Air Circuit Breakers, 1600 to 6300A BT3 Series
-
Upload
cty-tnhh-hao-phuong -
Category
Engineering
-
view
334 -
download
8
Transcript of Air Circuit Breakers, 1600 to 6300A BT3 Series
New Product News
62D9-E-0164
Air Circuit Breakers, 1600 to 6300A
BT3 Series
Breaking Capacity Icu is equal to Ics up to 120kA at maximum and Icw 1s is up to 120kA at maximum under AC415V distribution.
0
20
40
60
80
100
120
50 50
BT3-1600
BT3-2500
BT3-2500H
BT3-4000
BT3-4000H
BT3-6300
BT3-6300H
65 65
85 85 85 85
100
85
100 100
120 120
lcu = lcs lcw
Selection guide
Features• Compact design• Satisfied Icu = 50kA or above at 440V for all of ampere frame size• Available Icu / Ics rating at 440V, rated current from 200A to
6300A, Ics = 100% of Icu• Conform to IEC 60947-2 (DEKRA (KEMA) certificate will be
obtained.)
Series BT3 seriesFrame size 1600, 2500, 4000, 6300No. of poles 3, 4Installation Fixed Available
Draw-out AvailableClosing Mechanism Manual or motor spring charging mechanismTripping Mechanism Shunt trip, Under-voltage tripProtection function Long time delay, Short time delay, Instantaneous, Ground fault, etc.
BT3
New
Ha Noi O�ce:No. 95 - TT4, My Dinh Urban Area, My Dinh, Nam Tu Liem, Hanoi.Tel: (84 4) 3568 3740Fax: (84 4) 3568 3741
Cambodia O�ce:#140, Room 1-B, St430, Sangkat Toul Tompuong II, Khan Chamkamon, PP.Tel: 855 2322 3635Fax: 855 2322 3645
Head O�ce:No 88, Vinh Phu 40, Hoa Long,Vinh Phu, Thuan An, Binh Duong.Tel: (84 650) 37 37 619Fax: (84 650) 37 37 620
1800 6547THINK TOGETHER
Nhà phân phối thiết bị điện công nghiệphàng đầu Việt Nam
T
Clear indication of ready-for-switching-on to ensure safe manipulation and reliable operation.
More reliable safety protection with seconday terminals of protection grade IP30
Compact sizeBT3 series, Air Circuit Breakers, have four ampere frame sizes and physical dimensions.Ampere frame
1600 2500 4000 6300
Appearance
Width(3-poles, Draw-out type)
248mm 347mm 401mm 754mm
Installation The bus bar terminal of the BT3 series, Air Circuit Breakers, can be simply installed as follows:• Horizontal connection• Vertical connection• Composite connection
Safety performance Draw-out type BT3 series Air Circuit Breakers can be operated safety at 3 positions:1. Connected position2. Testing position3. Disconnected position
Indication of ready-for-switching-on:"ok"
21222324
21222324
21222324
21222324
Protection and selection BT3 Series, Air Circuit Breakers, can implement selective interlock of ZSI Region to ensure comprehensive selection of various protection and reduce the copper bar's bearing of thermodynamic.
Intelligent Controller (OCR)Selecting OCR's, it can be classified into ten types
Type EN35 EN36 EA35 EA36 EP35 EP36Option Option Standard Option Option Option
Pic
Display/setting LED indication LED indication LCD indicaiton LCD indication LCD indication LCD indicationProtection/function
t
I
Three levels protection
t
I
Three levels protection
t
I
Ground-fault-protection
t
I
Three levels protection
t
I
Three levels protection
t
I
Ground-fault-protection
t
I
Three levels protection
t
I
Three levels protection
t
I
Ground-fault-protection
Measurement CurrentOptional function(Voltage, Energy, Frequency, Power)
CurrentOptional function(Voltage, Energy, Frequency, Power)
Current Current CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand value
CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand value
EQ35 EQ36 EG35 EG36Option Option Option Option
LCD indication LCD indication LCD indication LCD indicationt
I
Three levels protection
t
I
Three levels protection
t
I
Ground-fault-protection
t
I
Three levels protection
t
I
Three levels protection
t
I
Ground-fault-protection
CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture function
CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture function
CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture functionOver frequencyUnder frequencyInverse power
CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture functionOver frequencyUnder frequencyInverse power
Intelligent controller (OCR) functions
Type EN35 EN36 EA35 EA36 EP35 EP36 EQ35 EQ36 EG35 EG36Option Option Standard Option Option Option Option Option Option Option
Display LED LED LCD LCD LCD LCD LCD LCD LCD LCDOvercurrent protection (Long-time, Short-time, instantaneous)Ground fault protection – – – – –Neutral protectionOverload pre-alarmCurrent-unbalance protectionPhase-loss protectionDemand current protection – – – –Over-voltage protection – – – –Under-voltage protection – – – –Voltage-unbalance protection – – – –Over-frequency protection – – – – – – – –Under-frequency protection – – – – – – – –Phase sequence protection – – – –Reverse power protection – – – – – – – –Current shedding Zone selective interlocking (ZSI)MCR function
Note: Reprensents fundamental functions, Represents optional functions, – Represent no such functions
Type number nomenclature
OCR type or Additional accessories
Frame size1600, 2500, 4000, 6300
PerformanceNone: StandardH : High breaking capacity
InstallationP: Fixed typeX: Draw-out type
Number of poles3: 3 poles4: 4 poles
Rated current1600AF: 0200, 0400, 0630, 0800, 1000, 1250, 16002500AF: 0630, 0800, 1000, 1250, 1600, 2000, 25004000AF: 1000, 1250, 1600, 2000, 2500, 2900, 3200
3600, 40006300AF: 4000, 5000, 6300
Basic type
English version
BT3-2500HP / 32500E
• Accessories
Type Code RemarksManual operated M1 For BT3-1600
M2 For BT3-2500M3 For BT3-4000,6300
Under voltage release R11 Instananeous : AC220V-AC240VR12 Instananeous : AC380V-AC415VR21 Time delay (0.5s, 1s, 2s, 3s) : AC220V-AC240VR22 Time delay (0.5s, 1s, 2s, 3s) : AC380V-AC415V
Switching OFF lock device Q1 One lock and one keyQ2 Two lock and one keyQ3 Three lock and two key
Mechanical interlock device(Two sets of ACB's)
MW1 Steel lock interlockMB1 Link rod interlock
Mechanical interlock device(Three sets of ACB's : for BT3-2500 and over)
MW2 Steel lock interlockMB2 Pattern one of rod interlockMB3 Pattern two of rod interlockMB4 Pattern three of rod interlock
Pushbutton lock mechanism LInterphase barriers B3 Three-phase
B4 Four-phaseCounter CMElectrical module for indication of ready-for-switching-on E1Remote reset RMR AC220-240VElectrical indication mechanism of socket's position D1Electrical indication mechanism of storage signal S1Accessories monitoring units AMCurrent transformer with the neutral line N connected externally
N1 For BT3-1600N3 For BT3-2500N4 For BT3-4000N6 For BT3-6300
Unit with transformer's center erath extermaily connected. UTProgrammable output expansion module EM6 6 lines Communication choices of accessories S1 Components of draw-out socket communication module
S2 Signal of ready-for-closeS3 Signal of under-voltageS4 Signal of fault releaseS5 Signal of charging
Normal power supply module PD1 DC24VPA1 AC220-240VPA2 AC380-415V
DC power supply module PD2 DC110VPD3 DC220V
Automatic Transfer Switch (ATS)(included automatic controller, connector and 1.8m cable)
AS1 R typeAS2 S typeAS3 F type
3 lines over-current fault output module OCF
• OCR type (note: EA35 is standard), refer to in the Intelligent controller (OCR) functions
Type Code RemarksEN35 N35EN36 N36EA35 – (None)EA36 A36EP35 P35EP36 P36EQ35 Q35EQ36 Q36EG35 G35EG36 G36
Information in this catalog is subject to change without notice.
5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan
URL http://www.fujielectric.co.jp/fcs/eng
2014-09 PDF FOLS 62D9-E-0164
Specifications
Operation environments
Frame size 1600A 2500A 2500A 4000A 4000A 6300A 6300ABasic type BT3-1600 BT3-2500 BT3-2500H BT3-4000 BT3-4000H BT3-6300 BT3-6300H No. of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4Rated current (A) 200, 400, 630,
800, 1000, 1250, 1600
630, 800, 1000, 1250, 1600, 2000, 2500
630, 800, 1000, 1250, 1600, 2000, 2500
1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000
1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000
4000, 5000, 6300
4000, 5000, 6300
Rated current of the neutral pole (IN) 100% In 100% In 100% In 100% In 100% In 100% In 100% InRated insulation voltage (Ui) 1000 1000 1000 1000 1000 1000 1000Rated operational volage (Ue) 690 690 690 690 690 690 690Rated ultimate short-circuit breaking capacity(Icu kA, sym)
AC690V 50 55 65 75 85 85 100AC415/440V 50 65 85 85 100 100 120AC400V 65 65 85 85 100 120 135
Rated service short-circuit breaking capacity(Ics kA, sym)
AC690V 42 55 65 75 85 85 100AC415/440V 50 65 85 85 100 100 120AC400V 55 65 85 85 100 120 135
Rated making current(kA, peak)
AC690V 105 121 143 165 187 187 220AC415/440V 105 143 187 187 220 220 264AC400V 143 143 187 187 220 264 297
Rated short time withstand current (Icw) (kA, rms) -1s
AC690V 42 55 65 75 75 85 100AC415/440V 50 65 85 85 85 100 120AC400V 50 65 85 85 85 120 135
Rated impulse withstand voltage (Uimp) (kV)
12 12 12 12 12 12 12
InstallationsFixed PDraw-out X
Main circuit terminal connectionFixed Horizontal
Vertical – – – – – – – – – – – –
Draw-out HorizontalVertical
DimensionsFixed W 259 329 362 457 362 457 414 527 414 527 769 995 769 995
H 320 320 395 395 395 395 395 395 395 395 395 395 395 395D 195 195 290 290 290 290 290 290 290 290 290 290 290 290
Draw-out W 248 318 347 442 347 442 401 514 401 514 754 980 754 980H 351.5 351.5 438 438 438 438 438 438 438 438 475.5 475.5 475.5 475.5D 297 297 395 395 395 395 395 395 395 395 395 395 395 395
Available, – Not Available
Note: If the ACB is used in IT distribution system at AC415V or above, please inform to Fuji at the time of ordering.
Ambient temperature -5°C to +40°CAltitude < 2000mRelative humidity Not exceed 50% at +40°CPollution degree 3Vertical gradient no more than 5°