Advanced Concepts Power Quality FLUKE [email protected]
-
Upload
marco-ramos -
Category
Documents
-
view
69 -
download
6
Transcript of Advanced Concepts Power Quality FLUKE [email protected]
© 2007 Fluke Corporation. All rights reserved.1
Advanced Power Quality Concepts
© 2007 Fluke Corporation. All rights reserved.2
Standards
• Primary international standards for power quality
• How they affect our business
• How they influence the market
© 2007 Fluke Corporation. All rights reserved.3
Cat IV• Outside and
service entrance• Service drop from
pole to building• Run between
meter and panel• Overhead line to detached building
• Underground line to well pump
IEC 61010 safety ratings – CAT {x}
© 2007 Fluke Corporation. All rights reserved.4
NFPA 70E
Hazard/Risk Category 2: 240 – 600V electrical environments
• FR long sleeved shirt with sleeves rolled down and front fully buttoned up• FR work pants (not denims) or coveralls over natural fiber• 600 V rated leather over rubber gloves• Leather work boots• Switching hood containing hearing protection • No jewelry or watch
© 2007 Fluke Corporation. All rights reserved.5
IEC 61000-4-30
First Edition February 2003
Testing and measurement techniques
– power quality measurement methods
© 2007 Fluke Corporation. All rights reserved.6
Scope Of IEC 61000-4-30
• IEC 61000-4-30 defines the methods for measurement and interpretation of results for power quality parameters in 50/60 Hz a.c. power supply systems.
• Measurement of parameters covered by this standard is limited to those phenomena that can be conducted in a power system, including the voltage and/or current parameters, as appropriate.
© 2007 Fluke Corporation. All rights reserved.7
The Standard Identifies Measured Parameters Relating To Power Quality
• Power frequency• Magnitude of the supply voltage• Flicker• Supply voltage dips and swells• Voltage interruptions• Transient voltages• Supply voltage unbalance• Voltage and current harmonics • Inter-harmonics• Mains signaling on the supply voltage • Rapid voltage changes• Measure of underdeviation and overdeviation
© 2007 Fluke Corporation. All rights reserved.8
• Class A Performance - where high precision measurements are necessary, for example:• Contractual applications• Compliance with standards• Resolving disputes
• Class B Performance – where less uncertainty is required, for example:• Statistical surveys• Troubleshooting
Two classes of performance
© 2007 Fluke Corporation. All rights reserved.9
Testing PQ Instrumentation• The standard defines the critical PQ parameters that must be varied to
insure proper measurement performance• For Class A measurements, IEC 61000-4-30 identifies 9 different power
quality parameters of the input signal that can affect measurements due to their variation• Frequency• Voltage Magnitude• Flicker• Unbalance• Harmonics (THD)• Interharmonics• Mains signaling voltage• Transient voltages• Fast Transients
• It also identifies their range of influence• The intention is that a proper measurement is made under realistic
variations of all these parameters• For Class B the number of parameters is reduced to 6
© 2007 Fluke Corporation. All rights reserved.10
• IEC 61000-4-30 require that the measurements tests are repeated under three different states of overall power quality• 1 state with clean & balanced power quality• 2 other states with differing power quality conditions
(Note for class B measurements, there are no special power states defined.)
Testing PQ Instrumentation
© 2007 Fluke Corporation. All rights reserved.11
• In addition, all tests in each state are repeated while each influence is individually changed through a range of 5 equally spaced points• For example on the voltage magnitude influence, the test range
is from 0 to 200% of the nominal value. Tests are done at 0%, 50%, 100%, 150% and 200% of the normal input value while all the other influences are held steady
• The Class A test is very thorough – including 3 states, individually testing all 12 types of measurements while individually varying each of 9 parameters over a 5 point range
Testing PQ Instrumentation
© 2007 Fluke Corporation. All rights reserved.12
• Class A required accuracies• Power Frequency - ± 10 mHz• Magnitude of Supply Voltage - .1% of Nominal• Flicker - Per IEC 61000-4-15 • Voltage Dips & Swells - measured to ± 0.2%• Voltage Interruptions - measured within 2 cycles• Supply Voltage Unbalances - ±.15%• Voltage & Current Harmonics and Interharmonics - Per IEC
61000-4-7• Mains signaling voltage – less than 7% of reading
(Note: For Class B, the original manufacturer’s recommendations are used for the instruments tested.)
Testing PQ Instrumentation
© 2007 Fluke Corporation. All rights reserved.13
Flagging
• During a dip, swell, or interruption, the measurement algorithm for other parameters might produce an unreliable value. The flagging concept therefore avoids counting a single event more than once in different parameters and indicates that an aggregated value might be unreliable.
• Flagging is only triggered by dips, swells, and interruptions.
• The flagging concept is applicable for Class A measurement performance .
• If during a given time interval any value is flagged, the aggregated value including that value shall also be flagged.
© 2007 Fluke Corporation. All rights reserved.14
Mains Signaling
• Mains signaling voltage measurement shall be based on• either the corresponding 10/12-cycle rms value
interharmonic bin;• or the rms of the four nearest 10/12-cycle rms value
interharmonic bins • For example, a 316.67 Hz ripple control signal in a 50 Hz power
system shall be approximated by an r.m.s. of 310 Hz, 315 Hz, 320 Hz and 325 Hz bins, available from the FFT performed on a 10-cycle time interval.
• FFT on 10/12 cycles provides 5Hz resolution
300 Hz 350 Hz
316,67 Hz
325 Hz
© 2007 Fluke Corporation. All rights reserved.15
EN50160
• Followed primarily in Europe• Adopted in some countries
• Modified in others• Focus is mostly on minimum distribution limits
© 2007 Fluke Corporation. All rights reserved.16
EN50160
• Specifies the quality of electricity• Intended for Service Entrance Monitoring• Sets limits for:
• Frequency, Voltage Magnitude and variations ,Transients, Rapid voltage changes, Flicker severity, Voltage dips, Voltage Interruptions, Unbalance, Harmonic Voltage, Main signaling
• Concept: You can’t blame the electricity supplier when still having problems.
• Some parameters are assigned a tolerance they must meet 95% of the time, so they can be out of tolerance over 8 hours per week!
• Most measurements are “Averages of Averages” so short variations are smoothed out
• Staying within limits doesn’t guarantee good power quality
© 2007 Fluke Corporation. All rights reserved.17
Phenomena Parameter Limit Not exceeding probability
Power frequency Mean value over 10 sec +1%/-1%+4% / - 6%
99.5% of a year100% of the time
Supply voltage variations Mean rms over 10 min +10%/-10%+10% / -15%
95% of one week100% of the time
Rapid voltage changes Number of events Short duration and 5%UnShort duration and 10% Un
NormalSeveral time per day
Flicker severity Plt (2hr) ≤ 1 for 95% of one week
Voltage dip Number of events duration < 1 second and < 60% Un 10..1000 events per year> 50% of all dips
Short Interruptions Number of events duration < 1 second and < 1% Un 10..1000 events per year> 70% of all interruptions
Long interruption Number of events with duration >180 secondsand <1% Un
10...50 events per year
Overvoltages (50Hz) Number of events with few sec duration > 110% Un and ≤ 1.5kV
Transient Overvoltages Number of events μsec to msec duration > 1.5kV and < 6kV
Unbalance Uneg/Upos over 10 min <2% 95% of one week
Harmonic voltage Mean rms over 10 minTHD ≤ 8%
See harmonic Limits Table≤ 8%
95% of one week95% of one week
InterHarmonic Under consideration
Mains signaling Mean rms over 3 sec 99% of a day day
EN50160
© 2007 Fluke Corporation. All rights reserved.18
Upper limits for individual harmonic voltages at the supply terminals in % of nominal voltage. 95% of 10-minute average Vrms over 1 week must be below limits
Odd harmonics Even Harmonics
Not multiples of 3 Multiples of 3
Orderh
Relative voltage Orderh
Relative voltage Orderh
Relative voltage
5 6 % 3 5 % 2 2 %
7 5 % 9 1.5 % 4 1 %
11 3.5 % 15 0.5 % 6…24 0.5 %
13 3 % 21 0.5 %
17 2 %
19 1.5 %
23 1.5 %
25 1.5 %
EN50160 Harmonics
© 2007 Fluke Corporation. All rights reserved.19
How to Read EN50160
• RMS voltage readings over every 10 cycles (50Hz)• These readings are averaged over non-overlapping 10-minute intervals (50 x 10
cycles avg)• 168 hours x 6 = 1008 average voltages• 95% of the readings (958 readings) must be within 10% of nominal. • No readings may be 10% above or 15% below nominal. • So up to 5% of the readings (50 readings) may be below 207V, but no lower than
195.5V.
95% of the average Vrms samples taken during 1 week must be within this range
Average Vrms must never fall outside this range
Let’s assume we are monitoring voltage magnitude on a 230V system.Over a one week monitoring period we will take:
© 2007 Fluke Corporation. All rights reserved.20
Lower limit as specified by EN50160
Upper limit as specified by EN50160
Small: Maximum voltage measured relative to upper limit
Red indicates upper limit is exceeded.Example: 100% of the 10 min avg readings should be within +10/-15%. At least one reading exceeded this limit
Plt reading
Number of events–Dips, interruptions, “rapid voltage changes” and swells
Wide: Avg voltage measured relative to lower limit
430 EN50160 graphic
Unbalance and frequency
© 2007 Fluke Corporation. All rights reserved.21
• Bar Graphs have a wide base indicating adjustable time related limits (for instance 95 % of time within limit) and a narrow top indicating a fixed 100 % limit. If one of both limits is violated, the related bar changes from green to red. Dotted horizontal lines on the display indicate the 100% limit and the adjustable limit.
• The 100 % limit means that the 10-minute averages must always (i.e. 100 % of time or with 100 % probability) be within range. The bar graph will turn to red if a 10-minute average crosses the tolerance range. The adjustable limit of for instance 95 % (i.e. 95 % probability) means that 95 % of the 10-minute averages must be within tolerance. The 95 % limit is less stringent than the 100 % limit.
430 EN50160 graphic
© 2007 Fluke Corporation. All rights reserved.22
430 EN50160 graphic
© 2007 Fluke Corporation. All rights reserved.23
Value table
© 2007 Fluke Corporation. All rights reserved.24
Flicker
“Flicker is the subjective impression of fluctuating luminance, caused by the modulation of the RMS supply voltage”.
M. De Koster - E. De Jaeger – W.Vancoetsem
• Defined by standard IEC 61000-4-15• Perceptible flicker in lighting caused by periodic voltage sags. • Measured by a statistical “Lamp-Eye-Brain” model that duplicates
how most people are affected by flickering incandescent lights.• Causes
• Loads that draw in periodic “gulps” (ex: arc furnaces, welders)• The Basic Measurements
• PST -- A statistical figure derived over 10 minutes. A reading of 1.0 causes flicker that can be perceived by 50% of people
• PLT -- A statistical figure derived from PST over 2 hrs• Represents the likelihood that fluctuations will cause annoyance
© 2007 Fluke Corporation. All rights reserved.25
Flicker
• Penalties applied in South America• Generally unknown in North America• Standards applied in Europe and Asia
© 2007 Fluke Corporation. All rights reserved.26
(IEC 61000-4-15)Pst : Short time (10 min)Plt : long time (2 hours)
8,4Hz modulation
60 Hz
Effects
Flicker is the effect produced on the visual human perception by a changing emission of light by lamps subjected to fluctuations of their supply voltage.
Flicker
© 2007 Fluke Corporation. All rights reserved.27
Industry Low Voltage
Eolic Generators
Loads Variations
• Arc furnace (c.a. & c.c.)
• Welding machines
• Business copy machines• Large Motors• X-rays machines
Causes
Flicker sources
© 2007 Fluke Corporation. All rights reserved.28
IEC 61000-4-15
• “It has been shown in [19] that different digital flicker meter implementations that meet the performance tests defined in IEC 61000-4-15, Amendment 1 can still disagree significantly in some actual measurements. “
• IEC Flicker Meter used in Power System Voltage Monitoring• Prepared by: CCU2 – Cigré C4.05 / CIRED 2 / UIE WG2 Joint Working Group on Power Quality• DRAFT 10 October 2003
© 2007 Fluke Corporation. All rights reserved.29
61000-4-7
• General guidelines on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected
harmonic order n n+1 n+2 n+3
harmonic subgroup n+1
interharmonic subgroup n+2,5
DFT output
© 2007 Fluke Corporation. All rights reserved.30
Interharmonics
• IH voltages can cause flicker in electronic ballasts when the frequency is near a multiple of the fundamental.
• IH voltages can cause flicker in incandescent lamps primarily when the frequency is near the fundamental or second harmonic.
• 1%IH near the fundamental frequency can result in a Pst of 5.
• Interference with low frequency power line carrier (PLC) signals.
• IH currents cause IH voltage distortion according to the network impedance in the same manner as harmonic currents.
• IH currents have the same thermal effects as harmonic currents in the same frequency range.
• Can cause undesirable effects with tuned filters.
• IEC presently has a limit recommendation of 0.2% voltage distortion from 0-2 kHz.
© 2007 Fluke Corporation. All rights reserved.31
230 Vac
Vac
t
10 ms
10 values interval = 100 ms
Vmax
Vmin
Vavg
• A 10 min interval contains 10x60x100=60,000 cycles . • During 1 week 7 x 24 x 6 = 1,008 (x 3) values are recorded .
Voltage variations
A value each ½ cycle
© 2007 Fluke Corporation. All rights reserved.32
Dips, swell and interruptions are characterized by duration, magnitude and time of occurrence•Starts when from one of the phases the voltage goes below/above the threshold•Stops when all phases are above/below the threshold + hysteresis.•Levels and duration are specified by EN 50160
DipInterruption
Swell
What’s a Dip (sag), swell or interruption?
© 2007 Fluke Corporation. All rights reserved.33
Rapid Voltage change
A quick change of the RMS voltage between two steady voltages.
© 2007 Fluke Corporation. All rights reserved.34
Short Interruption
tShort Interruption
Voltage rms in [%] UN
10 ms 1s 1 h3 min
90%
110%
100%
te ts
1%0%
Duration
Voltage variations
© 2007 Fluke Corporation. All rights reserved.35
Long Interruption
t
Voltage rms in [%] UN
10 ms 1s 1 h3 min
90%
110%
100%
Long Interruption1%0%
Voltage variations
© 2007 Fluke Corporation. All rights reserved.36
Dips and Swells
1%0% Short Interruption Long Interruption
Voltage rms in [%] UN
10 ms 1s 1 h3 min
90%
110%
100%
Dip
1 min
Swell
Voltage variations ± 10%
+10 % / -15 %
© 2007 Fluke Corporation. All rights reserved.37
Sources and Effects
Causes
Effects• Rebooting of computers and similar• Loss of data• Light flashing
• Short circuits• Overload• Load variations
Voltage variations ± 10%
+10 % / -15 %
© 2007 Fluke Corporation. All rights reserved.38
PQ Solutions
A quick look into possible solutions and techniques
© 2007 Fluke Corporation. All rights reserved.39
Branch Circuit Solutions:Performance Wiring
Limit length of feeder and branch runs
Eliminate shared neutralsMax of 3 outlets per branch
Dedicated circuits for problem loads
© 2007 Fluke Corporation. All rights reserved.40
Sources of Noise: Ground Loops
© 2007 Fluke Corporation. All rights reserved.41
Bubble Principle
© 2007 Fluke Corporation. All rights reserved.42
The insidious 3rd harmonic
On a three-phase / four-wire system, triplen (zero sequence) harmonics will add up in the neutral.
This is true for all triplen harmonics including 6th, 9th, 12th, 15th
-400-300-200-100
0100200300400
0 90 180 270 360
-400-300-200-100
0100200300400
0 90 180 270 360
-400-300-200-100
0100200300400
0 90 180 270 360
The third harmonics are all in phase and create unbalance
© 2007 Fluke Corporation. All rights reserved.43
What to check? • Motors, transformers and neutral conductors serving
electronic loadsHow much is ok?
• Voltage distortion (THD) should be investigated if it is over 5 % on any phase
• Some current distortion (THD) is normal on any part of the system serving electronic loads
• Monitor current levels and temperature at transformers to be sure that they are not overstressed
• Neutral current should not exceed the capacity of the neutral conductor
When is distortion a problem?
© 2007 Fluke Corporation. All rights reserved.44
• Replace overheating transformers with higher K-factor rated units
• Reduce load on overheating transformers
• Rewire or redistribute loads to reduce source impedance and isolate non-linear loads
• Passive filters
• Active filters
• Zig-zag transformer or zero sequence filter
• Larger conductors will have lower source impedance - less prone to voltage distortion
• Double the size of neutral or pull parallel neutral cable to handle triplens
Solutions to harmonics problems
© 2007 Fluke Corporation. All rights reserved.45
Transformer Derating Curve
© 2007 Fluke Corporation. All rights reserved.46
Separately Derived System
Transformer as SDS• Secondary is source• Lower source impedance• Electrical isolation• Ground reference
© 2007 Fluke Corporation. All rights reserved.47
Single-point ground: single N-G bond at the source
Correct Grounding of SDS
© 2007 Fluke Corporation. All rights reserved.48
Lightning Protection
© 2007 Fluke Corporation. All rights reserved.49
Transients
Causes of transients:• Utility transformer tap switching• Capacitors switching on• Lightning• Motors switching off • Switch and relay contact “bounce”Effects of transients:• Damage semiconductor junctions• Damage Insulation• Couple into adjacent circuits because of high
frequency (fast rise times)• Corrupt data signals
© 2007 Fluke Corporation. All rights reserved.50
Transient waveform capture
• Set a tolerance around an ideal sinewave
• Any event that goes outside the envelope triggers the instrument to capture the waveform
• Products that do peak detect via capacitor charging do not.
Most instruments that support transient capture use Envelope Triggering
© 2007 Fluke Corporation. All rights reserved.51
Reading the waveforms
Capacitive transients will exhibit some ringing
Switching and lightning transients usually show a single prominent spike with a fast decay
© 2007 Fluke Corporation. All rights reserved.52
• Transient Voltage Surge Suppressors (TVSS)• Uninterruptible power supply with built-in surge
suppression• Isolation transformer
Protecting against transients
© 2007 Fluke Corporation. All rights reserved.53
Motors: Inrush Current
•Nuisance breaker tripping•Voltage sags
© 2007 Fluke Corporation. All rights reserved.54
Application notes
© 2007 Fluke Corporation. All rights reserved.55
Summary & Questions
• Importance of understanding the standards.• How they effect our business• How they effect the customer• The benefit of our product to the customer
• Being able to relate to the customer.• Know the terminology or lingo• Understand what the customer is trying to relate• Recognize what you see and hear