
CD
NO
CD
NC
EA- Exhaust AirOA- Outside AirRA- Return AirHC- Heating CoilCC- Cooling CoilCD- ActuatorZT- Zone temperature Sensor
NO-Normally OpenNC-Normally Closed
51
![Page 52: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/52.jpg)
Example Partial SOP: Single Zone System• The hot water valve shall modulate to control a zone air temperature
of 70 F. +/- 2 F.
• The chilled water valve shall modulate to control a zone air temperature of 76 F. +/- 2 F.
• The mixed air dampers shall modulate to control a mixed air temperature set point which is reset based on the zone temperature. The OA dampers will close on fan shut down. The OA dampers shall maintain 20% OA when the building is occupied. The OA dampers shall maintain minimum (occupied) or bypass minimum (unoccupied.) when the OA temperature exceeds 68 F. with a 2 F. differential.
• The supply fan runs based on a time schedule. During unoccupied periods, fans will run when space temperature drops below 60 F. or rises above 85 F(with 3 F. differential) .
• The return fan runs when the supply fan runs.
52
![Page 53: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/53.jpg)
Ideas for Controls Maintenance• Calibrations
• Examples of sensors that need to be calibrated periodically
(usually code requirement): CO, CO2, OA Flow Meters,
Refrigeration Detectors
• Check sensor calibrations and replace if not accurate
• Trends
• Check for hunting (when controlled device constantly modulates excessively, never getting to set point), response to upsets, etc.
• Ensure modes and sequences (Start up mode, shut down
mode, cooling sequences, heating sequences ) are working
• If DDC, review system activity logs of what has happened
• Look for excessive alarms
53
![Page 54: and Performance: an Introduction to Building Operator ...€¦ · Certification – Lesson 10: Control Principles, Terms, and Concepts CUNY Institute for Urban Systems Building Performance](https://reader035.fdocuments.us/reader035/viewer/2022070808/5f07787a7e708231d41d24d3/html5/thumbnails/54.jpg)
Class Review and Reading Assignment
Today’s topics:• How Air Moves• Ventilation Rates• Air-Side Mechanical Systems and Components• HVAC Conservation
Readings for next class:• Read FEMP Chap. 8 (METERING FOR O&M)• Herzog, Chaps. 1 & 2