Advanced Electrical Safety

download Advanced Electrical Safety

of 123

Transcript of Advanced Electrical Safety

  • 8/3/2019 Advanced Electrical Safety

    1/123

    Two Day National Course forExecutives

    4/29/2012 Prashant Srivastava 1

  • 8/3/2019 Advanced Electrical Safety

    2/123

    Hazards of electricity Shock

    Burns

    Arc FlashArc Blast

    Hazards from static charge

    Secondary Hazards

    All of above may cause injury and death.

    4/29/2012 2Prashant Srivastava

  • 8/3/2019 Advanced Electrical Safety

    3/123

    ShockFactors which determine severity of shock

    Level and type of Voltage

    Current Path through body

    Duration of shock

    Even a voltage as low as 50 Volts andcurrent as low as 10 mA can be fatal.

    4/29/2012 Prashant Srivastava 3

  • 8/3/2019 Advanced Electrical Safety

    4/123

    VoltageAC or DC

    Level

    Frequency

    4/29/2012 Prashant Srivastava 4

  • 8/3/2019 Advanced Electrical Safety

    5/123

    4/29/2012 Prashant Srivastava 5

  • 8/3/2019 Advanced Electrical Safety

    6/123

    Current Low current < 3mA Tingling

    Slightly higher current 10mA Cause paralysis, Can not releaselive part due to temporary muscular paralysis causingincreased duration of shock

    Still Higher, 30mA Respiratory Paralysis

    Still higher> 75mA May affect electrical activity ofheart like fibrillation

    >4A Tissue burning

    4/29/2012 Prashant Srivastava 6

  • 8/3/2019 Advanced Electrical Safety

    7/123

    Path Through Body Through skin only- Less dangerous

    Through Heart can cause heart failure

    Through Respiratory system Cause breathingparalysis.

    4/29/2012 Prashant Srivastava 7

  • 8/3/2019 Advanced Electrical Safety

    8/123

    Duration Long duration can cause burning of tissues

    But even small duration of current passing through

    vital organs can cause its failure leading to death orpermanent damage.

    4/29/2012 Prashant Srivastava 8

  • 8/3/2019 Advanced Electrical Safety

    9/123

    Shock ProtectionStrategies that are used

    Reduce shock voltage to very low level by earthing

    Reduce Shock current by increasing resistancebetween man and touched part and between man andearth.

    Sense leakage to earth and trip supply

    4/29/2012 Prashant Srivastava 9

  • 8/3/2019 Advanced Electrical Safety

    10/123

    Shock protection by rubber gloves

    and matsClass of rubber gloves and mats

    Class 00 ((Only gloves) For use up to 500 VAC

    phase to phase Class 0 For use up to 1000 VAC phase to phase

    Class 1 For use up to 7500 VAC phase to phase

    Class 2 For use up to 1700 VAC phase to phase

    Class 3 For use up to 26500 VAC phase to phase

    Class4 For use up to 36000 VAC phase to phase

    4/29/2012 Prashant Srivastava 10

  • 8/3/2019 Advanced Electrical Safety

    11/123

    Arc FlashArc flash is caused by one of the several reasons

    Dielectric breakdown causes short circuit and limiting

    impedance is low.When air becomes superheated and metal vaporizes

    When high current is broken

    4/29/2012 Prashant Srivastava 11

  • 8/3/2019 Advanced Electrical Safety

    12/123

    Conditions conducive to Arc Flash High voltage

    High current

    Overheating of conductors Large inductance in the circuit

    4/29/2012 Prashant Srivastava 12

  • 8/3/2019 Advanced Electrical Safety

    13/123

    Dangers of Arc flashArc Flash can cause many of the following injuries

    Shock

    Burns Blindness

    Deafness

    Can burn almost any type of clothes increasing danger

    of secondary burns.Arc Flash can cause second degree burns

    at very large distance.

    4/29/2012 Prashant Srivastava 13

  • 8/3/2019 Advanced Electrical Safety

    14/123

    Arc Blast In confined space Arcing heats up air rapidly

    Air Expands rapidly

    Can blow out panel doors, shatter insulators and evenknock down walls

    Throw molten metal over large distance

    Can puncture ear drum

    Normal panel doors are not designed

    to withstand Arc Blast pressure.Specially designed panel doors are needed.

    4/29/2012 Prashant Srivastava 14

  • 8/3/2019 Advanced Electrical Safety

    15/123

    BurnsElectric shock causes local burns but Arc Flash can cause

    extensive burns in face, Chest, Back and limbs.

    First degree Burn- Superficial burns on the skin,Painful but no permanent damage.

    Second degree burn- Skin and growth tissues areburnt. Growth of skin is slow. Usually leaves scar.

    Third degree burn- Skin and growth glands are alsoburnt. Skin can not grow without grafting. Leaves scarand some permanent damage.

    4/29/2012 Prashant Srivastava 15

  • 8/3/2019 Advanced Electrical Safety

    16/123

    Hazards from Static Charge Static charge accumulates on human body specially

    during winter by rubbing against clothes

    It may also be passed through touching chargedsurface

    Rapid transfer of electric charge to and from humanbody can give severe electric shock

    Electric charge develops when liquid passes throughpipe lines both on liquid as well as in pipe line

    Specially hazardous when transferring petroleum orother easily ignitable liquids.

    4/29/2012 Prashant Srivastava 16

  • 8/3/2019 Advanced Electrical Safety

    17/123

    Hazards from Static ChargeStatic charge accumulates during

    Agitation or mixing of liquid or solid material.

    Transfer of material Running on belt conveyor

    Pneumatic conveying

    4/29/2012 Prashant Srivastava 17

  • 8/3/2019 Advanced Electrical Safety

    18/123

    Hazards of static electricityFilling inflammable liquid

    4/29/2012 Prashant Srivastava 18

  • 8/3/2019 Advanced Electrical Safety

    19/123

    Secondary Hazard Shock can cause person to fall down from height and

    cause fractures or death

    Person may fall on the live conductor and continuereceiving shock till help is available

    Person may drop tools etc. on live parts causing arcflash

    Short circuits can cause fires leading to large scaledeaths and injuries.

    Arc Flash can start secondary fires.

    4/29/2012 Prashant Srivastava 19

  • 8/3/2019 Advanced Electrical Safety

    20/123

    Reasons for Electrical Accidents Ignorance

    Misuse

    Overload Switch in neutral instead of phase in 1 f circuits

    Sparking due to loose contacts

    Not proper grounding

    Inappropriate design or workmanship

    Bad maintenance

    Use of earth in place of neutral

    4/29/2012 Prashant Srivastava 20

  • 8/3/2019 Advanced Electrical Safety

    21/123

    Reasons for Electrical AccidentsWrong instruments or instruments in bad condition

    Improper PPE

    Unnecessary risk by working on live parts Un insulated tools

    Bypassing protection

    Improper display of hazard

    Improper of missing fence in hazardous areas

    Not testing residual voltage before starting work

    Ignoring visual or available information about status

    4/29/2012 Prashant Srivastava 21

  • 8/3/2019 Advanced Electrical Safety

    22/123

    4/29/2012 Prashant Srivastava 22

  • 8/3/2019 Advanced Electrical Safety

    23/123

    Incidence of Arc FlashAn arc flash can occur while;

    Doing work on live system e.g. bus bars, switches etc.

    Racking in breaker Touching any live part by a tool

    Spontaneously when air and metal parts becomeoverheated in closed space like panel boards

    4/29/2012 Prashant Srivastava 23

  • 8/3/2019 Advanced Electrical Safety

    24/123

    Properties of Arc FlashArc is a very heavy current passing through air under

    certain conditions.

    The current further heats up air through which itpasses and creates state of Plasma or ionized air.

    This plasma is conductive and supports f low ofcurrent.

    This current creates strong thermo-magnetic force.

    This force moves plasma through space

    Temperature at the core of arc can be > 20,000 o K

    4/29/2012 Prashant Srivastava 24

  • 8/3/2019 Advanced Electrical Safety

    25/123

    Properties of Arc Flash Large part of heat is radiated to large distance

    It can inflict second degree burns at a distance of even12 feet

    All type of clothing can be set on fire by arc flash

    Molten metal flies at large distances

    In oil immersed devices like transformers, arc flash on

    bushings can set fire to oil and destroy entiretransformer and even may set establishment on fire

    4/29/2012 Prashant Srivastava 25

  • 8/3/2019 Advanced Electrical Safety

    26/123

    Flash Energy Light- Intense light is emitted which can cause loss of

    sight temporarily

    Heat is intense in the form of radiation andconduction to the person in touch.

    Mechanical- In form of blast

    Heat energy intensity is measured as cal/cm2

    4/29/2012 Prashant Srivastava 26

  • 8/3/2019 Advanced Electrical Safety

    27/123

    Incident Flash EnergyDefined as Arc Flash energy experienced by a person

    Depends upon

    Bolted short circuit current System Voltage

    Distance from arcing electrode

    Duration of fault

    Absorbent coefficient of the victim

    Box effect

    4/29/2012 Prashant Srivastava 27

  • 8/3/2019 Advanced Electrical Safety

    28/123

    Factors affecting injury by Arc Flash

    4/29/2012 Prashant Srivastava 28

  • 8/3/2019 Advanced Electrical Safety

    29/123

    4/29/2012 Prashant Srivastava 29

  • 8/3/2019 Advanced Electrical Safety

    30/123

    Flash Protection boundaries Restricted Approach Boundary-A shock protectionboundary to be crossed by only qualified persons. Whencrossed, shock protection techniques and equipment isrequired.

    Prohibited Approach boundary-A shock protectionboundary to be crossed by only qualified persons. Whencrossed, same protection is to be used as with live contact.

    Flash Protection boundary- Distance at which incident

    energy levels equals 1.2 cal/cm2

    for fault clearing time of 0.1sec or more. For fault clearing time less than 0.1 sec, thiscan be considered a distance at which incident energy levelis 1.5 cal/cm2.

    4/29/2012 Prashant Srivastava 30

  • 8/3/2019 Advanced Electrical Safety

    31/123

    4/29/2012 Prashant Srivastava 31

  • 8/3/2019 Advanced Electrical Safety

    32/123

    Class of Arc Flash HazardThe NFPA 70E 2004 standard provides 5 Arc Rating

    levels

    Class 0 for incident energy up to 1.2 cal/cm2

    Class 1 for incident energy up to 4 cal/cm2

    Class 2 for incident energy up to 8 cal/cm2

    Class 3 for incident energy up to 25 cal/cm2

    Class 4 for incident energy up to 40 cal/cm2

    4/29/2012 Prashant Srivastava 32

  • 8/3/2019 Advanced Electrical Safety

    33/123

    Arc Flash Hazard AnalysisReasons for arc flash Hazard Analysis

    To know hazard level at each location

    To know safe boundaries for approach To determine suitable clothing for approaching near

    live area

    To know suitable PPE for workers to work on live parts

    4/29/2012 Prashant Srivastava 33

  • 8/3/2019 Advanced Electrical Safety

    34/123

    Arc Flash Hazard AnalysisNecessary information for doing Arc Flash hazard

    analysis;

    Bolted fault current at each location

    Clearing time for the source side protective device

    Working distance for energized work

    ATPV (Arc Thermal Performance Value) for PPE

    combinations use at site Site specific issues e.g. ingress, egress, working space,

    illumination etc.

    4/29/2012 Prashant Srivastava 34

  • 8/3/2019 Advanced Electrical Safety

    35/123

    Steps required to do Arc Flash

    Hazard Analysis Site assessment and data gathering

    Short circuit analysis

    Protective device coordination Use of software for detailed analysis.

    IEEE standard 1584-2002 comes with software

    Other free wares are available on the net

    Checkwww.cadickcorp.com andwww.oberoncompany.com

    4/29/2012 Prashant Srivastava 35

    http://www.cadickcorp.com/http://www.oberoncompany.com/http://www.oberoncompany.com/http://www.cadickcorp.com/
  • 8/3/2019 Advanced Electrical Safety

    36/123

    Arc Flash Labeling Depending upon Arc Flash analysis Various locations

    will have different classes of Arc Flash Hazard

    Labels clearly describing hazard class, Flash hazardboundary, Limited approach, Restricted approach,Prohibited approach, Incident Energy level,Recommended clothing etc. is prominently put atlocations in a way that it can not be missed byworkmen.

    4/29/2012 Prashant Srivastava 36

  • 8/3/2019 Advanced Electrical Safety

    37/123

    4/29/2012 Prashant Srivastava 37

  • 8/3/2019 Advanced Electrical Safety

    38/123

    PPE for Arc FlashMaterial for Arc flash resistant clothing should; Be in two part; One overall or long jacket and other

    face shield

    Be made from Flame Resistant (FR) material Gloves are also of same material. Additionally, rubber

    gloves are put on over this glove for electricalinsulation

    Typically heavier grade NOMEX or PBI is usedATPV should be 40cal/cm2

    4/29/2012 Prashant Srivastava 38

  • 8/3/2019 Advanced Electrical Safety

    39/123

    4/29/2012 Prashant Srivastava 39

  • 8/3/2019 Advanced Electrical Safety

    40/123

    4/29/2012 Prashant Srivastava 40

  • 8/3/2019 Advanced Electrical Safety

    41/123

    TrainingWorkers who are required to do hot work on live parts

    are to be trained for this type of work.

    Training in safety

    Precautions to be taken

    Tools permitted to be used

    Instruments permitted to be used

    PPE training

    4/29/2012 Prashant Srivastava 41

  • 8/3/2019 Advanced Electrical Safety

    42/123

    Mitigation of Arc Flash HazardStrategies

    Reduction of bolted fault current

    Reduction in response time of Protection system Increase of working distance

    Reduced relay settings during hot work

    Arc Detection devices

    4/29/2012 Prashant Srivastava 42

  • 8/3/2019 Advanced Electrical Safety

    43/123

  • 8/3/2019 Advanced Electrical Safety

    44/123

    Reduction of Bolted current; Use

    Current limiting Fuse

    4/29/2012 Prashant Srivastava 44

    Fuse should clear fault within half cycle

    Reduces voltage sag duration

    Reduces transients and thus improves power quality

  • 8/3/2019 Advanced Electrical Safety

    45/123

    Reduction of fault currentCurrent; Actual andProspective

    Voltage: Source and fuse

    4/29/2012 Prashant Srivastava 45

  • 8/3/2019 Advanced Electrical Safety

    46/123

    Reduction in response time By protective relay coordination, correct the response

    time

    Use of lower operating time relays

    Bus differential protection

    Use of lower settings reducing operating time

    4/29/2012 Prashant Srivastava 46

  • 8/3/2019 Advanced Electrical Safety

    47/123

    4/29/2012 Prashant Srivastava 47

  • 8/3/2019 Advanced Electrical Safety

    48/123

    Increase working distance Incident energy is inversely proportional to square of

    distance.

    Hence increasing working distance can increase safetyimmensely

    Distance can be increased by;

    Using remote operated racking, remote operated

    breaker closing and opening and using extension toolsand hot sticks.

    4/29/2012 Prashant Srivastava 48

  • 8/3/2019 Advanced Electrical Safety

    49/123

    4/29/2012 Prashant Srivastava 49

  • 8/3/2019 Advanced Electrical Safety

    50/123

    Reduced relay settings during hot

    work Temporarily reduce relay settings during hot work.

    (Instantaneous settings just above peak demand)

    Least expensive solution

    Numerical relays can have two programs ; one fornormal operation and another for Hot Work

    SCADA control can also implement this program.

    4/29/2012 Prashant Srivastava 50

  • 8/3/2019 Advanced Electrical Safety

    51/123

    4/29/2012 Prashant Srivastava 51

  • 8/3/2019 Advanced Electrical Safety

    52/123

    Arc Detection devices Principle

    Arc results in very bright light flash whose intensity ismuch higher than sun light or any other illumination

    used. Optical sensors, based upon sudden increase in

    intensity of light, sense beginning of arc flash and givesignal to trip coil of breaker.

    To protect a zone optical fiber cable without outersheath is run throughout the protected zone.

    Optical sensor can send signal within 2.5 msec. of startof the flash.

    4/29/2012 Prashant Srivastava 52

  • 8/3/2019 Advanced Electrical Safety

    53/123

    Optical Fiber Cable Routing

    4/29/2012 Prashant Srivastava 53

  • 8/3/2019 Advanced Electrical Safety

    54/123

    Arc Detection and Relay block

    diagram

    4/29/2012 Prashant Srivastava 54

  • 8/3/2019 Advanced Electrical Safety

    55/123

    Tripping time comparison

    4/29/2012 Prashant Srivastava 55

  • 8/3/2019 Advanced Electrical Safety

    56/123

    Incident energy reduction

    4/29/2012 Prashant Srivastava 56

  • 8/3/2019 Advanced Electrical Safety

    57/123

    Arc Detection relay covering a zone

    4/29/2012 Prashant Srivastava 57

  • 8/3/2019 Advanced Electrical Safety

    58/123

    A Zero Potential surface

    4/29/2012 Prashant Srivastava 58

  • 8/3/2019 Advanced Electrical Safety

    59/123

    Reasons for earthing To create a reference voltage

    To create a safe zero potential surface.

    To create a return path for neutral currents

    To reduce transients

    To reduce harmonics

    4/29/2012 Prashant Srivastava 59

  • 8/3/2019 Advanced Electrical Safety

    60/123

    Earthing Pit Earth surface has high resistance and therefore we

    have to create a pit which maintains low resistancebonding with earth and brings out a low resistance

    connection which can be distributed. Neutral has to be earthed either directly or through

    grounding resistors to create reference voltage otherwise lines can assume very high voltages which can be

    a serious safety threat.

    4/29/2012 Prashant Srivastava 60

  • 8/3/2019 Advanced Electrical Safety

    61/123

    4/29/2012 Prashant Srivastava 61

  • 8/3/2019 Advanced Electrical Safety

    62/123

    Requirements from earthing For substations and industrial users, Earthing resistanceshould be between 0.1 ~ 1.0 ohms

    If resistance is higher, saline water should be added to the

    pit. Many pits should be connected together to create a low

    resistance path for large short circuit current withoutcreating large voltage drop

    Every motor, panel and switchgears body should be

    earthed at two places. Neutral of generators and Transformers should be

    connected to two earthing pit which are independent ofbody earthing pits.

    4/29/2012 Prashant Srivastava 62

  • 8/3/2019 Advanced Electrical Safety

    63/123

    Some important notesWater pipes should not be used for earthing

    Lead sheathing and armor of cables should be earthed.

    Wherever RCC poles are used as in substations, Fourpoles can be tied with earthing strip and thenconnected to earthing pit.

    Earthing electrode should not get corroded. GI or

    tinned copper is preferred. Aluminum can be usedabove ground connections

    4/29/2012 Prashant Srivastava 63

  • 8/3/2019 Advanced Electrical Safety

    64/123

    Substation EarthingCriteria Low earthing resistance

    Low step potential

    Low touch potential

    4/29/2012 Prashant Srivastava 64

  • 8/3/2019 Advanced Electrical Safety

    65/123

    Earthing resistance requirements EHV AC Installations 33 kV

  • 8/3/2019 Advanced Electrical Safety

    66/123

    Step potential hazard

    4/29/2012 Prashant Srivastava 66

  • 8/3/2019 Advanced Electrical Safety

    67/123

    Touch Potential Hazard

    4/29/2012 Prashant Srivastava 67

  • 8/3/2019 Advanced Electrical Safety

    68/123

    Earthing mesh

    4/29/2012 Prashant Srivastava 68

  • 8/3/2019 Advanced Electrical Safety

    69/123

    Transmission Line earthing

    4/29/2012 Prashant Srivastava 69

    EHT Lines 110 kV One aerial earthing wire 220 kV lines Two aerial earthing wires to be run through

    towers At least at 4 towers every mile, aerial earthing wire is to be

    earthed. HT Lines Earthing rods are driven in ground at each tower if

    resistance is less than 15 ohms. For higher resistance two rods are driven in ground whose

    distance should not exceed 200ft. Even then resistanceshould not exceed 25 ohms.

  • 8/3/2019 Advanced Electrical Safety

    70/123

    If it can not be done safely, it neednot be done

    4/29/2012 Prashant Srivastava 70

  • 8/3/2019 Advanced Electrical Safety

    71/123

    Basic six steps to safety1. Think Be Aware2. Understand Procedures

    3. Follow Procedures

    4. Use Appropriate safety equipment

    5. If not sure, ask; do not assume

    6. Do not answer if you do not know

    4/29/2012 Prashant Srivastava 71

  • 8/3/2019 Advanced Electrical Safety

    72/123

    Pre Job Briefing, SHEPP Special Precautions to be taken

    Hazard Associated with the job

    Energy control Procedures

    Procedures and policies

    Personal Protective Equipment

    4/29/2012 Prashant Srivastava 72

  • 8/3/2019 Advanced Electrical Safety

    73/123

    When?At the beginning of new shift

    At the beginning of new job

    Any time job conditions change

    Any time when new personnel are introduced in anongoing job

    4/29/2012 Prashant Srivastava 73

  • 8/3/2019 Advanced Electrical Safety

    74/123

    Energized or De-energized?As much as possible de-energize before start of work

    If job requires energized work, assess the hazard anduse proper tools, equipment and PPE

    If control circuit is to be tested, shut power to powercircuit.

    Production loss should not be the sole reason for

    doing energized work Only qualified and trained workers to do energized

    work

    4/29/2012 Prashant Srivastava 74

  • 8/3/2019 Advanced Electrical Safety

    75/123

    Energized work Excessive restart time in continuous process plant

    High product loss in un scheduled stoppage

    Testing electrical circuit

    Trouble shooting controls

    Infrared scan

    4/29/2012 Prashant Srivastava 75

  • 8/3/2019 Advanced Electrical Safety

    76/123

    Safe conditions for De-Energized work Only qualified people who know about system should

    switch it off.

    As far as possible switches and breakers should be

    remotely operated. No load isolating switches should not be used for load

    interruption.

    All energy control devices feeding the area should beopened.

    Locks and tags should be placed on energy controldevices.

    4/29/2012 Prashant Srivastava 76

  • 8/3/2019 Advanced Electrical Safety

    77/123

    Safe conditions for De-Energized work

    Locks and Tags

    4/29/2012 Prashant Srivastava 77

  • 8/3/2019 Advanced Electrical Safety

    78/123

    Safe conditions for De-Energized workAll previously energized parts e.g. bus bars should be

    discharged and grounded.

    Voltage measurement to ensure all live parts are dead

    and at zero potential. The work areas must be inspected by qualified person

    to ensure no parts are still energized. This step is oftenmissed by many.

    Remove all conducing material on body

    e.g. rings, watches, ornaments, metal buttons etc.

    4/29/2012 Prashant Srivastava 78

  • 8/3/2019 Advanced Electrical Safety

    79/123

    Proximity Tester

    4/29/2012 Prashant Srivastava 79

  • 8/3/2019 Advanced Electrical Safety

    80/123

    Contact Voltage tester

    4/29/2012 Prashant Srivastava 80

  • 8/3/2019 Advanced Electrical Safety

    81/123

    Voltage measurement

    4/29/2012 Prashant Srivastava 81

  • 8/3/2019 Advanced Electrical Safety

    82/123

    Voltage measurement

    4/29/2012 Prashant Srivastava 82

  • 8/3/2019 Advanced Electrical Safety

    83/123

    Racking in and out metal clad breakers Many Arc Flash accidents happen while racking in and out

    of breakers

    Safe way to do so is to do this by remotely operated gear.Even a handle with long operating rod is better thanmanually operating from near the breaker.

    Keep face and eyes away from breaker. Stand at an anglerather than face full square on.

    Do not forget to put on PPE. Depending upon class of

    hazard, if required, Arc Flash suit should be put on. Always have two people operating the breaker. One to do

    the physical work and other to monitor from a distance andcall for help if necessary.

    4/29/2012 Prashant Srivastava 83

  • 8/3/2019 Advanced Electrical Safety

    84/123

    Racking in and out metal clad breakers Racked out breakers springs or pneumatic operating

    energy should be discharged if not done so already.

    Similarly make sure operating spring or other operatingdevice is off before racking in the breaker. Usually breakershave mechanical and electrical interlocks to take care ofthis but making sure is a good practice.

    External safety grounding should be doneby using proper grounding connections with tested earth

    bus. All previously live parts should be looped and a singleground connection should be made firmly to the earth busby suitable clamps.

    4/29/2012 Prashant Srivastava 84

  • 8/3/2019 Advanced Electrical Safety

    85/123

    Remote racking of Breakers

    4/29/2012 Prashant Srivastava 85

  • 8/3/2019 Advanced Electrical Safety

    86/123

    Safety groundingEarthing Clamps

    4/29/2012 Prashant Srivastava 86

  • 8/3/2019 Advanced Electrical Safety

    87/123

    GroundingSwitchgear Grounding Metal Tower Grounding

    4/29/2012 Prashant Srivastava 87

  • 8/3/2019 Advanced Electrical Safety

    88/123

    Operation of Gang Operated Switch Gang operated switches are usually used on overhead

    lines.

    A zero potential surface should be created below the

    pole on which operator should stand. Using rubber gloves and glasses with side shields and

    standing upon zero potential plate operate the switch.

    4/29/2012 Prashant Srivastava 88

  • 8/3/2019 Advanced Electrical Safety

    89/123

    4/29/2012 Prashant Srivastava 89

  • 8/3/2019 Advanced Electrical Safety

    90/123

    Re-energizing equipment Before re-energizing inspect thoroughly to ensure that the

    work which was to be done is completed satisfactorily.

    Ensure re-insulation and other closing work has been doneproperly. Remove temporary ground connection.

    Ensure that no tools are left where they should not be.

    Inform all concerned people to move away.

    Remove locks and tags

    Recheck that breaker spring is de- energized.

    Rack in the breaker Close doors

    Close switch and energize

    4/29/2012 Prashant Srivastava 90

  • 8/3/2019 Advanced Electrical Safety

    91/123

    Energized working Pre Job briefing , SHEPP Inspect all energized working tools and PPE

    Only qualified personnel to be near place of work

    Work only with special tools and measuringinstruments.

    Reduce protective relay setting , if required

    At least two persons should work in teams with at leastone person monitoring the process.

    4/29/2012 Prashant Srivastava 91

  • 8/3/2019 Advanced Electrical Safety

    92/123

    Hot sticks and Insulated Tools

    4/29/2012 Prashant Srivastava 92

  • 8/3/2019 Advanced Electrical Safety

    93/123

    Safety Electrical One Line DiagramAn updated single Line diagram which is made for the

    purpose of safety.

    It should be Accurate and should be updated from

    time to time Concise- Too much information clutters up the

    drawing and many important information goes hidingSEOLD should clearly show sources of power,

    disconnect switches, interconnections.

    Legibility- If the drawing has become old and notlegible, new drawings should be made.

    4/29/2012 Prashant Srivastava 93

  • 8/3/2019 Advanced Electrical Safety

    94/123

    4/29/2012 Prashant Srivastava 94

  • 8/3/2019 Advanced Electrical Safety

    95/123

    One minute safety Audit Notify responsible person of your presence in the area.

    Listen for any abnormal sound and sniff for unusualodor.

    Locate emergency exits.

    Locate fire alarms and telephones.

    Inspect all transformers liquid levels, temp. and

    pressure gauges to ensure the readings are inacceptable range.

    Locate Single line Safety Diagram. It should be legible.

    4/29/2012 Prashant Srivastava 95

  • 8/3/2019 Advanced Electrical Safety

    96/123

    One minute safety AuditArea should be neat and tidy. Panels should not be

    used as almirah for storage of material and equipment.

    All safety equipment should be within easy reach.

    Check to see that all protective relay flags are reset.

    4/29/2012 Prashant Srivastava 96

  • 8/3/2019 Advanced Electrical Safety

    97/123

    Accidents dont just happen.

    They can be prevented.

    4/29/2012 Prashant Srivastava 97

  • 8/3/2019 Advanced Electrical Safety

    98/123

    By PlanningPlan after making detailed studies

    Arc Flash Hazard Studies

    Load flow studies

    About Voltage , Amp., Active and Reactive power. Used forsizing equipment.

    Stability StudiesTransient and steady state stability of Power system. These

    studies inform about stability during slow and fast changes

    Motor starting analysis It is a computer generated model of a large motor under

    starting condition, how it affects power system

    4/29/2012 Prashant Srivastava 98

  • 8/3/2019 Advanced Electrical Safety

    99/123

    By Planning Harmonic Analysis

    Harmonics and other power quality problems which cancause equipment malfunction , failures and safety hazards

    Switching Transient analysisCertain loads create switching transients. Switch

    malfunctions also creates transients. Study shows magnitudeof transients and allows to develop solutions

    Reliability Analysis It is a study of frequency of interruptions an number of

    interruptions in a year. A reliability study will help evolvestrategies to operate system safely during interruption.

    4/29/2012 Prashant Srivastava 99

  • 8/3/2019 Advanced Electrical Safety

    100/123

    By Planning Cable Amp analysisThis study recommends proper size of cable for each

    application depending upon capacity, type of cable, route andenvironment.

    Ground Mat analysisStudy of earth resistance, touch and step voltages

    Fault currents magnitude and duration

    Geometry of grounding system

    Soil resistivityProbability of contact

    Human body resistance and assumptions on conditions ofindividual

    4/29/2012 Prashant Srivastava 100

  • 8/3/2019 Advanced Electrical Safety

    101/123

    By Planning Short Circuit study and Protective device CoordinationStudy about short circuit and earth fault currents

    magnitude at various locations.

    Study also shows protective Zones relay coordinationand selectivity

    Time curves and coordination

    Study of collateral damage to cables and other currentcarrying devices during short circuits

    This study is one of the most important from safetypoint of view and should be repeated every five years inan operating plant.

    4/29/2012 Prashant Srivastava 101

  • 8/3/2019 Advanced Electrical Safety

    102/123

    By Design Select Switch gear, cables etc. with extra capacity keeping

    in mind safety factor, over and above, plans for expansion Select arc flash protected switchgear Select switches for remote operation Select only good brand products with relevant safety

    certification Make good layout with adequate space for ingress and

    egress. Plan for adequate number of disconnect switches for

    isolation for maintenance Plan for motor disconnect switch near a motor for

    operation during maintenance

    4/29/2012 Prashant Srivastava 102

  • 8/3/2019 Advanced Electrical Safety

    103/123

    By Design Specify transformer with Pressure relief valve and drain pipe

    instead of explosion vent

    Design sufficient and strategically located safety fences to keepout un authorized entry by man and animals.

    Plan proper routing for cables with proper ventilation and access. Plan for proper measuring and testing instruments

    Specify flame proof switchgear and motors in locations wherethey are needed.

    Plan for static earthing plates earthing tankers of Petroleumproducts loading and unloading.

    Use low voltage for controls.

    Purchase adequate number and type of PPE

    4/29/2012 Prashant Srivastava 103

  • 8/3/2019 Advanced Electrical Safety

    104/123

    By installation Select only Certified contractor Insist upon contractor providing proper uniform and safety kit to

    their worker as part of contract. Insist upon contractors workersusing them. Take adequate managerial steps to ensurecompliance.

    Make quality plan for each work, discuss with contractor andinspect its implementation.

    Put safety inspectors on the job of monitoring hot work likewelding, cutting by gas with adequate arrangement for firefighting.

    Provide training in specific jobs to contractors workers. Inspect contractors tools and machines for safety. Machines e.g.

    welding machine, hand tools, power tools etc. Maintain overall discipline at work site

    4/29/2012 Prashant Srivastava 104

  • 8/3/2019 Advanced Electrical Safety

    105/123

    By Operation

    Provide training to workers Provide safety kits and PPE

    Provide suitable tools and measuring instruments

    Provide competent supervision

    Make detailed plan for maintenance Use of Predictive maintenance tools

    Provide good quality spares

    Make safety teams including workers and actively

    participate in their meetingPlan for a rapid response team to provide rescue andmedical aid in case accidents still do happen.

    4/29/2012 Prashant Srivastava 105

  • 8/3/2019 Advanced Electrical Safety

    106/123

    Grounding of power systems for

    safety

    4/29/2012 Prashant Srivastava 106

  • 8/3/2019 Advanced Electrical Safety

    107/123

    What & why of System Grounding It is connecting one of the supply conductors to the

    earth.

    Grounded systems provide sufficiently high short

    circuit and earth fault currents to operate protectiveequipment.

    They are less prone to transient over voltages

    They are generally more protected from lightening

    Solidly grounded systems are less prone to resonanceand to insulation failure.

    4/29/2012 Prashant Srivastava 107

  • 8/3/2019 Advanced Electrical Safety

    108/123

    System Grounding In DC supply, either + ve or ve can be grounded.

    In single phase supply neutral is grounded

    In star connected three phase system, star point is

    grounded and used as neutral for single phase supply.

    In three wire delta connected supply, earthingtransformer is used for grounding.

    4/29/2012 Prashant Srivastava 108

  • 8/3/2019 Advanced Electrical Safety

    109/123

    Solid grounding

    4/29/2012 Prashant Srivastava 109

  • 8/3/2019 Advanced Electrical Safety

    110/123

    Solid grounding

    4/29/2012 Prashant Srivastava 110

    Used mostly for LT where earth fault current is low.

    Also used for voltages above 33kV where line capacitivecurrents and inductive earth fault current neutralize

    each other to such an extent that effective neutralcurrent is not very high during earth fault.

  • 8/3/2019 Advanced Electrical Safety

    111/123

    Neutral Grounding Resistance

    4/29/2012 Prashant Srivastava 111

  • 8/3/2019 Advanced Electrical Safety

    112/123

    Neutral Grounding Resistance Used mostly in 3.3 kV to 33 kV systems.

    At these voltages line capacitive currents are not highenough and earth fault current is large enough.

    Is so chosen that it does not affect neutral voltagemuch in normal operation.

    In earth fault conditions, it limits earth fault current atthe cost of raising neutral voltage but makes thesystem safer.

    4/29/2012 Prashant Srivastava 112

    G di d d 3 i l

  • 8/3/2019 Advanced Electrical Safety

    113/123

    Grounding ungrounded 3 wire supply

    4/29/2012 Prashant Srivastava 113

  • 8/3/2019 Advanced Electrical Safety

    114/123

    For sustained growth and safe

    operation

    4/29/2012 Prashant Srivastava 114

  • 8/3/2019 Advanced Electrical Safety

    115/123

    Necessity of safety management Legal requirement

    Employees health and safety

    Money involved in accidents and down time

    Industrial Relations

    Social Obligation

    4/29/2012 Prashant Srivastava 115

  • 8/3/2019 Advanced Electrical Safety

    116/123

    Legal Requirement There are certain mandatory requirements which must

    be fulfilled.

    Some of these requirements start from design of

    system and continue in purchase, installation andcommissioning of equipment and continue inOperation and maintenance.

    An alert management knows about these requirementsand complies.

    In case any changes are required to be done, thenagain legal requirements need to be studied andimplemented.

    4/29/2012 Prashant Srivastava 116

  • 8/3/2019 Advanced Electrical Safety

    117/123

    Employee Health and safety Every employer has responsibilities towards safety and

    health of his employees.

    With out proper planning and implementing safe and

    healthy practices health and safety of employees cannot be ensured.

    4/29/2012 Prashant Srivastava 117

  • 8/3/2019 Advanced Electrical Safety

    118/123

    Financial loss Man hour loss

    Production loss

    Bad reputation

    Market share loss

    4/29/2012 Prashant Srivastava 118

  • 8/3/2019 Advanced Electrical Safety

    119/123

    Industrial RelationsAccidents lead to bad IR

    Loss of man hours and production

    4/29/2012 Prashant Srivastava 119

  • 8/3/2019 Advanced Electrical Safety

    120/123

    Electrical Safety Program Structure

    4/29/2012 Prashant Srivastava 120

    Company Electrical Safety Team

  • 8/3/2019 Advanced Electrical Safety

    121/123

    p y y

    CEST Consists of a senior electrical person as chair person

    And many more qualified electrical persons

    Management provides representative as advisor to

    advise company policiesA SHE member who has ultimate responsibility to run

    safety program.

    A legal advisor to inform and clarify legal obligations

    4/29/2012 Prashant Srivastava 121

  • 8/3/2019 Advanced Electrical Safety

    122/123

    Responsibilities of CEST To develop, implement, evaluate and modify company

    safety procedures.

    Degree of authority to this team should be high

    CEST should have a member at management level todevelop company safety policy

    4/29/2012 Prashant Srivastava 122

  • 8/3/2019 Advanced Electrical Safety

    123/123

    Companys commitment To safe work practices

    To comply with legal requirement

    In any electrical work safety is prime consideration

    All employees are required to follow safety procedures If a job can not be done safely, it need not be done.

    Each employee is responsible for his own safety

    The commitment and cooperation of all employees is

    required to sustain safety program

    To ensure regular safety team meeting