An Introduction to An Introduction to the R3 19 inch Rackthe R3 19 inch Rack
The R3 control system comprises a number of
different plug in modules, each of which is dedicated
to a particular function within the complete control
panel.
Modules cover all requirements -
Fire detection
Alarm signalling
Gas detection
Extinguishing
Data transmission
Plant control
The modular approach means that the system is
inherently reliable, easy to install and commission and
easy to maintain, repair and fault find.
The R3 control system comprises a number of
different plug in modules, each of which is dedicated
to a particular function within the complete control
panel.
Modules cover all requirements -
Fire detection
Alarm signalling
Gas detection
Extinguishing
Data transmission
Plant control
The modular approach means that the system is
inherently reliable, easy to install and commission and
easy to maintain, repair and fault find.
R3 19 inch Rack ApprovalsR3 19 inch Rack Approvals
The R3 panel is type approved to BS 5839 Part 4 and
Lloyds Test Specification No: 1 (ENV 2 level) by
Lloyds Register.
Approved to BS 3116 Part 4 by The Loss Prevention
Certification Board.
The R3 is also approved to carry the CE mark in
accordance with European Union directives
91/263/EEC and 89/336/EEC.
In addition, the rack panel has been fully tested and
approved by the Shenyang Test Centre in the
Peoples’ Republic of China.
The R3 panel is type approved to BS 5839 Part 4 and
Lloyds Test Specification No: 1 (ENV 2 level) by
Lloyds Register.
Approved to BS 3116 Part 4 by The Loss Prevention
Certification Board.
The R3 is also approved to carry the CE mark in
accordance with European Union directives
91/263/EEC and 89/336/EEC.
In addition, the rack panel has been fully tested and
approved by the Shenyang Test Centre in the
Peoples’ Republic of China.
In addition to Control Equipment’s range of quality system and company
approvals, the R3 rack panel is approved by a number of bodies to various
rigorous standards.
In addition to Control Equipment’s range of quality system and company
approvals, the R3 rack panel is approved by a number of bodies to various
rigorous standards.
System CapacitySystem Capacity
Module No Module Description Maximum Quantity
K1412 Analogue addressable loop module 64
K1261 Conventional zone module 84
K1314 Gas detection module 42
K1219 Extinguishing module 128
K1304 Alarm module 84
K1205 Relay module 84
K1222 Input module 42
K1222L Input module with indications 42
K1222-1K Input module with 1 key-switch 42
K1222-2K Input module with 2 key-switches 42
K1225 Output module 21
K1225L Output module with indications 21
K1316 Normally energised output module 21
K1316L Normally energised output module with indications 21
K1525 Annunciator driver module 21
K1525L Annunciator driver module with indications 21
K1223 Timer module 21
K1224 Initial/reserve changeover module 128
K1241 Earth leakage detection module 1
Module No Module Description Maximum Quantity
K1412 Analogue addressable loop module 64
K1261 Conventional zone module 84
K1314 Gas detection module 42
K1219 Extinguishing module 128
K1304 Alarm module 84
K1205 Relay module 84
K1222 Input module 42
K1222L Input module with indications 42
K1222-1K Input module with 1 key-switch 42
K1222-2K Input module with 2 key-switches 42
K1225 Output module 21
K1225L Output module with indications 21
K1316 Normally energised output module 21
K1316L Normally energised output module with indications 21
K1525 Annunciator driver module 21
K1525L Annunciator driver module with indications 21
K1223 Timer module 21
K1224 Initial/reserve changeover module 128
K1241 Earth leakage detection module 1
42 Total
21 Total
21 Total
ConstructionConstruction
Modules are located within a 3U high sub
rack.
A legend plate may be located underneath
each sub rack.
Cabinet sizes are flexible within the
constraints of the 19 inch rack.
From 380mm high x 600mm wide x 369
deep for a single rack to 2000mm high x
800mm wide x 600mm deep for a system
containing 10 racks.
Modules are located within a 3U high sub
rack.
A legend plate may be located underneath
each sub rack.
Cabinet sizes are flexible within the
constraints of the 19 inch rack.
From 380mm high x 600mm wide x 369
deep for a single rack to 2000mm high x
800mm wide x 600mm deep for a system
containing 10 racks.
CabinetsCabinets
All standard cabinets are at minimum IP55.
Constructed of 1.5mm steel, coated with an
electrophoresis primer and flint grey surface
coat.
Within the standard design, indications and
controls are mounted in an aluminium framed
lockable door and are visible behind a full
sized polycarbonate window.
The R3 rack system is very flexible and other
cabinet constructions can be incorporated.
All standard cabinets are at minimum IP55.
Constructed of 1.5mm steel, coated with an
electrophoresis primer and flint grey surface
coat.
Within the standard design, indications and
controls are mounted in an aluminium framed
lockable door and are visible behind a full
sized polycarbonate window.
The R3 rack system is very flexible and other
cabinet constructions can be incorporated.
What We Need to KnowWhat We Need to Know
Do you have any special cabinet requirements?
for example -
Special colour
IP rating
Sizes
For the purposes of quotation we need the
following information -
Input and output requirements
Power requirements
Hardware requirements
Approval and specification requirements
Do you have any special cabinet requirements?
for example -
Special colour
IP rating
Sizes
For the purposes of quotation we need the
following information -
Input and output requirements
Power requirements
Hardware requirements
Approval and specification requirements
Planning the DesignPlanning the Design
Up to fourteen 19inch racks may be incorporated
into a system, subject to cabinet size limitations.
When planning the design of the R3, the following
should be considered -
• all racks, identification plates and special
switch plates need to fit
• all internally mounted equipment, terminals,
power supplies, special equipment etc. need to
be fitted.
Up to fourteen 19inch racks may be incorporated
into a system, subject to cabinet size limitations.
When planning the design of the R3, the following
should be considered -
• all racks, identification plates and special
switch plates need to fit
• all internally mounted equipment, terminals,
power supplies, special equipment etc. need to
be fitted.
Capability of a large R3 Rack SystemCapability of a large R3 Rack System
Smoke detection
Heat detection
Protection system monitoring
Turbine fire system monitoring
Plant control
Alarm system via public address
Visual alarms in noisy areas
Infra-red flame detection
Water deluge systems
Automatic/manual CO2 systems
Audible and visual alarms with personnel
warning lamps
Networking
Smoke detection
Heat detection
Protection system monitoring
Turbine fire system monitoring
Plant control
Alarm system via public address
Visual alarms in noisy areas
Infra-red flame detection
Water deluge systems
Automatic/manual CO2 systems
Audible and visual alarms with personnel
warning lamps
Networking
FlexibilityFlexibility
Networking capability with: -
other R3 systems
wall mounted panels
repeater and mimic panels
Alarm Manager graphics package
Standard 19 inch rack frame, each carrying a
system backplane and the required function
modules.
Supremely flexible - during manufacture or after
installation and commissioning.
Modules may be added or removed without
major modifications.
Networking capability with: -
other R3 systems
wall mounted panels
repeater and mimic panels
Alarm Manager graphics package
Standard 19 inch rack frame, each carrying a
system backplane and the required function
modules.
Supremely flexible - during manufacture or after
installation and commissioning.
Modules may be added or removed without
major modifications.
Common Control ModuleCommon Control Module
Every R3 system must contain a Common
Control Module.
This module incorporates all executive action
user controls.
There are two types -
K1321 - Conventional systems only
K1339 - Both analogue addressable and
conventional systems
The Common Control Module is always fitted in
the right hand module position of its designated
rack.
Every R3 system must contain a Common
Control Module.
This module incorporates all executive action
user controls.
There are two types -
K1321 - Conventional systems only
K1339 - Both analogue addressable and
conventional systems
The Common Control Module is always fitted in
the right hand module position of its designated
rack.
K1215 Decoding ModuleK1215 Decoding Module
Used in second and all subsequent racks
to control data flow between rack modules
and the system common control module
(K1339 or K1321)
Used in second and all subsequent racks
to control data flow between rack modules
and the system common control module
(K1339 or K1321)
Blank Sub-Rack AssemblyBlank Sub-Rack Assembly
This is the basic layout of a sub-rack
assembly. Each rack must have 1 Common
Control Module and a Decoding Module
where more than 1 sub-rack is required.
This is the basic layout of a sub-rack
assembly. Each rack must have 1 Common
Control Module and a Decoding Module
where more than 1 sub-rack is required.
Maximum number of modules per rack -
K1321 Common Control - 14 modules
K1339 Common Control - 10 modules
K1215 Decoding Module - 14 modules
Maximum number of modules per rack -
K1321 Common Control - 14 modules
K1339 Common Control - 10 modules
K1215 Decoding Module - 14 modules
Space allocated for K1321 Common Control Module or
K1215 Decoding Module.
Space allocated for K1321 Common Control Module or
K1215 Decoding Module.
Space allocated for K1339 Common Control Module.
Space allocated for K1339 Common Control Module.
K1412 Loop ModuleK1412 Loop Module
The K1412 uses the Apollo XP95 protocol and allows
up to 126 devices per loop.
A maximum of 32 K1412 loop modules are permitted
per R3.
An LED indicates loop isolations.
The module has an engineer’s loop auto
configuration switch.
Configuration information is stored in non volatile
memory.
The K1412 module automatically reports loop
configuration upon power up.
The K1412 uses the Apollo XP95 protocol and allows
up to 126 devices per loop.
A maximum of 32 K1412 loop modules are permitted
per R3.
An LED indicates loop isolations.
The module has an engineer’s loop auto
configuration switch.
Configuration information is stored in non volatile
memory.
The K1412 module automatically reports loop
configuration upon power up.
K1261 Zone ModuleK1261 Zone Module
84 modules may be incorporated as maximum. Each module provides
3 zones.
2 Fire and Fault LEDs are incorporated per circuit.
The user switch gives options for Normal, Isolate or Test.
Engineer’s facilities -
Zone 1 non latch Zone 1 Zener Barrier
Zone 2 non latch Zone 2 Zener Barrier
Zone 3 non latch Zone 3 Zener Barrier
Zone 1 Fire delay (0.5 - 60 seconds)
Zone 2 Fire delay (0.5 - 60 seconds)
Zone 3 Fire delay (0.5 - 60 seconds)
Latching faults
Fault signal to Common Control on “Isolate”
Short circuit disable
84 modules may be incorporated as maximum. Each module provides
3 zones.
2 Fire and Fault LEDs are incorporated per circuit.
The user switch gives options for Normal, Isolate or Test.
Engineer’s facilities -
Zone 1 non latch Zone 1 Zener Barrier
Zone 2 non latch Zone 2 Zener Barrier
Zone 3 non latch Zone 3 Zener Barrier
Zone 1 Fire delay (0.5 - 60 seconds)
Zone 2 Fire delay (0.5 - 60 seconds)
Zone 3 Fire delay (0.5 - 60 seconds)
Latching faults
Fault signal to Common Control on “Isolate”
Short circuit disable
K1314 Flammable Gas K1314 Flammable Gas Detection ModuleDetection Module
42 flammable gas detection modules are permitted
as maximum.
The gas sensor circuit is monitored for open and
short circuits.
The digital display shows -
% LEL
LED indications show the following -
Alarm level1
Alarm level 2
Power on
Fault
42 flammable gas detection modules are permitted
as maximum.
The gas sensor circuit is monitored for open and
short circuits.
The digital display shows -
% LEL
LED indications show the following -
Alarm level1
Alarm level 2
Power on
Fault
K1219 Extinguishing ModuleK1219 Extinguishing Module
Up to 128 modules are permitted per R3 rack system.
LED indications -
Discharged
Auto / Manual
Low Pressure
Actuator Circuit Fault
Pressure Switch Fault
Actuator Discharge Signal
Alarm Circuit Active
The K1219 module incorporates an auto / manual key-switch.
Engineer’s functions -
Actuator Delay (0 - 255 Seconds at 1 second intervals)
Short Circuit Fault disable
2nd Stage NC / NO Select (normally closed / open)
Latching / Non Latching fault indication.
Remote Auto / Manual / Discharged / Locked Off
Up to 128 modules are permitted per R3 rack system.
LED indications -
Discharged
Auto / Manual
Low Pressure
Actuator Circuit Fault
Pressure Switch Fault
Actuator Discharge Signal
Alarm Circuit Active
The K1219 module incorporates an auto / manual key-switch.
Engineer’s functions -
Actuator Delay (0 - 255 Seconds at 1 second intervals)
Short Circuit Fault disable
2nd Stage NC / NO Select (normally closed / open)
Latching / Non Latching fault indication.
Remote Auto / Manual / Discharged / Locked Off
K1224 Initial / Reserve ModuleK1224 Initial / Reserve Module
A maximum of 128 initial/reserve modules is permitted.
The K1224 is used in conjunction with the K1219 extinguishing module.
Key-switch facilities -
Initial / Reserve Selection of actuator outputsIsolate actuator outputs (lock off)
LED indications -
Initial SelectedReserve SelectedLocked Off
A maximum of 128 initial/reserve modules is permitted.
The K1224 is used in conjunction with the K1219 extinguishing module.
Key-switch facilities -
Initial / Reserve Selection of actuator outputsIsolate actuator outputs (lock off)
LED indications -
Initial SelectedReserve SelectedLocked Off
K1304 Alarm ModuleK1304 Alarm Module
Up to 84 modules are permitted and each module provides 3 alarm circuits at 2A 24V DC.
LED indications -
Alarm Circuit A Operated Alarm Circuit A FaultAlarm Circuit B Operated Alarm Circuit B
FaultAlarm Circuit C Operated Alarm Circuit C
Fault
The K1304 module provides the following user controls -
Isolate Normal Test
Engineer’s functions -
Short Circuit Fault Monitoring DisableUser Test DisableUser Isolate DisableLatching / Non Latching Faults
Up to 84 modules are permitted and each module provides 3 alarm circuits at 2A 24V DC.
LED indications -
Alarm Circuit A Operated Alarm Circuit A FaultAlarm Circuit B Operated Alarm Circuit B
FaultAlarm Circuit C Operated Alarm Circuit C
Fault
The K1304 module provides the following user controls -
Isolate Normal Test
Engineer’s functions -
Short Circuit Fault Monitoring DisableUser Test DisableUser Isolate DisableLatching / Non Latching Faults
K1205 Relay ModuleK1205 Relay Module
Up to 84 relay modules may be incorporated.
Each K1205 module provides 3 double pole changeover contacts, each rated at 1A 24V DC.
Relay coils are monitored.
LED Indications -
Relay A OperatedRelay B OperatedRelay C OperatedRelay A FaultRelay B FaultRelay C Fault
Engineer’s Functions via internal switch -
Isolate Relay AIsolate Relay BIsolate Relay C
Up to 84 relay modules may be incorporated.
Each K1205 module provides 3 double pole changeover contacts, each rated at 1A 24V DC.
Relay coils are monitored.
LED Indications -
Relay A OperatedRelay B OperatedRelay C OperatedRelay A FaultRelay B FaultRelay C Fault
Engineer’s Functions via internal switch -
Isolate Relay AIsolate Relay BIsolate Relay C
K1222 Input ModuleK1222 Input Module
Up to 42 input modules are permitted per R3 system.
6 inputs are available on each module.
A K1222 input operates when 0V is applied to the input
terminals.
The module may be supplied with LED indications which
light when the input is active (K1222L).
It may also be supplied with 1 or 3 keyswitches for
control of critical functions (K1222-1K, K1222-3K).
Up to 42 input modules are permitted per R3 system.
6 inputs are available on each module.
A K1222 input operates when 0V is applied to the input
terminals.
The module may be supplied with LED indications which
light when the input is active (K1222L).
It may also be supplied with 1 or 3 keyswitches for
control of critical functions (K1222-1K, K1222-3K).
K1225 Output ModuleK1225 Output Module
Up to 21 K1225 modules are permitted and each module provides up
to 12 open collector outputs.
Each output is rated at 80mA.
Outputs are normally inactive.
The module switches to 0V when active.
The K1225 is supplied as standard without LEDs.
Other available options are as follows -
With LEDs (K1225L) - as illustrated
With normally energised outputs (K1316)
With normally energised outputs and LEDs (K1316L)
Up to 21 K1225 modules are permitted and each module provides up
to 12 open collector outputs.
Each output is rated at 80mA.
Outputs are normally inactive.
The module switches to 0V when active.
The K1225 is supplied as standard without LEDs.
Other available options are as follows -
With LEDs (K1225L) - as illustrated
With normally energised outputs (K1316)
With normally energised outputs and LEDs (K1316L)
K1525 Annunciator Driver ModuleK1525 Annunciator Driver Module
A maximum of 21 modules may be incorporated. Each module provides 12
open collector outputs, each rated at 100mA maximum.
Test Lamps input (0V from an external switch)
Accept input (0V from an external switch)
First to Fire input select - means that more than one signal may be sent to the
same output
Flash rate synchronisation
Engineer’s functions are as follows -
Accept External only (Ignores Silence Alarms from Common Control)
First to Fire Flash (Flashes first to fire LED dim when accepted)
First to fire flash (normal no dim)
External pulse to allow synchronisation from another K1525
Slow Flash of LEDs (1/2 speed)
Dim / Bright Flash
Brightness 1 & 2 allows specifying first fire signal brightness
Available as an option with 12 LEDs (K1525L)
A maximum of 21 modules may be incorporated. Each module provides 12
open collector outputs, each rated at 100mA maximum.
Test Lamps input (0V from an external switch)
Accept input (0V from an external switch)
First to Fire input select - means that more than one signal may be sent to the
same output
Flash rate synchronisation
Engineer’s functions are as follows -
Accept External only (Ignores Silence Alarms from Common Control)
First to Fire Flash (Flashes first to fire LED dim when accepted)
First to fire flash (normal no dim)
External pulse to allow synchronisation from another K1525
Slow Flash of LEDs (1/2 speed)
Dim / Bright Flash
Brightness 1 & 2 allows specifying first fire signal brightness
Available as an option with 12 LEDs (K1525L)
K1539Timer ModuleK1539Timer Module
Up to 21 timer modules are permitted.
0 -510 seconds delay function.
LED delay indications -
LED pulses when delay is activeLED changes to continuous when delay ends
Up to 21 timer modules are permitted.
0 -510 seconds delay function.
LED delay indications -
LED pulses when delay is activeLED changes to continuous when delay ends
K1241 Earth Leakage ModuleK1241 Earth Leakage Module
One K1241 earth leakage module only may be
incorporated per R3 system.
This module is designed for the detection of earth
faults on the panel and in the field wiring.
Fault is identified by means of an LED indication.
One K1241 earth leakage module only may be
incorporated per R3 system.
This module is designed for the detection of earth
faults on the panel and in the field wiring.
Fault is identified by means of an LED indication.