0CDDC-01A Air Handling Unit

Transcript of AHU PD 22-07-2010

Page 1: AHU PD 22-07-2010

0CDDC-01A

Air Handling Unit

Page 2: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

General Description

3

Thank you very much for your special patronage of LG air conditioners.

This PDB(Product Data Book) has been prepared as a guide for selecting LG's AHU (Air Handling Unit).

LG has produced a high quality product that is adaptable to almost any application such as large halls, schools,offices, banks, workshops, laboratories, restaurants, cinemas, hospitals, departmental stores and super marketsetc.

However, proper installation, operation and maintenance must be followed to comprehend the fully capacity andlife of the product.

This PDB contains standard & general specification of LG's AHU.

Standard model of LG's AHU are available in 15 type to deliver from 1,770CFM(830LPS) to44,150CFM(20,830LPS) nominal air flow rate, but it is possible to supply the specific requirements of AHU specifi-cation demanded customers.

Double skin panels of LG's AHU are designed to meet the indoor air quality requirements, and are insulated with afull 2 inches of insulation.

Drain pan is designed to be well drained for applying the proper grade. That is made by over stainless steel 1.5twith insulating under part(Pu 15t).

Fan applied LG's AHU is selected by optimal fan selection using selection program certified by AMCA certificationprogram. LG’s AHU use a Fan on a guarantee of AMCA 210-99(Fan performance) & AMCA 200-97(Sound level).

A lot of information regarding the design & detail specification of LG's AHU is provided In this PDB.

Please utilize all the information for conducting your business efficiently. Make sure the specification, size or oth-ers technical data are same as provided in this PDB before you start the project.

We look forward to your continuing support.

LG Electronics Inc.Air Conditioning Company

Page 3: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit 4

Air Handling Unit

1. Design & Component Features

2. Quick Selection

3. Standard Specification

4. Dimensions

5. Fan Data

6. Nominal Capacity

7. Pressure Drop

8. Installation

9. Workscope

Contents

Page 4: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

5

1. Design(structure)Air Handling Unit(AHU) consists of supply air fan part that ventilates cooled(or heated) air into loaded space,return air fan to ventilate air in the loaded space, filter part, mixing part that combines outside and returned air,and coil part that accomplishes air-cooling and heating being connected to chiller or EHP.

The detailed items consist of fan(supply, return), motor, filter(pre, medium), damper(return, exhaust, outdoor ,mixing), coil, isolator, drain pan, casing, base frame, and other accessories.

2. Component Features2.1 FrameCasing is constructed of framed modules for maximum rigidi-ty and strength. structure frame is made of aluminum or steelprofile which has excellent mechanical characteristics.

2.2 CasingThe panel's structure is double skin type with 50 mm thick Urethane form board insulation, which has good heat insulation, sandwiched between sheet steel panels.

Ventilation part

• Fan / Motor / Pully• Frame / Vibration proof spring

Damper part

• Inner Damper (1EA)• Outer Damper (2EA)

Filter part

• Pre Filter• Medium Filter

Humidification part

• Evaporative type• Steam Injection

Casing part

• Case• Inspection Door

Coil part

• Chilled/Hot water coil• DX coil

occo FanSir

nrd FaBackwar nrd Fackward

<Double Skin Type Casing>

<Typical Air Handling Unit>

Page 5: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

6

The outside panel is made of cold rolled steel sheet(SPCC 1.0mm) with electrostatic powder coating, and theinside panel is made of galvanized steel sheet(SGCC 0.6mm).

2.3 DoorsFor inspection and fix of AHU inside, facilitate service andmaintenance by setting up access door as panel structure atnecessary locations such as ventilator part, filter part, and soon.

To inspect AHU inside, single and double glazed glass win-dows can be fitted to many sections.

The window is normally placed centrally on the panel.

Access door is made as air tight structure by applying twocircle handles and specially designed door hinge.

2.4 Base & Drain PanBase is made as enough solid structure to maintain the established structure according to AHU'S load. Drain pan is made as a structure to be well drained for applying the proper grade.

-. Base Material : SGCC 2.0t

-. Drain Pan Material : Over Stainless steel 1.5t (Insulate under part with Pu 15t)

-. Drain Socket Material : STS, 40A

2.5 FanDouble suction, belt driven centrifugal fan must be guaranteed for the performance based upon AMCA 210-99,and AMCA Seal by AMCA 211 and AMCA certification program must be attached and guaranteed.

Classification Urethane Form Board E.P.S Poly Urethane Glass Wool

Density (g/cm2) 0.032~0.035 0.015~0.030 0.030~0.035 0.048

Heat conductivity Less than Less than Less than Less than (kal/mh°C) 0.022 0.030~0.034 0.021 0.039

Winding intensity More than More than More than -(kg/cm2) 5.5 2.0~2.5 2.0~2.5

Absorption rate Less than Less than Less than -(%Vol) 0.05 1.0~1.5 3.0 (g/100cm2)

A property of matter comparison table classified by middle heat insulator

< Inspection Sight Glass >

Page 6: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

7

FAN's characteristic and merit consisting of LG AHULG’s AHU use a Fan on a guarantee of AMCA 210-99(Fan perfor-mance) & AMCA 300(Sound level).

<Characteristic>

- Optimal fan selection using electric selection program certified byAMCA (Air Movement & Control Association)

- High tension steel sheet coating for high efficiency and low noise real-ization.

- The best level balancing of ISO 1940 G2.5.

- The world best bearing use

HousingFan housing is made by the thickness to prevent vibration and housing sound.

If fan’s standard is less than1000(Impeller diameter size, mm), make housing scroll and side plate by highfusion galvanizing steel sheet based on “Pittsburg Lock” method.

For more than 1250, after completely welding by general steel sheet, and finish by polyester powder coating ofthe minimum of 60 µm.

ImpellerFor supply air fan’s airfoil wheel (both inhaling), after welding by cold rolled steelsheet, finish by polyester powder coating.

Return air fan’s forward curved wheel (sirocco type) is made through non-weldingConnection by high fusion galvanizing steel sheet.

Every Impeller must be balanced at static and dynamic state based on ISO 1940and AMCA 204/3-G2.5 standard.

ShaftThe quality of the shaft must be elaborately machine processed within an allowable error based on ISO 286-2-G6 Grade standard selecting standard which doesn’t happen sink obtained by C45 carbon steel’s additionalweight and high-speed rotation, and after assembling at the factory, do rust proof coating.

Select to keep safety for critical speed which is made 1.25 times more than maximum operation speed or largerthan that.

BearingEvery bearing should use SKF product.

Apply self-aligning ball type enough to bear circumference direction andshaft’s load.

Bearing durability is more than 40,000 hours

<Backward type>

<Impeller>

Page 7: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

8

2.6 MotorMotor is a belt-drive type's product and applies more than insulationclass, " F " Class.

Motor’s airtight and watertight protection grade is IP54, and although awater drop Invades from any direction, it can be a structure to be pro-tected.

Make easily adjust V-belt tension by manufacturing motor base as aslide style.

2.7 Drive UnitFan & motor pulley is able to maximize power delivery efficiency by applying multi ribbed pulley.

For rubber belt (V-BELT)’s quality, by applying multi ribbed pulley and thus excelling in belt’s pliability and flexi-bility, it is stable power delivery at high-speed rotation and small size and, electric motion efficiency is able toincrease up to 98% by minimizing belt slip.

2.8 IsolatorBy attaching Isolator to fan motor frame, make it capable of absorbingfan’s vibration.

By attaching canvas between fan’s exit and AHU casing, design andmake to prevent fan’s vibration and noise delivery.

When setting up motor outside of AHU, it is essential to set up horizon-tally being pushed preventer to prevent being pushed while driving fanbetween fan part and the part connected to it.

Prevent delivery of vibration and twisting originated from moving by set-ting up horizontally being pushed preventer between return fan sectionand other section.

< Pulley & V-Belt>

< Isolator Installation Scene>

Page 8: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

9

2.9 CoilDesign and make as counter flow style which is the most effi-cient fluid flowing form for heat exchange of coil and air.

When coil’s length is more than 1m, use middle reinforcingsteel sheet to prevent frame’s bending or transformation

Make it without winding and unevenness to minimize refriger-ant’s flow resistance.

Header and U-bend’s welding part have enough intensity tobear maximum use pressure.

By executing coil’s pressure test as 20kg/cm2 at Water coil(41kg/cm2 at DX coil), and maximum water tempera-ture as 150°C, there must not be a leak, transformation, explosion, and so on at coil’s each part.

Make coil’s safety rate more than 15-20%, and make it more than two rows

2.10 Air filterFilter must be selected and setup to fit option and handling air flow.

Pre Filter Characteristic and applying object

- Weight method 60~85% separate and collect efficiency

- For the use of previous handling of electric part, hospital, food manufacture line

Classification Quality of the material

Media Glass Fiber. Synthetic Fiber, Aluminum

Frame Galvanized Steel, Particle Board, AluminumSteel, Stainless Steel, Paper

Maximum use temperature 100°C

Maximum use humidity Relative humidity 100%

Quality of the material and use condition

594x287x25 28

594x594x25 564.0 14.0

594x287x50 28

594x594x50 56

Standard(H x W x D, mm) Air flow(CMM)Pressure loss(mmAq)

Clean Dirty

Standard specification (Aluminum filter)

Page 9: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

10

Medium Filter Characteristic and applying object

- Separate and collect efficiency of more than 60~90%

- Easy large amount of dust handling, transport / safekeeping and exchange

- Use final filter for the use of HEPA filter previoushandling at Clean room or at air purification, industri-al factory

2.11 DamperAirfoil shaped blade apparently reduces the pressure drop andsound level across the damper.

Soft and contact-easy blade seal gives good contact withÄadja-cent blade seal and this reduces leakage rates.

Stainless steel, aluminum and PVC materials only are used togive good operation and to prevent corrosion after time elapsed.

Classification Quality of the material

Media Glass Fiber. Synthetic Fiber

Frame Galvanized Steel, Particle Board, AluminumSteel, Stainless Steel, Paper

Maximum use temperature 120°C

Maximum use humidity Relative humidity 100%

594x287x300 28

594x594x300 56

594x287x600 28

594x594x600 56

60~90% 12.2 25.4

Standard(H x W x D, mm) Air flow(CMM) EfficiencyPressure loss(mmAq)

Clean Dirty

Standard specification (Bag filter)

Quality of the material and use condition

<Air tight Damper>

Page 10: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

11

2.12 Electric HeaterThe heater element is of the resistance open coil

type. Thermal overheat cut-outs and fusible links are providedto shut off power to heaters in case of airflow failure.

Standard specification

(1) Material

- Sheath Fin Heater : STS304

- Heater Casing : GI 1.6t

- Fin : STS304

- Insulation : Ceramic

(2) Material of heat generation: Electronic registor using Ni, Cr

(3) Heater safety device(Double safety device : Themostat + Thermo. Fuse)

- Thermostat Spec. : 320°C F Close, 50°C F Limit

- Thermo. Fuse : 144°C Cut off

(4) Rated Power : 380V

2.13 HumidifierSteam injection Type

This type of humidifier is fed by steam from a main supplyrather than being generated locally by a self-generative unit.

An effective system which ensures;

- Low operating cost

- Hygienic humidification

- High steam output per metre of lance.

- Very low noise levels.

- Simplified duct and piping requirements.

- Close spacing where multiple lances are needed.

- Low steam ejection velocity for efficient air / steam mixing.

Evaporative Type

Evaporative humidifiers provide very economic humidificationas, unlike steam humidifiers, the water does not need to beheated.

Running costs can be 150 times less than steam systemsrequiring only a single phase power supply. Many operating fea-tures make these humidifiers extremely hygenic and safe touse.

<Electric Heater>

<Steam Injection type>

<Evaporative type>

Page 11: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

1. Design & Component Features

12

2.14 Heat Recovery systemIn order to conserve the energy consumption by exchanging energy between the supply and exhaust airstreams, various types of heat recovery systems can be provided as an integral part of LG AHU unit. Thesedepend upon special installation and other Requirements

Plate Heat Exchanger

Plate heat exchangers are used in order to separate supply airand exhaust air completely. Air flows of different temperaturesare passed by each other by the crossflow principle. The airflows are 100% seperated by a divididing wall out of thin aluminium sheets. This excludes the possibility of impurity,odour and humidity.

Technology & Performance

Low space requirement

Statically ideal distance between plates

Due to double folding high tightness and strength up to 250(mmAq) pressure difference

Rotary Heat Recovery System

The energy recovered is used to precondition (precool/pre-heat) the supply air. Thereby reducing the energy needed tocondition fresh air.

The energy recovery is achieved when the enthalpy/energyrecovery rotor slowly rotates between the counter flowingexhaust and supply air streams absorbing the sensible as wellas the latent energy. Installing this system helps to reducecapital/operating cost of air conditioning equipment in new aswell as existing buildings.

<Plate Heat exchanger>

<Rotary Wheel>

Page 12: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

2. Quick Selection

13

Motor Data

* Due to our policy of innovation some specifications may be changed without notification

Rated Power supply(Voltage / Ph / Hz)

220/3/60 Amp.

380/3/60 Amp.

Nominal Output, kW

1.2 2.2 3.7 5.5 7.5 11 15 19 22 30 37

FLA 6.4 8.6 13.8 21.0 28.2 40.0 53.6 65.6 76.8 104.6 128.6

LRA 38.4 54.0 87.0 132.4 177.6 252.0 337.8 413.0 514.8 658.6 835.9

FLA 3.5 4.7 7.6 11.1 15.2 21.8 29.2 35.8 42.5 58.0 71.1

LRA 27.5 35.3 55.7 73.8 95.3 160.9 220.0 277.9 325.4 393.7 427.6

0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000

BAA-210BAA-180

BAA-155

BAA-140

BAA-125

BAA-110

BAA-100

BAA-85

BAA-70

BAA-55

BAA-45

BAA-35

BAA-25

BAA-15

BAA-8

Min. L/sat 300FPM

Nominal. L/sat 500FPM

Max. L/sat 600FPM

Air Flow Rate [Liter/Sec]

0

3

6

9

Page 13: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

3. Standard Specification

14

Model NameFan Supply Backward Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kWReturn Sirocco Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kW(HP)Coil Cooling Nominal kBtu/h

(6Rows) kWSize Step(H) x L mmFace Area m2

ft2

Face Velocity m/sft/m

Filter Pre AFI 80% + 24" eaMedium NBS 80% 12" ea

Damper R/A H x W mmE/A H x W mmO/A H x W mm

Pipe Water flow rate LPSConnection GPM(US)

Chilled Water In/Outlet ADrain A

Weight Horizontal Net kg(Include RA Fan) lb

Running kglb

BAA-8H BAA-15H BAA-25H RDH 250R RDH 355R RDH 400R

50 125 1671,770 4,410 5,900 830 2,080 2,780 750 1,750 2,500

1,030 2,330 3,330 85 90 90830 880 8801.5 3.7 5.5

ADH 200R ADH 280R ADH 315R50 100 135

1,770 3,530 4,770 830 1,670 2,250 750 1,400 1,920

1,030 1,920 2,330 40 45 45 390 440 4401.5 2.2 3.7 64.1 179 238 18.8 52.5 69.8

14(533)x650 22(838)x1,000 24(914)x1,2000.35 0.84 1.10

4 9 12 2.40 2.50 2.53 472 492 498 1 2 2 0 2 2

330x700 330x1,000 330x1,300330x700 330x1,000 330x1,300330x700 330x1,000 330x1,300

0.9 2.5 3.3 14.2 39.8 52.9 32 50 50 40 40 40 572 767 905

1,261 1,691 1,996 858 1,150 1,350

1,892 2,536 2,977

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6 F (27 C)DB / 66.2 F (19 C) WB

Entering water temperature 44.6 F (7 C) Water temperature rise 9 F (5 C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3. Due to our policy of innovation some specifications may be changed without notification.

Page 14: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

3. Standard Specification

15

Model NameFan Supply Backward Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kWReturn Sirocco Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kW(HP)Coil Cooling Nominal kBtu/h

(6Rows) kWSize Step(H) x L mmFace Area m2

ft2

Face Velocity m/sft/m

Filter Pre AFI 80% + 24" eaMedium NBS 80% 12" ea

Damper R/A H x W mmE/A H x W mmO/A H x W mm

Pipe Water flow rate LPSConnection GPM(US)

Chilled Water In/Outlet ADrain A

Weight Horizontal Net kg(Include RA Fan) lb

Running kglb

BAA-35H BAA-45H RDH 450R RDH 560R

200 3007,060 10,600 3,330 5,000 2,920 4,420 3,920 5,830

90 90880 8805.5 11

ADH 355R ADH 450R160 240

5,650 8,480 2,670 4,000 2,330 3,530 3,130 4,800

45 45 440 4403.7 5.5 290 437 85.0 128

28(1,067)x1,250 30(1,143)x1,7501.33 2.00 14 22

2.50 2.50 492 492 4 6 0 0

330x1,550 330x2,050330x1,550 330x2,050330x1,550 330x2,050

4.1 6.1 64.4 97.0 65 65 40 40

1,010 1,400 2,227 3,087 1,510 2,100 3,330 4,631

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6 F (27 C)DB / 66.2 F (19 C) WB

Entering water temperature 44.6 F (7 C) Water temperature rise 9 F (5 C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3. Due to our policy of innovation some specifications may be changed without notification.

Page 15: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

3. Standard Specification

16

Model NameFan Supply Backward Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kWReturn Sirocco Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kW(HP)Coil Cooling Nominal kBtu/h

(6Rows) kWSize Step(H) x L mmFace Area m2

ft2

Face Velocity m/sft/m

Filter Pre AFI 80% + 24" eaMedium NBS 80% 12" ea

Damper R/A H x W mmE/A H x W mmO/A H x W mm

Pipe Water flow rate LPSConnection GPM(US)

Chilled Water In/Outlet ADrain A

Weight Horizontal Net kg(Include RA Fan) lb

Running kglb

BAA-55H BAA-70H BAA-85H RDH 560R RDH 630R RDH 710R

333 417 50011,760 14,730 17,660 5,550 6,950 8,330 5,000 6,000 7,500 6,330 7,830 9,670

95 95 95930 930 93011 11 15

ADH 450R ADH 560R ADH 560R267 350 400

9,430 12,360 14,130 4,450 5,830 6,670 3,880 5,420 6,000 4,720 6,670 7,170

45 45 45 440 440 4405.5 7.5 7.5 484 611 734 142 179 215

38(1,448)x1,550 38(1,448)x1,900 44(1,676)x2,0002.24 2.75 3.35 24 30 36

2.48 2.52 2.49 488 496 490 6 6 9 3 3 3

480x1,850 480x2,250 480x2,350480x1,850 480x2,250 480x2,350480x1,850 480x2,250 480x2,350

6.8 8.6 10.3 107 136 163 80 80 100 40 40 40

1,430 1,690 1,970 3,153 3,726 4,344 2,140 2,530 2,950 4,719 5,579 6,505

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6 F (27 C)DB / 66.2 F (19 C) WB

Entering water temperature 44.6 F (7 C) Water temperature rise 9 F (5 C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3. Due to our policy of innovation some specifications may be changed without notification.

Page 16: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

3. Standard Specification

17

Model NameFan Supply Backward Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kWReturn Sirocco Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kW(HP)Coil Cooling Nominal kBtu/h

(6Rows) kWSize Step(H) x L mmFace Area m2

ft2

Face Velocity m/sft/m

Filter Pre AFI 80% + 24" eaMedium NBS 80% 12" ea

Damper R/A H x W mmE/A H x W mmO/A H x W mm

Pipe Water flow rate LPSConnection GPM(US)

Chilled Water In/Outlet ADrain A

Weight Horizontal Net kg(Include RA Fan) lb

Running kglb

BAA-100H BAA-110H RDH 710K RDH 800K

583 66720,590 23,560 9,720 11,120 9,000 10,000 10,500 12,500

95 95930 93019 19

ADH 630R ADH 710R483 542

17,060 19,140 8,050 9,030 7,500 8,470 8,750 10,280

45 45 440 44011.0 11.0 854 973 250 285

44(1,676)x2,300 24(914)x2,400x23.86 4.39 42 47

2.52 2.53 496 498 12 12 0 0

630x2,650 630x2,750630x2,650 630x2,750630x2,650 630x2,750

12.0 13.6 190 216 100 80x240 40

2,430 2,740 5,357 6,041 3,670 4,120 8,091 9,083

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6 F (27 C)DB / 66.2 F (19 C) WB

Entering water temperature 44.6 F (7 C) Water temperature rise 9 F (5 C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3. Due to our policy of innovation some specifications may be changed without notification.

Page 17: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

3. Standard Specification

18

Model NameFan Supply Backward Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kWReturn Sirocco Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kW(HP)Coil Cooling Nominal kBtu/h

(6Rows) kWSize Step(H) x L mmFace Area m2

ft2

Face Velocity m/sft/m

Filter Pre AFI 80% + 24" eaMedium NBS 80% 12" ea

Damper R/A H x W mmE/A H x W mmO/A H x W mm

Pipe Water flow rate LPSConnection GPM(US)

Chilled Water In/Outlet ADrain A

Weight Horizontal Net kg(Include RA Fan) lb

Running kglb

BAA-125H BAA-140H BAA-155H RDH 800K RDH 900K RDH 900K

750 833 91726,490 29,420 32,390 12,500 13,880 15,280 11,670 12,500 13,670 13,670 15,500 17,500

95 95 100930 930 98022 22 30

ADH 710R ADH 710R ADH 800K600 667 733

21,190 23,560 25,890 10,000 11,120 12,220 9,450 10,280 11,670 11,120 11,530 13,330

45 45 45 440 440 44011.0 15.0 15.0 1,092 1,231 1,350 320 361 396

24(914)x2,700x2 26(991)x2,800x2 28(1,067)x2,850x24.94 5.55 6.08 53 60 65

2.53 2.50 2.51 498 492 494 12 12 16 3 7 4

630x3,050 630x3,150 630x3,200630x3,050 630x3,150 630x3,200630x3,050 630x3,150 630x3,200

15.3 17.2 18.9 242 273 300 80x2 80x2 80x240 40 40

2,950 3,280 3,570 6,504 7,231 7,870 4,390 4,910 5,350 9,678 10,825 11,795

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6 F (27 C)DB / 66.2 F (19 C) WB

Entering water temperature 44.6 F (7 C) Water temperature rise 9 F (5 C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3. Due to our policy of innovation some specifications may be changed without notification.

Page 18: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

3. Standard Specification

19

Model NameFan Supply Backward Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kWReturn Sirocco Model Name

Air Flow Rate CMMCFMLPS

Range MIN(LPS)MAX(LPS)

Static Press. mmAqPa

Motor kW(HP)Coil Cooling Nominal kBtu/h

(6Rows) kWSize Step(H) x L mmFace Area m2

ft2

Face Velocity m/sft/m

Filter Pre AFI 80% + 24" eaMedium NBS 80% 12" ea

Damper R/A H x W mmE/A H x W mmO/A H x W mm

Pipe Water flow rate LPSConnection GPM(US)

Chilled Water In/Outlet ADrain A

Weight Horizontal Net kg(Include RA Fan) lb

Running kglb

BAA-180H BAA-210H RDH 1000K RDH 1000K

1,083 1,25038,250 44,150 18,050 20,830 16,670 19,170 20,830 23,330

100 100980 98030 37

ADH 900K ADH 900K917 1,000

32,390 35,320 15,280 16,670 14,450 15,550 16,380 17,780

45 45 440 44019.0 19.0 1,588 1,826 465 535

30(1,143)x3,100x2 30(1,143)x3,600x27.09 8.23 76 89

2.55 2.53 502 498 20 24 0 0

780x3,450 780x3,900780x3,450 780x3,900780x3,450 780x3,900

22.2 25.6 352 405

100x2 100x240 40

4,160 4,650 9,171 10,251 6,250 6,950 13,779 15,322

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6 F (27 C)DB / 66.2 F (19 C) WB

Entering water temperature 44.6 F (7 C) Water temperature rise 9 F (5 C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3. Due to our policy of innovation some specifications may be changed without notification.

Page 19: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

4. Dimensions

20

Horizontal, Included RA Fan

MxN MxN

[NOTE]1. Filter : Pre(50t)+Med (300t,Bag)2. Due to our policy of innovation some specifications may be changed without notification

Model

BAA-8HR 1,200 5,050 1,200 1,200 800 1,250 700 1,100 322x322 439 439 330x700 330x700

BAA-15HR 1,300 5,000 1,500 1,150 800 1,250 700 1,100 453x453 650 397 330x1,100 330x1,100

BAA-25HR 1,300 5,050 1,700 1,200 800 1,250 700 1,100 507x507 750 443 330x1,550 330x1,550

BAA-35HR 1,500 5,200 1,700 1,300 800 1,250 700 1,150 569x569 720 411 330x1,550 330x1,550

BAA-45HR 1,550 5,550 2,200 1,400 800 1,250 750 1,350 715x715 850 635 480x2,050 480x2,050

BAA-55HR 1,850 5,550 2,000 1,400 800 1,250 750 1,350 715x715 850 435 480x1,850 480x1,850

BAA-70HR 1,850 5,750 2,400 1,500 800 1,250 750 1,450 800x800 850 750 480x2,250 480x2,250

BAA-85HR 2,100 5,950 2,500 1,700 800 1,250 750 1,450 898x898 900 702 480x2,350 480x2,350

BAA-100HR 2,100 6,200 2,800 1,700 800 1,250 900 1,550 898x898 951 951 630x2,650 630x2,650

BAA-110HR 2,300 6,600 2,900 1,850 900 1,250 900 1,700 1,007x1,007 946 946 630x2,750 630x2,750

BAA-125HR 2,300 6,600 3,200 1,850 900 1,250 900 1,700 1,007x1,007 1,096 1,096 630x3,050 630x3,050

BAA-140HR 2,500 6,800 3,300 2,050 900 1,250 900 1,700 1,130x1,130 1,085 1,085 630x3,150 630x3,150

BAA-155HR 2,700 6,900 3,400 2,050 900 1,250 900 1,800 1,130x1,130 1,135 1,135 630x3,250 630x3,250

BAA-180HR 2,800 7,450 3,600 2,200 900 1,350 1,050 1,950 1,268x1,268 1,166 1,166 780x3,450 780x3,450

BAA-210HR 2,800 7,450 4,100 2,200 900 1,350 1,050 1,950 1,268x1,268 1,416 1,416 780x3,950 780x3,950

Outline Module

A B C D E FxF G(MOTOR) I JxK MxN

SupplyFan

Coil Filter Mixing Return

Fan

H(BASE) L W

S.FanDischarge

Motor Side RA

Damper EA/OADamper

Page 20: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

4. Dimensions

21

Horizontal, Separated RA Fan

MxN

JxK F G IF

[NOTE]1. Filter : Pre(50t)+Med (300t,Bag)2. Due to our policy of innovation some specifications may be changed without notification

Model

BAA-8H 1,200 3,250 1,200 1,200 800 1,250 322x322 439 439 330x700 330x700

BAA-15H 1,300 3,200 1,500 1,150 800 1,250 453x453 650 397 330x1,100 330x1,100

BAA-25H 1,300 3,250 1,700 1,200 800 1,250 507x507 750 443 330x1,550 330x1,550

BAA-35H 1,500 3,350 1,700 1,300 800 1,250 569x569 720 411 330x1,550 330x1,550

BAA-45H 1,550 3,450 2,200 1,400 800 1,250 715x715 850 635 480x2,050 480x2,050

BAA-55H 1,850 3,450 2,000 1,400 800 1,250 715x715 850 435 480x1,850 480x1,850

BAA-70H 1,850 3,550 2,400 1,500 800 1,250 800x800 850 750 480x2,250 480x2,250

BAA-85H 2,100 3,750 2,500 1,700 800 1,250 898x898 900 702 480x2,350 480x2,350

BAA-100H 2,100 3,750 2,800 1,700 800 1,250 898x898 951 951 630x2,650 630x2,650

BAA-110H 2,300 4,000 2,900 1,850 900 1,250 1,007x1,007 946 946 630x2,750 630x2,750

BAA-125H 2,300 4,000 3,200 1,850 900 1,250 1,007x1,007 1,096 1,096 630x3,050 630x3,050

BAA-140H 2,500 4,200 3,300 2,050 900 1,250 1,130x1,130 1,085 1,085 630x3,150 630x3,150

BAA-155H 2,700 4,200 3,400 2,050 900 1,250 1,130x1,130 1,135 1,135 630x3,250 630x3,250

BAA-180H 2,800 4,450 3,600 2,200 900 1,350 1,268x1,268 1,166 1,166 780x3,450 780x3,450

BAA-210H 2,800 4,450 4,100 2,200 900 1,350 1,268x1,268 1,416 1,416 780x3,950 780x3,950

Outline Module

A B C FxF G(MOTOR) I JxK MxN

SupplyFan

Coil Filter

H(BASE) L W

S.FanDischarge

Motor Side RA

Damper OA

Damper

Page 21: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

4. Dimensions

22

Combination, Included RA FanM

xNM

xN

E

D

C B

[NOTE]1. Filter : Pre(50t)+Med (300t,Bag)2. Due to our policy of innovation some specifications may be changed without notification

Model

BAA-8CR 2,350 3,250 1,200 1,200 800 1,250 800 1,100 322x322 439 439 330x700 330x700

BAA-15CR 2,550 3,200 1,500 1,150 800 1,250 800 1,050 453x453 650 397 330x1,100 330x1,100

BAA-25CR 2,550 3,250 1,700 1,200 800 1,250 800 1,100 507x507 750 443 330x1,550 330x1,550

BAA-35CR 2,750 3,350 1,700 1,300 800 1,250 800 1,150 569x569 720 411 330x1,550 330x1,550

BAA-45CR 2,900 3,550 2,200 1,400 800 1,350 800 1,350 715x715 850 635 480x2,050 480x2,050

BAA-55CR 3,200 3,700 2,000 1,400 800 1,500 950 1,350 715x715 850 435 480x1,850 480x1,850

BAA-70CR 3,400 3,900 2,400 1,500 800 1,600 950 1,450 800x800 850 750 480x2,250 480x2,250

BAA-85CR 3,650 4,100 2,500 1,700 800 1,600 950 1,450 898x898 900 702 480x2,350 480x2,350

BAA-100CR 3,800 4,200 2,800 1,700 800 1,700 950 1,550 898x898 951 951 630x2,650 630x2,650

BAA-110CR 4,150 4,500 2,900 1,850 900 1,750 950 1,700 1,007x1,007 946 946 630x2,750 630x2,750

BAA-125CR 4,150 4,500 3,200 1,850 900 1,750 950 1,700 1,007x1,007 1,096 1,096 630x3,050 630x3,050

BAA-140CR 4,350 4,700 3,300 2,050 900 1,750 950 1,700 1,130x1,130 1,085 1,085 630x3,150 630x3,150

BAA-155CR 4,750 4,950 3,400 2,050 900 2,000 1,100 1,800 1,130x1,130 1,135 1,135 630x3,250 630x3,250

BAA-180CR 4,900 5,400 3,600 2,200 900 2,300 1,250 1,950 1,268x1,268 1,166 1,166 780x3,450 780x3,450

BAA-210CR 4,900 5,400 4,100 2,200 900 2,300 1,250 1,950 1,268x1,268 1,416 1,416 780x3,950 780x3,950

Outline Module

A B C D E FxF G(MOTOR) I JxK MxN

SupplyFan

Coil Filter Mixing Return

Fan

H(BASE) L W

S.FanDischarge

Motor Side RA

Damper EA/OADamper

Page 22: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

4. Dimensions

23

Combination, Separated RA Fan

MxN

JxK

B

A

[NOTE]1. Filter : Pre(50t)+Med (300t,Bag)2. Due to our policy of innovation some specifications may be changed without notification

Model

BAA-8C 2,350 2,500 1,200 1,250 1,250 1,250 322x322 439 439 330x700 330x700

BAA-15C 2,550 2,450 1,500 1,200 1,200 1,250 453x453 650 397 330x1,100 330x1,100

BAA-25C 2,550 2,500 1,700 1,250 1,250 1,250 507x507 750 443 330x1,550 330x1,550

BAA-35C 2,750 2,600 1,700 1,350 1,350 1,250 569x569 720 411 330x1,550 330x1,550

BAA-45C 2,900 2,650 2,200 1,400 1,400 1,250 715x715 850 635 480x2,050 480x2,050

BAA-55C 3,200 2,650 2,000 1,400 1,400 1,250 715x715 850 435 480x1,850 480x1,850

BAA-70C 3,400 2,750 2,400 1,500 1,500 1,250 800x800 850 750 480x2,250 480x2,250

BAA-85C 3,650 2,950 2,500 1,700 1,700 1,250 898x898 900 702 480x2,350 480x2,350

BAA-100C 3,800 2,950 2,800 1,700 1,700 1,250 898x898 951 951 630x2,650 630x2,650

BAA-110C 4,150 3,150 2,900 1,900 1,900 1,250 1,007x1,007 946 946 630x2,750 630x2,750

BAA-125C 4,150 3,150 3,200 1,900 1,900 1,250 1,007x1,007 1,096 1,096 630x3,050 630x3,050

BAA-140C 4,350 3,300 3,300 2,050 2,050 1,250 1,130x1,130 1,085 1,085 630x3,150 630x3,150

BAA-155C 4,750 3,300 3,400 2,050 2,050 1,250 1,130x1,130 1,135 1,135 630x3,250 630x3,250

BAA-180C 4,900 3,550 3,600 2,200 2,200 1,350 1,268x1,268 1,166 1,166 780x3,450 780x3,450

BAA-210C 4,900 3,550 4,100 2,200 2,200 1,350 1,268x1,268 1,416 1,416 780x3,950 780x3,950

Outline Module

A B C FxF G(MOTOR) I JxK MxN

SupplyFan

Coil Filter

H(BASE) L W

S.FanDischarge

Motor Side RA

Damper OA

Damper

Page 23: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

4. Dimensions

24

650

Roll Type

400

Cell Type

650

Long Bag Type (25")

320

Short Bag Type (12")

500

Access Door

Note : If you apply for the Roll type filter, you have to follow the below combination. Air Filter combination - Roll type filter + Access door + Medium filter (Cell or Bag)

Air filter

300

Humidifier

150

Eliminator(3-Bend)

Humidifier & Eliminator

450

H/C

600

C/C

1,200

C/C+A/D+H/C

750

C/C +H/C

500

Access Door

1,390

H/C+C/C+A/D+H/C

Coil

* Due to our policy of innovation some specifications may be changed without notification

Humidifier type- Steam injection- Evaporative

Legend

C/C Cooling CoilH/C Heating CoilA/D Access Door

Page 24: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

25

Forward Curved Fan

ADH 200R ADH 250R

ADH 280R ADH 315R

Page 25: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

26

ADH 355R ADH 400R

ADH 450R ADH 560R

Page 26: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

27

ADH 630R ADH 710R

ADH 800K ADH 900K

Page 27: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

28

A

B

C

H M

L

Model A B C H L M

ADH 200R 306 370 256 343 306 420

ADH 250R 381 461 388 419 372 485

ADH 280R 429 518 361 466 421 555

ADH 315R 480 578 404 518 464 600

ADH 355R 544 655 453 578 533 675

ADH 400R 609 736 507 649 587 725

ADH 450R 579 827 569 726 649 815

ADH 560R 839 1,030 715 891 815 1,000

ADH 630R 940 1,157 801 996 901 1,085

ADH 710R 1,050 1,303 898 1,117 998 1,255

ADH 800K 1,181 1,468 1,007 1,255 1,107 1,360

ADH 900K 1,319 1,648 1,130 1,408 1,230 1,520

Dimensions

Page 28: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

29

Backward Curved Fan

RDH 180R RDH 200R

RDH 225R RDH 250R

Page 29: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

30

RDH 315R RDH 355R

RDH 400R RDH 450R

Page 30: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

31

RDH 500R RDH 560R

RDH 630R RDH 710R

Page 31: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

32

RDH 710K RDH 800K

RDH 900K RDH 1000K

Page 32: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

5. Fan Data

33

Dimensions

M

L

H

B

C

A

Model A B C H L M

RDH 250R 381 461 322 419 372 485

RDH 315R 480 578 404 518 464 600

RDH 355R 544 655 453 578 533 675

RDH 400R 609 736 507 649 587 725

RDH 450R 679 827 569 726 649 815

RDH 500R 748 918 638 800 718 885

RDH 560R 893 1,030 715 891 815 1,000

RDH 630R 940 1,157 801 996 901 1,085

RDH 710R 1,050 1,303 898 1,117 998 1,255

RDH 710K 1,050 1,303 898 1,121 998 1,255

RDH 800K 1,181 1,468 1,007 1,255 1,107 1,360

RDH 900K 1,319 1,648 1,130 1,408 1,230 1,520

RDH 1000K 1,451 1,810 1,267 1,541 1,367 1,660

Page 33: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

6. Nominal Capacity

34

Chilled water

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6°F (27°C)DB / 66.2°F (19°C) WB

Entering water temperature 44.6°F (7°C) Water temperature rise 9°F (5°C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3.Due to our policy of innovation some specifications may be changed without notification.

Rows RemarksModel

4 46.5 13.6 31.7 9.2 10.3 0.66 64.1 18.8 42.3 12.4 14.2 0.98 69.5 20.4 44.5 13.1 15.4 14 130 38.1 88.4 25.9 28.8 1.86 179 52.5 116 34.1 39.8 2.58 195 57.1 125 36.5 43.2 2.74 186 54.4 124 36.4 41.2 2.66 238 69.8 157 46.1 52.9 3.38 276 80.9 179 52.6 61.3 3.94 197 57.7 138 40.4 43.7 2.86 290 85.0 189 55.3 64.4 4.18 335 98.2 214 62.8 74.4 4.74 297 87.0 208 60.9 65.9 4.26 437 128 284 83.3 97.0 6.18 505 148 328 96.1 112 7.14 331 96.9 228 66.9 73.4 4.66 484 142 315 92.2 107 6.88 558 163 362 106 124 7.84 488 143 347 102 108 6.86 611 179 416 122 136 8.68 698 204 460 135 155 9.84 587 172 417 122 130 8.26 734 215 499 146 163 10.38 838 246 553 162 186 11.74 602 176 445 131 134 8.46 854 250 572 168 190 128 972 285 632 185 216 13.64 725 213 529 155 161 10.26 973 285 662 194 216 13.68 1,045 306 669 196 232 14.64 816 239 588 172 181 11.46 1,092 320 732 214 242 15.38 1,175 345 752 221 261 16.54 983 288 698 205 218 13.86 1,231 361 837 245 273 17.28 1,409 413 930 273 313 19.74 1,079 316 766 225 239 15.16 1,350 396 918 269 300 18.98 1,541 452 1,017 298 342 21.64 1,269 372 888 260 282 17.86 1,588 465 1,080 317 352 22.28 1,813 531 1,197 351 402 25.44 1,278 374 958 281 284 17.96 1,826 535 1,223 359 405 25.68 2,084 611 1,355 397 463 29.2

BAA-8 50 1,770 830 0.35 4 2.40 472

BAA-15 125 4,410 2,080 0.84 9 2.50 492

BAA-25 167 5,900 2,780 1.1 12 2.53 498

BAA-35 200 7,060 3,330 1.33 14 2.50 492

BAA-45 300 10,600 5,000 2 22 2.50 492

BAA-55 333 11,760 5,550 2.24 24 2.48 488

BAA-70 417 14,730 6,950 2.75 30 2.52 496

BAA-85 500 17,660 8,330 3.35 36 2.49 490

BAA-100 583 20,590 9,720 3.86 42 2.52 496

BAA-110 667 23,560 11,120 4.39 47 2.53 498

BAA-125 750 26,490 12,500 4.94 53 2.53 498

BAA-140 833 29,420 13,880 5.55 60 2.50 492

BAA-155 917 32,390 15,280 6.08 65 2.51 494

BAA-180 1,083 38,250 18,050 7.09 76 2.55 502

BAA-210 1,250 44,150 20,830 8.23 89 2.53 498

Air Flow RateCoil Face

AreaAir Velocity

TotalCapacity

SensibleCapacity

Water flowrate

CMM CFM l/s m2 ft2 m/s ft/m kBtu/h kW kBtu/h kW GPM l/s

Page 34: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

6. Nominal Capacity

35

Hot water

Notes

1. Capacities are based on the following conditions: - Cooling : Entering air temperature 80.6°F (27°C)DB / 66.2°F (19°C) WB

Entering water temperature 44.6°F (7°C) Water temperature rise 9°F (5°C)

2. Coil Spec. : OD 5/8" Copper tube + Al Fin(8 FPI) 3.Due to our policy of innovation some specifications may be changed without notification.

Correction Factor for FPI

Rows RemarksModel

1 27.0 7.9 6 0.42 47.6 14.0 10.6 0.71 70.1 20.5 15.5 12 124 36.3 27.5 1.71 93.8 27.5 20.8 1.32 165 48.4 36.6 2.31 107 31.4 23.8 1.52 206 60.4 45.7 2.91 162 47.5 36 2.32 310 90.9 68.8 4.31 178 52.2 39.5 2.52 346 101 77 4.81 253 74.1 56 3.52 430 126 95 61 304 89.1 68 4.32 516 151 115 7.21 305 89.4 68 4.32 602 176 134 8.41 430 126 95 62 834 244 185 11.71 520 152 115 7.32 938 275 208 13.11 583 171 129 8.22 1,041 305 231 14.61 642 188 143 92 1,146 336 254 161 797 234 177 11.22 1,354 397 301 191 927 272 206 132 1,563 458 347 21.9

BAA-8 50 1,770 830 0.35 4 2.40 472

BAA-15 125 4,410 2,080 0.84 9 2.50 492

BAA-25 167 5,900 2,780 1.1 12 2.53 498

BAA-35 200 7,060 3,330 1.33 14 2.50 492

BAA-45 300 10,600 5,000 2 22 2.50 492

BAA-55 333 11,760 5,550 2.24 24 2.48 488

BAA-70 417 14,730 6,950 2.75 30 2.52 496

BAA-85 500 17,660 8,330 3.35 36 2.49 490

BAA-100 583 20,590 9,720 3.86 42 2.52 496

BAA-110 667 23,560 11,120 4.39 47 2.53 498

BAA-125 750 26,490 12,500 4.94 53 2.53 498

BAA-140 833 29,420 13,880 5.55 60 2.50 492

BAA-155 917 32,390 15,280 6.08 65 2.51 494

BAA-180 1,083 38,250 18,050 7.09 76 2.55 502

BAA-210 1,250 44,150 20,830 8.23 89 2.53 498

Air Flow RateCoil Face

AreaAir Velocity Total Capacity Water flow rate

CMM CFM l/s m2 ft2 m/s ft/m kBtu/h kW GPM l/s

Inch 14 12 10 8 7 6

mm 1.81 2.12 2.54 3.18 3.63 4.23

Correction Factor 1.35 1.25 1.12 1 0.92 0.81

Page 35: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

7. Pressure Drop

36

14

1.9 5

12

1.6 0

10

1.3 5

8

1. 0

6

0.7 2

FPI

Correction factor

Cooling Coil

Correction factor for FPI

Heating Coil

Press. dropmmAq

Press. dropmmAq

Face velocity(m/s) Face velocity(m/s)

Base point

Correction factor for Temp.

Cor

rect

ion

fact

or

In/outlet average air temp.(DB, °C)

* Due to our policy of innovation some specifications may be changed without notification

Page 36: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

7. Pressure Drop

37

Air Filter

Casing

Eliminator

Damper

Face velocity (m/s)

Face velocity (m/s) Air Press. drop(mmAq)

Face

vel

ocity

(m

/s)

Sta

tic P

ress

. dro

p(m

mA

q)S

tatic

Pre

ss. d

rop(

mm

Aq)

Sta

tic P

ress

. dro

p(m

mA

q)

Face velocity (m/s)

* Due to our policy of innovation some specifications may be changed without notification

Page 37: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

8. Installation

38

8.1 Drain trap

Negativestatic

pressure

Negative static pressure + 25mm

Positivestatic

pressure

Positive static pressure

Draw - Thru Unit

• Draw - Thru System

• Blow - Thru System

Blow - Thru Unit

Page 38: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

8. Installation

39

8.2 Foundation

* D : Need to enough space for duct work

* L : On the designated access side of the unit, workingareas must be equal to the width of the unit.

* H : Allowance for coil connections, must be "L" + 200 mm.

When selecting and preparing the unit site, followthese guidelines:

1. Ensure that the site can support the total weight ofthe unit. Unit weight figures only provide total grossweights and do not include the additional weight forwater in any coils.

2. Confirm that the foundation of the mounting platformis large enough to include the unit dimensions plusservice plus service access.

3. The floor or foundation must be level for correct coildrainage and condensate flow.

4. Provide adequate lighting for maintenance person-nel to perform maintenance duties.

5. When the unit is positioned on site, there must besufficient space around the unit to ensure that cor-rect operation and effective maintenance can becarried out.

Page 39: AHU PD 22-07-2010

Air-Cooled ScrewAir Handling Unit

9. Workscope

40

9.1 Chilled water type

9.2 DX type

Contents Customer Vendor Remarks.

1. Transport, Shipping & Discharging, Installation work of AHU. ●

2. Foundation Work of Concrete. ●

3. Electric work of Main power supply. ● Include Motor Wiring

4. Automatic control components installation & Wiring work of AHU. ● BMS or AC Manager

5. Damper Actuator supply & installation/wiring work. ●

6. Supply of Damper & Flange of Supply duct. ●

7. Drain piping installation work of AHU. ● Include U-Trap installation

8. Water piping & Drain piping installation work of Humidifier ●

9. Supply & Installation work of Chiller Outdoor unit. ●

10. Piping work between AHU and Chiller Outdoor unit. ●

11. TAB (Testing, Adjusting and Balancing) ●

Contents Customer Vendor Remarks.

1. Transport, Shipping & Discharging, Installation work of AHU. ●

2. Foundation Work of Concrete. ●

3. Electric work of Main power supply. ● Include Motor Wiring

4. Control panel work (Wiring & Installation) of AHU. ●

5. Automatic control components installation & Wiring work of AHU. ● BMS or AC Manager

6. Damper Actuator supply & installation/wiring work. ●

7. Supply of Damper & Flange of Supply duct. ●

8. Drain piping installation work of AHU. ● Include U-Trap installation

9. Water piping & Drain piping installation work of Humidifier ●

10. Supply & Installation work of EHP Outdoor unit. ●

11. Piping work between AHU and EHP Outdoor unit. ●

12. Test run of DX Type AHU. ● Check Cycle

13. TAB (Testing, Adjusting and Balancing) ●

Page 40: AHU PD 22-07-2010

P/No.: MFL62537706

Air Conditioner20 Yeouido-dong, Yeongdeungpo-gu,Yeouido P.O.Box 335 Seoul, 150-721, Korea.http://www.lgeaircon.com

All rights reservedPrinted in Korea May/2009The specifications, designs, andinformation in this brochure are subject to change without notice.

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.