Air Conditioner CS-F14DB4E5 CU-J28DBE5 CS …. AIRE...• Multiple indoor units can be operated...
Transcript of Air Conditioner CS-F14DB4E5 CU-J28DBE5 CS …. AIRE...• Multiple indoor units can be operated...
Order No. MAC0605028C2
Air ConditionerCS-F14DB4E5 CU-J28DBE5CS-F14DB4E5 CU-J28DBE8CS-F18DB4E5 CU-J34DBE5CS-F18DB4E5 CU-J34DBE8CS-F24DB4E5 CU-J43DBE8CS-F28DB4E5 CU-J50DBE8
TABLE OF CONTENTSPAGE PAGE
1 Features ------------------------------------------------------------- 21.1. Twin ----------------------------------------------------------- 2
2 Product Specification ------------------------------------------- 32.1. CS-F14DB4E5 CU-J28DBE5--------------------------- 32.2. CS-F14DB4E5 CU-J28DBE8--------------------------- 42.3. CS-F18DB4E5 CU-J34DBE5--------------------------- 52.4. CS-F18DB4E5 CU-J34DBE8--------------------------- 62.5. CS-F24DB4E5 CU-J43DBE8--------------------------- 72.6. CS-F28DB4E5 CU-J50DBE8--------------------------- 8
3 Twin Systems ------------------------------------------------------93.1. Installation Manual-----------------------------------------9
4 Troubleshooting Guide --------------------------------------- 114.1. During twin operation ----------------------------------- 11
Please file and use this manual together with the service manual for Model No. CS-F24DB4E5 CU-J24DBE5 CS-F24DB4E5 CU-J24DBE8 CS-F34DB4E5 CU-J34DBE5 CS-F34DB4E5 CU-J34DBE8 CS-F43DB4E5 CU-J43DBE8 CS-F50DB4E5 CU-J50DBE8, Order No. MAC0509062C2 and CS-F14DB4E5 CU-J14DBE5 CS-F18DB4E5 CU-J18DBE5, Order No. MAC0602017C2.
© 2006 Panasonic HA Air-Conditioning (M) Sdn Bhd(11969-T). Unauthorized copying and distribution is aviolation of law.
1 Features1.1. Twin1.1.1. Twin Operation
• Simultaneous air conditioning of wide spaces and corners is possible. Indoor units with same horsepowers can even be used incombination.
• Master unit and slave-units can be set automatically in twin systems. No address setting is necessary.• Multiple indoor units can be operated simultaneously with a single remote control unit. Note that individual operation is not possi-
ble.
2
2 Product Specification2.1. CS-F14DB4E5 CU-J28DBE5
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°FD.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F14DB4E5 × 2 CU-J28DBE5
Panel CZ-BT03PRemoteControl
CZ-RD513C (Wired)CZ-RL513B (Wireless)
Cooling Capacity kW 7.30BTU/h 24,900
Refrigerant Charge-less m 30Standard Air Volume for High, m3/min 15 61
cfm 530 2154Outside Dimension (H x W x D) mm 246 × 840 × 840 795 × 900 × 320
inch 9-11/16 × 33-1/24 × 33-1/24 31-5/16 × 35-7/16 × 12-19/32Net Weight kg (lbs) 25 (55) 61 (135)PipingConnection
Refrigerant Gas mm (inch) O.D Ø 12.70 (1/2) Flared TypeLiquid mm (inch) O.D Ø 6.35 (1/4) Flared Type
Drain mm O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1
Starting Method - Permanent Split CapacitorMotor Type - 2-pole 1 phase brushless motor
Rated Output kW - 2.0Fan Type, Number of Set Turbo fan-1 Mix flow fan,1
Motor Type 8-pole DC motor 6-pole single phase induction motorRated Output kW 0.04 0.07
Air-heat Exchanger (Row x Stage x FPI) Louver-fin type (1 × 8 × 21) Corrugate-fin type (1 × 36 ×21)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - FV50S (1130)Refrigerant (Charged) R410a kg (oz) - 1.45 (51)RunningAdjustment
Control Switch Wireless or Wired Remote Control -Room Temperature Thermostat -
Noise Level dB (A) Cooling: 34/31 52/-Power Level
dBCooling: 59/46 67/-
Moisture Removal L/h (Pt/h) 4.3 (9.0)EER W/W 2.66/2.61/2.56
ITEM / MODEL Condition by ISO5151Volts V 220 230 240Phase Single Single SinglePower Consumption kW Cooling 2.74 2.80 2.85Running Current A Cooling 12.80 12.90 13.0Starting Current A 62 65 66Power Factor % Cooling 97 94 91*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.Panasonic Power source AC, 1~220V, 230V, 240V 50Hz
3
2.2. CS-F14DB4E5 CU-J28DBE8
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°FD.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F14DB4E5 × 2 CU-J28DBE8
Panel CZ-BT03PRemoteControl
CZ-RD513C (Wired)CZ-RL513B (Wireless)
Cooling Capacity kW 7.3BTU/h 24,900
Refrigerant Charge-less m 30Standard Air Volume for High, m3/min 15 61
cfm 530 2154Outside Dimension (H x W x D) mm 246 × 840 × 840 795 × 900 × 320
inch 9-11/16 × 33-1/24 × 33-1/24 31-5/16 × 35-7/16 × 12-19/32Net Weight kg (lbs) 25 (55) 61 (135)PipingConnection
Refrigerant Gas mm (inch) O.D Ø 12.70 (1/2) Flared TypeLiquid mm (inch) O.D Ø 6.35 (1/4) Flared Type
Drain O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1
Starting Method - Permanent Split CapacitorMotor Type - 2-pole 3 phase brushless motor
Rated Output kW - 2.0Fan Type, Number of Set Turbo fan-1 Mix flow fan,1
Motor Type 8-pole DC motor 6-pole single phase induction motorRated Output kW 0.04 0.07
Air-heat Exchanger (Row x Stage x FPI) Louver-fin type (1 × 8 × 21) Corrugate-fin type (1 × 36 × 21)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - FV50S (1130)Refrigerant (Charged) R410a kg (oz) - 1.45 (51)RunningAdjustment
Control Switch Wireless or Wired Remote Control -Room Temperature Thermostat -
Noise Level dB (A) Cooling: 34/31 52/-Power Level
dBCooling: 59/46 67/-
Moisture Removal L/h (Pt/h) 4.3 (9.0)EER W/W 2.66/2.61/2.56
ITEM / MODEL Condition by ISO5151Volts V 380 400 415
Phase Three Three ThreePower Consumption kW Cooling 2.74 2.80 2.85Running Current A Cooling 4.85 4.90 4.95Starting Current A 23 25 27Power Factor % Cooling 86 82 80*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.Panasonic Power source AC, 3~380V, 400V, 415V 50Hz
4
2.3. CS-F18DB4E5 CU-J34DBE5
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°FD.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F18DB4E5 × 2 CU-J34DBE5
Panel CZ-BT03PRemoteControl
CZ-RD513C (Wired)CZ-RL513B (Wireless)
Cooling Capacity kW 10.0BTU/h 34,100
Refrigerant Charge-less m 30Standard Air Volume for High, m3/min 20 103
cfm 706 3634Outside Dimension (H x W x D) mm 246 × 840 × 840 1170 × 900 × 320
inch 9-11/16 × 33-1/24 × 33-1/24 46-1/16 × 35-7/16 × 12-19/32Net Weight kg (lbs) 26 (57) 92 (203)PipingConnection
Refrigerant Gas mm (inch) O.D Ø 12.70 (1/2) Flared TypeLiquid mm (inch) O.D Ø 6.35 (1/4) Flared Type
Drain O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1
Starting Method - Permanent Split CapacitorMotor Type - 2-pole 1 phase brushless motor
Rated Output kW - 3.0Fan Type, Number of Set Turbo fan-1 Mix flow fan,1
Motor Type 8-pole DC motor 6-pole single phase induction motorRated Output kW 0.04 0.07 × 2
Air-heat Exchanger (Row x Stage x FPI) Louver-fin type (1 × 10 × 20) Corrugate-fin type (1 × 44 × 21)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - DAPHNE FVC68D (1500)Refrigerant (Charged) R410a kg (oz) - 1.70 (60)RunningAdjustment
Control Switch Wireless or Wired Remote Control -Room Temperature Thermostat -
Noise Level dB (A) Cooling: 35/32 55/-Power Level
dBCooling: 50/47 69/-
Moisture Removal L/h (Pt/h) 6.0 (12.6)EER W/W 2.58/2.54/2.51
ITEM / MODEL Condition by ISO5151Volts V 220 230 240Phase Single Single SinglePower Consumption kW Cooling 3.88 3.93 3.98Running Current A Cooling 17.8 18.1 18.4Starting Current A 92 95 98Power Factor % Cooling 99 94 90*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.Panasonic Power source AC, 1~220V,230V, 240V 50Hz
5
2.4. CS-F18DB4E5 CU-J34DBE8
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°FD.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F18DB4E5 × 2 CU-J34DBE8
Panel CZ-BT03PRemoteControl
CZ-RD513C (Wired)CZ-RL513B (Wireless)
Cooling Capacity kW 10.0BTU/h 34,100
Refrigerant Charge-less m 30Standard Air Volume for High, m3/min 20 103
cfm 706 3634Outside Dimension (H x W x D) mm 246 × 840 × 840 1170 × 900 × 320
inch 9-11/16 × 33-1/24 × 33-1/24 46-1/16 × 35-7/16 × 12-19/32Net Weight kg (lbs) 26 (57) 92 (203)PipingConnection
Refrigerant Gas mm (inch) O.D Ø 12.70 (1/2) Flared TypeLiquid mm (inch) O.D Ø 6.35 (1/4) Flared Type
Drain O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1
Starting Method - Permanent Split CapacitorMotor Type - 2-pole 3 phase brushless motor
Rated Output kW - 3.0Fan Type, Number of Set Turbo fan-1 Mix flow fan,1
Motor Type 8-pole DC motor 6-pole single phase induction motorRated Output kW 0.04 0.07 × 2
Air-heat Exchanger (Row x Stage x FPI) Louver-fin type (1 × 10 × 20) Corrugate-fin type (1 × 44 × 21)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - DAPHNE FVC68D (1500)Refrigerant (Charged) R410a kg (oz) - 1.70 (60)RunningAdjustment
Control Switch Wireless or Wired Remote Control -Room Temperature Thermostat -
Noise Level dB (A) Cooling: 35/32 55/-Power Level
dBCooling: 50/47 69/-
Moisture Removal L/h (Pt/h) 6.0 (12.6)EER W/W 2.67/2.63/2.60
ITEM / MODEL Condition by ISO5151Volts V 380 400 415Phase Three Three ThreePower Consumption kW Cooling 3.75 3.80 3.85Running Current A Cooling 6.10 6.20 6.30Starting Current A 41 44 47Power Factor % Cooling 93 88 85*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.Panasonic Power source AC, 3~380V,400V, 415V 50Hz
6
2.5. CS-F24DB4E5 CU-J43DBE8
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°FD.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F24DB4E5 × 2 CU-J43DBE8
Panel CZ-BT03P × 2RemoteControl
CZ-RD513C (Wired)CZ-RL513B (Wireless)
Cooling Capacity kW 12.5BTU/h 42,600
Refrigerant Charge-less m 30Standard Air Volume for High, m3/min 18 94
cfm 636 3316Outside Dimension (H x W x D) mm 246 × 840 × 840 1170 × 900 × 320
inch 9-11/16 × 33-1/24 × 33-1/24 46-1/16 × 35-7/16 × 12-19/32Net Weight kg (lbs) 26 (58) 97 (214)PipingConnection
Refrigerant Gas mm (inch) O.D Ø 15.88 (5/8) Flared TypeLiquid mm (inch) O.D Ø 9.52 (3/8) Flared Type
Drain O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1
Starting Method - Permanent Split CapacitorMotor Type - 2-pole 3 phase brushless motor
Rated Output kW - 3.75Fan Type, Number of Set Turbo fan-1 Mix flow fan,1
Motor Type 8-pole DC motor 6-pole single phase induction motorRated Output kW 0.04 0.07 × 2
Air-heat Exchanger (Row x Stage x FPI) Louver-fin type (2 × 10 × 20) Corrugate-fin type (2 × 44 × 20)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - DAPHNE FVC68D (1500)Refrigerant (Charged) R410a kg (oz) - 3.10 (109)Running Adjustment
Control Switch Wireless or Wired Remote Control -Room Temperature Thermostat -
Noise Level dB (A) Cooling: 36/32 56/-Power Level
dBCooling: 51/47 70/-
Moisture Removal L/h (Pt/h) 7.9 (16.6)EER W/W 2.64/2.61/2.58
ITEM / MODEL Condition by ISO5151Volts V 380 400 415Phase Three Three ThreePower Consumption kW Cooling 4.74 4.79 4.84Running Current A Cooling 7.8 8.0 8.2Starting Current A 54 57 60Power Factor % Cooling 92 86 82*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.Panasonic Power source AC, 3~380V,400V, 415V 50Hz
7
2.6. CS-F28DB4E5 CU-J50DBE8
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor airtemperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°FD.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL Indoor Unit Outdoor UnitMain Body CS-F28DB4E5 × 2 CU-J50DBE8
Panel CZ-BT03P × 2RemoteControl
CZ-RD513C (Wired)CZ-RL513B (Wireless)
Cooling Capacity kW 13.5BTU/h 46,000
Refrigerant Charge-less m 30Standard Air Volume for High, m3/min 20 96
cfm 706 3387Outside Dimension (H x W x D) mm 246 × 840 × 840 1170 × 900 × 320
inch 9-11/16 × 33-1/24 × 33-1/24 46-1/16 × 35-7/16 × 12-19/32Net Weight kg (lbs) 26 (58) 97 (214)Piping Connection
Refrigerant Gas mm (inch) O.D Ø 15.88 (5/8) Flared TypeLiquid mm (inch) O.D Ø 9.52 (3/8) Flared Type
Drain O.D Ø 20 I.D Ø 20Compressor Type, Number of Set - Hermetic, 1
Starting Method - Permanent Split CapacitorMotor Type - 2-pole 3 phase brushless motor
Rated Output kW - 4.5Fan Type, Number of Set Turbo fan-1 Mix flow fan,1
Motor Type 8-pole DC motor 6-pole single phase induction motorRated Output kW 0.04 0.07 × 2
Air-heat Exchanger (Row x Stage x FPI) Louver-fin type (2 × 10 × 20) Corrugate-fin type (2 × 44 × 20)Refrigerant Control - Expansion ValveRefrigerant Oil (Charged) cm3 - DAPHNE FVC68D (1500)Refrigerant (Charged) R410a kg (oz) - 3.25 (114)Running Adjustment
Control Switch Wireless or Wired Remote Control -Room Temperature Thermostat -
Noise Level dB (A) Cooling: 38/33 56/-Power Level
dBCooling: 53/48 70/-
Moisture Removal L/h (Pt/h) 8.6 (18.1)EER W/W 2.63/2.61/2.58
ITEM / MODEL Condition by ISO5151Volts V 380 400 415Phase Three Three ThreePower Consumption kW Cooling 5.13 5.18 5.23Running Current A Cooling 8.3 8.5 8.7Starting Current A 55 58 61Power Factor % Cooling 94 88 84*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.Panasonic Power source AC, 3~380V,400V, 415V 50Hz
8
3 Twin Systems3.1. Installation Manual
9
10
4 Troubleshooting Guide4.1. During twin operationSystem example
1. The main power is turned on while the transmission wires between the indoor units are not connected.(open circuit at A or B)SymptomRemote control unit: “check” flashesError code: F30-01 (connected indoor capacity error)Indoor unit No. 1: LED1 on P.C.B flashesIndoor unit No. 2: no power supplyOutdoor unit: LED6, 7 on P.C.B flashes (connected indoor capacity error)
2. The main power is turned on while the transmission wires between the indoor units are not connected.(open circuit at section C)SymptomRemote control unit: “check” flashesError code: F30-01 (connected indoor capacity error)Indoor unit No. 1: LED1 on P.C.B flashesIndoor unit No. 2: no power supplyOutdoor unit: LED5, 6 on P.C.B flashes (connected indoor capacity error)
3. The main power is turned on and the connection wire is all ok.If operation starts in this condition, combination of the B50DBE8 outdoor unit and F24DB4E5 indoor unit will result inabnormal operation.SymptomRemote control unit: “check” flashesError code: F30-01 (connected indoor capacity error)
11
Indoor unit: LED1 on P.C.B flashesOutdoor unit: LED6, 7 on P.C.B flashes
4. The main power is turned on and the connection wire is all ok.If operation starts in this condition, combination of the B50DBE8 outdoor unit and F24DB4E5 indoor unit will result inabnormal operation.SymptomRemote control unit: “check” flashesError code: F30-01 (connected indoor capacity error)Indoor unit: LED1 on P.C.B flashesOutdoor unit: LED6, 7 on P.C.B flashes (connected indoor capacity error)
Remedy1. Turn off the main power.
↓2. Connect the disconnected wire correctly.
↓3. Turn on the main power.
↓4. After 1 minute, start the operation using the remote control.
(Indoor unit operation will start according to the remote control setting.)(Outdoor unit operation will start after 3-5 minutes.)
[PHAAM] Printed in MalaysiaSSBZ0605-00