AECT480 Lecture 7
-
Upload
reazcuet994468 -
Category
Documents
-
view
7 -
download
0
description
Transcript of AECT480 Lecture 7
Lecture 7 – Page 1 of 13
Lecture 7 – Two-Way Slabs Two-way slabs have tension reinforcing spanning in BOTH directions, and may take the general form of one of the following:
Types of Two-Way Slab Systems
Lecture 7 – Page 2 of 13
The following Table may be used to determine minimum thickness of various two-way slabs based on deflection:
Minimum Suggested Thickness “h” for Two-Way Slabs Two-Way Slab System: Minimum Thickness h:
Flat plate Ln/30 Flat plate with spandrel beams Ln/33 Flat slab Ln/33 Flat slab with spandrel beams Ln/36 Two-way beam-supported slab Ln/33
Ln = clear distance in long direction Flat Plates
Flat plates are the most common type of two-way slab system. It is commonly used in multi-story construction such as hotels, hospitals, offices and apartment buildings. It has several advantages:
• Easy formwork • Simple bar placement • Low floor-to-floor heights
Direct Design Method of Flat Plates per ACI 318-02
Two-way slabs are inherently difficult to analyze by conventional methods of statics because of the two-way bending occurring. Accurately determining the moments on a two-way slab is typically accomplished by finite element computer analysis.
Computer analysis of two-way slab
Lecture 7 – Page 3 of 13
The ACI 318 code allows a direct design method that can be used in most typical situations. However, the following limitations apply:
1. Must have 3 or more continuous spans in each direction. 2. Slab panels must be rectangular with a ratio of the longer span to
shorter span(measured as centerline-to-centerline of support) not greater than 2.0.
3. Successive span lengths in each direction must not differ by more than 1/3 of the longer span.
4. Columns must not be offset by more than 10% of the span (in direction of offset) from either axis between centerlines of successive columns.
5. Loads must be uniformly distributed, with the unfactored live load not more than 2 times the unfactored dead load (L/D < 2.0).
Design Strips
a) If L1 > L2:
Mid
dle
Stri
p
L1
L2/4
Mid
dle
Stri
p
L2 L2
L2/4
Inte
rior C
olum
n S
trip
Ext
erio
r Col
umn
Stri
p
Inte
rior C
olum
n S
trip
L2/4
Column (typ.)
Lecture 7 – Page 4 of 13
b) If L2 > L1: Design Moment Coefficients for Flat Plate Supported Directly by Columns
End Span Interior Span 1 2 3 4 5
Slab Moments
Exterior Negative
Positive First Interior
Negative
Positive Interior Negative
Total Moment
0.26Mo 0.52Mo 0.70Mo 0.35Mo 0.65Mo
Column Strip
0.26Mo 0.31Mo 0.53Mo 0.21Mo 0.49Mo
Middle Strip
0 0.21Mo 0.17Mo 0.14Mo 0.16Mo
Mo = Total factored moment per span
Mo = 8
22 nu LLw where Ln = clear span (face-to-face of cols.) in the direction of analysis
1
Mid
dle
Stri
p L1
L1/4
Mid
dle
Stri
p
L2 L2
L1/4
Inte
rior C
olum
n S
trip
Ext
erio
r Col
umn
Stri
p
Inte
rior C
olum
n S
trip
L1/4
2 3 4 5
End Span Interior Span
Lecture 7 – Page 5 of 13
Bar Placement per ACI 318-02
The actual quantity of bars required is determined by analysis (see Example below). However, usage of the Direct Design Method prescribes bar placement as shown below:
Lecture 7 – Page 6 of 13
Example 1 GIVEN: A two-way flat plate for an office building is shown below. Use the following:
• Column dimensions = 20” x 20” • Superimposed service floor Dead load = 32 PSF (not including slab weight) • Superimposed service floor Live load = 75 PSF • Concrete f’c = 4000 PSI • #4 Grade 60 main tension bars • Concrete cover = ¾”
REQUIRED: Use the “Direct Design Method” to design the two-way slab for the design strip in the direction shown.
L2 = 16’-0” L2 = 16’-0”
Col. strip
Ln
Design Strip = 16’
L2 = 16’-0”
20’-0”
20’-0”
20’-0”
L2/4 L2/4 ½ Middle strip = ½(16’ – Col. strip) ½ Middle strip
= ½(16’ – Col. strip)
Lecture 7 – Page 7 of 13
Step 1 – Determine slab thickness h:
Since it is a flat plate, from Table above, use h = 30
nL
where Ln = clear span in direction of analysis = (20’-0” x 12”/ft) – 20” = 220” = 18.33’
h = 30
"220
= 7.333” Use 8” thick slab
Step 2 – Determine factored uniform load, wu on the slab:
wu = 1.2D + 1.6L = 1.2[(32 PSF) + (8/12)(150 PCF)] + 1.6[(75 PSF)] = 278.4 PSF = 0.28 KSF
Step 3 – Check applicability of “Direct Design Method”:
1) Must have 3 or more continuous spans in each direction. YES 2) Slab panels must be rectangular with a ratio of the longer span to
shorter span(measured as centerline-to-centerline of support) not greater than 2.0. YES
3) Successive span lengths in each direction must not differ by more than
1/3 of the longer span. YES
4) Columns must not be offset by more than 10% of the span (in direction of offset) from either axis between centerlines of successive columns. YES
5) Loads must be uniformly distributed, with the unfactored live load not
more than 2 times the unfactored dead load (L/D < 2.0). YES
Column size
Slab weight
Lecture 7 – Page 8 of 13
Step 4 – Determine total factored moment per span, Mo:
Mo = 8
22 nu LLw
= 8
)'33.18)('16)(28.0( 2KSF
Mo = 188 KIP-FT
Step 5 – Determine distribution of total factored moment into col. & middle strips:
Design Moment Coefficients for Flat Plate Supported Directly by Columns
End Span Interior Span 1 2 3 4 5
Slab Moments
Exterior Negative
Positive First Interior
Negative
Positive Interior Negative
Total Moment
0.26Mo = 48.9 0.52Mo = 97.8 0.70Mo = 131.6 0.35Mo = 65.8 0.65Mo = 122.2
Column Strip
0.26Mo = 48.9 0.31Mo = 58.3 0.53Mo = 99.6 0.21Mo = 39.5 0.49Mo = 92.1
Middle Strip
0 0.21Mo = 39.5 0.17Mo = 32.0 0.14Mo = 26.3 0.16Mo = 30.1
Mo = Total factored moment per span = 188 KIP-FT
Step 6 – Determine tension steel bars for col. & middle strips:
a) Column strip for region 1 :
Factored NEGATIVE moment = 48.9 KIP-FT (see Table above) = 586.8 KIP-IN = 586,800 LB-IN
b = 96”
d 8”
d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7”
Lecture 7 – Page 9 of 13
22 )"7)("96)(9.0(800,586 INLB
bdM u −
=φ
= 138.6 PSI From Lecture 4 → Table 2:
Use ρmin = 0.0033
ρ = bdAs
Solve for As:
As = ρbd = (0.0033)(96”)(7”) = 2.22 in2
Number of bars required = barperA
A
s
s
__
= barperin
in_4_#_20.0
22.22
2
= 11.1 → Use 12 - #4 TOP bars
Lecture 7 – Page 10 of 13
b) Column strip for region 2 :
Factored POSITIVE moment = 58.3 KIP-FT (see Table above) = 699,600 LB-IN
22 )"7)("96)(9.0(600,699 INLB
bdM u −
=φ
= 165.2 PSI From Lecture 4 → Table 2:
Use ρ = 0.0033
As = 2.22 in2 (see calcs. above) Use 12 - #4 BOTTOM bars
d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7”
b = 96”
d 8”
Lecture 7 – Page 11 of 13
c) Middle strip for region 2 :
Factored POSITIVE moment = 39.5 KIP-FT (see Table above) = 474,000 LB-IN
22 )"7)("96)(9.0(000,474 INLB
bdM u −
=φ
= 112.0 PSI From Lecture 4 → Table 2:
Use ρ = 0.0033
As = 2.22 in2 (see calcs. above) Use 12 - #4 BOTTOM bars Use 6 - #4 Bottom bars at each ½ Middle Strip
b = 96”
d 8”
d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7”
Lecture 7 – Page 12 of 13
Step 7 – Draw “Summary Sketch” plan view of bars:
4’-0”
Col. strip for region 2 12 - #4 BOTTOM bars
16’-0” 16’-0”
Col. strip
16’ – 0”
16’-0”
20’-0”
20’-0”
20’-0”
4’-0”
½ Middle strip = 4’-0” ½ Middle strip = 4’-0”
Col. strip for region 1 12 - #4 TOP bars
½ Middle strip for region 2 6 - #4 BOTTOM bars
8” Thick concrete slab
Lecture 7 – Page 13 of 13
Example 2 GIVEN: The two-way slab system from Example 1. REQUIRED: Design the steel tension bars for design strip shown (perpendicular to those in Example 1).
Solution → Similar to the procedure shown in Example 1, except:
• Re-check slab thickness to verify that 8” is still acceptable • Re-calculate “M0” • Using new value of M0, determine “Design Moment Coefficients” • Design tension steel based on these moment coefficients
20’-0”
½ Middle strip = 6’-0”
½ Middle strip = 6’-0”
Col. strip = 8’-0”
16’-0” 16’-0” 16’-0”
20’-0”
20’-0”
20’-0”