AHU Coil Selection

8
COOLING COIL SELECTION AHU Load Load D air ADP CFA sft BF in Rows Near actual Act ACT Chart Chart Act Temp gpm gpm no. TR btuh cfm deg F 400 fpm load Std AH cfa 5/8 CFV Q Q gpm gpm rise F per x sft fpm ewt TR temp 45 F rise 1 28.26 339120 11337 53 28.3 0.12 6 say 9 22.6 502 42.4 21.2 28 56 12.11 1.98 678.2 2 5.78 69360 2201 53.37 5.5 0.06 6 3 6.1 361 8.3 16.57 18 9.0 15.41 1.56 138.7 3 3.91 46920 1184 53.1 3.0 0.06 6 2 3.7 320 5.8 17.38 18 6.0 15.64 1.53 93.8 4 5.74 68880 1944 53.5 4.9 0.06 6 2 3.7 525 8.1 24.31 32 10.7 12.92 1.86 137.8 5 5.01 60120 2021 53.1 5.1 0.06 6 3 6.1 331 7.4 14.84 17 8.5 14.15 1.70 120.2 6 7.56 90720 2591 53 6.5 0.06 6 3 6.1 425 11.3 22.68 28 14.0 12.96 1.85 181.4 7 8.58 102960 4121 53 10.3 0.06 6 6 11.19 368 12.9 12.9 16 16.0 12.87 1.86 205.9 8 5.93 71160 2544 53 6.4 0.06 6 3 6.1 417 8.9 17.79 21 10.5 13.55 1.77 142.3 9 5.53 66360 1816 53.5 4.5 0.06 6 2 3.7 491 7.8 23.42 30 10.0 13.27 1.81 132.7 10 6.47 77640 1892 53.4 4.7 0.12 6 say 2 3.7 511 9.2 27.73 34 11.3 13.70 1.75 155.3 11 10.05 120600 3239 53 8.1 0.06 6 5 8.25 393 15.1 15.1 20 20.0 12.06 1.99 241.2 12 10.05 120600 3239 53 8.1 0.06 6 5 8.25 393 15.1 15.1 20 20.0 12.06 1.99 241.2 13 2.62 31440 1441 53 3.6 0.12 4 2 3.7 389 3.9 11.79 18 6.0 10.48 2.29 62.9 14 21.69 260280 7157 54.3 17.9 0.06 6 7 17.5 409 28.0 14 18 36.0 14.46 1.66 520.6 AHUs 127 46727 234.0 ### Acs 10.2 13.044 average temp rise 13.044 total 137

description

AHU Coil Selection

Transcript of AHU Coil Selection

Page 1: AHU Coil Selection

COOLING COIL SELECTION

AHU Load Load D air ADP CFA sft BF in Rows Near actual Act ACT Chart Chart Act Temp gpm gpmno. TR btuh cfm deg F 400 fpm load Std AH cfa 5/8 CFV Q Q gpm gpm rise F per x

sft fpm ewt TR temp45 F rise

1 28.26 339120 11337 53 28.3 0.12 6 say 9 22.6 502 42.4 21.2 28 56 12.11 1.98 678.22 5.78 69360 2201 53.37 5.5 0.06 6 3 6.1 361 8.3 16.57 18 9.0 15.41 1.56 138.73 3.91 46920 1184 53.1 3.0 0.06 6 2 3.7 320 5.8 17.38 18 6.0 15.64 1.53 93.84 5.74 68880 1944 53.5 4.9 0.06 6 2 3.7 525 8.1 24.31 32 10.7 12.92 1.86 137.85 5.01 60120 2021 53.1 5.1 0.06 6 3 6.1 331 7.4 14.84 17 8.5 14.15 1.70 120.26 7.56 90720 2591 53 6.5 0.06 6 3 6.1 425 11.3 22.68 28 14.0 12.96 1.85 181.47 8.58 102960 4121 53 10.3 0.06 6 6 11.19 368 12.9 12.9 16 16.0 12.87 1.86 205.98 5.93 71160 2544 53 6.4 0.06 6 3 6.1 417 8.9 17.79 21 10.5 13.55 1.77 142.39 5.53 66360 1816 53.5 4.5 0.06 6 2 3.7 491 7.8 23.42 30 10.0 13.27 1.81 132.7

10 6.47 77640 1892 53.4 4.7 0.12 6 say 2 3.7 511 9.2 27.73 34 11.3 13.70 1.75 155.311 10.05 120600 3239 53 8.1 0.06 6 5 8.25 393 15.1 15.1 20 20.0 12.06 1.99 241.212 10.05 120600 3239 53 8.1 0.06 6 5 8.25 393 15.1 15.1 20 20.0 12.06 1.99 241.213 2.62 31440 1441 53 3.6 0.12 4 2 3.7 389 3.9 11.79 18 6.0 10.48 2.29 62.914 21.69 260280 7157 54.3 17.9 0.06 6 7 17.5 409 28.0 14 18 36.0 14.46 1.66 520.6

AHUs 127 46727 234.0 ###

Acs 10.2 13.044 average temp rise 13.044

total 137

Page 2: AHU Coil Selection

TOTAL LOAD SUMMARY AHU wise for Monsoon with reheaters & Summer FOR MACLOEDS PHARMA load summer summer SUM summer summer

S.n AHU RM Room name MON Mon MON Load Load D airno. no. heaters gth TR TR RSH RLH btuh cfm

1 1 34 Secondary room 6750 48695 4.06 3.75 14624 1543 45000 7132 1 33 Accessories - 2 3600 13113 1.09 1.01 6897 659 12120 3474 1 31 Spare room 7400 24596 2.05 1.96 15991 773 23520 8466 1 38 Corridor - 2 61000 222977 18.58 17.6 129074 4853 211200 77167 1 35 IPQC office - 1 7200 22948 1.91 1.82 14884 746 21840 7879 1 6 CF room(staircase) 8800 26666 2.22 2.12 17206 808 25440 928

AHU1 94750 29.92 28.26 198676 9382 339120 11337

3 2 32 Quarantine - 2 5200 20302 1.69 1.61 11702 597 19320 5798 2 36 Quarantine - 1 6800 21588 1.80 1.72 13766 579 20640 695

16 2 29 FG - Quarantine 8700 30697 2.56 2.45 18342 676 29400 927AHU2 20700 6.05 5.78 43810 1852 69360 2201

5 3 30 Packing hall 9600 49550 4.13 3.91 23920 1161 46920 118413 4 2 Blender & Shifter - 1 10000 72658 6.05 5.74 38491 1544 68880 194415 5 3 Tray drier - VTD 11000 62636 5.22 5.01 40836 1288 60120 202110 6 5 CF - 4 15500 95345 7.95 7.56 52600 1721 90720 259111 7 4 FBD - 2 13000 105105 8.76 8.58 83671 1288 102960 412112 8 7 CF - 3 13500 73811 6.15 5.93 51660 1291 71160 254414 9 1 Blender & Shifter - 2 10000 70108 5.84 5.53 35941 1544 66360 18161 10 3 Corridcor - 4 21000 88381 7.37 6.47 35249 2448 77640 18922 11 4 Crystalizer - 1 17000 127680 10.64 10.05 65767 1686 120600 32393 12 2 Crystalizer - 2 17000 127680 10.64 10.05 65767 1686 120600 3239

72.75 68.83

13 1 AC room 5500 12524 1.04 1.01 10816 266 12120 56913 7 BSR 7500 19361 1.61 1.61 16575 542 19320 872

AHU13 13000 2.66 2.62 27391 808 31440 1441

14 21 Media preprn/auto 6000 30607 2.55 2.43 12746 800 29160 64114 20 Incubator 7500 40660 3.39 3.07 13244 756 36840 66614 19 LAF 7000 60223 5.02 4.58 18300 1057 54960 90614 24 Air lock - 1 3000 9995 0.83 0.79 6446 554 9480 33914 25 Air lock - 2 6000 18738 1.56 1.49 12311 475 17880 66414 23 Sample collection 6000 24783 2.07 1.91 13078 652 22920 732

14 AL - 1,2,3,RAL 8500 45142 3.76 3.36 15920 1990 40320 790

14 1 Retain sample 2500 23027 1.9189 1.77 14313 552 21240 77014 4 Instrument room 8300 27904 2.3253 2.29 22723 1868 27480 1192

AHU14 54800 281079 23.42 21.69 129081 8704 260280 6700

Total heaters equals 320850 btuh 94.3676 KW

15,16,17,18

Page 3: AHU Coil Selection

summer summerFA Adpcfm deg F

498 52.883 52.1125 53.1

1331 53.4115 53.1138 53.5

2290 53.00

122 53.1109 53.5179 53.5410 53.37

376 53.1498 53.5311 53.1627 53311 53313 53498 53.5736 53.4916 53916 53

18 5341 5359 53

270 53.4537 53.4614 53.145 5395 53.5148 53.4

412 51.8

135 58.753 58.5

2309 54.3

Page 4: AHU Coil Selection

TOTAL HEAT LOAD SUMMARYAHU wise Summer FOR MACLOEDS PHARMA

S.n AHU Room Room name Load Load D air FA Adpno. no. TR RSH RLH btuh cfm cfm deg F

1 1 34 Secondary room 3.75 14624 1543 45000 713 498 52.82 1 33 Accessories - 2 1.01 6897 659 12120 347 83 52.14 1 31 Spare room 1.96 15991 773 23520 846 125 53.16 1 38 Corridor - 2 17.6 129074 4853 211200 7716 1331 53.47 1 35 IPQC office - 1 1.82 14884 746 21840 787 115 53.19 1 6 CF room(staircase) 2.12 17206 808 25440 928 138 53.5

AHU1 28.26 198676 9382 339120 11337 2290 53.00

3 2 32 Quarantine - 2 1.61 11702 597 19320 579 122 53.18 2 36 Quarantine - 1 1.72 13766 579 20640 695 109 53.5

16 2 29 FG - Quarantine 2.45 18342 676 29400 927 179 53.5AHU2 5.78 43810 1852 69360 2201 410 53.37

5 3 30 Packing hall 3.91 23920 1161 46920 1184 376 53.113 4 2 Blender & Shifter - 1 5.74 38491 1544 68880 1944 498 53.515 5 3 Tray drier - VTD 5.01 40836 1288 60120 2021 311 53.110 6 5 CF - 4 7.56 52600 1721 90720 2591 627 5311 7 4 FBD - 2 8.58 83671 1288 102960 4121 311 5312 8 7 CF - 3 5.93 51660 1291 71160 2544 313 5314 9 1 Blender & Shifter - 2 5.53 35941 1544 66360 1816 498 53.51 10 3 Corridcor - 4 6.47 35249 2448 77640 1892 736 53.42 11 4 Crystalizer - 1 10.05 65767 1686 120600 3239 916 533 12 2 Crystalizer - 2 10.05 65767 1686 120600 3239 916 53

13 1 AC room 1.01 10816 266 12120 569 18 5313 7 BSR 1.61 16575 542 19320 872 41 53

AHU13 2.62 27391 808 31440 1441 59 53

14 21 Media preprn/auto 2.43 12746 800 29160 641 270 53.414 20 Incubator 3.07 13244 756 36840 666 537 53.414 19 LAF 4.58 18300 1057 54960 906 614 53.114 24 Air lock - 1 0.79 6446 554 9480 339 45 5314 25 Air lock - 2 1.49 12311 475 17880 664 95 53.514 23 Sample collection 1.91 13078 652 22920 732 148 53.4

14 AL - 1,2,3,RAL 3.36 15920 1990 40320 790 412 51.8

14 1 Retain sample 1.77 14313 552 21240 770 135 58.714 4 Instrument room 2.29 22723 1868 27480 1649 53 58.5

AHU14 21.69 129081 8704 260280 7157 2309 54.3

15,16,17,18

Page 5: AHU Coil Selection

TOTAL HEAT LOAD room & floor wise for SUMMER FOR MACLOEDS PHARMA DT. 19/8/2005 - vasanth

S.n AHU Room Room name Load Load D air FA no. no. TR RSH RLH btuh cfm cfm

GTHA PB - GR. FLOOR1 1 34 Secondary room 3.75 14624 1543 45000 713 4982 1 33 Accessories - 2 1.01 6897 659 12120 347 833 2 32 Quarantine - 2 1.61 11702 597 19320 579 1224 1 31 Spare room 1.96 15991 773 23520 846 1255 3 30 Packing hall 3.91 23920 1161 46920 1184 3766 1 38 Corridor - 2 17.6 129074 4853 211200 7716 13317 1 35 IPQC office - 1 1.82 14884 746 21840 787 1158 2 36 Quarantine - 1 1.72 13766 579 20640 695 1099 1 6 CF room(staircase) 2.12 17206 808 25440 928 138

10 6 5 CF - 4 7.56 52600 1721 90720 2591 62711 7 4 FBD - 2 8.58 83671 1288 102960 4121 31112 8 7 CF - 3 5.93 51660 1291 71160 2544 31313 4 2 Blender & Shifter - 1 5.74 38491 1544 68880 1944 49814 9 1 Blender & Shifter - 2 5.53 35941 1544 66360 1816 49815 5 3 Tray drier - VTD 5.01 40836 1288 60120 2021 31116 2 29 FG - Quarantine 2.45 18342 676 29400 927 179

B PB - First FLOOR1 10 3 Corridcor - 4 6.47 35249 2448 77640 1892 7362 11 4 Crystalizer - 1 10.05 65767 1686 120600 3239 9163 12 2 Crystalizer - 2 10.05 65767 1686 120600 3239 916

C PB - Second Floor

D Stores blk - G floor13 1 AC room 1.01 10816 266 12120 569 1813 7 BSR 1.61 16575 542 19320 872 41

E Stores Blk - First floor14 21 Media preprn/auto 2.43 12746 800 29160 641 27014 20 Incubator 3.07 13244 756 36840 666 53714 19 LAF 4.58 18300 1057 54960 906 61414 24 Air lock - 1 0.79 6446 554 9480 339 4514 25 Air lock - 2 1.49 12311 475 17880 664 9514 23 Sample collection 1.91 13078 652 22920 732 148

14 AL - 1,2,3,RAL 3.36 15920 1990 40320 790 41214 1 Retain sample 1.77 14313 552 21240 770 135

AC3 3 PM Testing 1.51 12674 508 18120 697 11314 4 Instrument room 2.29 22723 1868 27480 1649 53

AC2 9 QA office 2.11 22160 1354 25320 1247 45AC1 10 QC office 2.11 22160 1354 25320 1247 45AC4 13 Library 1.17 11537 1333 14040 644 30AC5 14 Meeting room 2.6 25817 2258 31200 1468 77split 16 Office 0.7 6692 888 8400 371 20

137.38 993900 44098 52401 10900LESS for rooms with individual Acs -10.2

15,16,17,18

Page 6: AHU Coil Selection

NET total load of AHUs 127.18

Page 7: AHU Coil Selection

TOTAL HEAT LOAD room & floor wise for SUMMER FOR MACLOEDS PHARMA DT. 19/8/2005 - vasanth

Adpdeg F

52.852.153.153.153.153.453.153.553.5535353

53.553.553.153.5

53.45353

5353

53.453.453.153

53.553.4

51.858.759.158.558.358.3

58.1658.558