![Page 1: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/1.jpg)
BICSI US Western Regional
Meeting
An Inside Look
atOutside Plant
![Page 2: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/2.jpg)
BICSI Regional Meeting
Presented byJohn C. AdamsRCDD/OSP SpecialistConsultantBICSI® Master [email protected]
![Page 3: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/3.jpg)
• What is CO-OSP?• A close look at the 758 standard• Available Resources
Agenda
![Page 4: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/4.jpg)
What is CO-OSP?
• Customer Owned Outside Plant• “Telecommunications infrastructure
designed for installation exterior to buildings” ANSI/TIA/EIA-758-A terminology
![Page 5: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/5.jpg)
CO-OSP Standard
• ANSI/TIA/EIA-758-A (2004) Customer-Owned Outside Plant Telecommunications Infrastructure Standard.
This standard replaces the ANSI/TIA/EIA-758 and 758-1documents. (1999)
![Page 6: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/6.jpg)
Why do I have to know these standards?
You have to know these standards if:
• You do work on customer ownedproperty
• You’d like to give your customer a system that will work regardless of the electronics they choose
![Page 7: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/7.jpg)
LET’S TAKE A LOOK INSIDETHE CO-OSP STANDARD
ANSI/TIA/EIA-758-A
Customer-owned Outside PlantTelecommunicationsInfrastructure Standard
![Page 8: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/8.jpg)
Discussion of the contents !
• Introduction and Scope• Definitions, Acronyms, Weights,
and Symbols• Cabling Infrastructure• Pathways and Spaces• Cabling Hardware• Annexes
![Page 9: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/9.jpg)
INTRODUCTION
• “Telecommunications” is defined in this standard as any transmission, emission, and reception of signs, signals, writings, images and sound, that is, information of any nature by cable, radio, optical or other electromagnetic system.
![Page 10: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/10.jpg)
INTRODUCTION
• Customer owned campus facilities are typically termed “outside plant”
• In this standard they’re called “Customer-owned OSP”
![Page 11: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/11.jpg)
INTRODUCTION
• Two categories of criteria are specified:Mandatory and Advisory Terms
Mandatory word is “SHALL”
Advisory words are “SHOULD”, “MAY”, and “DESIRABLE”
![Page 12: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/12.jpg)
INTRODUCTION
• Mandatory criterion applies to performance and compatibility requirements
• Advisory criterion is “above minimum” goals.
![Page 13: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/13.jpg)
Introduction
• Metric dimensions are “soft” conversions of US units(100mm soft converts to 4 inches)
• Conduit dimensions are listed as follows: 21 (3/4) trade size conduitThat’s 21mm and/or 3/4”(You won’t see the mm or in)
![Page 14: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/14.jpg)
INTRODUCTION
• The standard is a “living document” which means it can be revised or updated due to advances in construction techniques or technology.
![Page 15: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/15.jpg)
SCOPE-Applicability
• The standard specifies minimumrequirements for CO-OSP
• Specifies cabling and the pathways and spaces to support it
• Useful life of OSP Pathways and Spaces is 40 years
• Useful life of OSP Cabling is 30 years
![Page 16: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/16.jpg)
Scope - Applicability
Now isn’t that convenient !
The useful life of pathways is 40 yearsThe useful life of the OSP cable is 30 yearsThe useful life of an OSP engineer is………
29 years 364 days
![Page 17: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/17.jpg)
SCOPE-Pathways and Spaces
• There are two basic types of cable pathway systems:
Underground and Aerial
![Page 18: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/18.jpg)
SCOPE
• Underground Pathways andSpaces
Direct BuriedBuried Duct/ConduitMaintenance Holes, HandholesShared Spaces (utility tunnels)
![Page 19: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/19.jpg)
SCOPE-Pathways and Spaces
• Aerial Pathways and Spaces
PolesMessenger Wire or StrandAnchoring Guy WiresAnchors
![Page 20: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/20.jpg)
SCOPE-Customer Owned OSP Cabling
• Consists of recognized cable• Conforming connecting
hardware• Protective Devices which….
Can be located on the exterior or interior of a building or in an outdoor pedestal or cabinet
![Page 21: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/21.jpg)
SCOPE-Customer Owned OSP Cabling
• Can have intermediate splices• Fiber Optic Cabling may pass
through a building entrance facility as part of the cable route
• Star topology recommended
![Page 22: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/22.jpg)
Normative References
• The standard references 54 other standards and codes which, by reference, constitute part of the standard
![Page 23: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/23.jpg)
TERMS AND DEFINITIONS
The CO-OSP standard contains:
• 77 definitions• 49 acronyms• 14 weights and measures• 59 symbols
![Page 24: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/24.jpg)
TERMS AND DEFINITIONSLet’s look at one definition
Entrance facility(telecommunications):An entrance to a building for both public and private network service cables, (including wireless), including the entrance point of the building and continuing to the entrance room or space.
![Page 25: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/25.jpg)
Terms and Definitions
• For most service providers or access providers, that represents a change to “one entry facility” per customer
• The entrance facility was the point in the building where we stopped our cable and terminated it.
![Page 26: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/26.jpg)
CABLING INFRASTRUCTURETopology
• Recommended topology is a star• Large Campuses use a hierarchical
star• Stars offer centralized
management and administration• Distance limitations may prohibit
the use of a star topology
![Page 27: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/27.jpg)
CABLING INFRASTRUCTURERecognized Cables
• 50/125 optical fiber cable• 62.5/125 optical fiber cable• Singlemode optical fiber cable• 100 ohm Twisted Pair Cable• 75 ohm Coaxial Cable
![Page 28: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/28.jpg)
CABLING INFRASTRUCTUREMedia Selection
• Choose the cable considering:Characteristics of the applicationsDistancesFuture growth (population)Customer preferenceRequired useful lifeFlexibility with respect to supported services
![Page 29: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/29.jpg)
CABLING INFRASTRUCTUREBonding and Grounding
• A critical component of design• Protects people and property• Improper bonding and grounding can
affect other telecomm circuits• Comply with ANSI-J-STD-607-A, The
National Electrical Safety Code®
(NESC®) and National Electrical Code (NEC®)
![Page 30: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/30.jpg)
CABLING INFRASTRUCTUREBonding and Grounding
POOR or incomplete Bonding and Grounding can create:
• Equipment malfunction or failure• Insurance issues you don’t want• Injury or death to personnel• Noise on voice circuits• Loss of manufacturer’s warranty
![Page 31: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/31.jpg)
PATHWAYS AND SPACES
Pathways may be aerial,direct buried, or underground.
Underground or direct buried preferred over aerial
Underground is preferred over direct buried
![Page 32: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/32.jpg)
PATHWAYS AND SPACESSubsurface Pathways
• Design should consider:
Excavation -Clearances and separations,Depth, Backfill, and Restoration,Trenching, Boring, Plowing.Street Crossings, Casings.
![Page 33: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/33.jpg)
PATHWAYS AND SPACESConduit/Duct
• EB Type - Encasement in concrete• DB Type - Direct Buried or encased• Rigid Non-Metallic Sched. 40 or 80• MPD- Multiple Plastic Duct• Rigid Metallic Conduit• IMC- Intermediate Metallic Conduit• Fiberglass Duct - DB or encased• Inner duct - PE or PVCNote- The NEC says “metal” not
“metallic”
![Page 34: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/34.jpg)
PATHWAYS AND SPACESConduit/Duct
• Encase bends (non-metallic)• 600 ft max. between pulling points• No more then (2) 90’s or a total of
180 degrees• Drain slope should be is 1/8” per
foot:Exiting or entering a building orfrom the middle of a conduit span(each way)
![Page 35: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/35.jpg)
PATHWAYS AND SPACES
• Innerduct may be placed within a duct to facilitate initial and subsequent placement of multiple cables in a single duct.
Note- Innerduct can be plastic or fabric
![Page 36: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/36.jpg)
PATHWAYS AND SPACESSubsurface Considerations
• Duct plugs on ALL conduits• Axial Movement- Bridge Crossing• Tunnel Requirements
OSHASheath properties and clearances
![Page 37: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/37.jpg)
PATHWAYS AND SPACESAerial Construction
Consider:• Pole class, length, type, depth.• All loading factors• Grounding, clearances, separation• Anchors/guys, riser protection• Span lengths, slack spans, etc.• Lashing, strand tension, sag.
![Page 38: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/38.jpg)
AERIAL CONSTRUCTION
• Poles commonly used in the telecommunications world are:Height- 30’, 35’, 40’ or 45’Class- 9 classes – 1 thru 10
(Class 8 not used) Most common - 3, 4, 5, 6, 7
This info is not in the standard
![Page 39: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/39.jpg)
PATHWAYS AND SPACESMaintenance Holes
Location considerations:• Ground (Topography)• Soil Conditions• Surrounding Structures• Personnel Access• Placing and Splicing Ease
![Page 40: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/40.jpg)
PATHWAYS AND SPACESMaintenance Holes
• Maximum distance shall not exceed 600 feet
• Not within 50’ of curb radius at an intersection
• In the right of way but outside the traveled portion(if placed within the traveled portion then 5 feet from the curb)
![Page 41: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/41.jpg)
PATHWAYS AND SPACESMaintenance Holes
• Concrete, steel, or cast iron• Must have proper load ratings• Can be pre-cast or site poured• May have multiple openings
![Page 42: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/42.jpg)
PATHWAYS AND SPACESMaintenance Holes
• Maintenance holes shall be equipped with:Corrosion resistant pulling ironsCorrosion resistant cable racksSump for drainage and………..
![Page 43: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/43.jpg)
PATHWAYS AND SPACESMaintenance Holes
SHALL NOT BE SHAREDWITH ELECTRICALINSTALLATIONS
(other than those needed for telecommunications equipment)
![Page 44: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/44.jpg)
PATHWAYS AND SPACESMaintenance Holes
• TYPESA - end wall entrance onlyB - handholeJ - end and sidewall entranceV - one end wall and two side
walls
The BICSI manual lists four types A, J, L, and T
![Page 45: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/45.jpg)
PATHWAYS AND SPACESMaintenance Holes
• “Covers shall meet the environmental conditions”Heavy Vehicle TrafficLighter LoadsSidewalk
![Page 46: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/46.jpg)
PATHWAYS AND SPACESHandholes (Advanced Warning)
The slide you are about to see may cause nausea, disbelief, glazed vision, or create some serious doubt about your presenter’s credibility.
![Page 47: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/47.jpg)
PATHWAYS AND SPACESHandholes
• Shall not be used in place of a MH• Shall not to be used for splicing• Shall not be shared with electrical• Shall not exceed a 4’ X 4’ X 4’• Should not be used in runs of more
than (3) 4” conduits• Should align conduits on opposite
walls at the same elevation
![Page 48: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/48.jpg)
PATHWAYS AND SPACESPedestals and Cabinets
• Should accommodate 4 cables• Cable bend radii not less then 15
times the diameter of the cable• Corrosion Resistance• Customer Preferences• Meet ASTM requirements
![Page 49: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/49.jpg)
PATHWAYS AND SPACESPedestals and Cabinets
• Resistant to rodent and insects• Secure - Locks, special bolts, etc.• Chemically resistant• Grounding and bonding to Codes
![Page 50: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/50.jpg)
PATHWAYS AND SPACESOther Spaces
• Vaults:
Are open or closed bottom housings which provide grade level or below grade level environmental protection, access, and security to splices, cable, and distribution equipment.
![Page 51: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/51.jpg)
PATHWAYS AND SPACESVault Selection Concerns
• Cable bend radii (15x cable)• Accommodate four cables• Accommodate both inline and
butt splices• Secure with locks, bolts, etc• Provisions to relocate if needed• Resistant to rodents/insects
![Page 52: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/52.jpg)
PATHWAYS AND SPACESTraffic Loadings
• Maintenance Holes and Vaultshave three basic load ratingsH-5 Sidewalk applications
(11K lbs..)H-10 Driveways/Parking Area (22K)H-20 Heavy Traffic (40K)
![Page 53: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/53.jpg)
CABLING Twisted Pair Cable
• 19, 22, 24, or 26 AWG• Meet all ANSI/ICEA requirements• Recommended applications for
Filled and Air Core cables (R,S,N)• Meet AHJ and applicable codes
![Page 54: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/54.jpg)
FIBER OPTIC CABLINGRecommendations
Cable Conduit Direct Type or Duct Tunnel Buried AerialNon-armored R R S R
Armored S S R S
Indoor/Outdoor S S N S
Drop S S N S
• R – Recommended, S – Suitable• N – Not Recommended
![Page 55: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/55.jpg)
CABLINGTwisted Pair Specifications
• Filled cable is recommended (R) for aerial, direct buried, and UG.
• Air Core is suitable (S) for aerial and UG and not recommended (N) for direct buried.
![Page 56: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/56.jpg)
CABLING Twisted Pair Cabling
• Buried Service Wire (700’ max.)• Aerial Service Wire (700’ max.)
plus a 200’ max. span length
![Page 57: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/57.jpg)
CABLINGTwisted Pair Terms
• Buried and Aerial service wiresextend from the distribution cable to the entrance facility of a structure with limited cable needs.
Common pair counts are 3, 4, 5, & 6
Common gauges are 19, 22, 24, & 26
![Page 58: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/58.jpg)
CABLING Connecting Hardware
• Withstand temperature range of -40 degrees F to 158 degrees F
• Can be plastic or metal• Must meet requirements of
ANSI/TIA/EIA 568-B• Terminal blocks must allow access to
test points without disconnecting the service drop or puncturing the insulation
![Page 59: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/59.jpg)
CABLINGTermination Blocks
• Provide a means to connect the service wire to the distribution cable
• Typically available in 5-6 pair increments, and from 5 to 50 pairs
• Shall be compatible for all gauges26, 24, 22, 19, and 18 1/2
![Page 60: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/60.jpg)
CABLINGCross Connects
• Cross Connection Blocks are used to connect feeder pair to distribution pair. Terminals SHALL have:Tip on the left, ring on the right orTip above and ring below andRemovable red markers for special circuit ID
![Page 61: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/61.jpg)
CABLINGBuilding Entrance Terminals
• Available in 2, 4, 6, and multiples of 10 and 25 pairs.
• Protected and Non-protected(Protected type must meet UL 497)
• Can be equipped with various protective modules (carbon, gas tube, solid state, etc.)
![Page 62: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/62.jpg)
CABLING Splicing
• Single Wire Connectors are also known as “discrete” connectors
• Multiple Pair Connectors (modules)• Splicing Connectors have 10
separate tests performed on them in order to meet requirements
![Page 63: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/63.jpg)
CABLING General Concerns (Splicing)
• Bridge taps (not recommended)• Do not split binder groups• Bend Radii shall not be less than
10 times the cable diameter during installation or 8 times after install(Gopher proof is 15 and 10)
• Perform 8 primary field tests
![Page 64: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/64.jpg)
CABLING8 Primary Tests
• DC Loop Resistance• Wire Map• Continuity• Shorts• Crosses• Reversals• Splits• Any other mis-wiring
![Page 65: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/65.jpg)
CABLINGCoaxial Cable
• 75 ohm cable semi-rigid• Trunk, feeder, and distribution• N type connecting hardware• Meet requirements of SCTE
Society of Cable Television Engineers (Doc. IPS-SP-100)
![Page 66: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/66.jpg)
CABLINGFiber Optic Cable
• Singlemode, multimode, or a combination of these types
• Non-conductive and conductive• Armored and Non-Armored• Indoor/Outdoor (50 foot rule)
![Page 67: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/67.jpg)
CABLINGFiber Optic Cable Types
• Generally non-armored is referred to as duct cable
• All dielectric have no metallic components
![Page 68: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/68.jpg)
CABLINGFiber Optic Cable Types
Armored cables• Similar to duct cable in design• Steel Armor under outer sheath• Rodent resistant• Added protection in rocky soil
![Page 69: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/69.jpg)
CABLINGFiber Optic Cable Types
Aerial Cables• Same construction as duct cables• All dielectric recommended• Not as susceptible to lightning
(if they’re all dielectric)
![Page 70: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/70.jpg)
CABLINGFiber Optic Cable Types
Self Supporting• Designed to be installed without
the need for a pre-installed messenger.
• Can be installed quicker than duct type construction
![Page 71: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/71.jpg)
CABLINGFiber Optic Cable Types
All dielectric, self supporting cable or ADSS cables
Duct cables that contain a layer of strength members that allows installation without a messengerbut have length limits
![Page 72: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/72.jpg)
CABLINGFiber Optic Cable Types
Indoor/Outdoor Cables
• Should be water blocked and be UV Resistant
• Must pass NEC flame test andcarry a flame rating (e.g. OFNR)
![Page 73: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/73.jpg)
CABLINGFiber Optic Cable Types
Drop Cables:- Typically• Small diameter• Low fiber count• Limited unsupported span lengths• Used as a feed from a larger fiber to
a single location
![Page 74: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/74.jpg)
CABLINGFiber Optic Cable
• Fusion and Mechanical Splices(fusion is recommended for OSP)
• Splice Attenuation (Insertion Loss) should not exceed .1dB mean or .3dB maximum
• Provide Mechanical Protection
![Page 75: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/75.jpg)
FIBER OPTIC CABLESplicing/Terminating
Mechanical protection
• Each splice shall be protected in a splice tray
• Stripped fibers shall be protected with a shrink sleeve or silicon adhesive
• Prevents exposure to moisture
![Page 76: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/76.jpg)
FIBER OPTIC CABLEInstallation
Bonding and Grounding
• All metallic components shall be bonded to each other and grounded.
• Metallic components include armor, central strength members and closures.
![Page 77: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/77.jpg)
CABLING Fiber Optic Cable
• Bend radius shall be no less then 20 times the cable diameter during install and 15 times after install
• Field Test per ANSI/TIA/EIA 568-B
![Page 78: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/78.jpg)
CABLINGFiber Optic Housings
Fiber Distribution Units (FDU)
• Typically use factory prepared pigtails
• Recommends splicing to pigtails for higher performance connections
![Page 79: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/79.jpg)
CABLING Air Pressurization
• Air core cable installed in subsurface pathways shall be pressurized
• Aerial air-core should be vented• Pressure should be a minimum of
1.5PSI plus .43PSI per foot of hydrostatic head
• Static, Single and Dual Feed Systems. (Dual Feed suggested)
![Page 80: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/80.jpg)
CABLINGAir Pressurization
Where dry air pressure systems are deployed consider:
• Compressor Size• Dryer• Manifolds, flow meters, cut-offs• Pneumatic resistance of the cable• Alarms and air plugs• Location of air feeds and air pipes
![Page 81: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/81.jpg)
CABLING HARDWARE
• Specifications on Closures• Buried Service Wire Closure shall
maintain electricals/mechanicals for 40 years
• Closures shall accommodate Straight, Branch, Butt , and Special Applications
![Page 82: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/82.jpg)
CABLING HARDWAREClosures
• Weight must be suitable for installation by one person
• Reentry without destroying housing• Avoid the use of specialized tools• Minimize onsite assembly or
disassembly• Must accommodate 4 cables (fiber)
![Page 83: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/83.jpg)
ANNEXES A, B, C and D What they address
• A- OSP Symbols• B- Typical OSP Lengths for
Specific Applications• C- OSP Optical fiber cabling
practices• D- Bibliography and References
![Page 84: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/84.jpg)
Annexes
• Annex A is normative and considered as requirements of the CO-OSP Standard
• Annex B, C, and D are informative and not considered as requirements.
![Page 85: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/85.jpg)
ResourcesOSP READING MATERIAL
• ANSI Standards, especially TIA758-A• Trade Journals (i.e OSP Magazine)• GTEPs, BSPs, Telecordia and AT&T
OSP Engineering Manuals• BICSI CO-OSP Manual• BICSI OSP Training courses
![Page 86: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/86.jpg)
SOME SCARY THOUGHTS
• What happens when the AHJ starts to check all your jobs?
• What happens if the customer hires a third party to do a quality check?
• What happens when your design or placing techniques injure or kill?
• Would you be happy if you were paying for the work you’re doing?
![Page 87: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/87.jpg)
BE CAREFUL !!!!!!
OUTSIDE PLANT
IS INHERENTLYDANGEROUS
![Page 88: An Inside Look at Outside Plant - BICSI Adams - An Inside... · BICSI Regional Meeting Presented by John C. Adams RCDD/OSP Specialist Consultant BICSI® Master Instructor 813-653-3207](https://reader034.fdocuments.us/reader034/viewer/2022051508/5aa409c37f8b9ae7438b7c69/html5/thumbnails/88.jpg)
WRAP UP
Questions?THANK YOU FOR
COMING
MAHALOIT’S BEEN A PLEASURE