ADPH LSC June 2011

24
Alabama Department of Public Health June 21, 2011 Life Safety Code Presentation 1 Candy Easterling K-063 Adequate and Reliable Water Supply for the Sprinkler System CITY WATER or WATER TANK for Sprinkler System

Transcript of ADPH LSC June 2011

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 1

Candy Easterling

K-063Adequate and Reliable Water Supply for the Sprinkler System

CITY WATER or WATER TANK forSprinkler System

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 2

K-0642000 NFPA 101, 21.3.5.2, 2000 NFPA 101, 9.7.4.1

►Inspected monthly

►Annual maintenance

►Wall mounted or in a fire

Fire Extinguishers

►Wall mounted or in a fire extinguisher cabinet

1998 NFPA 10, 1-6.10 Fire extinguishers having a gross weight not exceeding 40 lb (18.14 kg) shall be installed so that the top of the fire extinguisher is not more than 5 ft (1.53 m) above the floor.

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 3

K-066

Smoking Regulations

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 4

K-067

Heating Ventilating and Heating, Ventilating, and Air Conditioning Systems (HVAC)

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 5

K-068

C b ti d Combustion and Ventilation Air

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 6

K-069 # 8 Tag

Commercial Kitchen Equipment

1998 NFPA 96

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 7

K-070

P t bl S H ti Portable Space Heating Devices

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 8

K-071

Trash Chutes, Trash Chutes, Incinerators andLaundry Chutes

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 9

K-160

Existing Elevators t li 25 f t traveling 25 feet or more must have recall capability.

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 10

K-161

E i ti D b itExisting Dumbwaiters

K-072

Unobstructed Means of EEgress

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 11

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 12

K-073

No Highly FlammableNo Highly FlammableFurnishings or Decorations

K-074

Draperies, Curtains and Cubicle Curtains

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 13

K-075

Soiled Linen or Soiled Linen or Trash CollectionReceptacles

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 14

Laboratories Section –

K31, K136, K131, K132, K133 K134 and K135K133, K134, and K135

We are not aware of any in Alabama nursing facilities.

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 15

K-076

M di l G C li dMedical Gas Cylinders1999 NFPA 99, 4-3.1.1.2 & CGA G-4, 4.1.10 &

1999 NFPA 99, 4-3.5.2.2(b)2 &

1999 NFPA 99, 4-5.5.2.2(b)2

Cylinders secure

Separate Full & Empty

K-076

Separate Full & Empty

Electrical – at least 5 feet above the floor

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 16

K-077

Piped Medical Gas Piped Medical Gas Systems

1999 NFPA 99, 4-3.5.2.3 Patient Gas Systems - Level 1

(a) * Piping systems shall not be used for the distribution of flammable anesthetic gases.(b) Nonflammable medical gas systems used to supply gases for respiratory therapy shall be installed in accordance with 4-3.1 of this chapter.(c) Maintenance programs in accordance with the(c) Maintenance programs in accordance with the manufacturers’ recommendations shall be established for the medical air compressor supply system as connected in each individual installation.(d) * The responsible authority of the facility shall establish procedures to ensure that all signal warnings are promptly evaluated and that all necessary measures are taken to reestablish the proper functions of the medical gas system.

Continued

(e) Piping systems for gases shall not be used as a grounding electrode.(f) The facility shall have the capability and organization to implement a plan to cope with a complete loss of any medical gas system.(g) A periodic testing procedure for nonflammable medical gas and related alarm systems shall be implemented.(h) Th t t ifi d i 4 3 4 1 3(i) h ll b d t d th(h) The test specified in 4-3.4.1.3(i) shall be conducted on the

downstream portions of the medical gas piping system whenever a system is breached or whenever modifications are made or maintenance performed.

(i) * Periodic retesting of audible and visual alarm indicators shall be performed to determine that they are functioning properly, and records of the test shall be maintained until the next test.

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 17

Periodic InspectionsExisting medical gas system performance testing: 1. Each medical gas outlet within the facility is tested for flow capability. 2. All area alarm panels are simulated and adjusted where possible. 3. All medical gas sources of supply are inspected and master alarm conditions simulated to ensure proper function. 4. Zonal pressure testing is applied to the medical gas systems to determine the condition of the piping seal. 5. Particulate filter testing is performed upon each system to determine contamination levels.

K-078

Anesthetizing LocationsLocationsNot Applicable in Nursing Facilities

K-140

Medical GasAlarm SystemsAlarm SystemsNot Applicable in our Nursing Facilities

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 18

K-141“No Smoking” signs No Smoking signs where oxygen is being stored or used

K-142

Hyperbaric FacilitiesypNot Applicable in Nursing Facilities

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 19

K-143

Transferring Oxygen

K-106Type I EES powered by generator is required if life support equipment is life support equipment is used.Rare in Alabama Nursing Facilities.

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 20

K‐144 Generator Weekly Inspections

1999 NFPA 110, 6‐4.1   Level 1 and Level 2 EPSSs, including all appurtenant components, shall be inspected weekly and shall be exercised under load at least monthly.

K‐144 Generator Weekly Inspections

1999 NFPA 110, 6‐3.4   A written record of the EPSS inspections, tests, exercising, operation, and repairs shall be maintained on the premises. The written record shall include the following:(a) The date of the maintenance report(b) Identification of the servicing personnel(c) Notation of any unsatisfactory condition and the corrective action taken, including parts replaced(d) Testing of any repair for the appropriate time as recommended by the manufacturer

K-145

Type I EES divided into b hbranches

Rare in Alabama Nursing Facilities.

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 21

Alternate Source of

K-146 # 9 Tag

Alternate Source of Power

K-146 Generator Remote Annunciator1999 NFPA 99, 3‐4.1.1.15:   A  remote annunciator, storage battery powered, shall be provided to operate outside of the generating room in a location readily observed by operating personnel at a regular work station (see NFPA 70, National Electric Code, Section 700‐12).

1999 NFPA 99, 3‐4.1.1.15 (continued):  The annunciator shall indicate alarm conditions of the emergency or auxiliary power source as follows:

(a) Individual visual signals shall indicate the following:

K-146 Generator Remote Annunciator

(a) Individual visual signals shall indicate the following:

1. When emergency or auxiliary power source is operating to supply power to load

2. When battery charger is malfunctioning

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 22

(b) Individual visual signals plus a common audible signal  to warn of an engine‐ generator alarm condition shall indicate the following:

1. Low lubricating oil pressure

K-146 Generator Remote Annunciator

2. Low water temperature (below those required in 3‐4.1.1.9)

3. Excessive water temperature4. Low fuel ‐ when main fuel storage tank contains 

less than a 3‐hour operating supply5. Over crank (failed to start)6. Overspeed

K-147 # 4 Tag

Electrical Wiring and Electrical Wiring and Equipment

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 23

Clearance at electrical panels

K-130

MiscellaneousMiscellaneous

Alabama Department of Public Health June 21, 2011

Life Safety Code Presentation 24

Question # 4

Q i # 4Question # 4 continued