Air Conditioning (1)
Transcript of Air Conditioning (1)
-
7/25/2019 Air Conditioning (1)
1/60
Air Conditioning
Definition, advantages and disadvantages,
brief introduction to psychrometric process,
air-cycle and refrigeration cycle.
Summer and winter air-conditioning,
calculation of air-contitioning loads,
Zoning: purpose and advantages.
Air-distribution systems: Ducts and duct systems.
Air-outlets
Air-conditioning methods and equipment: window units, split
units and central Air-conditioning systems.
Location of air-conditioning equipment in buildings.
Architectural requirement of various equipment.
-
7/25/2019 Air Conditioning (1)
2/60
Air conditioning is the process of altering the properties of
air (primarily temperature and humidity) to more comfortableconditions, typically with the aim of distributing the conditioned airto an occupied space to improve thermal comfort and indoor airquality.
Or
Air-conditioning is a process that simultaneously conditions air;
distributes it combined with the outdoor air to the conditionedspace; and at the same time controls and maintains the requiredspaces temperature, humidity, air movement, air cleanliness, sound
level, and pressure differential within predetermined limits for thehealth and comfort of the occupants, for product processing, orboth.
-
7/25/2019 Air Conditioning (1)
3/60
An air-conditioning process describes the change in
thermodynamic properties of moist air between the
initial and final stages of conditioning as well as thecorresponding energy and mass transfers between themoist air and a medium, such as water, refrigerant,
absorbent or adsorbent, or moist air itself. The energybalance and conservation of mass are the twoprinciples used for the analysis and the calculationof the thermodynamic properties of the moist air.
-
7/25/2019 Air Conditioning (1)
4/60
Psychrometrics is the science of studying the thermodynamic
properties of moist air. It is widely usedto illustrate and analyze the
change in properties and the thermal characteristics of the airconditioning process and cycles.
The psychrometric chart is a graphic representation of theproperties of moist airvarious air-conditioning processes and air-
conditioning cycles.
The approximate composition of dry air by volume is nitrogen,79.08%; oxygen, 20.95%; argon, 0.93%; carbon dioxide, 0.03%;other gases (e.g., neon, sulfur dioxide), 0.01%.
The amount of water vapor contained in the moist air within thetemperature range 0 to 100 F changes from 0.05 to 3% by mass.The variation of water vapor has a critical influence on thecharacteristics of moist air.
Psychrometrics
-
7/25/2019 Air Conditioning (1)
5/60
Important psychrometric properties:
Dry bulb temperature (DBT) is the temperature of the moist air as measured
by a standard thermometer or other temperature measuring instruments.The Dry Bulb Temperature refers basically to the ambient air temperature.
Dry bulb temperature
These lines are drawnstraight, not always parallel to each other, andslightly inclined from the vertical position.This is thetaxis, the abscissa (horizontal)axis. Each line represents a constanttemperature.
-
7/25/2019 Air Conditioning (1)
6/60
The water vapor in the air will be saturated when air is at a temperatureequal to the saturation temperature corresponding to the partial pressureexerted by the water vapor.
This temperature is called dew-point temperature.
Dew-point temperature
Dew point temperature
From the state point followthe horizontal line of constant humidity ratio to theintercept of 100% RH, also known as thesaturationcurve. The dew point temperature is equal to the
fully saturated dry bulb or wet bulb temperatures.
-
7/25/2019 Air Conditioning (1)
7/60
Wet bulb temperature
These lines are obliquelines that differ slightly from the enthalpylines. They are identically straight but are not
exactly parallel to each other. These intersectthe saturation curve at DBT point.
-
7/25/2019 Air Conditioning (1)
8/60
Humidity ratio: These are the horizontal lines on the
chart. Humidity ratio is usually expressed as mass of
moisture per mass of dry air (pounds or kilograms of
moisture per pound or kilogram of dry air, respectively).
The range is from 0 for dry air up to 0.03 (lbmw/lbma)on the right hand -axis, the ordinate or vertical axis of
the chart.
-
7/25/2019 Air Conditioning (1)
9/60
Specific enthalpy
These are oblique lines drawn diagonallydownward from left to right across the chart that are parallelto each other. These are not parallel to wet bulb temperaturelines.
-
7/25/2019 Air Conditioning (1)
10/60
Relative humidity
These hyperbolic lines areshown in intervals of 10%. The saturationcurve is at 100% RH, while dry air is at 0% RH.
-
7/25/2019 Air Conditioning (1)
11/60
-
7/25/2019 Air Conditioning (1)
12/60
-
7/25/2019 Air Conditioning (1)
13/60
A psychrometric chart is a graph of the thermodynamic parameters of moist air at
a constant pressure, often equated to an elevation relative to sea level.
Dew point temperature: From the state point follow the horizontal line of constant
humidity ratio to the intercept of 100% RH, also known as thesaturation curve. The dew
point temperature is equal to the fully saturated dry bulb or wet bulb temperatures.
* Wet bulb temperature: These lines are oblique lines that differ slightly from theenthalpy lines. They are identically straight but are not exactly parallel to each other. These
intersect the saturation curve at DBT point.
* Relative humidity: These hyperbolic lines are shown in intervals of 10%. The saturation
curve is at 100% RH, while dry air is at 0% RH.
* Humidity ratio: These are the horizontal lines on the chart. Humidity ratio is usually
expressed as mass of moisture per mass of dry air (pounds or kilograms of moisture per
pound or kilogram of dry air, respectively). The range is from 0 for dry air up to 0.03
(lbmw/lbma) on the right hand -axis, the ordinate or vertical axis of the chart.
* Specific enthalpy: These are oblique lines drawn diagonally downward from left to right
across the chart that are parallel to each other. These are not parallel to wet bulb
temperature lines.
-
7/25/2019 Air Conditioning (1)
14/60
Assume that the outside air temperature is 32C with a relative humidity =60%. Use the psychrometric chart to determine the specific humidity [18
gm-moisture/kg-air], the enthalpy h [78 kJ/kg-air], the wet-bulbtemperature Twb [25.5C], the dew-point temperature Tdp [23C], and the
specific volume of the dry air v [0.89m3/kg]. Indicate all the valuesdetermined on the chart.
-
7/25/2019 Air Conditioning (1)
15/60
Assume that the outside air temperature is 8C. If the air in a room is at 25Cwith a relative humidity = 40%, use the psychrometric chart to determine if thewindows of that room which are in contact with the outside will become foggy.
The air in contact with thewindows will become colderuntil the dew point isreached. Notice that underthe conditions of 25C and40% relative humidity thedew point temperature isslightly higher than 10C, Atthat point the water vaporcondenses as thetemperature approaches 8C
along the saturation line,and the windows willbecome foggy.
-
7/25/2019 Air Conditioning (1)
16/60
One of the major applications of the Psychrometric Chart is in air conditioning, and wefind that most humans feel comfortable when the temperature is between 22C and 27C,and the relative humidity between 40% and 60%. This defines the "comfort zone" whichis portrayed on the Psychrometric Chart as shown below. Thus with the aid of the chart
we either heat or cool, add moisture or dehumidify as required in order to bring the airinto the comfort zone.
-
7/25/2019 Air Conditioning (1)
17/60
In the refrigeration cycle, heat is transported from a colder
location to a hotter area. As heat would naturally flow inthe opposite direction, work is required to achieve this. A
refrigerator an example of such a system, as it transports
the heat out of the interior and into its environment (i.e.
the room). The refrigent is used as the medium which
absorbs and removes heat from the space to be cooled and
subsequently rejects that heat elsewhere.
REFRIGERATION CYCLE
A simple stylized diagram of the
refrigeration cycle: 1) condensing
coil, 2) expansion valve,
3) evaporator coil, 4) compressor
http://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Evaporator_coilhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Evaporator_coilhttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Condensing_coil -
7/25/2019 Air Conditioning (1)
18/60
Liquids absorb heat when changed from liquid to gas
Gases give off heat when changed from gas to liquid.
For an air conditioning system to operate with economy, the refrigerant mustbe used repeatedly. For this reason, all air conditioners use the same cycle of
compression, condensation, expansion, and evaporation in a closed circuit.
The same refrigerant is used to move the heat from one area, to cool this area,
and to expel this heat in another area.
The refrigerant comes into the compressor as a low-pressure gas, it is
compressed and then moves out of the compressor as a high-pressure gas.The gas then flows to the condenser. Here the gas condenses to a liquid, and
gives off its heat to the outside air.
The liquid then moves to the expansion valve under high pressure. This valve
restricts the flow of the fluid, and lowers its pressure as it leaves the
expansion valve.
The low-pressure liquid then moves to the evaporator, where heat from the
inside air is absorbed and changes it from a liquid to a gas.
As a hot low-pressure gas, the refrigerant moves to the compressor where the
entire cycle is repeated.
-
7/25/2019 Air Conditioning (1)
19/60
The refrigeration cycle uses four essential elements to cool.
The system refrigerant starts its cycle in a gaseous state. The compressorpumps the
refrigerant gas up to a high pressure and temperature.
From there it enters a heat exchanger (sometimes called a condensing coil or
condenser) where it loses energy (heat) to the outside, cools, and condenses into its
liquid phase.
An expansion valve (also called metering device) regulates the refrigerant liquid to
flow at the proper rate.
The liquid refrigerant is returned to another heat exchanger where it is allowed to
evaporate, hence the heat exchanger is often called an evaporating coil or evaporator.
As the liquid refrigerant evaporates it absorbs energy (heat) from the inside air, returns
to the compressor, and repeats the cycle. In the process, heat is absorbed from indoors
and transferred outdoors, resulting in cooling of the building.
A simple stylized diagram of therefrigeration cycle: 1) condensing
coil, 2) expansion valve,
3) evaporator coil, 4) compressor
Ci l ti f i t t th d i d t
http://en.wikipedia.org/wiki/Refrigeration_cyclehttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Evaporator_coilhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Evaporator_coilhttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Condensing_coilhttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Refrigeration_cyclehttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Gas_compressor -
7/25/2019 Air Conditioning (1)
20/60
Circulating refrigerant vapor enters the compressorand is compressed to a
higher pressure, resulting in a higher temperature as well. The hot,
compressed refrigerant vapor is now at a temperature and pressure at which
it can be condensed and is routed through a condenser. Here it is cooled by
air flowing across the condenser coils and condensed into a liquid. Thus, the
circulating refrigerant rejects heat from the system and the heat is carriedaway by the air.
The condensed and pressurized liquid refrigerant is next routed through
an expansion valve where it undergoes an abrupt reduction in pressure. That
pressure reduction results in flash evaporation of a part of the liquid
refrigerant, lowering its temperature. The cold refrigerant is then routed
through the evaporator. A fan blows the warm air (which is to be cooled)across the evaporator, causing the liquid part of the cold refrigerant mixture
to evaporate as well, further lowering the temperature. The warm air is
therefore cooled.
To complete the refrigeration cycle, the refrigerant vapor is routed back into
the compressor.
By placing the condenser inside a compartment, and the evaporator in theambient environment (such as outside), or by merely running an air
conditioner's refrigerant in the opposite direction, the overall effect is the
opposite, and the compartment is heated instead of cooled. See also heat
pump.
The engineering of physical and thermodynamic properties of gasvapor
mixtures is calledpsychrometrics.
http://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Condenser_(heat_transfer)http://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Flash_evaporationhttp://en.wikipedia.org/wiki/Evaporator_coilhttp://en.wikipedia.org/wiki/Refrigeration_cyclehttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Psychrometricshttp://en.wikipedia.org/wiki/Psychrometricshttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Refrigeration_cyclehttp://en.wikipedia.org/wiki/Evaporator_coilhttp://en.wikipedia.org/wiki/Flash_evaporationhttp://en.wikipedia.org/wiki/Thermal_expansion_valvehttp://en.wikipedia.org/wiki/Condenser_(heat_transfer)http://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Gas_compressor -
7/25/2019 Air Conditioning (1)
21/60
-
7/25/2019 Air Conditioning (1)
22/60
-
7/25/2019 Air Conditioning (1)
23/60
-
7/25/2019 Air Conditioning (1)
24/60
-
7/25/2019 Air Conditioning (1)
25/60
-
7/25/2019 Air Conditioning (1)
26/60
-
7/25/2019 Air Conditioning (1)
27/60
-
7/25/2019 Air Conditioning (1)
28/60
-
7/25/2019 Air Conditioning (1)
29/60
-
7/25/2019 Air Conditioning (1)
30/60
-
7/25/2019 Air Conditioning (1)
31/60
-
7/25/2019 Air Conditioning (1)
32/60
-
7/25/2019 Air Conditioning (1)
33/60
-
7/25/2019 Air Conditioning (1)
34/60
-
7/25/2019 Air Conditioning (1)
35/60
-
7/25/2019 Air Conditioning (1)
36/60
-
7/25/2019 Air Conditioning (1)
37/60
-
7/25/2019 Air Conditioning (1)
38/60
-
7/25/2019 Air Conditioning (1)
39/60
-
7/25/2019 Air Conditioning (1)
40/60
-
7/25/2019 Air Conditioning (1)
41/60
-
7/25/2019 Air Conditioning (1)
42/60
-
7/25/2019 Air Conditioning (1)
43/60
-
7/25/2019 Air Conditioning (1)
44/60
-
7/25/2019 Air Conditioning (1)
45/60
-
7/25/2019 Air Conditioning (1)
46/60
-
7/25/2019 Air Conditioning (1)
47/60
-
7/25/2019 Air Conditioning (1)
48/60
-
7/25/2019 Air Conditioning (1)
49/60
-
7/25/2019 Air Conditioning (1)
50/60
Pressurization
-
7/25/2019 Air Conditioning (1)
51/60
In multi-storey buildings, stairways and lobbies may be air
pressurised to clear smoke and provide an unimpeded escape
route. The air pressurization is usually between 25 and 50 Pa
depending on the building height and degree of exposure.
This pressure is insignificant for movement of personnel.
Pressurization is a technique for protecting escape routes
against the ingressof deadly smoke by maintaining the pressure within the
escape route at a
higher pressure than that in adjacent spaces.
Pressurization is provided to maintain safe conditions within
an area which could be used in the event of a fire for means
of escape/life safety and fire fighter access.
Pressurization
-
7/25/2019 Air Conditioning (1)
52/60
In large open spaced buildings, CAR PARKS, SHOPPING CENTRES,
-
7/25/2019 Air Conditioning (1)
53/60
EXHIBI- TION HALLS etc, the usual method of smoke control is by
ventilation - extracting the smoke from the area.
In high rise, multi room buildings, where the Staircases, Lift Lobbies
and Corridors pro- vide the escape route, SMOKE EXTRACTION may
only serve to worsen the situation.
-
7/25/2019 Air Conditioning (1)
54/60
However, it is possible to hold back smoke from a fire by simplysupplying clean air into the escape routes, thereby developing
excess, or POSITIVE pressure in the spaces requiring protection.
In a PRESSURISATION SYSTEM the air- flow must always be
away from the escape routes to ensure that they will be at a
higher pressure than the surrounding area.
-
7/25/2019 Air Conditioning (1)
55/60
A pressurization system
consists of two main
components:
Supply air (air injected
into the area that is to beprotected).
Air release (air and
smoke is released fromthe adjoining fire area).
-
7/25/2019 Air Conditioning (1)
56/60
SUPPLY AIR SYSTEM
-
7/25/2019 Air Conditioning (1)
57/60
SUPPLY AIR SYSTEM
A pressurisation system has TWO and occasionally
THREE, modes of operation
Mode 1 - DECTECTION PHASE - To raise a
pressure differential in the protection space -
staircase, corridor etc, by the required amount
(50Pa in the UK) when ALL DOORS ARE
CLOSED.
Mode 2 - ESCAPE PHASE - To maintain aspecified AIR VELOCITY (0.75m/sec) through
the OPEN DOOR(S) onto the fire floor with
various other doors open, OR a PRESSURE
DIFFERENCE OF 10+ Pa with the fire floor
door(s) closed and vari- ous other doors open
(fig 7-9)Mode 3 - FIRE FIGHTING PHASE - To
maintain a specified AIR VELOCITY (2.0
m/sec) through the OPEN DOOR(S) onto the
fire floor with various other doors open.
-
7/25/2019 Air Conditioning (1)
58/60
A k l bb i d i t ll b ildi h k t k t l
-
7/25/2019 Air Conditioning (1)
59/60
A sky lobby is used in supertall buildings, such as skyscrapers, to make travelbetween elevators convenient for all passengers.
These are intermediate floors used to section off the building. Most such
buildings have one elevator, called an express elevator, which only travelsbetween the different sky lobby floors.
Between each sky lobby, there are local elevators that lead to all the floors inthat section of the building.
The number of local elevators in each section typically ranges up to 10, withup to five in a row to make walking between elevators easier for visitors andemployees.In very large buildings, there are numerous floors with a constant flow of
visitors and workers going between the floors.If each elevator served the entire building, then most people wouldencounter a number of stops for others to get off before they arrived at theirdesired floor. This would make elevator travel inconvenient in largebuildings and would lead to massive delays for most elevator travelers.
ll i hi bl k l bb i d hi l bb i i
-
7/25/2019 Air Conditioning (1)
60/60
To alleviate this problem, a sky lobby is used. This lobby acts as a sectioning
device t hat separates the entire building into several zones. In each lobby, there
are separate elevators that only take travelers to a floor in that zone. For
example, if there is a 20-floor building and each lobby serves five floors, then
the first lobby would have elevators for floors one through five, and the secondlobby would serve floors six through 10.
Getting to a sky lobby also is streamlined. Aside from the local elevators thatserve each lobbys zone, there also is an express elevator. This elevator or set of
elevators only travels between the lobby zones. In this case, even if the travelerneeds the top lobby zone and the elevator stops at every other lobby, the
traveler still will only experience a few stops. Most buildings only contain afew lobbies, so express elevator travel would be easy on all visitors andworkers.Depending on the architecture, there may be 10 local elevators for each skylobby zone. These local elevators are usually placed on opposite ends of thelobby, so the area does not become congested. Each local elevator will only
serve several floors in the lobby zone, so those who need one of the bottomfloors will not impede people who need a top floor.