Advanced Electrical Safety
-
Upload
dhanshyam-mahavadi -
Category
Documents
-
view
224 -
download
0
Transcript of Advanced Electrical Safety
-
8/3/2019 Advanced Electrical Safety
1/123
Two Day National Course forExecutives
4/29/2012 Prashant Srivastava 1
-
8/3/2019 Advanced Electrical Safety
2/123
Hazards of electricity Shock
Burns
Arc FlashArc Blast
Hazards from static charge
Secondary Hazards
All of above may cause injury and death.
4/29/2012 2Prashant Srivastava
-
8/3/2019 Advanced Electrical Safety
3/123
ShockFactors which determine severity of shock
Level and type of Voltage
Current Path through body
Duration of shock
Even a voltage as low as 50 Volts andcurrent as low as 10 mA can be fatal.
4/29/2012 Prashant Srivastava 3
-
8/3/2019 Advanced Electrical Safety
4/123
VoltageAC or DC
Level
Frequency
4/29/2012 Prashant Srivastava 4
-
8/3/2019 Advanced Electrical Safety
5/123
4/29/2012 Prashant Srivastava 5
-
8/3/2019 Advanced Electrical Safety
6/123
Current Low current < 3mA Tingling
Slightly higher current 10mA Cause paralysis, Can not releaselive part due to temporary muscular paralysis causingincreased duration of shock
Still Higher, 30mA Respiratory Paralysis
Still higher> 75mA May affect electrical activity ofheart like fibrillation
>4A Tissue burning
4/29/2012 Prashant Srivastava 6
-
8/3/2019 Advanced Electrical Safety
7/123
Path Through Body Through skin only- Less dangerous
Through Heart can cause heart failure
Through Respiratory system Cause breathingparalysis.
4/29/2012 Prashant Srivastava 7
-
8/3/2019 Advanced Electrical Safety
8/123
Duration Long duration can cause burning of tissues
But even small duration of current passing through
vital organs can cause its failure leading to death orpermanent damage.
4/29/2012 Prashant Srivastava 8
-
8/3/2019 Advanced Electrical Safety
9/123
Shock ProtectionStrategies that are used
Reduce shock voltage to very low level by earthing
Reduce Shock current by increasing resistancebetween man and touched part and between man andearth.
Sense leakage to earth and trip supply
4/29/2012 Prashant Srivastava 9
-
8/3/2019 Advanced Electrical Safety
10/123
Shock protection by rubber gloves
and matsClass of rubber gloves and mats
Class 00 ((Only gloves) For use up to 500 VAC
phase to phase Class 0 For use up to 1000 VAC phase to phase
Class 1 For use up to 7500 VAC phase to phase
Class 2 For use up to 1700 VAC phase to phase
Class 3 For use up to 26500 VAC phase to phase
Class4 For use up to 36000 VAC phase to phase
4/29/2012 Prashant Srivastava 10
-
8/3/2019 Advanced Electrical Safety
11/123
Arc FlashArc flash is caused by one of the several reasons
Dielectric breakdown causes short circuit and limiting
impedance is low.When air becomes superheated and metal vaporizes
When high current is broken
4/29/2012 Prashant Srivastava 11
-
8/3/2019 Advanced Electrical Safety
12/123
Conditions conducive to Arc Flash High voltage
High current
Overheating of conductors Large inductance in the circuit
4/29/2012 Prashant Srivastava 12
-
8/3/2019 Advanced Electrical Safety
13/123
Dangers of Arc flashArc Flash can cause many of the following injuries
Shock
Burns Blindness
Deafness
Can burn almost any type of clothes increasing danger
of secondary burns.Arc Flash can cause second degree burns
at very large distance.
4/29/2012 Prashant Srivastava 13
-
8/3/2019 Advanced Electrical Safety
14/123
Arc Blast In confined space Arcing heats up air rapidly
Air Expands rapidly
Can blow out panel doors, shatter insulators and evenknock down walls
Throw molten metal over large distance
Can puncture ear drum
Normal panel doors are not designed
to withstand Arc Blast pressure.Specially designed panel doors are needed.
4/29/2012 Prashant Srivastava 14
-
8/3/2019 Advanced Electrical Safety
15/123
BurnsElectric shock causes local burns but Arc Flash can cause
extensive burns in face, Chest, Back and limbs.
First degree Burn- Superficial burns on the skin,Painful but no permanent damage.
Second degree burn- Skin and growth tissues areburnt. Growth of skin is slow. Usually leaves scar.
Third degree burn- Skin and growth glands are alsoburnt. Skin can not grow without grafting. Leaves scarand some permanent damage.
4/29/2012 Prashant Srivastava 15
-
8/3/2019 Advanced Electrical Safety
16/123
Hazards from Static Charge Static charge accumulates on human body specially
during winter by rubbing against clothes
It may also be passed through touching chargedsurface
Rapid transfer of electric charge to and from humanbody can give severe electric shock
Electric charge develops when liquid passes throughpipe lines both on liquid as well as in pipe line
Specially hazardous when transferring petroleum orother easily ignitable liquids.
4/29/2012 Prashant Srivastava 16
-
8/3/2019 Advanced Electrical Safety
17/123
Hazards from Static ChargeStatic charge accumulates during
Agitation or mixing of liquid or solid material.
Transfer of material Running on belt conveyor
Pneumatic conveying
4/29/2012 Prashant Srivastava 17
-
8/3/2019 Advanced Electrical Safety
18/123
Hazards of static electricityFilling inflammable liquid
4/29/2012 Prashant Srivastava 18
-
8/3/2019 Advanced Electrical Safety
19/123
Secondary Hazard Shock can cause person to fall down from height and
cause fractures or death
Person may fall on the live conductor and continuereceiving shock till help is available
Person may drop tools etc. on live parts causing arcflash
Short circuits can cause fires leading to large scaledeaths and injuries.
Arc Flash can start secondary fires.
4/29/2012 Prashant Srivastava 19
-
8/3/2019 Advanced Electrical Safety
20/123
Reasons for Electrical Accidents Ignorance
Misuse
Overload Switch in neutral instead of phase in 1 f circuits
Sparking due to loose contacts
Not proper grounding
Inappropriate design or workmanship
Bad maintenance
Use of earth in place of neutral
4/29/2012 Prashant Srivastava 20
-
8/3/2019 Advanced Electrical Safety
21/123
Reasons for Electrical AccidentsWrong instruments or instruments in bad condition
Improper PPE
Unnecessary risk by working on live parts Un insulated tools
Bypassing protection
Improper display of hazard
Improper of missing fence in hazardous areas
Not testing residual voltage before starting work
Ignoring visual or available information about status
4/29/2012 Prashant Srivastava 21
-
8/3/2019 Advanced Electrical Safety
22/123
4/29/2012 Prashant Srivastava 22
-
8/3/2019 Advanced Electrical Safety
23/123
Incidence of Arc FlashAn arc flash can occur while;
Doing work on live system e.g. bus bars, switches etc.
Racking in breaker Touching any live part by a tool
Spontaneously when air and metal parts becomeoverheated in closed space like panel boards
4/29/2012 Prashant Srivastava 23
-
8/3/2019 Advanced Electrical Safety
24/123
Properties of Arc FlashArc is a very heavy current passing through air under
certain conditions.
The current further heats up air through which itpasses and creates state of Plasma or ionized air.
This plasma is conductive and supports f low ofcurrent.
This current creates strong thermo-magnetic force.
This force moves plasma through space
Temperature at the core of arc can be > 20,000 o K
4/29/2012 Prashant Srivastava 24
-
8/3/2019 Advanced Electrical Safety
25/123
Properties of Arc Flash Large part of heat is radiated to large distance
It can inflict second degree burns at a distance of even12 feet
All type of clothing can be set on fire by arc flash
Molten metal flies at large distances
In oil immersed devices like transformers, arc flash on
bushings can set fire to oil and destroy entiretransformer and even may set establishment on fire
4/29/2012 Prashant Srivastava 25
-
8/3/2019 Advanced Electrical Safety
26/123
Flash Energy Light- Intense light is emitted which can cause loss of
sight temporarily
Heat is intense in the form of radiation andconduction to the person in touch.
Mechanical- In form of blast
Heat energy intensity is measured as cal/cm2
4/29/2012 Prashant Srivastava 26
-
8/3/2019 Advanced Electrical Safety
27/123
Incident Flash EnergyDefined as Arc Flash energy experienced by a person
Depends upon
Bolted short circuit current System Voltage
Distance from arcing electrode
Duration of fault
Absorbent coefficient of the victim
Box effect
4/29/2012 Prashant Srivastava 27
-
8/3/2019 Advanced Electrical Safety
28/123
Factors affecting injury by Arc Flash
4/29/2012 Prashant Srivastava 28
-
8/3/2019 Advanced Electrical Safety
29/123
4/29/2012 Prashant Srivastava 29
-
8/3/2019 Advanced Electrical Safety
30/123
Flash Protection boundaries Restricted Approach Boundary-A shock protectionboundary to be crossed by only qualified persons. Whencrossed, shock protection techniques and equipment isrequired.
Prohibited Approach boundary-A shock protectionboundary to be crossed by only qualified persons. Whencrossed, same protection is to be used as with live contact.
Flash Protection boundary- Distance at which incident
energy levels equals 1.2 cal/cm2
for fault clearing time of 0.1sec or more. For fault clearing time less than 0.1 sec, thiscan be considered a distance at which incident energy levelis 1.5 cal/cm2.
4/29/2012 Prashant Srivastava 30
-
8/3/2019 Advanced Electrical Safety
31/123
4/29/2012 Prashant Srivastava 31
-
8/3/2019 Advanced Electrical Safety
32/123
Class of Arc Flash HazardThe NFPA 70E 2004 standard provides 5 Arc Rating
levels
Class 0 for incident energy up to 1.2 cal/cm2
Class 1 for incident energy up to 4 cal/cm2
Class 2 for incident energy up to 8 cal/cm2
Class 3 for incident energy up to 25 cal/cm2
Class 4 for incident energy up to 40 cal/cm2
4/29/2012 Prashant Srivastava 32
-
8/3/2019 Advanced Electrical Safety
33/123
Arc Flash Hazard AnalysisReasons for arc flash Hazard Analysis
To know hazard level at each location
To know safe boundaries for approach To determine suitable clothing for approaching near
live area
To know suitable PPE for workers to work on live parts
4/29/2012 Prashant Srivastava 33
-
8/3/2019 Advanced Electrical Safety
34/123
Arc Flash Hazard AnalysisNecessary information for doing Arc Flash hazard
analysis;
Bolted fault current at each location
Clearing time for the source side protective device
Working distance for energized work
ATPV (Arc Thermal Performance Value) for PPE
combinations use at site Site specific issues e.g. ingress, egress, working space,
illumination etc.
4/29/2012 Prashant Srivastava 34
-
8/3/2019 Advanced Electrical Safety
35/123
Steps required to do Arc Flash
Hazard Analysis Site assessment and data gathering
Short circuit analysis
Protective device coordination Use of software for detailed analysis.
IEEE standard 1584-2002 comes with software
Other free wares are available on the net
Checkwww.cadickcorp.com andwww.oberoncompany.com
4/29/2012 Prashant Srivastava 35
http://www.cadickcorp.com/http://www.oberoncompany.com/http://www.oberoncompany.com/http://www.cadickcorp.com/ -
8/3/2019 Advanced Electrical Safety
36/123
Arc Flash Labeling Depending upon Arc Flash analysis Various locations
will have different classes of Arc Flash Hazard
Labels clearly describing hazard class, Flash hazardboundary, Limited approach, Restricted approach,Prohibited approach, Incident Energy level,Recommended clothing etc. is prominently put atlocations in a way that it can not be missed byworkmen.
4/29/2012 Prashant Srivastava 36
-
8/3/2019 Advanced Electrical Safety
37/123
4/29/2012 Prashant Srivastava 37
-
8/3/2019 Advanced Electrical Safety
38/123
PPE for Arc FlashMaterial for Arc flash resistant clothing should; Be in two part; One overall or long jacket and other
face shield
Be made from Flame Resistant (FR) material Gloves are also of same material. Additionally, rubber
gloves are put on over this glove for electricalinsulation
Typically heavier grade NOMEX or PBI is usedATPV should be 40cal/cm2
4/29/2012 Prashant Srivastava 38
-
8/3/2019 Advanced Electrical Safety
39/123
4/29/2012 Prashant Srivastava 39
-
8/3/2019 Advanced Electrical Safety
40/123
4/29/2012 Prashant Srivastava 40
-
8/3/2019 Advanced Electrical Safety
41/123
TrainingWorkers who are required to do hot work on live parts
are to be trained for this type of work.
Training in safety
Precautions to be taken
Tools permitted to be used
Instruments permitted to be used
PPE training
4/29/2012 Prashant Srivastava 41
-
8/3/2019 Advanced Electrical Safety
42/123
Mitigation of Arc Flash HazardStrategies
Reduction of bolted fault current
Reduction in response time of Protection system Increase of working distance
Reduced relay settings during hot work
Arc Detection devices
4/29/2012 Prashant Srivastava 42
-
8/3/2019 Advanced Electrical Safety
43/123
-
8/3/2019 Advanced Electrical Safety
44/123
Reduction of Bolted current; Use
Current limiting Fuse
4/29/2012 Prashant Srivastava 44
Fuse should clear fault within half cycle
Reduces voltage sag duration
Reduces transients and thus improves power quality
-
8/3/2019 Advanced Electrical Safety
45/123
Reduction of fault currentCurrent; Actual andProspective
Voltage: Source and fuse
4/29/2012 Prashant Srivastava 45
-
8/3/2019 Advanced Electrical Safety
46/123
Reduction in response time By protective relay coordination, correct the response
time
Use of lower operating time relays
Bus differential protection
Use of lower settings reducing operating time
4/29/2012 Prashant Srivastava 46
-
8/3/2019 Advanced Electrical Safety
47/123
4/29/2012 Prashant Srivastava 47
-
8/3/2019 Advanced Electrical Safety
48/123
Increase working distance Incident energy is inversely proportional to square of
distance.
Hence increasing working distance can increase safetyimmensely
Distance can be increased by;
Using remote operated racking, remote operated
breaker closing and opening and using extension toolsand hot sticks.
4/29/2012 Prashant Srivastava 48
-
8/3/2019 Advanced Electrical Safety
49/123
4/29/2012 Prashant Srivastava 49
-
8/3/2019 Advanced Electrical Safety
50/123
Reduced relay settings during hot
work Temporarily reduce relay settings during hot work.
(Instantaneous settings just above peak demand)
Least expensive solution
Numerical relays can have two programs ; one fornormal operation and another for Hot Work
SCADA control can also implement this program.
4/29/2012 Prashant Srivastava 50
-
8/3/2019 Advanced Electrical Safety
51/123
4/29/2012 Prashant Srivastava 51
-
8/3/2019 Advanced Electrical Safety
52/123
Arc Detection devices Principle
Arc results in very bright light flash whose intensity ismuch higher than sun light or any other illumination
used. Optical sensors, based upon sudden increase in
intensity of light, sense beginning of arc flash and givesignal to trip coil of breaker.
To protect a zone optical fiber cable without outersheath is run throughout the protected zone.
Optical sensor can send signal within 2.5 msec. of startof the flash.
4/29/2012 Prashant Srivastava 52
-
8/3/2019 Advanced Electrical Safety
53/123
Optical Fiber Cable Routing
4/29/2012 Prashant Srivastava 53
-
8/3/2019 Advanced Electrical Safety
54/123
Arc Detection and Relay block
diagram
4/29/2012 Prashant Srivastava 54
-
8/3/2019 Advanced Electrical Safety
55/123
Tripping time comparison
4/29/2012 Prashant Srivastava 55
-
8/3/2019 Advanced Electrical Safety
56/123
Incident energy reduction
4/29/2012 Prashant Srivastava 56
-
8/3/2019 Advanced Electrical Safety
57/123
Arc Detection relay covering a zone
4/29/2012 Prashant Srivastava 57
-
8/3/2019 Advanced Electrical Safety
58/123
A Zero Potential surface
4/29/2012 Prashant Srivastava 58
-
8/3/2019 Advanced Electrical Safety
59/123
Reasons for earthing To create a reference voltage
To create a safe zero potential surface.
To create a return path for neutral currents
To reduce transients
To reduce harmonics
4/29/2012 Prashant Srivastava 59
-
8/3/2019 Advanced Electrical Safety
60/123
Earthing Pit Earth surface has high resistance and therefore we
have to create a pit which maintains low resistancebonding with earth and brings out a low resistance
connection which can be distributed. Neutral has to be earthed either directly or through
grounding resistors to create reference voltage otherwise lines can assume very high voltages which can be
a serious safety threat.
4/29/2012 Prashant Srivastava 60
-
8/3/2019 Advanced Electrical Safety
61/123
4/29/2012 Prashant Srivastava 61
-
8/3/2019 Advanced Electrical Safety
62/123
Requirements from earthing For substations and industrial users, Earthing resistanceshould be between 0.1 ~ 1.0 ohms
If resistance is higher, saline water should be added to the
pit. Many pits should be connected together to create a low
resistance path for large short circuit current withoutcreating large voltage drop
Every motor, panel and switchgears body should be
earthed at two places. Neutral of generators and Transformers should be
connected to two earthing pit which are independent ofbody earthing pits.
4/29/2012 Prashant Srivastava 62
-
8/3/2019 Advanced Electrical Safety
63/123
Some important notesWater pipes should not be used for earthing
Lead sheathing and armor of cables should be earthed.
Wherever RCC poles are used as in substations, Fourpoles can be tied with earthing strip and thenconnected to earthing pit.
Earthing electrode should not get corroded. GI or
tinned copper is preferred. Aluminum can be usedabove ground connections
4/29/2012 Prashant Srivastava 63
-
8/3/2019 Advanced Electrical Safety
64/123
Substation EarthingCriteria Low earthing resistance
Low step potential
Low touch potential
4/29/2012 Prashant Srivastava 64
-
8/3/2019 Advanced Electrical Safety
65/123
Earthing resistance requirements EHV AC Installations 33 kV
-
8/3/2019 Advanced Electrical Safety
66/123
Step potential hazard
4/29/2012 Prashant Srivastava 66
-
8/3/2019 Advanced Electrical Safety
67/123
Touch Potential Hazard
4/29/2012 Prashant Srivastava 67
-
8/3/2019 Advanced Electrical Safety
68/123
Earthing mesh
4/29/2012 Prashant Srivastava 68
-
8/3/2019 Advanced Electrical Safety
69/123
Transmission Line earthing
4/29/2012 Prashant Srivastava 69
EHT Lines 110 kV One aerial earthing wire 220 kV lines Two aerial earthing wires to be run through
towers At least at 4 towers every mile, aerial earthing wire is to be
earthed. HT Lines Earthing rods are driven in ground at each tower if
resistance is less than 15 ohms. For higher resistance two rods are driven in ground whose
distance should not exceed 200ft. Even then resistanceshould not exceed 25 ohms.
-
8/3/2019 Advanced Electrical Safety
70/123
If it can not be done safely, it neednot be done
4/29/2012 Prashant Srivastava 70
-
8/3/2019 Advanced Electrical Safety
71/123
Basic six steps to safety1. Think Be Aware2. Understand Procedures
3. Follow Procedures
4. Use Appropriate safety equipment
5. If not sure, ask; do not assume
6. Do not answer if you do not know
4/29/2012 Prashant Srivastava 71
-
8/3/2019 Advanced Electrical Safety
72/123
Pre Job Briefing, SHEPP Special Precautions to be taken
Hazard Associated with the job
Energy control Procedures
Procedures and policies
Personal Protective Equipment
4/29/2012 Prashant Srivastava 72
-
8/3/2019 Advanced Electrical Safety
73/123
When?At the beginning of new shift
At the beginning of new job
Any time job conditions change
Any time when new personnel are introduced in anongoing job
4/29/2012 Prashant Srivastava 73
-
8/3/2019 Advanced Electrical Safety
74/123
Energized or De-energized?As much as possible de-energize before start of work
If job requires energized work, assess the hazard anduse proper tools, equipment and PPE
If control circuit is to be tested, shut power to powercircuit.
Production loss should not be the sole reason for
doing energized work Only qualified and trained workers to do energized
work
4/29/2012 Prashant Srivastava 74
-
8/3/2019 Advanced Electrical Safety
75/123
Energized work Excessive restart time in continuous process plant
High product loss in un scheduled stoppage
Testing electrical circuit
Trouble shooting controls
Infrared scan
4/29/2012 Prashant Srivastava 75
-
8/3/2019 Advanced Electrical Safety
76/123
Safe conditions for De-Energized work Only qualified people who know about system should
switch it off.
As far as possible switches and breakers should be
remotely operated. No load isolating switches should not be used for load
interruption.
All energy control devices feeding the area should beopened.
Locks and tags should be placed on energy controldevices.
4/29/2012 Prashant Srivastava 76
-
8/3/2019 Advanced Electrical Safety
77/123
Safe conditions for De-Energized work
Locks and Tags
4/29/2012 Prashant Srivastava 77
-
8/3/2019 Advanced Electrical Safety
78/123
Safe conditions for De-Energized workAll previously energized parts e.g. bus bars should be
discharged and grounded.
Voltage measurement to ensure all live parts are dead
and at zero potential. The work areas must be inspected by qualified person
to ensure no parts are still energized. This step is oftenmissed by many.
Remove all conducing material on body
e.g. rings, watches, ornaments, metal buttons etc.
4/29/2012 Prashant Srivastava 78
-
8/3/2019 Advanced Electrical Safety
79/123
Proximity Tester
4/29/2012 Prashant Srivastava 79
-
8/3/2019 Advanced Electrical Safety
80/123
Contact Voltage tester
4/29/2012 Prashant Srivastava 80
-
8/3/2019 Advanced Electrical Safety
81/123
Voltage measurement
4/29/2012 Prashant Srivastava 81
-
8/3/2019 Advanced Electrical Safety
82/123
Voltage measurement
4/29/2012 Prashant Srivastava 82
-
8/3/2019 Advanced Electrical Safety
83/123
Racking in and out metal clad breakers Many Arc Flash accidents happen while racking in and out
of breakers
Safe way to do so is to do this by remotely operated gear.Even a handle with long operating rod is better thanmanually operating from near the breaker.
Keep face and eyes away from breaker. Stand at an anglerather than face full square on.
Do not forget to put on PPE. Depending upon class of
hazard, if required, Arc Flash suit should be put on. Always have two people operating the breaker. One to do
the physical work and other to monitor from a distance andcall for help if necessary.
4/29/2012 Prashant Srivastava 83
-
8/3/2019 Advanced Electrical Safety
84/123
Racking in and out metal clad breakers Racked out breakers springs or pneumatic operating
energy should be discharged if not done so already.
Similarly make sure operating spring or other operatingdevice is off before racking in the breaker. Usually breakershave mechanical and electrical interlocks to take care ofthis but making sure is a good practice.
External safety grounding should be doneby using proper grounding connections with tested earth
bus. All previously live parts should be looped and a singleground connection should be made firmly to the earth busby suitable clamps.
4/29/2012 Prashant Srivastava 84
-
8/3/2019 Advanced Electrical Safety
85/123
Remote racking of Breakers
4/29/2012 Prashant Srivastava 85
-
8/3/2019 Advanced Electrical Safety
86/123
Safety groundingEarthing Clamps
4/29/2012 Prashant Srivastava 86
-
8/3/2019 Advanced Electrical Safety
87/123
GroundingSwitchgear Grounding Metal Tower Grounding
4/29/2012 Prashant Srivastava 87
-
8/3/2019 Advanced Electrical Safety
88/123
Operation of Gang Operated Switch Gang operated switches are usually used on overhead
lines.
A zero potential surface should be created below the
pole on which operator should stand. Using rubber gloves and glasses with side shields and
standing upon zero potential plate operate the switch.
4/29/2012 Prashant Srivastava 88
-
8/3/2019 Advanced Electrical Safety
89/123
4/29/2012 Prashant Srivastava 89
-
8/3/2019 Advanced Electrical Safety
90/123
Re-energizing equipment Before re-energizing inspect thoroughly to ensure that the
work which was to be done is completed satisfactorily.
Ensure re-insulation and other closing work has been doneproperly. Remove temporary ground connection.
Ensure that no tools are left where they should not be.
Inform all concerned people to move away.
Remove locks and tags
Recheck that breaker spring is de- energized.
Rack in the breaker Close doors
Close switch and energize
4/29/2012 Prashant Srivastava 90
-
8/3/2019 Advanced Electrical Safety
91/123
Energized working Pre Job briefing , SHEPP Inspect all energized working tools and PPE
Only qualified personnel to be near place of work
Work only with special tools and measuringinstruments.
Reduce protective relay setting , if required
At least two persons should work in teams with at leastone person monitoring the process.
4/29/2012 Prashant Srivastava 91
-
8/3/2019 Advanced Electrical Safety
92/123
Hot sticks and Insulated Tools
4/29/2012 Prashant Srivastava 92
-
8/3/2019 Advanced Electrical Safety
93/123
Safety Electrical One Line DiagramAn updated single Line diagram which is made for the
purpose of safety.
It should be Accurate and should be updated from
time to time Concise- Too much information clutters up the
drawing and many important information goes hidingSEOLD should clearly show sources of power,
disconnect switches, interconnections.
Legibility- If the drawing has become old and notlegible, new drawings should be made.
4/29/2012 Prashant Srivastava 93
-
8/3/2019 Advanced Electrical Safety
94/123
4/29/2012 Prashant Srivastava 94
-
8/3/2019 Advanced Electrical Safety
95/123
One minute safety Audit Notify responsible person of your presence in the area.
Listen for any abnormal sound and sniff for unusualodor.
Locate emergency exits.
Locate fire alarms and telephones.
Inspect all transformers liquid levels, temp. and
pressure gauges to ensure the readings are inacceptable range.
Locate Single line Safety Diagram. It should be legible.
4/29/2012 Prashant Srivastava 95
-
8/3/2019 Advanced Electrical Safety
96/123
One minute safety AuditArea should be neat and tidy. Panels should not be
used as almirah for storage of material and equipment.
All safety equipment should be within easy reach.
Check to see that all protective relay flags are reset.
4/29/2012 Prashant Srivastava 96
-
8/3/2019 Advanced Electrical Safety
97/123
Accidents dont just happen.
They can be prevented.
4/29/2012 Prashant Srivastava 97
-
8/3/2019 Advanced Electrical Safety
98/123
By PlanningPlan after making detailed studies
Arc Flash Hazard Studies
Load flow studies
About Voltage , Amp., Active and Reactive power. Used forsizing equipment.
Stability StudiesTransient and steady state stability of Power system. These
studies inform about stability during slow and fast changes
Motor starting analysis It is a computer generated model of a large motor under
starting condition, how it affects power system
4/29/2012 Prashant Srivastava 98
-
8/3/2019 Advanced Electrical Safety
99/123
By Planning Harmonic Analysis
Harmonics and other power quality problems which cancause equipment malfunction , failures and safety hazards
Switching Transient analysisCertain loads create switching transients. Switch
malfunctions also creates transients. Study shows magnitudeof transients and allows to develop solutions
Reliability Analysis It is a study of frequency of interruptions an number of
interruptions in a year. A reliability study will help evolvestrategies to operate system safely during interruption.
4/29/2012 Prashant Srivastava 99
-
8/3/2019 Advanced Electrical Safety
100/123
By Planning Cable Amp analysisThis study recommends proper size of cable for each
application depending upon capacity, type of cable, route andenvironment.
Ground Mat analysisStudy of earth resistance, touch and step voltages
Fault currents magnitude and duration
Geometry of grounding system
Soil resistivityProbability of contact
Human body resistance and assumptions on conditions ofindividual
4/29/2012 Prashant Srivastava 100
-
8/3/2019 Advanced Electrical Safety
101/123
By Planning Short Circuit study and Protective device CoordinationStudy about short circuit and earth fault currents
magnitude at various locations.
Study also shows protective Zones relay coordinationand selectivity
Time curves and coordination
Study of collateral damage to cables and other currentcarrying devices during short circuits
This study is one of the most important from safetypoint of view and should be repeated every five years inan operating plant.
4/29/2012 Prashant Srivastava 101
-
8/3/2019 Advanced Electrical Safety
102/123
By Design Select Switch gear, cables etc. with extra capacity keeping
in mind safety factor, over and above, plans for expansion Select arc flash protected switchgear Select switches for remote operation Select only good brand products with relevant safety
certification Make good layout with adequate space for ingress and
egress. Plan for adequate number of disconnect switches for
isolation for maintenance Plan for motor disconnect switch near a motor for
operation during maintenance
4/29/2012 Prashant Srivastava 102
-
8/3/2019 Advanced Electrical Safety
103/123
By Design Specify transformer with Pressure relief valve and drain pipe
instead of explosion vent
Design sufficient and strategically located safety fences to keepout un authorized entry by man and animals.
Plan proper routing for cables with proper ventilation and access. Plan for proper measuring and testing instruments
Specify flame proof switchgear and motors in locations wherethey are needed.
Plan for static earthing plates earthing tankers of Petroleumproducts loading and unloading.
Use low voltage for controls.
Purchase adequate number and type of PPE
4/29/2012 Prashant Srivastava 103
-
8/3/2019 Advanced Electrical Safety
104/123
By installation Select only Certified contractor Insist upon contractor providing proper uniform and safety kit to
their worker as part of contract. Insist upon contractors workersusing them. Take adequate managerial steps to ensurecompliance.
Make quality plan for each work, discuss with contractor andinspect its implementation.
Put safety inspectors on the job of monitoring hot work likewelding, cutting by gas with adequate arrangement for firefighting.
Provide training in specific jobs to contractors workers. Inspect contractors tools and machines for safety. Machines e.g.
welding machine, hand tools, power tools etc. Maintain overall discipline at work site
4/29/2012 Prashant Srivastava 104
-
8/3/2019 Advanced Electrical Safety
105/123
By Operation
Provide training to workers Provide safety kits and PPE
Provide suitable tools and measuring instruments
Provide competent supervision
Make detailed plan for maintenance Use of Predictive maintenance tools
Provide good quality spares
Make safety teams including workers and actively
participate in their meetingPlan for a rapid response team to provide rescue andmedical aid in case accidents still do happen.
4/29/2012 Prashant Srivastava 105
-
8/3/2019 Advanced Electrical Safety
106/123
Grounding of power systems for
safety
4/29/2012 Prashant Srivastava 106
-
8/3/2019 Advanced Electrical Safety
107/123
What & why of System Grounding It is connecting one of the supply conductors to the
earth.
Grounded systems provide sufficiently high short
circuit and earth fault currents to operate protectiveequipment.
They are less prone to transient over voltages
They are generally more protected from lightening
Solidly grounded systems are less prone to resonanceand to insulation failure.
4/29/2012 Prashant Srivastava 107
-
8/3/2019 Advanced Electrical Safety
108/123
System Grounding In DC supply, either + ve or ve can be grounded.
In single phase supply neutral is grounded
In star connected three phase system, star point is
grounded and used as neutral for single phase supply.
In three wire delta connected supply, earthingtransformer is used for grounding.
4/29/2012 Prashant Srivastava 108
-
8/3/2019 Advanced Electrical Safety
109/123
Solid grounding
4/29/2012 Prashant Srivastava 109
-
8/3/2019 Advanced Electrical Safety
110/123
Solid grounding
4/29/2012 Prashant Srivastava 110
Used mostly for LT where earth fault current is low.
Also used for voltages above 33kV where line capacitivecurrents and inductive earth fault current neutralize
each other to such an extent that effective neutralcurrent is not very high during earth fault.
-
8/3/2019 Advanced Electrical Safety
111/123
Neutral Grounding Resistance
4/29/2012 Prashant Srivastava 111
-
8/3/2019 Advanced Electrical Safety
112/123
Neutral Grounding Resistance Used mostly in 3.3 kV to 33 kV systems.
At these voltages line capacitive currents are not highenough and earth fault current is large enough.
Is so chosen that it does not affect neutral voltagemuch in normal operation.
In earth fault conditions, it limits earth fault current atthe cost of raising neutral voltage but makes thesystem safer.
4/29/2012 Prashant Srivastava 112
G di d d 3 i l
-
8/3/2019 Advanced Electrical Safety
113/123
Grounding ungrounded 3 wire supply
4/29/2012 Prashant Srivastava 113
-
8/3/2019 Advanced Electrical Safety
114/123
For sustained growth and safe
operation
4/29/2012 Prashant Srivastava 114
-
8/3/2019 Advanced Electrical Safety
115/123
Necessity of safety management Legal requirement
Employees health and safety
Money involved in accidents and down time
Industrial Relations
Social Obligation
4/29/2012 Prashant Srivastava 115
-
8/3/2019 Advanced Electrical Safety
116/123
Legal Requirement There are certain mandatory requirements which must
be fulfilled.
Some of these requirements start from design of
system and continue in purchase, installation andcommissioning of equipment and continue inOperation and maintenance.
An alert management knows about these requirementsand complies.
In case any changes are required to be done, thenagain legal requirements need to be studied andimplemented.
4/29/2012 Prashant Srivastava 116
-
8/3/2019 Advanced Electrical Safety
117/123
Employee Health and safety Every employer has responsibilities towards safety and
health of his employees.
With out proper planning and implementing safe and
healthy practices health and safety of employees cannot be ensured.
4/29/2012 Prashant Srivastava 117
-
8/3/2019 Advanced Electrical Safety
118/123
Financial loss Man hour loss
Production loss
Bad reputation
Market share loss
4/29/2012 Prashant Srivastava 118
-
8/3/2019 Advanced Electrical Safety
119/123
Industrial RelationsAccidents lead to bad IR
Loss of man hours and production
4/29/2012 Prashant Srivastava 119
-
8/3/2019 Advanced Electrical Safety
120/123
Electrical Safety Program Structure
4/29/2012 Prashant Srivastava 120
Company Electrical Safety Team
-
8/3/2019 Advanced Electrical Safety
121/123
p y y
CEST Consists of a senior electrical person as chair person
And many more qualified electrical persons
Management provides representative as advisor to
advise company policiesA SHE member who has ultimate responsibility to run
safety program.
A legal advisor to inform and clarify legal obligations
4/29/2012 Prashant Srivastava 121
-
8/3/2019 Advanced Electrical Safety
122/123
Responsibilities of CEST To develop, implement, evaluate and modify company
safety procedures.
Degree of authority to this team should be high
CEST should have a member at management level todevelop company safety policy
4/29/2012 Prashant Srivastava 122
-
8/3/2019 Advanced Electrical Safety
123/123
Companys commitment To safe work practices
To comply with legal requirement
In any electrical work safety is prime consideration
All employees are required to follow safety procedures If a job can not be done safely, it need not be done.
Each employee is responsible for his own safety
The commitment and cooperation of all employees is
required to sustain safety program
To ensure regular safety team meeting