8/12/2019 Advantage of Sluice Gates as Per IS13349 Over Sluice Gates as Per IS3042
1/6
Advantage ofSluice Gates as per IS:13349over
Sluice Gate as per IS:3042
-
8/12/2019 Advantage of Sluice Gates as Per IS13349 Over Sluice Gates as Per IS3042
2/6
Opening in Wall
Wall
Spigot on back side of Gate
Frame to be permanentlyembedded in the wall
Sluice Gate IS:3042Sluice Gate as per IS CodeIS:3042 have Spigot on the
back side of frame, which ispermanently embedded in thewall
Sluice Gate IS:13349Sluice Gate as per IS CodeIS:13349 has flat surface on
the back side of frame, and donot have any extended part tobe embedded in the wall.
Hence civil work & time oferection is reducedconsiderably.
Flat Surface on the back sideof Gate Frame directly fitted onthe wall by Anchor fasteners.
Opening inWall
Wall
Mounting
-
8/12/2019 Advantage of Sluice Gates as Per IS13349 Over Sluice Gates as Per IS3042
3/6
Sluice Gate IS:3042 Sluice Gate IS:13349
View showing gate assembly mounteddirectly on the face of wall with gasket& secondary grout in between.
Wall
View showing gate assembly withembedded spigot inside the wallwith secondary grout in between.
Mounting
-
8/12/2019 Advantage of Sluice Gates as Per IS13349 Over Sluice Gates as Per IS3042
4/6
Sluice Gate IS:3042 Sluice Gate IS:13349
Opening inWall
Wall
Application
IS: 13349 Standard, Page 1, Point 1.1.1These Sluice Gates are designed for either seatinghead or unseating head or both
IS: 3042 Standard, Page 4, Point 1.5This standard does not cover the types ofsluice gates where the operating forces tendto push the door away from the frame.
Seating Water HeadWhen the water pressure
tends to press the door /shutter on to the gate frame
then the type of water head
is called seating /
on-seating water head.
Unseating Water HeadWhen the water pressure tendsto push the door/shutter away
i.e. unseat from the gate framethen the type of water head iscalled unseating /off-seatingwater head.
Seating + Unseating Water Head
-
8/12/2019 Advantage of Sluice Gates as Per IS13349 Over Sluice Gates as Per IS3042
5/6
Sluice Gate IS:3042 Sluice Gate IS:13349
Opening inWall
Wall
IS: 13349 Standard, Page 6
Testing
Point 11: Shop Testing
11.1 All Sluice gates shall be subjected to thetests specified in 11.2, 11.3, 11.4, and 11.5for their conformity to the specified
requirements.
11.2 Seat Clearance Check: By 0.10 mmthick feeler gauge.
11.3 Smooth Movement Test
11.4 Shop Leakage Test by applyingUnseating Hydraulic Pressure
11.5 Hydrostatic Test to confirm bodysoundness by applying water pressure of1.5 times the unbalanced specified maximumoperating head on closed gate for a period of5 minutes.
IS: 3042 Standard, Page 10Point 8: Testing
8.1 After completion each sluice gate shall betested in the shop for smooth working of thecomponent parts including the operatinggear.
Comments: IS:3042 insist on only smoothworking of sluice gate and silent aboutleakage testing & body soundness.
In general IS:3042 gates are tested atatmospheric pressure for leakages only byborrowing leakage test parameter fromIS:13349 standard.
Due to spigot construction on the back side,IS:3042 gates can not fit on the test
bench and hence can not be tested forleakage at operating head as well as for bodysoundness.
-
8/12/2019 Advantage of Sluice Gates as Per IS13349 Over Sluice Gates as Per IS3042
6/6
When comparing IS:13349 Sluice Gates with IS:3042 Sluice Gates, we can seethat technically IS:13349 Gates are superior and they are designed for Seatingas well as unseating water head.
We can test the IS:13349 Sluice gates to confirm their suitability for designparameter, which can not be tested in case of IS:3042 gates.
Once the gate will be installed on site, nothing can bedone, even in case ofheavy leakage. The IS:3042 Gates can not be removed without damaging civilwork considerably.
The IS:13349 gates not only can be tested before installation itself to verify thesuitability in advance. These gates can be fitted as well as can be removed easilyby minimum damage i.e. by removing secondary grouting only.
As for as price are concerned, if we compare IS:3042 gate, which is wallmounted with the Wall mounted IS:13349 gate i.e. without wall thimble, it is a
proven fact that the IS:13349 gates are more cost effective, even in case ofinitial cost.
Wall
Conclusion