ADVANCED RTU FOR SMART WATER NETWORK ... 60870-5-101/104 COMMUNICATION MODE: REAL-TIME / BATCH /...

2
THE CONTROL TECHNOLOGY GROUP ADVANCED RTU FOR SMART WATER NETWORK MANAGEMENT AQUALOG Master is the most complete RTU dedicated to the water systems managing of crucial importance such as pumping stations, pressures control, levels control and flows coordination in the water network and water treatment. Its advanced features make it essential to manage the water network smartly, by implementing solutions that help to save water and to reduce operating costs. Automation of water systems thanks to LADDER LOGIC LANGUAGE installed on board Low power: at least 3 years autonomy or 7 years with NarrowBand- IOT It can be integrated in any public or private network thanks to the wide range of local and remote communications Equipped with a powerful WEB Server which makes it accessible from remote Real-Time pressure adjustment on the basis of values at critical point Capture of “Water Hammer” events thanks to high speed virtual logger It allows the fast evaluation of critical situations (LCD TS 7” colour display optional) IOT Cloud operation via LPWAN radio modem suited for NarrowBand-IOT or LoRa-IOT IOT READY

Transcript of ADVANCED RTU FOR SMART WATER NETWORK ... 60870-5-101/104 COMMUNICATION MODE: REAL-TIME / BATCH /...

Page 1: ADVANCED RTU FOR SMART WATER NETWORK ... 60870-5-101/104 COMMUNICATION MODE: REAL-TIME / BATCH / FILE TRANSFER / FTP NarrowBand-IOT RADIO MODEM INTEGRATED or 1 LoRa-IOT RADIO MODEM

THE CONTROL TECHNOLOGY GROUP

ADVANCED RTU FOR SMART WATER NETWORK MANAGEMENT AQUALOG Master is the most complete RTU dedicated to the water systems managing of crucial importance such as pumping stations, pressures control, levels control and flows coordination in the water network and water treatment. Its advanced features make it essential to manage the water network smartly, by implementing solutions that help to save water and to reduce operating costs.

Automation of water systems thanks to LADDER LOGIC LANGUAGE installed on board

Low power: at least 3 years autonomy or 7 years with NarrowBand-IOT

It can be integrated in any public or private network thanks to the wide range of local and remote communications

Equipped with a powerful WEB Server which makes it accessible from remote

Real-Time pressure adjustment on the basis of values at critical point Capture of “Water Hammer” events thanks to high speed virtual

logger It allows the fast evaluation of critical situations (LCD TS 7”

colour display optional) IOT Cloud operation via LPWAN radio modem suited for

NarrowBand-IOT or LoRa-IOT

IOT READY

Page 2: ADVANCED RTU FOR SMART WATER NETWORK ... 60870-5-101/104 COMMUNICATION MODE: REAL-TIME / BATCH / FILE TRANSFER / FTP NarrowBand-IOT RADIO MODEM INTEGRATED or 1 LoRa-IOT RADIO MODEM

SUPERVISION REAL-TIME: up to 5000 variables

DATA ACQUISITION

Base Time Acquisition: 1" Base Time Storage: 1’ – 1 h Max. Acquisition Variables Num.: 1000 Stored Samples Max Num.: 6000000 Sample processing: instantaneous, min, max, medium

HIGH SPEED DATA ACQUISITION (indispensable for WATER HAMMER investigations)

High speed acquisition SOFTWARE module for sampling up to 20 msec for a 30 sec / 5 min deepness. It is activated by trigger and produces a CSV format file (optional)

COUNTERS Max Nr. 8 - Range: 32 bit Conversion into engineering units Associable to the time derivative for calculation of flow

AUTOMATION PLC EMBEDDED with LADDER LOGIC STANDARD IEC 61131-3

LOCAL COMMUNICATION: Protocols RS232 / 485 port: MODBUS RTU, DLMS, OMRON FINS, IEC 62056-21, IEC 60870-5-101/104 ETHERNET: TCP/IP, MODBUS TCP, SNMP CANBUS: CAN, CAN OPEN

REMOTE COMMUNICATION TRANSMISSION MEAN: GSM / GPRS / SMS / ADSL / PPSTN / UMTS / WI-FI / F.O. for wired networks / VPN / RADIO MODEM

PROTOCOLS and STANDARDS FOR REMOTE COMMUNICATION

MODBUS RTU / SNMP / MODBUS TCP/IP / DLMS / IEC 62056-21 / IEC 60870-5-101/104 COMMUNICATION MODE: REAL-TIME / BATCH / FILE TRANSFER / FTP 1 NarrowBand-IOT RADIO MODEM INTEGRATED or

1 LoRa-IOT RADIO MODEM INTEGRATED

MESSAGES SMS / E-MAIL

WEB FACILITIES WEB portal with view of: REAL-TIME, ALARMS, TRENDS

ALARMS Signalling and managing of alarms and events generated by threshold overcoming / reaching of both physical and logical states. Messages service for the alarms notification.

OPC COMPLIANT (by OPC SERVER) CONFIGURATION FROM PC USING RAINBOW CONFIGURATOR INTEGRATION WITH AQUAWORKS, OVERLAND Advanced and PLANT VIEW SCADA DIRECT BY WIZARD

USER APPLICATION By LADDER languages / C++ in LINUX platform OPERATIVE SYSTEM LINUX EMBEDDED

TECHNICAL FEATURES

DIGITAL INPUTS 16 DI 10-30 V DC optoisolated and with galvanic insulation 2500 V DIGITAL OUTPUTS 8 DO 10-30 V DC optoisolated and with galvanic insulation 2500 V ANALOGIC INPUTS 8 AI 16 bit 4-20 mA / 0-10 V DC with galvanic insulation 2500 V ANALOGIC OUTPUTS (optional) 1 AO 16 bit 0-10 V DC with galvanic insulation 2500 V

EXPANDIBILITY up to 160 DI, 64 DO, 32 AI, 16 AO with MODBUS RS485 / RS422 / ETHERNET / CANBUS

COMMUNICATION PORTS 1 RS232 - 1 RS232/485 - 2 RS485/422 - 1 Ethernet 10/100 Mb/s 1 CANBUS (optional) - 1 USB

HMI Local LCD 7" colour display touch screen: Mod. DE VISU (optional) ALPHANUMERIC 2 x 16 local display with 12 keys (optional) INTERNET MODE: by standard browser

CASE IP 20

POWER SUPPLY 10-30 V DC

CONSUMPTION 2-4 WATT (max consumption 10 Watt) BATTERY – GSM/GPRS Operating Mode : 3 years Life Time BATTERY – IOT Operating Mode : 7 Years Life Time

ENVIRONMENTAL CONDITIONS -20°C +80°C RTC CLOCK YES MEMORY 256 MB FLASH/128 MB RAM MEMORY EXPANSION SD CARD/USB CERTIFICATION CE

FUNCTIONS

FAST SpA - Via Talete, 2/4 – 42048 Rubiera (RE) – ITALY Tel. (+39) 0522.622411 – Fax (+39) 0522.627194 www.fastautomation.it – [email protected]