Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard...
6
Transcript of Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard...
![Page 1: Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard as 208Y/120Vac, however the panel schedule on Sheet E-501 for PPI shows this panel](https://reader035.fdocuments.us/reader035/viewer/2022063016/5fd5a31e965dde26060d941d/html5/thumbnails/1.jpg)
![Page 2: Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard as 208Y/120Vac, however the panel schedule on Sheet E-501 for PPI shows this panel](https://reader035.fdocuments.us/reader035/viewer/2022063016/5fd5a31e965dde26060d941d/html5/thumbnails/2.jpg)
![Page 3: Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard as 208Y/120Vac, however the panel schedule on Sheet E-501 for PPI shows this panel](https://reader035.fdocuments.us/reader035/viewer/2022063016/5fd5a31e965dde26060d941d/html5/thumbnails/3.jpg)
![Page 4: Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard as 208Y/120Vac, however the panel schedule on Sheet E-501 for PPI shows this panel](https://reader035.fdocuments.us/reader035/viewer/2022063016/5fd5a31e965dde26060d941d/html5/thumbnails/4.jpg)
![Page 5: Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard as 208Y/120Vac, however the panel schedule on Sheet E-501 for PPI shows this panel](https://reader035.fdocuments.us/reader035/viewer/2022063016/5fd5a31e965dde26060d941d/html5/thumbnails/5.jpg)
![Page 6: Amazon Web Services Government...5.) Drawing E-501 Grounding Detail shows the downstream panelboard as 208Y/120Vac, however the panel schedule on Sheet E-501 for PPI shows this panel](https://reader035.fdocuments.us/reader035/viewer/2022063016/5fd5a31e965dde26060d941d/html5/thumbnails/6.jpg)