Air Demand Analysis
-
Upload
jason-acker -
Category
Engineering
-
view
20 -
download
0
Transcript of Air Demand Analysis
2016 Kaeser Compressors, Inc., USA (V1.0)
Air Demand Analysis (ADA) and Kaeser Energy Saving System (KESS) analysis
performed by Palmetto Compressors, Inc. and prepared by Kaeser Compressors, Inc.
**********– January 2016
2016 Kaeser Compressors, Inc., USA (V1.0) 2
As recorded during initial site survey.
System Sketch
Motor Signal
Load Signal
Pressure Transducer
kW Meter
SSR EP100
SSR EP100
ZHA1000 Dryer
250 gallon tank
2016 Kaeser Compressors, Inc., USA (V1.0) 3
The above calculations were based on the measured data from the testing period. The energy cost was based on the sample week between Saturday 1/9/2016 and Friday 1/15/2016 and extrapolated over 364 days per year at $0.08/kWh.
Existing System Data Summary
Total Energy Consumption (kWh/yr)Maximum kW Draw (kW)Average kW Draw (kW)Specific Power (kW/100 CFM)Total Energy Cost ($/YR)Total Flow (CF/YR)Available Capacity (CFM)Peak Flows: Excluding Startup (CFM)Duration of Peak Flow (Minutes)Average Flow (CFM)Minimum Flow (CFM)
Wet Pressure
Dry Pressure
Maximum Pressure (PSIG) 111 110Minimum Pressure (PSIG) 77 76Average Pressure (PSIG) 102 101
Pressure
$62,644223,251,081
783,05015690
21.04
Energy
Flow
868761
3426251
DATA SUMMARY
2016 Kaeser Compressors, Inc., USA (V1.0) 4
Averaged over 5 minutes. This chart highlights the cumulative flow throughout the test as measured via the load signals of the Ingersoll Rand SSR EP100 compressors.
Compressor System Capacity868 cfm-fad at 125 psig
Cumulative Flow Profile – Summary
2016 Kaeser Compressors, Inc., USA (V1.0) 5
Averaged over 5 minutes. This chart highlights the cumulative flow throughout the test as measured via the load signal of the Ingersoll Rand SSR EP100 compressor.
Compressor Capacity434 cfm-fad at 125 psig
Cumulative Flow Profile – Ingersoll Rand SSR EP100 Unit 1
2016 Kaeser Compressors, Inc., USA (V1.0) 6
Averaged over 5 minutes. This chart highlights the cumulative flow throughout the test as measured via the load signal of the Ingersoll Rand SSR EP100 compressor.
Compressor Capacity434 cfm-fad at 125 psig
Cumulative Flow Profile – Ingersoll Rand SSR EP100 Unit 2
2016 Kaeser Compressors, Inc., USA (V1.0) 7
Cumulative Pressure Profile – Wet Pressure
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 8
Cumulative Pressure Profile – Dry Pressure
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 9
Cumulative kW Profile – Ingersoll Rand SSR EP100 Unit 1
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 10
Cumulative kW Profile – Ingersoll Rand SSR EP100 Unit 2
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 11
KESS Energy Cost Comparisons – As Measured
The above calculations were based on the measured data from the testing period. The energy cost was based on the sample week between Saturday 1/9/2016 and Friday 1/15/2016 and extrapolated over 364 days per year at $0.08/kWh.
Note: If demands change from the recorded flow profile, the proposed solutions may no longer be feasible for plant operations and savings potential may differ.
Energy Cost ($/kWh) $0.080Interval of Calculation 5 Minutes
Total Energy Cost ($/yr) $62,644 $51,939 $60,422 $60,327
Total Energy Consumption (kWh/yr) 783,050 649,232 755,280 754,088
Maximum Power Consumption (kW) 156.5 127.7 125.1 137.4
Specific Power (kW / 100 CFM) 21.04 17.45 20.30 20.27
Existing SystemProposal 1: SFC 132 + Storage
Proposal 2: DSD 200 +
Storage
Proposal 3: (2) CSD 100S +
Storage
Annual Energy Cost Savings ($/yr) - $10,705 $2,222 $2,317
Annual Energy Consumption Savings (kWh/yr) - 133,818 27,770 28,962
Power Consumption Reduction (kW) - 28.8 31.4 19.0
Savings Potential
Totals
Existing SystemProposal 1: SFC 132 + Storage
Proposal 2: DSD 200 +
Storage
Proposal 3: (2) CSD 100S +
Storage
2016 Kaeser Compressors, Inc., USA (V1.0) 12
Daily Charts
2016 Kaeser Compressors, Inc., USA (V1.0) 13
Daily Charts
Averaged over 5 minutes. The Ingersoll Rand 100hp compressors are rated for 434 cfm at 125 psig, typical operation only requires one unit to run and the second unit to trim. These compressors are set to run in Load/Unload control. Therefore, the load signals are scaled for flow as these units will provide their rated flow at rated pressure.
Load Signals
Pressure Signals
kW Signals
2016 Kaeser Compressors, Inc., USA (V1.0) 14
Daily Charts
Averaged over 5 minutes.
Unit at full load and pressure drops
2016 Kaeser Compressors, Inc., USA (V1.0) 15
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 16
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 17
Daily Charts
Averaged over 5 minutes.
Peak demand
2016 Kaeser Compressors, Inc., USA (V1.0) 18
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 19
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 20
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 21
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 22
Daily Charts
Averaged over 5 minutes.
2016 Kaeser Compressors, Inc., USA (V1.0) 23
Daily Charts
Averaged over 5 minutes.
End of ADA test
2016 Kaeser Compressors, Inc., USA (V1.0) 24
Miscellaneous Charts
2016 Kaeser Compressors, Inc., USA (V1.0) 25
Miscellaneous Charts – Typical Peak Operation
Averaged over 20 seconds.
2016 Kaeser Compressors, Inc., USA (V1.0) 26
Miscellaneous Charts – Sample Day
Averaged over 20 seconds.
2016 Kaeser Compressors, Inc., USA (V1.0) 27
Existing Receiver Tank Storage
The existing receiver tank storage is capable of providing 45.6 cfm of air for 30 seconds based on the 10 psi differential as measured. It is recommended by the Compressed Air Challenge (CAC) to have 30 seconds of the largest cycling base load compressor’s capacity available from storage. Since the existing compressor is rated for 434 cfm, the storage volume is marginally undersized.
The calculations above are based on the formula: C = [V (P1 - P2)] / (T Pa)
V = storage capacity in FT3, C = air flow in cfm (peak demand flow), Pa = absolute atmospheric pressure, P1 = initial receiver pressure (normal unload setting), P2 = final receiver pressure (normal load setting)
CFM FLOW TANK SIZEPSIA Ambient 14.7 Enter Data 14.7 Enter Data
PSIG 2 110 Enter Data 110 Enter DataPSIG 1 100 Enter Data 100 Enter DataPSIA 2 124.7 124.7PSIA 1 114.7 114.7
Pressure Differential 10 10
Receiver Size-Gallons 250 Enter Data 2386.19 Answer
Receiver Size-CF 33.50 319.75CF Storage at PSIG 2 250.68 2392.69CF Storage at PSIG 1 227.89 2175.17
Useable Storage 22.8 217.5
Cycle time in minutes 0.50 Enter Data 0.50 Enter Data30.0 Seconds 30.0 Seconds
CFM Flow 45.6 Answer 434 Enter Data
2016 Kaeser Compressors, Inc., USA (V1.0) 28
TANK SIZEPSIA Ambient 14.7 Enter Data
PSIG 2 110 Enter DataPSIG 1 100 Enter DataPSIA 2 124.7PSIA 1 114.7
Pressure Differential 10
Receiver Size-Gallons 2292.72 Answer
Receiver Size-CF 307.22CF Storage at PSIG 2 2298.96CF Storage at PSIG 1 2089.97
Useable Storage 209.0
Cycle time in minutes 0.50 Enter Data30.0 Seconds
CFM Flow 417 Enter Data
TANK SIZEPSIA Ambient 14.7 Enter Data
PSIG 2 110 Enter DataPSIG 1 100 Enter DataPSIA 2 124.7PSIA 1 114.7
Pressure Differential 10
Receiver Size-Gallons 4739.40 Answer
Receiver Size-CF 635.08CF Storage at PSIG 2 4752.29CF Storage at PSIG 1 4320.27
Useable Storage 432.0
Cycle time in minutes 0.50 Enter Data30.0 Seconds
CFM Flow 862 Enter Data
Recommended Receiver Tank Storage
For the DSD 200 unit, the recommended receiver tank storage would be capable of providing 862 cfm from provided cfm of air for 30 seconds based on the 10 psi differential as measured. It is recommended by the Compressed Air Challenge (CAC) to have 30 seconds of the largest cycling base load compressor’s capacity available from storage. Therefore, it is recommended to integrate an additional 5,000 gallons of receiver tank storage volume (or larger) downstream of air treatment equipment but prior to the distribution piping network based on largest compressor’s full flow capacity and control method (load/no load). It is recommended to install an additional 2,200 gallons of dry storage with the CSD 100S and SFC 132 compressors.
The calculations above are based on the formula: C = [V (P1 - P2)] / (T Pa)
V = storage capacity in FT3, C = air flow in cfm (peak demand flow), Pa = absolute atmospheric pressure, P1 = initial receiver pressure (normal unload setting), P2 = final receiver pressure (normal load setting)
SFC 132 DSD 200 (2) CSD 100S
* It is recommended to integrate an additional 2,200 gallons of dry storage to this system with the SFC 110.