DPN000347 REV 01/12 REV 3 AIR COOLED LIEBERT CHALLENGER 3000 MODELS STANDARD FEATURES 65,000 AMP SHORT CIRCUIT CURRENT RATING (SCCR) The 60Hz electrical panel provides 65kA SCCR. Certain features or combinations of features may reduce the rating; contact factory for limitations. COMPRESSOR WITH HOT GAS BYPASS Scroll with a suction gas cooled motor, internal centrifugal oil pump, vibration isolating mountings, internal thermal overloads, manual reset high pressure switch, and operates at 3500 RPM @ 60 HZ and 2900 RPM @ 50 HZ. Factory piped hot gas solenoid valve and externally equalized regulating valve in the refrigerant circuit. REFRIGERATION SYSTEM Single refrigeration circuit, includes a liquid line filter drier, refrigerant sight glass with moisture indicator, adjustable externally equalized expansion valve, and liquid line solenoid valve. COOLING COIL A-frame/V-frame coil design is constructed of copper tubes and aluminum fins. A stainless steel drain pan is provided. FAN Centrifugal type, double width, double inlet, with lifetime lubricating self aligning ball bearings rated at a minimum life of 100,000 hours. The motor operates at 1750 RPM for 60 HZ and 1450 RPM for 50 HZ. The drive package is variable speed, sized for 200% of the fan motor horsepower (the motor is on an adjustable base). The fan draws air through the coil. The fan assembly is located on an isolated fan deck. FILTER shall be deep pleated 2” ASHRAE 52.2 MERV 8 rating (40% ASHRAE 52.1) located within the cabinet, and accessible from the front of the unit. CABINET AND FRAME Custom powder painted steel panels with 1” (25.4mm), 1 1/2 lbs. (.68kg) insulation. A hinged control access panel opens to a second front panel which is a protection enclosure for high voltage components. The frame corner posts are constructed of 14 gauge MIG welded steel. The frame is painted with a powder coat finish to protect against corrosion. The unit is totally front accessible including any component removal. HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system maintains water level in the pan and a timed flush system greatly reduces mineral precipitation, and is field adjustable to change the cycle time. ELECTRIC REHEAT Electric low watt density 304 stainless steel fin tubular electric reheat elements provide two stages of reheat to control room dry bulb temperature.

Transcript of AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... ·...

Page 1: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000347 REV 01/12

REV 3

AIR COOLED LIEBERT CHALLENGER 3000 MODELS

STANDARD FEATURES

65,000 AMP SHORT CIRCUIT CURRENT RATING (SCCR) The 60Hz electrical panel provides 65kA SCCR. Certain features or combinations of features may reduce the rating; contact factory for limitations.

COMPRESSOR WITH HOT GAS BYPASS Scroll with a suction gas cooled motor, internal centrifugal oil pump, vibration isolating mountings, internal thermal overloads, manual reset high pressure switch, and operates at 3500 RPM @ 60 HZ and 2900 RPM @ 50 HZ. Factory piped hot gas solenoid valve and externally equalized regulating valve in the refrigerant circuit.

REFRIGERATION SYSTEM Single refrigeration circuit, includes a liquid line filter drier, refrigerant sight glass with moisture indicator, adjustable externally equalized expansion valve, and liquid line solenoid valve.

COOLING COIL A-frame/V-frame coil design is constructed of copper tubes and aluminum fins. A stainless steel drain pan is provided.

FAN Centrifugal type, double width, double inlet, with lifetime lubricating self aligning ball bearings rated at a minimum life of 100,000 hours. The motor operates at 1750 RPM for 60 HZ and 1450 RPM for 50 HZ. The drive package is variable speed, sized for 200% of the fan motor horsepower (the motor is on an adjustable base). The fan draws air through the coil. The fan assembly is locatedon an isolated fan deck.

FILTER shall be deep pleated 2” ASHRAE 52.2 MERV 8 rating (40% ASHRAE 52.1) located within the cabinet, and accessible from the front of the unit.

CABINET AND FRAME Custom powder painted steel panels with 1” (25.4mm), 1 1/2 lbs. (.68kg) insulation. A hinged control access panel opens to a second front panel which is a protection enclosure for high voltage components. The frame corner posts are constructed of 14 gauge MIG welded steel. The frame is painted with a powder coat finish to protect against corrosion. The unit is totally front accessible including any component removal.

HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system maintains water level in the pan and a timed flush system greatly reduces mineral precipitation, and is field adjustable to change the cycletime.

ELECTRIC REHEAT Electric low watt density 304 stainless steel fin tubular electric reheat elements provide two stages of reheat to control room dry bulb temperature.

Page 2: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000348 REV 11/11

REV 5

AIR COOLED LIEBERT CHALLENGER 3000 MODELS

OPTIONAL FEATURES (Refer to specification sheet for options supplied)

DIGITAL COMPRESSOR Scroll with a suction gas cooled motor, internal centrifugal oil pump, vibration isolating mountings, internal thermal overloads, manual reset high pressure switch, unloading solenoid valve and piping and operates at 3500 RPM @ 60 Hz and 2900 RPM @ 50 Hz.

CONDENSATE PUMP Has a minimum capacity of 100 GPH (379 l/h) at 20 ft. head (58 kPa). (Consult factory for 200V or 230V, 50Hz applications). Pump is complete with integral primary and secondary float switches, pump, motor assembly, and reservoir. (Shipped loose for field installation on Downflow (BF) Units).

UNIT DISCONNECT SWITCH For 60Hz units: A “Locking-Type” fused disconnect switch is available. For 50Hz units: Two types of non-fused disconnect switches are available, the “Locking-Type” and a “Non-Locking Type”. The “Non-Locking Type” consists of a main unit switch operational from the outside of the unit. Access to the high voltage electric panel compartment can be obtainedwith the switch in either the “on” or “off” position. The “Locking-Type” is similar except access to the high voltage electric panelcompartment can be obtained only with the switch in the “off” position.

FIRESTAT Is mounted in the unit with the sensing element in the return air flow. Upon activation the high temperature stat will immediately shut down the entire unit.

SMOKE DETECTOR The smoke detector senses the return air, shuts down the unit upon detection, and sends visual and audible alarm. Dry contacts are available for a remote customer alarm. This smoke detector is not intended to function as or replace any room smoke detection system that may be required by local or national codes.

FILTERS The standard and optional filters are available with optional pre-filters. A 2” ASHRAE 52.2 MERV 8 (40% ASHRAE 52.1) pre-filter, and 4” ASHRAE 52.2 MERV 8 (40% ASHRAE 52.1) or 4” ASHRAE 52.2 MERV 11 (60-65% ASHRAE 52.1) main filter may be specified.

LIQUI-TECT SENSOR Is a solid state water sensor that has no moving parts and is hermetically sealed to keep out dust and dirt. When the sensor detects the presence of moisture the alarm system is activated.

REMOTE TEMPERATURE AND HUMIDITY SENSORS Are provided in a vented case for mounting in the room to be conditioned. Includes 30 ft. (9m), 60 ft. (18m), 90 ft. (27m), 120 ft. (36m), or 150 ft. (45m) of cable supplied for connecting sensors to unit.

FLOOR STAND Is constructed of MIG welded tubular steel and available in heights from 9” to 24” (229mm to 610mm) with vibration

isolation pads provided on the adjustable legs. An optional factory supplied turning vane is available for field installation if desired.

PLENUM(S) 4 plenums are available for upflow units: 2 way, 3 way, or 4 way discharge and top duct connection. Each plenum is 18” (457mm) high and constructed of steel with 1” (25.4mm), 1 1/2 Ib. (.68kg) insulation and is custom painted in unit matching colors.

STEAM GENERATING CANISTER HUMIDIFIER This system is housed in a steel enclosure and includes a replaceable canister with integral fill cup, fill and drain valves, and high water indicator. System automatically fills and drains as well as maintains therequired water level based on conductivity.

HEAVY GAUGE INDUSTRIAL PANELS Are 16 ga. outside panels and heavy duty gaskets which replace the standard 20 ga. Panels and gaskets.

REHEAT/HUMIDIFIER LOCKOUT Includes the necessary relays to disable the reheat and humidifier from an external 24 volt signal.

SCR ELECTRIC REHEAT Is controlled by the unit microprocessor by pulsing the reheat elements for tight temperature control. Not available in 575 volts.

HIGH EXTERNAL STATIC BLOWERS This blower/motor package is available only on upflow models where external static pressures are up to 2.0 inches/500 Pa (60Hz) or 1.5 inches/370 Pa (50Hz). These blowers are rigidly mounted for ducting directly to the blower housing. Heavy gauge panels are recommended with this option.

200K HOUR BEARINGS Lifetime lubricated self-aligning pillow-block ball bearings rated at a minimum L10 life of 200,000 hours; available on upflow units only.

TWO (2) ADDITIONAL REMOTE SHUTDOWN TERMINALS Provides the customer with a total of three locations to remotely shut down the unit.

TWO (2) EXTRA COMMON ALARM CONTACTS Provides the customer with a total of three sets of n/o contacts for remote indication of unit alarms.

MAIN FAN AUXILIARY SWITCH Provides the unit with one n/o set of contacts to indicate that the motor/unit is on.

REMOTE HUMIDIFIER CONTACTS allow the unit’s humidity controller to control a humidifier outside the unit. Power to operate the remote humidifier does not come from the Challenger unit.

INTELLISLOT ISWEB-LBDS CARD Provides 10/100 baseT Ethernet connectivity for unit monitoring and management. The supported management interfaces include: SNMP for Network Management Systems and HTTP for web page viewing.

INTELLISLOT OC485-LBDS CARD Provides RS-485 Modbus network connectivity to Building Management Systems for unit monitoring and management.

Page 3: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN001726 REV 06/11

TYPICAL GENERAL ARRANGEMENT DIAGRAM

CondenserCoil

SchraderValve

EvaporatorCoil

ExpansionValve

SolenoidValve

SightGlass

FilterDrier

Liquid Return

Shut-Off*Valve

SensingBulb

ExternalEqualizer

ServiceValves

Hot GasDischarge

Check Valve

SINGLE CIRCUIT SHOWN

FACTORYPIPINGFIELDPIPING

*Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance.

REV 3

DigitalCompressor

DigitalSolenoid Valve

AIR COOLED CHALLENGER MODELS WITH DIGITAL SCROLL COMPRESSOR

For rises over 25ft. (7.6m),trap every 20ft. (6m) orevenly divided*

Inverted Trap * ondischarge and liquidlines to extendabove base of coilby a minimum of7 1/2" (190mm)

Trap at base of risersover 5ft. (1.5m)*

SchraderValve

OPTIONAL FIELD INSTALLEDFUSIBLE PLUG

OPTIONAL FIELD INSTALLEDSUB COOLING COIL

Page 4: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000352 REV 9/08

PIPING: AIR COOLED MODELSUPFLOW (BU) MODELS

Piping outlet locations through the plenum arethe same as the unit. See below fordescriptions and connection sizes.

Humidifier Water Supply Line1/4" OD CU

Hot Gas Refrigerant Line5/8" OD CU on Models BU042A/BU040A7/8" OD CU on Models BU067A/BU065A

Condensate Pump Line1/2" OD CUUsed only if optional condensatepump is ordered.

Hot Water Return5/8" OD CU (optional)

Liquid Refrigerant Line3/8" OD CU on Models BU042A/BU040A1/2" OD CU on Models BU067A/BU065A

Hot Water Supply5/8" OD CU (optional)

iCOM ControlPanel

Condensate Drain3/4" FPTField pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units withouta condensate pump have a factory-supplied trap in the unit, so afield trap should not be added. Units with a condensate pump willrequire a field-supplied trap downstream from the pump. Thedrain line must comply with all applicable codes. (If condensatepump is ordered piping is out top of unit).

PIPING OUTLET LOCATIONS(See Cabinet and Floor Planning

Dimensional Data for PipingOpening Sizes.)

REV 1

Page 5: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000350 REV 4/09

CABINET AND FLOOR PLANNING DIMENSIONAL DATAUPFLOW (BU) MODELS

32 1/2 "32 1/2 "

18 "

6 7/8 "(175mm)

(826mm)Overall

Dimension

(826mm)Overall

Dimension

(457mm)Standard Electrical OutletLocation Through Plenum

Air Discharge Grille

94 "(2388mm)

76 "(1930mm)

Blower Outlet with1" (25.4mm) Flange

7/8" (22.2mm) Flange forDuct or Plenum Connection

Return Air Louvers

Shaded area indicates a recommendedclearance of 34" (864mm) be providedfor component access. Right sideaccess suggested for "GLYCOOL" units.

UNIT DIMENSIONAL DATAFRONT VIEW

(front return configuration)

UNIT DIMENSIONAL DATAREAR VIEW

(rear return configuration)

29 3/4 "(756mm)

7 1/2 "(191mm)

29 "(737mm)

2 1/2 "(67mm)

1 3/4 "(44mm)

LBS. (KG) BU035E BU036E 535 (243) BU059E BU060E 545 (247) BU040A BU042A 615 (279) BU065A BU067A 670 (304) BU045W BU046W 700 (318) BU070W BU071W 750 (340) BU072C BU068C 545 (247) BU101C BU102C 555 (252) BK058G BK061G 785 (356)

UNIT WEIGHT50 HZ

MODELS60 HZ

MODELS

Plenum available with: -2, 3 or 4 grilles. -Solid sides with a 7/8" (22mm) duct flange on top.

1" (25mm)FRONT &SIDES3/4" (19mm)REAR

Filter AccessThrough Top

8 1/2"

30 1/2"

32 1/2"

1 7/8"12 1/2"

30 1/2"32 1/2"

1 5/8"13"

9 5/8" A

Standard Piping Location

5/8"Projection of Display Bezel(16mm)

(826mm)

(775mm)

(216mm) (244mm)

(826mm)(775mm)

(41mm)(330mm)

(318mm) (48mm)

10 1/4"(260mm)

5 1/2"(140mm) Standard Electrical Outlet

Location Through Unit

UNITTOP VIEW

REV 1

ASTD 3 & 5T 11 3/4 (299mm)Hi Static 3T 8 5/8 (219mm)Hi Static 5T 11 3/4 (299mm)

LIEBERT CHALLENGER 3000

Page 6: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000354 REV 03/13 REV 4

LIEBERT® CHALLENGER

ELECTRICAL FIELD CONNECTION DEFINITIONS AND LOCATIONS

15

w/ MAIN DISCONNECT

3

1

7

8

4

w/o MAIN DISCONNECT

2 60Hz Only

17

8

5

Electrical Handy Box*(factory installed with cover)

73

72

71

70

12

91 92 93 1 2 3 4

13 16

82 83 84 85 88 89

17 18

24 50 51 55 56

1110

37 38

10

37C38C37B 38B

14

94 95 96 97

14

75 76

Terminal Block*(for customer connections)

1 1

99

2 50Hz Only

6 6

1) Electric conduit knockouts on top and bottom of electric box. Knockout size 1 3/4” (44.5mm).

2) Three phase connection. Electric service connection terminals when factory disconnect is NOT supplied.

3) Three phase connection. Electric service connection terminals when factory disconnect switch is supplied.

4) Factory installed disconnect switch (Optional). Fused disconnect switch provided on 60Hz units, non-fused disconnect switch provided on 50Hz units.

5) Factory installed main fuse block (60Hz only). Factory installed when fused disconnect switch is NOT supplied.

6) Three phase electric service field supplied.

7) Earth ground connection (50/60Hz). Connection terminal for field supplied earth grounding wire.

8) Earth ground bar (50Hz only). Connection terminals with factory ground from each high voltage component for field supplied earth grounding wire.

9) Control and monitoring section of electric box.

10) Remote unit shutdown. Replace existing jumper between terminals 37 + 38 with normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring. Two additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace existing jumper for appropriate pair as done for 37 & 38.

11) Remote Alarm Device (RAD) Connections. Field supplied 24V Class 1 wiring for special alarm. Connection made by adding normally open contacts. Special alarm connections may be factory wired or field wired. See schematic, RADS1-4, for factory wired special alarms. For field wired special alarms, use 24V Class 1 wiring to connect normally open contacts between terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56.

12) Remote condensing unit connection. Field supplied 24V Class 1 wiring to remote condensing unit terminals 1, 2, 3, & 4 from (R2) relay (split system only.)

13) Smoke detector alarm connections. Field supplied 24V Class 1 wiring to remote alarm circuits. Factory wired contacts from optional smoke detector are #91-comm., #92-NO, and #93-NC.

14) Common alarm connection. Field supplied 24V Class 1 wiring to common alarm terminals 75 + 76 (and optional 94 + 95, and 96 + 97), which are factory connected to common alarm relay (R3).

15) Heat rejection connection. Field supplied 24V Class 1 wiring to interlock heat rejection from pigtails 70 + 71 which are factory connected to compressor side switch (self contained units only) or to GLYCOOL relay (K11, GLYCOOL units only). On Dual Cool units only, pigtails 72 + 73 connect auxiliary cooling source to GLYCOOL relay K11. See indoor and outdoor electric schematic for more information.

16) Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier: connections provided for remote 24V AC source.

17) Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field wiring compartment for remote indication that the evaporator fan motor/unit is on. Field to connect 24V maximum.

18) Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in field wiring compartment for remote indication.

*Located inside unit on top for Upflow and on base for Downflow.

NOTE: Refer to specification sheet for full load amp and wire size amp ratings.

Page 7: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

UPFLOW LIEBERT CHALLENGER MODELS WITH iCOM CONTROLS

CAT5 Ethernet connections - field installedAvoid routing near high voltage wiring.Secure wiring to prevent damage anduse bushing or edge guard to avoid sharp edges.

To Display

Crossover Coupler

2

Use cutout on the electricbox to access control board.

Crossover Coupler

ToDisplay

Notes:

1. On units with the standard Small Graphics Display, the customer connection point for unit to unit (U2U) networking is to P64 on the I/O Board.

2. On units with the optional Large Graphics Display, a crossover coupler is provided for unit to unit (U2U) networking. Unplug the red cable from P64 on the I/O Board and connect to one side of the crossover coupler. The first customer connection point is to P64 on the I/O Board. The second customer connection point is to the other side of the crossover coupler. This connects the I/O Board and display to the private U2U network.

To P64

A DETAIL A

LooseCableTies

Channel

EthernetWiring

Cable Tie ToSecure Wiring

BlowerBlockoff

Plate

ELECTRICAL FIELD CONNECTIONS - NETWORKING - U2U

DPN001733 REV 12/12

REV 2

PAGE 1 OF 3

Page 8: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

UPFLOW LIEBERT CHALLENGER MODELS WITH iCOM CONTROLS

19) Opening for field wiring. Suggested entry point for HV field wiring to unit. Hole size O 2.5" (63.5 mm)20) Opening for field wiring. Suggested entry point for LV field wiring to unit.21) Vacant Intellisot. May contain optional Intellislot cards.22) Populated Intellislot. Optional Intellislot cards may be placed in either of two supplied Intellislot locations.23) Remote Temperature / Humidity Sensor connection location. 6-wire CAN cable supplied with optional remote T/H sensor.24) Loose cable ties. Use to secure field supplied network cables to Intellislot.

1921 22

23 24 20

Terminal Blocks

ELECTRICAL FIELD CONNECTIONS - NETWORKING - U2U

DPN001733 REV 12/12

REV 2

PAGE 2 OF 3

Page 9: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

UPFLOW LIEBERT CHALLENGER MODELS WITH iCOM CONTROLS

DPN001733 REV 12/12

REV 2

PAGE 3 OF 3

Customer Connection

Point

Customer Connection

Points

1. When Large Display is used, two cables are required.

2. To run both wires through the channel at the same time, bundle them together as Figure 1 shows.

FIGURE 1

On units with the optional Large Graphics Display, a crossover coupler is provided for unit to unit (U2U) networking. Unplug the red cable from P64 on the I/O Board and connect to one side of the crossover coupler. The first customer connection point is to P64 on the I/O Board. The second customer connection point is to the other side of the crossover coupler. This connects the I/O Board and display to the private U2U network.

ELECTRICAL FIELD CONNECTIONS - NETWORKING - U2U

U2U NETWORKING CONNECTIONS - SMALL DISPLAY

U2U NETWORKING CONNECTIONS - LARGE DISPLAY

P66

P64

P66

P64

When Large Display is used,two cables are required.

Page 10: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000794 REV 4/09 REV 2      

Liebert iCOM® Control System Intelligent Communications & Monitoring

Large Graphic Display (Unit or Wall-mounted)

Large Graphic Display shown in unit bezel Large Graphic Display for Wall-Mounting

The Liebert iCOM® Large Graphic Display shall be microprocessor based with a 320x240 dot matrix graphic monitor with control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be viewable while the unit panels are open or closed. All parameter changes are password protected. Wall-Mounted Large Graphic Displays shall be capable of being mounted on a wall and are provided with a power supply. Wall-mounted displays can be added to a Unit-to-Unit network and remotely located from the cooling unit(s) to provide convenient monitoring and control capabilities. Large Graphic Display only features: The Large Graphic Display provides all of the same features of the Small Graphic Display, plus Large Graphic Display only features. Event Log – Automatically stores the last 400 unit and system (U2U communication required) events (messages, warnings, and alarms) Spare Parts List - shows a list of key spare parts, their quantity and respective parts numbers Unit Diary - A free field area where unit history may be stored for reference View Network – Shows a summarized view of all the cooling units connected on a U2U network Centralized Operation – View and configure any cooling unit on a U2U network from a Large Graphic Display System View – View the averages of all operations being performed on the U2U network Active Alarms on Status Screen – Last two unit/system events are displayed at the bottom of the Status Screen for rapid identification of critical events without having to enter submenus Full Text Descriptions – The large screen size eliminates the need for abbreviated text, simplifying user operation

Page 11: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN000793 REV 4/09 REV 1 

 

Liebert iCOM® Control System Intelligent Communications & Monitoring

Small Graphic Display (Unit-mounted only)

Small Graphic Display shown in unit bezel

The Liebert iCOM® Small Graphic Display shall be microprocessor based with a 128x64 dot matrix graphic monitor with control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be viewable while the unit panels are open or closed. All parameter changes are password protected. Small Graphic Display Features (additional features available with Large Graphic Display): Temperature Control – Precision temperature control is maintained while maximizing efficiency based on a user entered setpoint and tolerance. Humidity Control – The dewpoint level of the room is monitored and controlled based on a user specified Relative Humidity setpoint and tolerance. Various Control Types – Selectable Proportional, PI (proportional-integral), PID (proportional-integral-derivative), Intelligent control types for supply or return temperature; Relative, Compensated, or Predictive humidity control types. These control types have been developed to maximize component life and maintain precise environmental control. Unit Alarms – All unit alarms are annunciated, displayed on the screen, automatically recorded in the event log, communicated to available IntelliSlot monitoring cards, and a red light flashes on the display Event Log – Automatically stores the last 400 unit-only events (messages, warnings, and alarms). Temperature and Humidity Graphs – Provides a graphical view of historical room conditions, selectable from 8 minutes to 16 days Automatic Component Sequencing – runtimes of multiple components within a unit are automatically balanced to extend component life Wellness / Maintenance – Monitors system components to warn of potential issues in advance (helps avoid unplanned downtime) and prolong component life Auto Restart – After a loss of power, a cooling unit will return to is previous operating status. Cooling units can be stagger started to minimize system current draw. IntelliSlot Cards – IntelliSlot cards allow for external unit communication and control Service Contact Information – Local service or sales contact information can be conveniently stored Upgradeable – Multiple units connected through a Unit-to-Unit network can be upgraded simultaneously or cascaded. Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation). Small Graphic Displays can only configure the cooling unit they are physically connected to, while Large Graphic Displays can configure any unit on the network. Cascade – Standby units on a U2U network are automatically activated if active unit(s) cannot control the environment Lead-Lag – A standby unit on a U2U network is automatically activated if an alarm occurs in an active unit Standby Rotation – Standby units are rotated through a U2U network to balance system run hours. Units can be set to automatically rotate daily, weekly, or monthly Teamwork modes

• Mode No – Units share data but operate independently using local sensor readings • Mode 1 – All units perform the same operation with the same intensity based on sensor readings from the entire

network; typically for rooms with balanced heat loads • Mode 2 – All units perform the same operation with varying intensity based on sensor readings from the entire

network; typically for rooms with un-balanced heat loads

Page 12: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

REV 05/06DPN001136REV 0

LIEBERT vNSANetwork Switch Assembly with iCOM: Dimensions

12"305mm

14.25"362mm

3.298"84mm

12.50"318mm

A

DETAIL A

.213"5mm

.375"10mm

MOUNTING SLOT(TYP 2 PLACES)

.88"22mm

O .213"5mm (2 PLACES)

1.00"25mm

Inside view of back of box & back plate

1.40"36mm

.694"18mm

.352"9mm

Page 13: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

REV 05/06DPN001137REV 0

LIEBERT vNSANetwork Switch Assembly

Internal Details

16 Ports supplied on:Model vNSA16-iCOM: 13 free ports availableModel vNSA16: 14 free ports available

8 Ports supplied on:Model vNSA8-iCOM: 7 free ports availableModel vNSA8: 8 free ports available

100-240 Vac, Single Phase 47-63 Hz 0.4 A Volt Power ConnectionRequires field supplied hard wiring 16AWGstranded maximum or connector/plug.

NOTE: Field to supply CAT5 or better cables.

Ground Lug for fieldground wire connection

Knockouts (6) & trap door (1)available for field wiring/cablingentrance on top & bottom sides

w/ Small iCOM Display w/ Large iCOM DisplayvNSA8-iCOM 7 Units 3 Units

vNSA16-iCOM 13 Units 6 UnitsvNSA8 8 Units 4 UnitsvNSA16 14 Units 7 Units

Maximum # of Connected Cooling UnitsNetwork Switch Model

Page 14: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

1

LIEBERT LIQUI-TECT® 410Point Leak Detection SensorProduct Specification Sheet

Description The Liebert Liqui-tect 410 (LT410) provides a single-point detection of leaks. The point detection sensor has two gold-plated sensing probes to prevent corrosion resistance and to provide accurate readings. The LT410 constantly monitors points for leaks, internal faults and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling.

The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans. Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel and a remote building management system or external equipment, such as motorized water shut-off valves.

The LT410 is also ideally suited for the following:

Dimensions - Top, Front & Side Views

Applications Locations• Glycol, Chilled Water Cooling• Humidification Feed Water Piping• Condensate Pumps and Drains• Unit and Ceiling Auxiliary Drip Pans• Overhead Piping Troughs

• Large-Scale Network Control Centers

• Data Centers• Server Rooms - Closets• Unattended Remote Shelters

• Mechanical EquipmentRooms

• Sensitive Areas With Overhead Piping

• Industrial ProcessControl Rooms

5.85"(148.5mm)

Shipping weight: 2 Ibs (0.9 kg)Mounting holes: #8 screws

TOP VIEW

Form-C relay outputs & power wiring connection

4.46"(113.2mm)

FRONT VIEW

Adjustable probe height0.0–0.5" (0.0–12.7mm)

2.25"(57.2mm)

SIDE VIEW

6.35"(161.2mm)

Page 15: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

2

Specifications

Wiring Interconnections(Circuits shown in powered, non-alarm state)

NOTE: All power and alarm connections Class 2 circuits only

Liqui-tect 410 SensorPower requirements

24 VAC 100 mA, 50/60 Hz, 3 VA (max.)

Dimensions, in. (mm)W x D x H

6.35" x 2.25" x 4.46"(161.2 x 57.2 x 113.2)

Weight (assembled) 2.0 lb. (0.9 kg)Metal enclosure NEMA 1, IP 30Environmental ConditionsOperating temperature

50°F to 104°F (10°C to 40°C)

Operating humidity

10% to 95% relative humidity(non-condensing)

Operating altitude

0 to 10,000 ft. (0 to 3,048 m)

Output Relays

Contact rating 2 Form-C; 3 A rating at 24 VAC

Agency ListingsUL UL916C-UL C22.2, No. 205-M1983CE YesFCC Compliance 47 CFR, Part 15

Red Wires Orange Wires Yellow Wires24 V, AC/DC Alarm Contact Rating Alarm Contact Rating

@ 0.10A, 50-60 Hz, DC 24 VAC @ 3A 24 VAC @ 3AClass 2 Circuit Only Class 2 Circuit Only Class 2 Circuit Only

Placement on Subfloor Under Cooling Support Equipment

* Output connections to external alarm monitoring panelssuch as the Liebert contact closure alarm panels

Leak detection zone (directly beneath unit)

To a Liebertenvironmental

unit andan optional*

monitoringpanel

To external power supply or directly from unit(seePower Wiringon 3) LT410

Pow

er

Pow

er

1-N

O

1-N

C

1-C

OM

2-N

O

2-N

C

2-C

OM

Gold-plated probes

Height adjustable0-0.5" (0-12.7mm)

Page 16: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

3

Power WiringThe LT410 is rated for 24 VAC, 50/60 Hz and 0.10 amp.

Figure 1 24V from Liebert environmental units to LT410

Figure 2 24V from transformer to LT410

Power Wiring

24V from Liebert Environmental Unit to LT460

Liebert Deluxe Sys/3,Challenger, Himod orMM2 (8 Ton)

TB1

T5 (24V)

G5 (Ground)

LT460

TB1

TB1-1

TB1-2

24V from Transformer to LT460

Liebert MM2 (1 to 5 Ton) LT460

TB1

TB1-1

TB1-2

4V transformer ofhere are noated terminaltions)

(24V)

(Ground)From 24V

transformer* Red

Red

Red wiresLiebert Mini-Mate2 (1 to 5 ton) LT410

* Requires a 24V external transformer (there are no designated terminal connections on the unit)

Challenger, Himod orMM2 (8 Ton)

TB1

T5 (24V)

G5 (Ground)

LT460

TB1

TB1-1

TB1-2

Transformer LT460

TB1

TB1-1

TB1-2

From 24Vtransformer

24V from Transformer to LT460

Liebert MM2 (1 to 5 Ton) LT460

TB1

TB1-1

TB1-2

4V transformer ofhere are noated terminaltions)

(24V)

(Ground)

T5 (24V)

Red

Red

G5 (Ground)

Red wiresTB1

Liebert DS, Deluxe System/3, Challenger, Himod or Mini-Mate2 (8 ton) LT410

Location of T5 (24V) connection on main controller board of Liebert unit

Transformer LT460

TB1

TB1-1

TB1-2

From 24Vtransformer

From 24Vtransformer Red

Red

Red wiresTransformer LT410

Page 17: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

4

© 2007 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.

® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

SL-31050_REV0_06-07

Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, OH 43229

Telephone: 1-800-877-9222Facsimile: 1-614-841-6022www.liebert.com

Wiring to Auxiliary Alarm PanelsThe LT410 has two Form-C dry contact alarm output contacts: orange wires (1) and yellow wires (2). Each contact is rated for 24 VAC at 3 amp. Figure 3 LT410 to Liebert environmental units

Figure 4 LT410 to Liebert contact monitor panel

Ordering Information

Liebert Deluxe Sys/3,Challenger, Himod orMM2 (8 Ton)

24 (24V)

51

LT460

TB2

TB2-2 (C)

TB2-1 (N.O.)

TB2-3 (N.C.) Env. Unit

Liebert MM2 (1 to 5 Ton)

TB1-1 (24V)

TB1-2

LT460

TB2

TB2-2 (C)

TB2-1 (N.O.)

TB2-3 (N.C.) Env. Unit

OR

TB2

TB2-2 (C)

TB2-1 (N.O.)

TB2-3 (N.C.) Env. Unit

TB1-1 (24V)

TB1-3

Liebert MM2 (1 to 5 Ton)LT460

1-NC

Orange wires

Liebert Deluxe System/3, Challenger, Himod or

Mini-Mate2 (8 ton)

LT410

1-COM

1-NO

Environmental unit

24 (24V)

51, 55 or 56

1-NC

Orange wires

Liebert DSLT410

Orange wiresLiebert Mini-Mate2

(1 to 5 ton)LT410

1-COM

1-NO

1-NC

1-COM

1-NO

Environmental unit

Environmental unit

24 (24V)

50, 51, 55 or 56

TB1-1 (24V)

TB1-2 or TB1-3

Product Number Quantity Description

LT410 Point Leak Detection Sensor

TB2

TB2-2 (C)

TB2-1 (N.O.)

TB2-3 (N.C.)

LT460 Liebert ContactMonitor Panel

InputContact(N.O.)

Alarm Panel2-NC

2-COM

2-NO

Yellow wiresLT410

Alarm panel

Liebert contact monitor panel

Input contact (N.O.)

Page 18: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

1

LIEBERT® INTELLISLOT® UNITY PLATFORM CARDSProduct Specification/Installation Sheet

Liebert Intellislot Unity cards are a form, fit and function replacement for several existing Liebert Intellislot Web and 485 cards.

DescriptionThe Liebert IntelliSlot Unity Platform brings SNMP, BACnet IP, BACnet MSTP, Modbus TCP, Modbus RTU, YDN23 and Web management capability to many models of Emerson Network Power’s power and cooling equipment. The cards employ Ethernet and RS-485 networks to monitor and manage a wide range of operating parameters, alarms and notifications.

See Table 1 for equipment supported and Table 2 for communication protocols supported.

Additional Features

Compatibility With Other Emerson Products and Communication Protocols

• SNMPv1, SNMPv2c and SNMPv3 with MIB-II support • DHCP per RFC2131/2132

• HTTP/HTTPS 1.1 • Remote firmware updates via a Web browser

• BootP • IPv4 and IPv6

Table 1 Compatibility with Liebert equipment

Liebert IntelliSlot Card Compatible with:

Liebert IS-UNITY-DPLiebert IS-UNITY-LIFE

Liebert APM™, Liebert APS™, Liebert CRV™, Liebert CW™, Liebert Challenger 3000™ Liebert DCP™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPC™

Liebert HPC-S/M/R/W/Generic™, Liebert HPM™, Liebert NXC™, Liebert NXL™ *, Liebert NXR™, Liebert PCW™/PDX™, Liebert PeX™ *, Liebert XDC™, Liebert XDP™, Liebert XDP-Cray™

Table 2 Liebert IntelliSlot card communication protocols

Liebert IntelliSlotCard (Part #)

Communication Protocol

HTTPHTTPS

EmersonProtocol

RemoteServiceDeliveryProtocol Email SMS

SNMPv1,v2c, v3

BACnet IPBACnet MSTP

Modbus TCPModbus RTU YDN23 *

Liebert IS-UNITY-DP(IS-UNITY-DP) ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

Liebert IS-UNITY-LIFE(IS-UNITY-LIFE) ✔ ✔ ✔ — — — — — —

* YDN23 supported only for Liebert PeX and Liebert NXL.

ActivityLink485

IS-UNITY-DP

Micro-USB AB(future release)

RJ-45-Ethernet—Trellis; Modbus TCP; BACnet IP; SNMPv1, v2c, v3; Liebert Protocol; HTTP; Building Management System; Network Management System

Reset Button(Reboot or reset to factory defaults)

RS-485 - Modbus RTU, BACnet MSTP, YDN23; Building Management System

Liebert Sensor Network(future release)

Page 19: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

2

© 2012 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.

® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

SL-52646_REV4_06-14

Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, OH 43229

Telephone: 1-800-877-9222Facsimile: 1-614-841-6022www.liebert.com

Dimensions

Specifications

Wiring Specifications

PowerRequirements

DC Inputs • 7 to 12VDC

Power Consumption • 3.6W maximum

Dimensions - W x D x H: in. (mm) • 2.97 x 5.2 x 1.45 (75.5 x 15 x 37)

WeightNet, oz. (kg) • 7 (0.2)

Shipping, lb. (kg) • 1.3 (0.6)

Ambient Operating Environment, °F (°C) • 32 to 104 (0 to 40); 10% to 90% RH (non-condensing)

Ambient Storage Temperature, °F (°C) • -4 to 140 (-20 to 60)

CommunicationPorts

Ethernet Communications • RJ-45

RS-485 • RJ-45 (RJ-45 to 2-Position Terminal Block Adapter)

Connection Supported Wire Type Maximum Wire Length

10/100Mb/s Ethernet Connector Standard Category 5E Cable 328 ft. (100m)

RJ-45 - One-Wire ConnectorLiebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire Sensor. 65.6 ft. (20m)

RJ-45 - RS-485 ConnectorADAPTER RJ45-2POS TERMINAL BLOCK EIA485 to 18-22 AWG Stranded & Shielded 18 AWG recommended Non Plenum - Belden 9461 Plenum - Belden 88761

3000 ft. (914m)

Micro-USB AB Standard Micro-USB AB 16.4 ft. (5m)

4-3/4"(121mm)

2-3/8" (60.3mm)

1/2" (11mm)

3" (76mm)

1- 1/2"(38mm)

Front of Liebert IntelliSlot Unity Card

Top of Liebert IntelliSlot Unity Card

Page 20: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

CABINET & ANCHOR DIMENSIONAL DATAVFD CONTROL CONDENSERS 50 AND 60Hz -- TCSV ONLY

A CLEARANCE OF 36 IN.(914.4mm) IS RECOMMENDEDON ALL SIDES FOR PROPEROPERATION AND COMPONENTACCESS.

LIEBERTMODEL NO.

Note 1

NO.FANS A B C

IN. MM.

TCSV165

TCSV205

TCSV251

TCSV308

3

1. All condenser fan motors are 3/4 H.P.

1"(25.4mm)

1 3/4"(44.5mm)

1 3/4"(44.5mm)

4 1/4"(108mm)

4 1/4"(108mm)

TYPICAL FOOTPRINT

UNIT ANCHOR PLAN

BC

37 11/16"(957mm)

1/2 (12.7mm) DIAMETER

ANCHOR BOLTS (TYP.)

DPN001637

REV 08/08

REV 0

22

3

91 1/2 232491 1/2 2324

131 1/2 3340

131 1/2 3340

IN. MM. IN. MM.

84 2134 82 2083

84 2134 82 2083

124 3150 122 3099

124 3150 122 3099

425 193495 225

500 227

670 305

LBS. KG.

NETWEIGHT

2"(50.8mm)

2"(50.8mm)

TCSV083

TCSV104

1

151 1/2 130851 1/2 1308

44 1118 42 1067

44 1118 42 1067295 134315 143

43 3/16"(1097 mm)

B

37 7/8"(962 mm)

HEIGHT TO TOPOF FAN GUARD

43 1/8"(1095 mm)

A

43 9/16"(1107 mm)

DISCONNECTSWITCHHANDLE

Page 21: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

LIEBERT AIR COOLED VFD CONTROL CONDENSERS  

 STANDARD FEATURES COIL  Liebert manufactured coil is constructed of copper tubes in a staggered tube pattern.  Tubes are expanded in 

continuous, rippled or enhanced aluminum type fins.  The fins have full depth fin collars completely covering the copper tubes which are connected to heavy wall type L headers.  Inlet coil connecter tubes pass through relieved holes in the tube sheet for maximum resistance to piping strain and vibration.  Coil are factory leak tested at a minimum of 300 PSIG, dehydrated, then filled with a nitrogen and refrigerant holding charge and sealed. 

 FAN(S)  Blades are constructed of zinc plated steel or aluminum with a maximum diameter of 30 inches and secured to the 

fan shaft by a heavy duty hub with set screw.  Fan guards are heavy gauge, close meshed, steel wire with corrosion resistant finish.  Fans are factory balanced and tested before shipment. 

 FAN MOTOR(S)   The variable speed fan motor is a specifically designed inverter duty motor with permanently lubricated 

ceramic bearings.  The Liebert variable frequency drive (VFD) control system provides overload protection for the variable speed motor.  Each ambient‐temperature‐controlled fan motor has built in overload protection.  All motors have rain slingers, permanently lubricated bearings and are rigidly mounted on die‐formed galvanized steel supports. 

 HEAD PRESSURE CONTROL   The Liebert VFD Condenser control system is complete with variable frequency drive (VFD), 

inverter duty fan motor operating from 0% to 100% motor RPM based on head pressure, refrigerant pressure transducers , ambient thermostat(s), ambient‐temperature thermostat(s), motor overload protection, and electrical control circuit factory wired in the control panel.   VFD control is always furnished on the fan adjacent to the connection end of the condenser which runs continuously with the compressors.  Other condenser fans are controlled by ambient thermostats and are either “on” or “off”.  This systems allows for operation at ambient conditions as low as ‐20°F (‐28.9°C). 

 HOUSING   The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full 

width baffles.  Structural support members, including coil support frame, motor, and drive support, are galvanized steel for strength and corrosion resistance.  Aluminum legs are provided with rigging holes for hoisting the unit into position. 

 TVSS & UNIT DISCONNECT SWITCH   Transient Voltage Surge Suppression and locking disconnect factory installed and wired in 

the enclosed condenser control section.   ALARM CONTACTS   Normally open dry contacts provided for indication of VFD and TVSS alarm condition. 

   OPTIONAL FEATURES FUSIBLE PLUG KIT   Provides compliance for local codes requiring fusible‐plug‐type pressure relief devices.  

Shipped loose for field installation on each liquid line. 

  DPN001048                    Rev 02/11                       Rev 2 

Page 22: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

ELECTRICAL FIELD CONNECTIONSVFD CONTROL CONDENSERS

NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

DPN001051 REV 03/13

REV 2

70 7111 12 13 14

VFD

Factory wired to 24Vcontrol circuit.

Heat Rjection Connection 70, 71

Field suppliedClass 1 wiring tointerlock condenser 24Vcontrols to Liebert indoor unit (70, 71). Reference thecondenser and indoor unitelectrical schematics fortermination. 7/8 in (22.2mm)diameter hole provided inbottom of electric box. SPD

Factory installed fuse block on60 HZ units. Circuit breaker suppliedin lieu of fuse block on 50 HZ units.

Electric Service Connectionterminals with factorysupplied disconnect.

Factory installed disconnectswitch.

Electric Service Entrance.A 7/8 in. (22.2mm) diameter hole ina 1 1/18 in. (28.6mm) knockoutprovided in bottom of electric box.

Electric Service , not by Liebert.

Earth Ground Connection (60 HZ)

Connection terminal for fieldsupplied earth grounding wirewhen factory disconnect is supplied.

Special Alarm Connections

Field supplied 24V Class 1wiring to remote alarm circuitsSurge Protection Device (SPD)normally open alarm contact connections (11, 12).Variable Frequency Drive (VFD)normally closed alarm contact connections (13, 14).Reference the indoor unit electricdiagram (RAD1-4) for termination.

Factory wired to components onelectric panel.

Earth Ground BAR (optional on 50HZ only).Connection terminals with factoryground from each high voltagecomponent for field suppliedearth grounding wire.

Page 23: AIR COOLED LIEBERT CHALLENGER 3000 MODELS - Rivesrives.com/wp-content/uploads/2015/03/2-5-Ton... · DPN000348 REV 11/11 REV 5 AIR COOLED LIEBERT CHALLENGER 3000 MODELS OPTIONAL FEATURES

DPN001638REV 11/11

REV 2

FOR RUNS LONGER THAN 150 FT. (45.7m) EQUIV. LENGTH CONSULT FACTORY FORPROPER LINE SIZING.

ISOLATOR

METAL CLAMP

DETAIL A-A

FASTEN LIQUID AND HOT GAS LINES TOLEG USING FLAT SURFACE CLAMPSWITH ISOLATORS (FIELD SUPPLIED).SUPPORT FIELD PIPING SEPERATELYTO AVOID COIL DAMAGE AND LOSS OF CHARGE. (SEE DETAIL A-A)

INVERTED TRAPS (FIELD SUPPLIED). TRAPS TO EXTEND ABOVE BASE OF COIL BY A MINIMUMOF 7 1/2" (190 mm)

ENTERING HOTGAS LINE

LEAVINGLIQUID LINE

HORIZONTAL

OPTIONAL FUSIBLE PLUG SERVICE KIT TO BE BRAZED INTO THE LIQUID LINE(S) IN EITHER THE VERTICAL OR HORIZONTAL POSITION. (WHERE REQUIRED)

(VERTICAL POSITION IS PREFERRED,HORIZONTAL POSITION IS OPTIONAL.)

VERTICAL

UNIT MODEL

NUMBER

TOTAL EQUIV. LENGTH FT. (m)

HOT GAS LINE IN.

LIQUID LINE IN.

50 (15.2) 5/8 1/2 BF/BU42A 100 (30.5) 3/4 1/2 BF/BU40A 150 (45.7) 3/4 5/8

50 (15.2) 7/8 1/2 BF/BU67A 100 (30.5) 7/8 5/8BF/BU65A 150 (45.7) 7/8 5/8

RECOMMENDED REFRIGERANT LINE SIZES CU. OD.

CONDENSER MODEL NUMBER

ENTERING HOT GAS LINE

IN.

RETURNING LIQUID LINE

IN.

TCSV083 7/8 5/8

TCSV104 1-1/8 5/8

TCSV165 1-1/8 7/8

TCSV205 1-1/8 7/8

TCSV251 1-1/8 7/8

TCSV308 1-5/8 1-1/8

TCSV415 1-3/8 1-1/8

CONDENSER PIPING CONNECTION SIZES CU. OD.

PIPING: VFD CONTROL CONDENSERS LIEBERT CHALLENGER 3000