, , ,. .- ~ Governmentof the People's Republic of Bangladesh Office of the Project Director Bangladesh Railway Reform Project Rail Bhaban,Dhaka No. PD/BR/Reform/Procurement/ICB/G-2/12 Date: 15/05/2012 Amendment Notice No-2 The Bid document for Bid No- PD/BR/Reform/ProcurementlICB/G-2/12, dated: 20/03/12 for Procurement of Computer Hardware and Networking Equipments in : Lot-A- supply, installation and commissioning of the data centre at Dhaka and disaster recovery centre at Rajshahi with necessary accessories at. data centres and other locations along with maintenance services of the data centres and accessories for two years etc. and Lot-B- supply, installation and commissioning of the transmission networks, LAN sand WAN s at various BR locations with necessary PCs and accessories along with maintenance services of the transmission networks, LANs & WANs and accessories for two years etc. is herby amended. Necessary amendments are attached as Annexure- A to the amendment notice-2. The bidders are requested to collect the amendments from the office of the Project Director/Reform, Rail Bhaban, Dhaka. , ~~~~~- d-~~ (Mohammad Moq bul AhameJ) ¥)..- Project Director Bangladesh Railway Reform Project Rail Bhaban, Dhaka \ Page 1 of8

description

hardware amendment

Transcript of Amendment Notice - 2 _Hardware Tender

  • , ,

    ,.

    .-

    ~

    Government of the People's Republic of BangladeshOffice of the Project Director

    Bangladesh Railway Reform ProjectRail Bhaban, Dhaka

    No. PD/BR/Reform/Procurement/ICB/G-2/12 Date: 15/05/2012

    Amendment Notice No-2

    The Bid document for Bid No- PD/BR/Reform/ProcurementlICB/G-2/12, dated: 20/03/12 forProcurement of Computer Hardware and Networking Equipments in : Lot-A- supply, installationand commissioning of the data centre at Dhaka and disaster recovery centre at Rajshahi withnecessary accessories at. data centres and other locations along with maintenance services of thedata centres and accessories for two years etc. and Lot-B- supply, installation and commissioningof the transmission networks, LAN sand WAN s at various BR locations with necessary PCs andaccessories along with maintenance services of the transmission networks, LANs & W ANs andaccessories for two years etc. is herby amended. Necessary amendments are attached as Annexure-A to the amendment notice-2. The bidders are requested to collect the amendments from the officeof the Project Director/Reform, Rail Bhaban, Dhaka.

    ,

    ~~~~~- d-~~(Mohammad Moq bul AhameJ) )..-Project DirectorBangladesh Railway Reform ProjectRail Bhaban, Dhaka

    \ Page 1 of8

  • Page 2 of 8

    Annexure-A to Amendment Notice-2 Sl. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-2 Section II Bid Data Sheet

    1. Section-II, Page-2-3, ITB-24.1 Bid Data Sheet The deadline for bid submission is:

    Date: 21 May 2012 Time: 11-30 hours

    The deadline for bid submission is: Date: 28 May 2012

    Time: 11-30 hours

    2.

    Section-II, Page-2-3, ITB-24.1 Bid Data Sheet The bid opening shall take place at: Street Address: 16 Abdul Gani Road, Floor/Room number: Room No-719 (6th floor), Rail Bhaban. City : Dhaka, Country: Bangladesh. Date: 21 May 2012. Time: 12-00 hours

    The bid opening shall take place at: Street Address: 16 Abdul Gani Road, Floor/Room number: Room No-719 (6th floor), Rail Bhaban. City : Dhaka, Country: Bangladesh. Date: 28 May 2012.

    Time: 12-00 hours Section IV Price Schedules

    3. Section: IV, Table-A-1, P-4-9, Section-VI, Table-A-1, new item added

    LED Monitor

    LED monitor (Console & Keyboard), 17" TFT display. Qty 01

    4. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added.

    LED Monitor

    LED monitor (Console & Keyboard), 17" TFT display. Qty 01

    5. Section: IV, Table-A-4, P-4-18.item-21, Section: IV, Table-A-5, P-4-19.item-12, Section: VI, Table-A-4, A-5

    LED Monitor LED monitor (Console & Keyboard), 15" TFT display.

    Deleted

    6. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added.

    KVM/IP Switch

    KVM / IP Switch (16 port) with Software. Qty - 03

    7. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added.

    KVM/IP Switch

    KVM / IP Switch (16 port) with Software. Qty - 03

    8. Section: IV, Table-A-4, P-4-18.item-22, Section: IV, Table-A-5, P-4-19. Item-13, Section: VI, Table-A-4, A-5

    KVM/IP Switch KVM / IP Switch (16 port) with Software. Deleted

    9. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added

    4.5 T comfort A/C

    4.5 Ton Comfort AC for Power Room. Qty - 02

    10. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added.

    4.5 T comfort A/C

    4.5 Ton Comfort AC for Power Room. Qty - 02

    11. Section: IV, Table-A-9, P-4-22. Item-2, Section: IV, Table-A-10, P-4-22, item-2, Section: VI, Table-A-4, A-5

    4.5 T comfort A/C 4.5 Ton Comfort AC for Power Room. Qty - 02

    Deleted

    12. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added

    1 T comfort A/C

    1 Ton Comfort AC for FME Room om. Qty - 02

    13. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2,new item added.

    1 T comfort A/C

    1 Ton Comfort AC for FME Room om. Qty - 02

    14. Section: IV, Table-A-9, P-4-22.item-3, Section: IV, Table-A-10, P-4-22, item-3, Section: VI, Table-A-9, A-10

    1 T comfort A/C

    1 Ton Comfort AC for FME Room. Qty - 02

    Deleted

    15. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added

    Dehumidifier Dehumidifier. Qty - 02

    16. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added

    Dehumidifier Dehumidifier. Qty - 02

    17. Section: IV, Table-A-9, P-4-22, item-4, Section: IV, Table-A-10, P-4-22,item-4, Section: VI, Table-A-9, A-10

    Dehumidifier

    Dehumidifier. Qty - 02 Deleted

    18. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added

    Fire Suppression System

    Fire Suppression System. Qty- 1 Set

  • Page 3 of 8

    Annexure-A to Amendment Notice-2 Sl. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-2 19. Section: IV, Table-A-2, P-4-11,

    Section: VI, Table-A-2, new item added.

    Fire Suppression System

    Fire Suppression System. Qty- 1 Set

    20. Section: IV, Table-A-9, P-4-22, item-6, Section: IV, Table-A-10, P-4-22, item-6, Section: VI, Table-A-9, A-10

    Access Control System

    Fire Suppression System. Qty- 1 Set Deleted

    21. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added

    Access Control System

    Access Control (Proximity Card) System. Qty- 1 Set

    22. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added.

    Access Control System

    Access Control (Proximity Card) System. Qty- 1 Set

    23. Section: IV, Table-A-9, P-4-22, item-7, Section: IV, Table-A-10, P-4-22, item-7, Section: VI, Table-A-9, A-10

    Access Control System

    Access Control (Proximity Card) System. Qty- 1 Set

    Deleted

    24. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added

    CCTV Monitoring System

    CCTV Monitoring System. Qty- 1 Set

    25. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added.

    CCTV Monitoring System

    CCTV Monitoring System. Qty- 1 Set

    26. Section: IV, Table-A-9, P-4-22, item-7, Section: IV, Table-A-10, P-4-22, item-7, Section: VI, Table-A-9, A-10

    CCTV Monitoring System

    CCTV Monitoring System. Qty- 1 Set Deleted

    27. Section: IV, Table-A-1, P-4-9, Section: VI, Table-A-1, new item added,

    Proximity Card system

    Proximity Card system. Qty- 1 Set

    28. Section: IV, Table-A-2, P-4-11, Section: VI, Table-A-2, new item added.

    Proximity Card system

    Proximity Card system. Qty- 1 Set

    29. Section: IV, Table-A-1, P-4-7, item-13

    Automatic Voltage Stabiliser

    Capacity is 300 KVA 400 KVA Automatic Voltage Stabiliser

    30. Section: IV, Table-A-2, P-4-10, item-13

    Automatic Voltage Stabiliser

    Capacity is 300 KVA 400 KVA Automatic Voltage Stabiliser

    31. Section: IV, Table-A-9, P-4-22, item-9, Section: IV, Table-A-10, P-4-22, item-9, Section: VI, Table-A-9, A-10

    Proximity Card system Proximity Card system. Qty- 1 Set

    Deleted

    32. Section: IV, Table-A-1, P-4-8. Section: VI, Table-A-1, New item added

    Cables 3C-2.5 mm2NYY. Qty: 250 Mtr

    33. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Cables 3C-2.5 mm2NYY. Qty: 250 Mtr

    34. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Earth conduit conductors

    1C-2.5mm2 BYA Cable(Green), Qty: 400 Mtr

    35. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Earth conduit conductors

    1C-2.5mm2 BYA Cable(Green), Qty: 400 Mtr

    36. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Earth conduit conductors

    1C-4.0mm2 BYA Cable(Green), Qty: 200 Mtr

    37. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Earth conduit conductors

    1C-4.0mm2 BYA Cable(Green), Qty: 200 Mtr

    38. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Earth conduit conductors

    1C - 16 mm2 BYA Cable(Green), Qty: 140 Mtr

    39. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item

    Earth conduit conductors

    1C - 16 mm2 BYA Cable(Green), Qty: 140 Mtr

  • Page 4 of 8

    Annexure-A to Amendment Notice-2 Sl. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-2 added.

    40. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Earth conduit conductors

    1C - 35 mm2 BYA Cable(Green) , Qty: 200 Mtr

    41. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Earth conduit conductors

    1C - 35 mm2 BYA Cable(Green) , Qty: 200 Mtr

    42. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-2, new item added.

    Earth conduit conductors

    1C - 50 mm2 BYA Cable(Green) , Qty: 210 Mtr

    43. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Earth conduit conductors

    1C - 50 mm2 BYA Cable(Green) , Qty: 210 Mtr

    44. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Earth conduit conductors

    1C-95mm2 BYA Cable(Green) , Qty: 24 Mtr

    45. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Earth conduit conductors

    1C-95mm2 BYA Cable(Green) , Qty: 24 Mtr

    46. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    HT Cables 3C-95 rm, NYSEYFG by, Qty: 100 Mtr

    47. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    HT Cables 3C-95 rm, NYSEYFG by, Qty: 100 Mtr

    48. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Light Fittings Qty: 70 Set

    49. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Light Fittings Qty: 70 Set

    50. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Socket Outlets Qty: 25 Set

    51. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Socket Outlets Qty: 25 Set

    52. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Socket Outlets Qty: 36 Set

    53. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Socket Outlets Qty: 36 Set

    54. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Electrical System: switches & sockets

    Single Pole Switch 4Gang Qty: 10 Set

    55. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Electrical System: switches & sockets

    Single Pole Switch 4Gang Qty: 10 Set

    56. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Electrical System: switches & sockets

    Single Pole Switch 2Gang Qty: 3 Set

    57. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Electrical System: switches & sockets

    Single Pole Switch 2Gang Qty: 3 Set

    58. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Electrical System: switches & sockets

    Single Pole Switch 3Gang Qty: 3 Set

    59. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Electrical System: switches & sockets

    Single Pole Switch 3Gang Qty: 3 Set

    60. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Cable Ladder/Tray Qty: 800 rft

    61. Section: IV, Table-A-2, P-4-10. Cable Ladder/Tray Qty: 800 rft

  • Page 5 of 8

    Annexure-A to Amendment Notice-2 Sl. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-2 Section: VI, Table-A-2, new item added.

    62. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Grounding/Earthing System

    Qty: 8 Sets

    63. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Grounding/Earthing System

    Qty: 8 Sets

    64. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    Grounding/Earthing System

    Qty: 8 Set

    65. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Grounding/Earthing System

    Qty: 8 Set

    66. Section: IV, Table-A-1, P-4-7. Section: VI, Table-A-1, new item added.

    TVSS Qty: 7 Set.

    67. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    TVSS

    Qty: 7 Set.

    68. Section: IV, Table-A-1, P-4-7, Section: VI, Table-A-1, new item added.

    Electrical Licensing

    HT Metering Panel including 400VA solar panel including charge controller battery backup time 2 hours input voltage 48V DC,output voltage 220V,50Hz AC & related accessories Qty: 1 Set

    69. Section: IV, Table-A-2, P-4-10. Section: VI, Table-A-2, new item added.

    Electrical Licensing

    HT Metering Panel including 400VA solar panel including charge controller battery backup time 2 hours input voltage 48V DC,output voltage 220V,50Hz AC related accessories Qty: 1 Set

    70. Section: IV, Table-A-4, P-4-17, Section: VI, Table-A-4

    Server Backup Tapes, Qty: 250 Nos Backup Tapes Qty: 150 Nos & cleaning tape 5 nos.

    71. Section: IV, Table-A-5, P-4-19, Section: VI, Table-A-5

    Server Backup Tapes, Qty: 250 Nos Backup Tapes Qty: 150 Nos & cleaning tape 5 nos.

    72. Section: IV, Table-A-5, P-4-19, Section: VI, Table-A-5, new item added.

    Server Servers for antivirus - 6 Core, 24 GB Memory, Disk 2X600 GB, Qty: 01 Nos

    73. Section: IV, Table-A-5, P-4-19, Section: VI, Table-A-5, new item added.

    Server

    Servers for Integrated Service Management (Data centers) - 6 Core, 24 GB Memory, Disk 2X600 GB, Qty: 03 Nos

    74. Section: IV, Table-A-5, P-4-19, Section: VI, Table-A-5, new item added.

    Server Servers for Patch deployment 6 Core, 24 GB Memory, Disk 2X600 GB, Qty: 01 Nos

    75. Section: IV, Table-A-3, P-4-12, Section: VI, Table-A-3, new item added

    Civil Works Window grill works made of flat bar along with necessary coating, painting as per direction of Engineer in charge, qty- 100 M2

    76. Section: IV, Table-A-3, P-4-15, Section: VI Table-A-3, item-20.1

    Civil Works 200 Amps TPMCCB (25 KA) Qty 150 each

    200 Amps TPMCCB (25 KA) Qty 02 each

    77. Section: IV, Table-A-3, P-4-15, Section: VI, Table-A-3, item-25

    Civil Works Supply, installation, fitting & fixing of MDB made of 16 SWG sheet steel size 3x4x1 Qty 10 Each

    Supply, installation, fitting & fixing of MDB made of 16 SWG sheet steel size 3x4x1 Qty 04 Each

    78. Section: IV, Table-B-1, P-4-28, Section: VI, Table-B-1,new item added

    Minor construction works required for installation off DG sets at remote sites or similar works Qty L.S.

    79. Section: IV, Table-B-1, P-4-28, Section: VI, Table-B-1, new item added

    Note: Item-23, 24, 25, 26 & 27 of Amendment Notice-1 will be added at end of Table-B-1 instead of Table B-3.

    80. Section: IV, Section-VI, Note (at end of Table A-13)

    If the bidder assumes that any item/items are required for supply/installation/commissioning and are not included in table A-1 A-13, the bidder can include the missing item/items in appropriate table of Section-IV with cost and in Section-VI giving proper justification. BR will check and examine the appropriateness of inclusion of additional items by the bidder.

    81. Section: IV, Section-VI, Note (at end of Table B-5)

    If the bidder assumes that any item/items are required for supply/installation/commissioning and are not included in table B-1 B-5, the bidder can

  • Page 6 of 8

    Annexure-A to Amendment Notice-2 Sl. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-2 include the missing item/items in appropriate table of Section-IV with cost and in Section-VI giving proper justification. BR will check and examine the appropriateness of inclusion of additional items by the bidder.

    82. Section: IV,Table-A-8,item-2, P-4-21,Section-VI,Table-A-8,item-2

    Active network components

    Zonal distribution Switch Qty 10 nos. (as per Amendment-1)

    Building distribution Switch Qty 10 nos.

    83. Section: IV, Table-B-3, item-1 & 3, P-4-29, Section-VI, Table-B-3

    Passive network equipments

    Mux-STM-1, Qty-30 nos, Mux-STM-16, Qty-22 nos

    Mux-STM-1, Qty-26 nos, Mux-STM-16, Qty-26 nos

    Section-VI - Schedule of Supply (Schedule of Requirements) Server Hardware

    84. Section: VI, Table-A-4, P-6-11 Section: VI, Table-A-5, P-6-11

    Server Backup Tapes, Qty: 250 Nos Backup Tapes, Qty: 150 Nos

    85. Section: VI, Table-A-5, P-6-11, new item added.

    Server

    Servers for antivirus - 6 Core, 24 GB Memory, Disk 2X600 GB, Qty: 01 Nos

    86. Section: VI, Table-A-5, P-6-11, new item added.

    Server

    Servers for Integrated Service Management (Data centers) - 6 Core, 24 GB Memory, Disk 2X600 GB, Qty: 03 Nos

    87. Section: VI, Table-A-5, P-6-11, new item added.

    Server

    Servers for Patch deployment 6 Core, 24 GB Memory, Disk 2X600 GB, Qty: 01 Nos

    88. Section-VI, Page 6-51 : Item 1.11.1.09 :

    16 port KVM Switch 16 port IP KVM switch for servers along with cables, converter and connectors for server connectivity. 21 TFT- LED collapsible flat panel monitor console kit with keyboard and mouse including cables (1U).

    16 port IP KVM switch for servers along with cables, converter and connectors for server connectivity. 17 TFT- LED collapsible flat panel monitor console kit with keyboard and mouse including cables (1U).

    89. Section-VI, Page 6-51 : Item 1.11.1.09 :

    16 port KVM Switch LAN connectivity: 10/100/1000 MPPS

    LAN connectivity: 10/100 MPPS

    90. Section-VI, Page 6-51 : Item 1.11.1.10 :

    Keyboard Wireless English Keyboard

    USB English Keyboard

    91. Section: VI, P-6-61, Clause-1.11.2.3.

    Edge switch [24 ports and 48 ports], Management

    For enhanced traffic management, monitoring, and analysis, the Embedded Remote Monitoring (RMON) software agent should support four RMON groups (history, statistics, alarms, and events). All nine RMON groups should be supported through a SPAN port, which permits traffic monitoring of a single port, a group of ports, or the entire stack from a single network analyzer or RMON probe.

    For enhanced traffic management, monitoring, and analysis, the Embedded Remote Monitoring (RMON) software agent should support four RMON groups (history, statistics, alarms, and events).

    92. Section: VI, P-6-68, Clause-1.11.2.5.

    Router for Zonal Offices & Remote offices, Management & maintenance

    SNMP v1, v2c, v3, Standard and enterprise MIBs, Telnet, SSH, Syslog, RMON, Configuration rollback, NetStream packet statistics

    SNMP v1, v2c, v3, Standard and enterprise MIBs, Telnet, SSH, Syslog, RMON, Configuration rollback, packet/IP statistic

    93. Section: VI, P-6-71, Clause-1.11.2.9.

    Load Balancer Inbound and Outbound Deleted

    94. Section: VI, P-6-76, Clause-1.11.2.10

    AAA server Lightweight Directory Access Protocol (LDAP) and Open Database Connectivity (ODBC) user authentication support

    Lightweight Directory Access Protocol (LDAP) user authentication support

    95. Page 6-75 1.11.2.9

    NMS NMS should provide inbuilt Correlation Composer Graphical User Interface (GUI), which enables users to tailor the event correlation behaviour of the correlators that are shipped with product.

    Deleted

    96. Page 6-75 1.11.2.9

    NMS It shall detect and isolate the root cause of layer 3 network instabilities and anomalies and shall verify and alerts on changes to routing redundancy provided by the device traps to NMS preventing costly service outages

    Deleted

    97. Section: VI, Page 6-75 1.11.2.9

    NMS It shall monitor the routing protocols that direct the flow of traffic throughout the network, and construct the routers view of the network, compute and display changes in routes by the next polling interval.

    Deleted

  • Page 7 of 8

    Annexure-A to Amendment Notice-2 Sl. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-2 98. Section: VI, Page 6-75

    1.11.2.9 NMS NMS should provide Discovery of

    interface to VRF and VPN relationships on regular intervals and by user-initiated discovery.

    Deleted

    99. Section: VI, Page 6-76 1.11.2.9

    NMS NMS should be able to conduct and configure reach ability tests of the connections between PE CE devices for real time monitoring of MPLS label switch paths

    Deleted

    100. Section: VI, Page 6-76 1.11.2.9

    NMS NMS should provide data on the PE routers when failure occurs about the VRF impacted and the VPN impacted with complete audit details of the routing events.

    Deleted

    101. Section: VI, Page 6-76 1.11.2.9

    NMS NMS should Detect and provide alerts on potential VPN privacy issues by checking that Provider Edge (PE) router configurations are not causing route leakage due to mis-configurations.

    Deleted

    102. Section: VI, 1.11.2.9, P-6-71

    Server Farm and DMZ Switch

    24 Ethernet 10/100/1000 ports and 2x10GE port (DMZ)

    24 Ethernet 10/100/1000 ports and 2x10GE/4x1GE port (DMZ)

    103. Section: VI, 1.11.8, P-6-108

    Supplying, Laying and Installation of various Telecom Cables is not required and hence Table 1.11.8 deleted.

    Data Center

    104. Section VI, Page-6-119 Fire suppression system

    Physical Properties of gas: Qty

    Physical Properties of gas, Qty: CDC Qty 180 Kg & DR Qty 180 Kg

    105. Section VI, Page-6-120 Fire suppression system

    140 Ltr Cylinder(approx.): Qty

    140 Ltr Cylinder(approx.), Qty: CDC 2 Nos & DR 2 Nos

    106. Section VI, Page-6-120 Fire suppression sys. 68 Ltr Cylinder(approx.): Qty 68 Ltr Cylinder(approx.),Qty: DC 1 No & DR 1No 107. Section VI, Page-6-120 Fire suppression sys. Heat Detector: Qty Heat Detector,Qty: CDC 12 Nos & DR 12 Nos 108. Section VI, Page-6-121 Fire suppression sys. Smoke Detector: Qty Smoke Detector, Qty: CDC 12 Nos & DR 12 Nos 109. Section VI, Page-6-121 Fire suppression sys. Rotating Light: Qty Rotating Light, Qty: CDC 1 Nos & DR 1 Nos 110. Section VI, Page-6-121 Fire suppression sys. Alarm Bell: Qty Alarm Bell, Qty: CDC 3 Nos & DR 3 Nos 111. Section VI, Page-6-121 Fire suppression sys. Auto Exit Sign: Qty Auto Exit Sign, Qty: CDC 4 Nos & DR 4 Nos 112. Section VI, Page-6-121 Fire suppression

    system Manual Call Point or Break Glass: Qty

    Manual Call Point or Break Glass, Qty: CDC 2 Nos & DR 2 Nos

    113. Section VI, Page-6-122 Environment Monitoring System ( EMS)

    Message Master 4000 (Rack mount) built-in GSM Modem, Brand : PICOBOX , Model : RMC1-R or equivalent: Qty

    Message Master 4000 (Rack mount) built-in GSM Modem, Brand : PICOBOX , Model : RMC1-R or equivalent; Qty: CDC 1 Nos & DR 1 Nos

    114. Section VI, Page-6-122 Environment Monitoring System

    Temperature / humidity sensor , Model: THS-90R or equivalent: Qty:1 No

    Temperature / humidity sensor , Model: THS-90R or equivalent; Qty: CDC 6 Nos & DR 6 Nos

    115. Section VI, Page-6-122 Environment Monitoring System

    Water & Liquid Leakage Detector, Model: SP-10 16 or equivalent: Qty

    Water & Liquid Leakage Detector, Model: SP-10 16 or equivalent; Qty: CDC 8 Nos & DR 8 Nos

    116. Section VI, Page-6-122 Access Control System

    Single Door Access Control System (Biometric IP Based), Brand: Suprema or equivalent. Model: BLR-OC or equivalent. Origin: Korea. Finger + RF Card+ Pin Reader; Qty: 1 Nos

    Single Door Access Control System (Biometric IP Based), Brand: Suprema or equivalent. Model: BLR-OC or equivalent. Origin: Korea. Finger + RF Card+ Pin Reader; Qty: CDC 4 Nos & DR 4 Nos

    117. Section VI, Page-6-122 Access Control System

    Proximity card Reader for Exit with TCP/IP communication; Qty

    Proximity card Reader for Exit with TCP/IP communication;Qty: CDC 4 Nos & DR 4 Nos

    118. Section VI, Page-6-123 CCTV System Stand Alone DVR, 16 Channels, Model : AVC 789 AD or equivalent; Qty

    Stand Alone DVR, 16 Channels, Model : AVC 789 AD or equivalent; Qty: CDC 1 Nos & DR 1 Nos

    119. Section VI, Page-6-123 CCTV System Dome Type Colour CCD Dome camera , 3.6mm lens Model: CP- DY 42L2 or equivalent; Qty : 1no

    Dome Type Colour CCD Dome camera , 3.6mm lens, Model: CP- DY 42L2 or equivalent; Qty : CDC 12 Nos & DR 12 Nos

    120. Section VI, Page-6-123 CCTV System SMPS Power Supply Unit for Camera Operation; Qty

    SMPS Power Supply Unit for Camera Operation; Qty: CDC 12 Nos & DR 12 Nos

    121. Section VI, Page-6-123 CCTV System LCD Monitor 17" , Accessories and Cabling with conduit (Co-axial Video and Power Cable; Qty

    LCD Monitor 17" , Accessories and Cabling with conduit (Co-axial Video and Power Cable; Qty: CDC 1 Nos & DR 1 Nos

    122. Section: VI, P-6-141 Grounding/Earthing System

    Construction 300X300X300mm earth ( Qty : 03)

    Construction of 300X300X300mm earth ( Qty : 08)

    123. Section VI, Page-6-102 12U Network Equipment Rack 27U Network Equipment Rack

    124. Section VI, Page-6-105, Clause-1.11.7.3

    Network Printer-Laser Jet Printer

    Processor Speed : 400 MHz or Higher Processor Speed : 300 MHz or higher

  • ,Annexure-A to Amendment Notice-2SI. Ref. Page, Para/Clause No. Related to Existing Clause/Para/Sentence/Word Replaced/Added Clause/Para/Sentence/Word

    by this Amendment Notice-l126' Section -VI, Page-6-I08, Clause- Multi Function 34/33 ppm (black/colour) 30/20 or 27 ppm (black/colour)

    I. I 1.7.5 Devices(Print,Scan,COpy), print speed

    I2~ Section -VI, Page-6- I 08, Clause- Multi Function Black Colour Inkjet Black Colour Inkjetl Laserjet '.I. I 1.7.5 Devices(Print,Scan,

    Copy), printTechnology

    12' Section-VL Page-6-I08, Clause- Multi Function Memory: 128 MB or Higher1.11.7.5 Devices(Print,Scan, .Memory:I60MBorHigher

    COpy)12~ Section -VL Page-6-103, Clause- Desktop Machines Chipset: Intel Q35 Chipset or better on Chipset: Intel H61 Chipset or better on OEM

    1.11.7.1 OEM Motherboard Motherboard12~ Section -VL Page-6-103, Clause- Laptop Intel Core i5 processor or higher (clock Intel Core i5 processor or higher (clock speed

    1.11.7.2 speed 2.5GHz or higher, 4 threads, 8MB 2.5GHz or higher, 4 threads, 3/6/8 MB L3 cache orL3 cache or better) better)

    I~ Section -VL Page-6-103, Clause- Laptop Power Supply: 250W ATX 12 V Surge Power Supply: 65W Slim AC Adapter1.11.7.2 Protected

    1'!.1. Section -VL Page-6-103, Clause- Laptop Battery: 6-cell LI-ION primary battery, Battery: 6-cell Lithium ION primary battery,1.11.7.2 backup minimum 4.00 hours backup minimum 3.00 hours

    1~1 Section: VL Page-6-151, item-12 Civil works 11/2" thick patent stone flooring ,., as 1'/2" thick patent stone flooring ...",.. as perper direction of Enl!ineer, Qtv: 500 M2 direction of Engineer, Qty: 1000 M2

    1~3 Section: VL Page-6-151, item-25 Civil works Providing 4" (IOOmm) thick (average) Deleted.lime terracing (7:2:2) specification ofthe Engineer.Otv: 50 M3M3

    , 7~W~~~) ~

    (Mohammad Moqbul Ahamed) d ~ fiv-a:::Project DirectorBangladesh Railway Reform ProjectRoom number: 701 (6th floor), Rail BhabanCity: Dhaka, Country: Bangladesh