AMPAC Fire Finder DataSheet

7
PRODUCT DATA SHEET FireFinder SPX SERIES FIRE ALARM CONTROL PANEL PDS8550-1100 PDS8550-1100-3 FireFinder 4428.doc 1 DESCRIPTION The FireFinderSPX series is an Intelligent Analogue / Addressable and / or Conventional Fire Alarm Control Panel capable of supporting; ü Apollo Discovery and XP95 Intelligent Detectors, Multisensor, Photoelectric, Ionisation, Thermal (heat) and CO detectors. ü addressable initiating devices and modules that monitor any conventional normally open contact such as supervisory switches and flow switches. ü conventional two wire zone detector circuits ü multiple input/outputs ü high level interfaces ü graphical interfaces ü remote LCD Repeaters ü remote LED mimics ü peer to peer networking ü master slave (Main - Sub) networking ü main and data gathering panels networking and is built to comply with the; ü Australian Standard: AS 4428.1 ü New Zealand Standard: NZ4512 ü European Standard: EN54 ü Malaysian Standard: MS1404 ü Singapore Standard: CP10 E.O.L 3K3 CONVENTIONAL ZONE USING CONVENTIONAL DETECTORS AND BASES CONVENTIONAL ZONE CIRCUIT ADDRESSABLE LOOP ISOLATOR ION OPTICAL HEAT ANALOGUE DETECTORS MANUAL CALL POINT ( MCP ) ISOLATOR E.O.L 6K2 FIRE ALARM PRESS HERE TO BREAK EXTERNAL COMMUNICATION LOOP 4K7 4K7 FIRE ALARM PRESS HERE TO BREAK FIRE ALARM PRESS HERE TO BREAK HIGH LEVEL INTERFACE HIGH LEVEL INTERFACE ANCILLARY SERVICES EARTH FAULT TEST MODE SYSTEM FAULT SUPPLY FAULT POWERON PRE-ALARM AUX ALARM WARNING SYSFAULT Finder Fire WARNING SYS ISOLATE EXTERNAL BELL ISOLATE PREVIOUS NEXT ACKNOWLEDGE ISOLATE RESET ISOLATED ALARM FAULT AUXILIARY FAULT / ISOLATE FAULT OUTPUT ISOLATE AIF ACTIVE DE-ISOLATE LOOP 1 2 3 SENSOR 4 5 6 ZONE 7 8 9 TO 0 ENTER DISPLAY FUNCTION MENU CANCEL ENTRY FIREFIGHTER FACILITY FIREFINDER 15/1/2003 14:00:00 AMPAC PH: 08 9242 3333 SYSTEM IS NORMAL AS PER INPUT 1 AS PER INPUT 1 20K EOL 4K7 N/O INPUT SWITCH RELAY O/P 1 IN-1 IN-2 IN-3 C1 NC NO C2 NC NO C3 NC NO RELAY O/P 2 RELAY O/P 3 FIREFINDER FACP SINGLE INPUT DEVICE FLOW SWITCH E.O.L 20K LOOP SOUNDER L1 L2 E.O.L 10K SOUNDER SOUNDER CONTROL + - +24V DC N/O C N/C RELAY OUTPUT AUX OUTPUTS INPUT/OUTPUT UNIT CONVENTIONAL DETECTORS MAXIMUM OF 20 ZONE MONITOR OUT IN SPECIFICATIONS: MAX LENGTH = 2KM MAX RESISTANCE = 50ohms MIN CABLE SIZE = 1.5mm² MONITORED INPUT + - +24V DC THREE INPUT / OUTPUT DEVICE E.O.L 20K Typical Application FireFinder™ SP1X FireFinder™ SP8X

Transcript of AMPAC Fire Finder DataSheet

Page 1: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 1

DESCRIPTION

The FireFinder™ SPX series is an Intelligent Analogue / Addressable and / or Conventional Fire Alarm Control Panel capable of supporting; ü Apollo Discovery and XP95 Intelligent

Detectors, Multisensor, Photoelectric, Ionisation, Thermal (heat) and CO detectors.

ü addressable initiating devices and modules that monitor any conventional normally open contact such as supervisory switches and flow switches.

ü conventional two wire zone detector circuits ü multiple input/outputs ü high level interfaces ü graphical interfaces ü remote LCD Repeaters ü remote LED mimics ü peer to peer networking ü master slave (Main - Sub) networking ü main and data gathering panels networking and is built to comply with the; ü Australian Standard: AS 4428.1 ü New Zealand Standard: NZ4512 ü European Standard: EN54 ü Malaysian Standard: MS1404 ü Singapore Standard: CP10

E.O.L3K3

CONVENTIONAL ZONEUSING CONVENTIONAL DETECTORS

AND BASES

CONVENTIONAL ZONE CIRCUIT

ADDRESSABLE LOOP

ISOLATORION OPTICAL HEAT

ANALOGUE DETECTORSMANUAL CALLPOINT ( MCP )

ISOLATOR

E.O.L6K2

FIREALARM

PRESS HERE

TO BREAK

EXTERNAL COMMUNICATIONLOOP

4K7

4K7

FIREALARM

PRESS HERE

TO BREAK

FIREALARM

PRESS HERE

TO BREAK

HIGH LEVELINTERFACE

HIGH LEVELINTERFACE

ANCILLARYSERVICES

EARTH FAULT

T E S T M O D E

SYSTEM FAULT

SUPPLY FAULT

P O W E R O N

PRE-ALARM

AUX ALARM

W A R N I N GS Y S F A U L T

FinderTMFire

WARNING SYSISOLATE

EXTERNAL BELLISOLATE

PREVIOUS NEXTACKNOWLEDGE ISOLATER E S E T

ISOLATED

ALARM

FAULT

AUXILIARYFAULT / ISOLATE

FAULTOUTPUT ISOLATE

A I FACTIVE

DE-ISOLATE L O O P 1ABC

2DEF GHI

3

SENSORJ K L

4MNO5

PQRS6

Z O N ET U V

7 8WXYZ

9SYMB

TO 0SPACE

ENTERDISPLAY FUNCTIONMENU

C A N C E L E N T R Y

FIREFIGHTER FACILITY

FIREFINDER 15/1/2003 14:00:00AMPACPH: 08 9242 3333SYSTEM IS NORMAL

AS PER INPUT 1

AS PER INPUT 1

20KEOL

4K7

N/O INPUTSWITCH

RELAY O/P 1

IN-1

IN-2

IN-3

C1

NC

NO

C2

NC

NO

C3

NC

NO

RELAY O/P 2

RELAY O/P 3

FIREFINDERFACP

SINGLE INPUTDEVICE

FLOW SWITCHE.O.L 20K

LOOP SOUNDER

L1

L 2

E.O.L 10K

SOUNDER

SOUNDER CONTROL

+-+24V DC

N/O C N/C

RELAYOUTPUT

AUX OUTPUTS

INPUT/OUTPUT UNIT

CONVENTIONAL DETECTORSMAXIMUM OF 20

ZONE MONITOR

OUT

IN

SPECIFICATIONS:MAX LENGTH = 2KMMAX RESISTANCE = 50ohmsMIN CABLE SIZE = 1.5mm²

MONITORED INPUT

+- +24V DC

THREE INPUT / OUTPUTDEVICE

E.O

.L 2

0K

MENU

PREVIOUS NEXT B U Z Z E RMUTE

PRE-ALARMISOLATEDEFECTALARMNORMAL

A l a r mIsolate Fault Alarm

Isolate F a u l t

Typical Application

FireFinder™ SP1X

FireFinder™ SP8X

Page 2: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 2

BASIC CONFIGURATION

Main Board The Main Board is the " heart " of the FACP and carries the devices for interconnecting to all the other Boards, a buzzer for auditory indication, the backlight power supply for the LCD and CPU Reset. The Main CPU is mounted on and connected to this board which provides interfacing to ü Up to 4 Slave CPU’s ü A printer ü A Modem/Graphics Output ü An Expansion Panel ü An Internal serial bus ü An External communication bus. Front Panel Board The Front Panel Board provides the buttons used to control the FACP as well as all LED indications. All LED’s are surface mounted and the buttons are embedded within the board. The LCD is viewed / protected by a clear perspex screen. Brigade PSU Monitor Board The Brigade / PSU Monitor Board monitors and controls the power supply, battery charging, monitored / un-monitored inputs, outputs and the 7 relay outputs.

TB Function Type of O/P Bell 1 2 Amp Fused 3 Bell 2 2 Amp Fused Plant (Aux) Monitored 1 Amp Fused 4 Plant (Aux) Un-Monitored 1 Amp (VFC) Warn Sys (Evac) Monitored 1 Amp Fused 5 Warn Sys (Evac) Un-Monitored

1 Amp (VFC)

Fault Monitored 1 Amp Fused 6 Fault Un-Monitored 1 Amp (VFC)

7 Isolate 1 Amp (VFC) 8 Alarm 1 Amp (VFC) 9 Valve Monitor 1 Amp (VFC)

10 Batt Fail (Normally Energised ) 1 Amp (VFC) 1 Battery Output Protected

Aux Power Output 1 1 Amp Fused 2 Aux Power Output 1–EV40 use 3 Amp Fused

Aux Power Output 2 1 Amp Fused Note: VFC = Voltage Free Contacts

Main CPU The Main CPU holds the main central processing unit for the FACP. Slave CPU The Slave CPU (Central Processing Unit) provides the interfacing signals and I/O’s required to allow the FACP to connect / communicate to a variety of termination boards. A single chip micro controller controls all operations of the FACP Slave CPU. This device contains the control program within Read Only Memory (ROM). Conventional Board Under the control of a Slave CPU the Conventional Zone Board provides the interface between it and the external conventional devices. 16 Conventional zones can be connected to Conventional Zone Board. All un-used zone connections MUST be terminated in an EOL resistor of 3K3Ω. Addressable Loop Termination Board The Addressable Loop Termination Board acts as the interface between the external addressable devices and the control and monitoring functions of the FireFinder™. The board provides terminations for two loops each requiring one slave CPU per loop. Each loop is monitored by way of LED’s mounted on the board Note: Apollo devices L2 is +ve (positive), L1 is -ve (negative) Note: AMPAC strongly recommend that the LoopManager test set is used to check that the Apollo loop has been correctly installed and commissioned before connecting it to the FireFinder™. Loop Parameters ü 126 Apollo Devices ü 250mA Current Max ü S/C protection circuitry activates at

approximately 300mA

Page 3: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 3

SPECIFICATION Temperature: -5ºC to + 55ºC Humidity: 25% to 75% IP Rating: IP51 Maximum Number of Devices per Loop:

126

Maximum Number of Devices per Conventional Zone:

40

Cable Loop Characteristics:

2 core. 1.5 to 2.5mm²

Power Supply Output Voltage:

27V ( Set to 27.2V )

Power Supply Output Current:

2Amp, 5.6Amp or 18Amp

Power Supply Input: 85 - 264VAC Panel Current Draw: 450 mA (min) Battery Type and Capacity:

2 x 12V sealed lead-acid batteries

Capacity is determined by the installation configuration and supplementary documentation Power Supply and Battery Calculation. Minimum Operating Voltage:

19.2 V

SSL Listing Number afp-1160

Battery Capacity 7 Ah (min)

Compliance AS4428.1&5:1998

Mechanical

Construction Modular

Case finish Arch White powder coat

Model Material Dimension

SP1X 1.2mm steel 500H x 405W x 145Dmm

SP8X 1.2mm steel 840H x 515W x 170Dmm

SP16X 1.6mm steel 1200H x 625W x 240Dmm

10U 1.6mm steel 700H x 625W x 240Dmm

16U 2.0mm steel 1200H x 700W x 375Dmm

29U 2.0mm steel 1800H x 700W x 375Dmm

SP1X Anc Cab

1.2mm steel 250H x 405W x 145Dmm

SP8X Anc Cab

1.2mm steel 418H x 515W x 170Dmm

Note: Configurations SP1, 8 and 16 relate to a standard cabinet size while 10,16 and 29U relate to the number of rack units available.

ORDER CODES & CONFIGURATIONS

Order Code Panel Description

8550-1150 SP1X 16Zone AS4428 8550-1100 SP1X 1Loop AS4428 8550-1250 SP1X 16Zone ASE AS4428

8550-1200 SP1X 1Loop ASE AS4428 8550-1450 SP1X 16Zone EV20+Mic 5.6A AS4428

8550-1400 SP1X 1Loop EV20+Mic 5.6A AS4428 8550-1430 SP1X 16Zone EV40+Mic 5.6A AS4428

8550-1440 SP1X 1Loop EV40+Mic 5.6A AS4428 8550-4150 SP8X 16Zone 5.6A AS4428

8550-4100 SP8X 1Loop 5.6A AS4428 8550-4250 SP8X 16Zone ASE 5.6A AS4428

8550-4200 SP8X 1Loop ASE 5.6A AS4428 8550-4450 SP8X 16Zone EV40+Mic 5.6A AS4428

8550-4400 SP8X 1Loop EV40+Mic 5.6A AS4428 8550-4460 SP8X 16Zone EV60+Mic 5.6A AS4428 8550-4470 SP8X 1Loop EV60+Mic 5.6A AS4428

8550-4480 SP8X 16Zone EV120+Mic 18A AS4428 8550-4490 SP8X 1Loop EV120+Mic 18A AS4428

8550-5150 SP16X 16Zone 5.6A AS4428 8550-5100 SP16X 1Loop 5.6A AS4428

8550-6150 10U 16Zone 5.6A AS4428 8550-6100 10U 1Loop 5.6A AS4428

8550-6250 16U 16Zone 5.6A AS4428 8550-6200 16U 1Loop 5.6A AS4428

8550-6350 29U 16Zone 5.6A AS4428 8550-6300 29U 1Loop 5.6A AS4428

8510-9003 SP1X Ancillary Cabinet 8510-9010 SP8X Ancillary Cabinet

ENC1798-F SP1X Surround 158-0033 SP8X Surround

ENC2844-F SP16X Surround

ENC1797-F SP1X+Ancillary Cabinet Surround 158-0027 SP8X+Ancillary Cabinet Surround

Power Supply Specifications Type No Output R & N Effic S-60-27 27VDC @ 2.2A ± 1% 150mV 79% SP-150-27 27VDC @ 5.6A ± 1% 150mV 84% SP-500-27 27VDC @ 18A ± 1% 200mV 86% Input Voltage: 85 to 264 VAC Input Freq 47 to 63Hz. PFC 0.95~230VAC Tolerance at 27V ±1% Load Regulation ±0.5% Line Regulation ±0.5%

Page 4: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 4

Power Supplies AC Mains will be connected to either a 2 Amp, 5 Amp or 18Amp 27 volt supply. When the 18Amp power supply is used a Current Limiter, Fuse Board is required to provide protection for the boards, cards and other 27VDC distribution within the FACP.

CABLING RECOMMENDATIONS Conventional Zones Cabled in red Twin Plastic Sheath (TPS) or fire rated Radox or approved equivalent. Analogue Loop Two core cable. The minimum cable size is 0.75mm2, the maximum loop resistance is 50 ohms and the maximum loop distance is 2km. RS 422 Loop Two twisted pair screened (4 core) cable originating from FACP extending through the protected areas and returning to the FACP. Cable Specifications Capacitance of 100 picofarads per metre or less Resistance of 100 milliohms per metre or less Impedance of loop typical 100 to 120 ohms Maximum distances between modules 1.2km providing cable meets above specifications. Recommended cable type Belden 8132 or 9842 (non fire rated) Radox FR Communication 0.75mm 1 pair (fire rated) x 2 LCD Repeater Two by two twisted pair shielded cable (4 core) plus 2 core power, or local supply. Maximum distance between LCD mimic panel and FACP. is 1.2km.

+ Note: If the LCD operates in a redundant path mode the total cores including power is 10. The preferred cabling method in this case is 1 X 2 pair twisted shielded cable (4 core) and 1 X two pair twisted shielded cable (4 core) plus 2 core power LED Mimic ( RS485 ) Two core twisted shielded cable (No return loop) plus 2 core power or local supply. Maximum distance between each LED repeater card and FACP. is 1.2km.

Recommended Cable Type Hartland HC2335 Belden 9841 Radox FR Communication Fire Alarm Bell Connection Two core 1.5mm2 PVC sheathed MIMS ( Mineral Insulated Metal Sheathed ) to the bell location. Brigade Connection Via Landline Two core 1.5mm² PVC sheathed MIMS from the FACP to the landline MDF. RJ45 Multi-drop Serial Port

NETWORKING Expanding the system can be achieved in various ways and requires the use of boards specifically designed for communications purposes and boards that actually expand the system. When FACP’s are connected to each other they form a “ NETWORK “. Individual FACP’s in the Network are referred to as NODES. The Network as defined by the limitations of the installation can consist of a number of Nodes, the number of Nodes being dependant on the configuration of each Node. Typically an entire Network could consist of 128 Slave CPU’s connected to loops, zones and or input / output devices spread over several nodes. The Network is Peer to Peer with the entire system configuration being stored at each Node. The system is then programmed so that information can be made invisible to particular Nodes or visible to all Nodes. Likewise system commands can be global or restricted to specific parts of the network. The entire system can be programmed from Node 1 in the Network and is connected as a data loop which provides redundancy should there be a single cabling fault. Communications: Controller Interface Card The Controller Interface Card ( CIC ) provides 1 X RS232 O/P for High Level Interfaces, Graphics etc., 1 X half duplex RS485 O/P for external LED Mimic Boards, EWIS and to allow for multiple CIC interconnection Product Data Sheet Controller Interface Card PDS159-0054

Page 5: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 5

Communications: Network Interface Card The Network Interface Card provides two communication buses, RS232 and RS422, to allow the networking of multiple panels in different combinations, eg. from Data Gathering panels to Peer to Peer panels. Intercommunication can be via the Main Controller (Loop Comms) or by way of a Controller Interface Card connector. Fitted to the rear of the NIC is the CPU IO Controller with NIC software to control the flow of communications in and out of the NIC. Product Data Sheet Network Interface Card PDS159-0053 Expansion Board The Expansion Connection Board is used to increase the capacity of the controller from 4 Slave CPU’s to 8. Connection from the Controller to the Expansion Board, which must be mounted within 200mm of the Controller. Expansion Controller An Expansion Controller can be described as a Main Controller without a Front Panel. A maximum of 3 can be introduced into any one Node, that is into any one FACP and require Controller Interface Cards (CIC) and Network Interface Cards in order to communicate with the Main Board / Controller. Connecting Controllers together (Networking within the same cabinet) expands the system beyond 8 Slave CPU’s, that is the Main Board plus an Expansion Board. Networking in this way enables the connection of up to 4 Expansion Controllers within the same cabinet. This requires the use of CIC’s and NIC’s but offers the added advantage that the RS422 communication bus is internal and all Controllers are physically located at the same Node. It is now possible to Network up to 32 Slave CPU’s in one cabinet with each Slave CPU connected to an Addressable Loop, 16 Conventional Zone Boards or Digital I/O Board. With this configuration only one Controller has a Front Panel Board. Once the system has been expanded to this degree it is obviously quite large and some form of indication at a point remote from the FACP may become necessary. This is achieved with the use of a Controller Interface Card (CIC) and a Remote LED Mimic or a CIC, a Network Interface Card (NIC) and a Remote LCD Repeater.

RS232 MODEM / PROGRAMMING & DEBUG INTERFACING

The modem I/O port is a DB9 connector on the Main Board that is normally used for programming of the FACP via the serial port of a PC or Laptop. The Controller also has the required hand shaking to support connection to a Modem, thus allowing the FACP to be programmed from a remote site that has an established telephone connection. This allows the system software to be upgraded by simply transmitting a file via the serial port of the PC or Modem external to the FACP. Diagnostic facilities are also available via the same connection.

Modem / Programming / Debug Cabling

OCCUPANT WARNING SYSTEMS

The EV20, 40, 60, 120, 240 generate alert / evacuation signals, provide for PA facilities and are normally mounted on the back pan of the FACP. Should an alarm condition exist the “Warning System” output on the Brigade PSU Monitor Board initiates the Alert / Evacuation sequence. The Ampac EV3000 Occupant Warning and Intercommunication System (OWIS) is a microprocessor based OWIS system that complies with the appropriate Australian standards. The OWIS comprises of two sub-systems, 1. Occupant Warning System ( EWS ) The prime function of an OWS is to transmit via speakers in evacuation zones, alert signals, evacuation signals and public address. The OWS can automatically initiate evacuation procedures or be manually operated as well being used for non-emergency functions, eg. background music and general PA facilities.

1

2

3

4

5

6

7

8

9

DB9F CONNECTOR( Female Rear View )

2 CORE SHIELDED CABLE

DB9F CONNECTOR( Female Rear View )

1

2

3

4

5

6

7

8

9

Rx Data

Tx Data

Rx Data

Tx Data

Plugs into FACPTo Modem or PC

Page 6: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 6

2. Occupant Intercommunication System (OIS).

The OIS is an independent intercommunication system provided to communicate on a one to one basis from the Master Emergency Control Panel (MECP) to individual Warden Intercommunication Points (WIPs) within the evacuation zones. The Occupant Warning and Intercommunications System (OWIS) main central processing unit communicates via a RS485 bus with a Controller Interface Card (CIC) in an FACP. A fault in the EV3000 will be indicated by the Master Control Panel which in turn initiates, via the Common Fault Relay Board and Brigade PSU Monitor Board, a Warning System Fault indication on the FACP.

GRAPHICS

SmartGraphics is a purpose built graphics product for the monitoring of the Ampac FireFinder™ FACP. Features ü Remote control of the fire system ü Display status of devices, zones and

network nodes ü Supports user defined maps ü Security / password protection ü Option for mouse driven, touch screen

interface or other pointing devices ü Operates using industry standard

ModBus protocol ü Event and user access logs ü User may embed photographs. Supports

passive symbols eg, fire extinguishers, hose reels, hydrants etc.

ü Key map helps user to navigate throughout the site

ü Supports user defined messages for

each map eg Haz-Chem information, special instructions etc.

ü Supports multiple user levels ü Multiple zoom levels There are two alternative ways to connect the Ampac SmartGraphics to a FireFinder Fire Alarm Control Panel. 1. Via an RS485 communications port; or 2. an RS232 communications port RS485 provides the user with the opportunity to locate SmartGraphics a farther distance from FireFinder as compared with the RS232 protocol. The protocol adopted is based on the industry standard ModBus and has worldwide acceptance because of its high data integrity and reliability. Minimum Requirements

ü Pentium II 400Mhz, 64M RAM,

ü 2 GIG Hardrive, CDROM

ü Serial Comms for mouse or touch screen interface

ü Parallel Comms port for hardware security key / printer

ü Serial Comms port for connection to FACP, RS232 or RS485 as required

Computer (Rec Min)

ü Windows 98, 2000, NT, XP

Monitor 17” min (resolution 1024 x 768)

RS232 Comms 1 pair twisted & screened 15m maximum from FireFinder™ Baud rate – 9600 to 38400

RS485 Comms 1 pair twisted & screened 1200m maximum from FireFinder™ Baud rate – 9600 to 38400

Product code 159-0073 License package only 159-0074 Complete system package

Product Data Sheet PDS159-0067

Page 7: AMPAC Fire Finder DataSheet

PRODUCT DATA SHEET

FireFinder SPX SERIES FIRE ALARM CONTROL PANEL

PDS8550-1100

PDS8550-1100-3 FireFinder 4428.doc 7

COMPATIBLE EXPANSION CARDS, MODULES & BOARDS

i Numbers in Italic are Panel Add On Order Codes

Module / Function .................................................... Order Codes Max Number Off • 16/16 Input / Output Board ........................................ (302-6720) 8 per Slave CPU

( SP1X: 159-0113, SP8X: 159-0051, SP16X: 159-0009 )

• 8 Way Relay Board ................................................... (302-6760) 16 per Slave CPU ( SP1X: 159-0013, SP8X: 159-0013, SPX16X: 159-0015 )

• 16 Way Input Board .................................................. (302-6770) 8 per Slave CPU ( SP1X: 159-114, SP8X: 159-0010, SP16X: 159-0011 )

• Serial Relay Board .................................................... (302-7320) 16 per Controller ( SP1X: 159-0079, SP8X: 159-0072, SP16X: 159-0072)

• Fire Fan Module / Fire Fan Termination Board............. (159-0103 H/W) 15 per Controller ( SP1X: 159-0103, SP8X:159-0104, SP16X: 159-0119 )

• Fire Fan Module ( Loop Driven ) ................................. (159-0105) • General Indicator Card [ 32 Zone Alarm ] .................... (85BRDGIBB) * 16

( SP1X: 159-0106 ) * Configuration dependant ( SP8X: 159-0089, SP16X: 159-0120 )

• General Indicator Card [ 16/16 Zone Alarm / Fault ] ..... (85BRDGIBB) * 16 ( SP1X: 159-0107) * Configuration dependant ( SP8X: 159-0108, SP16X: 159-0121 )

• General Indicator Card ( Amber LED’s )...................... SP1X: 159-0123, SP8X &16: 159-0124 • Printer....................................................................... (TPUP-AT) 1 per Controller

( SP1X: 159-0084, SP8X: 159-0110 )

• Sounder/Bell Controller Board 8 X 1A per Circuit ......... (302-7420) 8 per Controller ( SP1X, SP8X: 159-0071 )

• Sounder/Bell Controller Board 4Volt free, 4x1Amp ....... (302-7421) 8 per Controller ( SP1X, SP8X: 150-0069 )

• Agent Release Module / Agent Termination Board ....... (BRD25ARB-A) 8 per Controller ( SP1X:159-0099, SP8X: 159-0100, SP16X: 159-0117 )

• Local Control Station (IP40) ....................................... (BRD25ARB-B) 4 per Termination Board • Expansion Board ...................................................... (302-6880) 1 per Controller

( SP8X: 159-0112, SP16X: 159-0022 )

• Expansion Controller ................................................. (SP16X: 159-0077) 3 per Node ( Rack: 159-0067 )

• Occupant Warning System – EV20 / 40 / 60 / 120........ Factory fit • Occupant Warning System – EV3000 ......................... Factory fit • Brigade Devices ........................................................ Factory fit

Compatible Networking Devices • Network Interface Card ............................................. (302-7240) 1 per Controller

( SP1: 159-0053, SP8X: 159-116, SP16X: 159-0053 )

• Controller Interface Card ........................................... (302-7250) 1 per Controller ( SP1X: 159-0054, SP8X: 159-0115, SP16X: 159-0054 )

• LCD Repeater ( Supplied Complete ) .......................... (302-7200) Note # 2 ( 159-0044 )

+ Note # 1 : This comprises 4 on the Main Controller and 4 on the Expansion Board.

+ Note # 2 : Depends on the configuration and the number of Panels in the System.