ADDENDUM NUMBER ONE To the Drawings Dated: 23 May 2016 Entitled: GRADY Atlanta, Georgia Minor Renovations Projects- Cardiology Expansion Prepared By: BSA LIFESTRUCTURES 3348 Peachtree Road NE Suite 1460 Atlanta, GA 30326 __________________________________ Joseph I. Mynhier Georgia Certificate No. 013741 Addendum Dated: 23 May 2016 Project Number: 17220004

Transcript of ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby...

Page 1: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

ADDENDUM NUMBER ONE

To the Drawings

Dated: 23 May 2016

Entitled:

GRADY

Atlanta, Georgia

Minor Renovations Projects- Cardiology Expansion

Prepared By:

BSA LIFESTRUCTURES

3348 Peachtree Road NE Suite 1460

Atlanta, GA 30326

__________________________________

Joseph I. Mynhier

Georgia Certificate No. 013741

Addendum Dated: 23 May 2016

Project Number: 17220004

Page 2: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

GRADY ADDENDUM NUMBER ONE

Atlanta, Georgia

Cardiology Expansion

BSA LifeStructures #17220004 Page 1

CHANGES TO DRAWINGS

1. DRAWING A 100:

a. A cubicle curtain specification section was added.

2. DRAWING A 101:

a. A note on Detail 3 has changed.

b. Elevation 5 – Casework Rm 2E307 has changed.

c. The Second Floor Architectural Plan has changed to show the sink at a new location.

END OF ADDENDUM NUMBER ONE

Attachments:

A100, A101

Newcomb and Boyd Addendum One

Page 3: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

www.bsalifestructures.com

3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326

ph 404.814.9090 fx 317.819.7288

80 JESSE HILL JR DRIVE SEATLANTA, GA 30303

ISSUE FORCONSTRUCTIONFEB 21 201617220004

CONSTRUCTION DOCUMENTS

CARDIOLOGY EXPANSION

01 - ARCHITECTURE

A100 LOCATION PLAN/ SPECS

A 101 ARCH PLAN / ELEVATIONS / DETAILS/ FINISHES

DRAWING INDEX - BP1

05 - PLUMBING

P001 PLUMBING SPECIFICATIONS AND LEGEND

P101 PLUMBING SECOND FLOOR PLAN

06 - ELECTRICAL

E101 ELECTRICAL POWER SECOND FLOOR PLAN

PF # F 2015 010

GRADY PROJECT MANAGER:

TYRONE WILLIAMSFACILITIES DEVELOPMENTTel: 404 616 9650Cell: 404 717 0882Email: [email protected]

Page 4: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

ROOF

ROOF

LIGHT WELL

LIGHT WELL

LIGHT WELL

LIGHT WELL

LOCKER

ROOM

SUPPLIES

2A01

4

2A01

5

2A01

7

TOILET

2A01

9A

E262

E261

E263

E257

E231

E232

E233

E234 E235 E236 E237 E238

E272E271E269E267E266E264

E253

E254

E250

E241

2E038

2E037

E223

E224

E222

E229

E228

E221 E219 E218

E227-1

E212 E214E216 E215

E227

E230

E286E282

E283

E286-1

E287

E281

E288

2E100

E280E278-1 E278 E275 E274 E273E203

EXAM 1

ALCOVE

EXAM 2 EXAM 3 EXAM 4 EXAM 5

EQUIP

RR

SUPPLY

STATION

ATTENDING EXAM 6

NURSES

EXAM 7

ALCOVE

SUPPLY

EXAM 8 EXAM 9 EXAM 10 EXAM 11 EXAM 12

EQUIP

REGISTRATION REGISTRATION

WAITING ROOM

CARDIACCARDIAC CARDIAC CARDIAC CARDIAC

CARDIAC

CARDIACCARDIACCARDIACCARDIACCARDIAC

CARDIAC ENTRYEXIT

ROOMCONFERENCE

REHABILITATIONCARDIAC

(FUTURE)

E220

OFFICEMANAGER

OFFICEPHYSICIAN

LOCKER ROOMSTAFF

EXAM 13HOLDINGCLEAN

HOLDINGSOILED

FILE ROOMCARDIAC

ROOM

OFFICE

FAX

FAX

FILE

COPY/

COPY/

CARDIAC

EKG

ATTENDING OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ECHO TECH EXAM 2EXAM 1

WORKROOM

EXAM 1EKG

EXAM 2EKG

OFFICE

EQUIPMENT

SUPPLY

EDIT/

OFFICE

LOCKERSSTAFF

GARAGECART

EXAM 14CLASSROOMOFFICE & SUPPLYEDUCATION PATIENT EDU CARDIAC ECHO ECHO

HOLTER

P13

ALLSPICE CA F E

2B044

2B046

2B047

2B045

2B043

2B042

2E027

2B054

2B075

2B076

2B073

2B074

2B049

2B048

2B051

2B050

2B052

2B071

2B068

2B077

2B069

2B067

2B066

2B064

2B065

2B063

2B056

2B055

2B057

2E106

2B058

2B062

2A002

2B061

2A006

2A000

2A010

2A004

2A003

2A005

2A009

2A007

2A008

2E108

2E011

2E012

2E107

2E104

2E008

2E014

2E006

2E013

2E015

2E114

2E017

2E016 2E021

2E018

2E023

2E004

2E005

2E003

2E025

2E024

2E022

2E026

2A013

E297

MECH (AC #12)

E255

CORRIDOR

CORRIDOR

E217

MECH

2E088

MECH

FE

FE

J.C

COMM

ASSIST.

SPEC.

DIR.

DEV.

P.R.

ROOM

WORK

DIR.

P.R.

P.R.

SPEC.

CLOTHING

VOLUNTEERS'

STORAGE

ELEC.

CLOSET

ADMINISTRATIVE OFFICES

COPY/FAX

STORAGE

STORAGE

VISITOR

ELEVATOR

LOBBY

ELEC.

COMM

P.R.

ASSIST.

P.R.

SEC'Y

SEC'Y

DIR.

VOL.

DIRECTOR

SEC'Y.

CORRIDOR

DRG. STOR.

DRG. STAFF

WKRM.

ENTRY/

P-16

ELEV

DRG.

E.A.N.

DRG. MGR

DRG. STAFF

OFFICE

SEC'Y

ASSIST.

ASSIST.

VOL.

DIR.

VOL.

TLT.

EXIST. P.S.

MECH

ELEV

ELEV

P-1

P-2

LOBBY

ELEVATOR

SERVING

CAFETERIA

CAFETERIA

SERVING

CREDIT UNION

SPACE

PIPE

CORRIDOR

SE-3

ELEV

VENT SHAFT ELEC. ROOM

SE-4

ELEV

DIRECTOR

OFFICE

ROOM

CONFERENCE

COSTELLO

ELEVATORS

STORAGE

VISITOR

LOBBY

HSKG

ELEVATOR

VISITOR

P-19

STORAGE

ELEV

P-4

ELEV

P-3

STORAGE

TLT

EXIST. P.S.

CORRIDOR

COMM.

ELEC

CLINICAL SPEC.

STAFF DEV/

PROJ. (1) &

SPECIAL

(2)

DISHWASHING

CLOSET

COMMUN.

PAPER

STORES

PARK

DISH

VEST SUPR.

OFFICE

CASHIER

OFFICE

AND SVR

WALK-IN

REF.

SPACE

PIPE

MGR'S

KITCHEN

OFFICE

PREP

AREA

VENDOR

WAITING

OFFICE

ASSIST.

MGR.

P.S.

TOILET

ROOM

ELEV.

SE-4

SE-3

VENT SHAFT ELEV.

E-CORRIDOR

2E027

MEDICAL RECORDS

CLO.

ROOM

COMMUN

TRASH RM

STAIR #4

NURSING DIVISION OFFICES-

SE5/T1

STAIR-6

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

PROCEDURAL

WAITING

2A01

9

PSFE

PS

F E

PS

FE

FE

PS

PS

FE

PS

FE

PS

FE

FE

G

R

F

PS FE

PS F E

E F

B A

E E FG H K

L

LAB

C D

KEY PLAN

Newcomb&&&&Boyd

www.bsalifestructures.com

3340 Peachtree Road NE, Suite 1800

Atlanta, GA 30326

ph 404.814.9090

DATE

COORD

DRAWN

APPROVED

CLIENT NO.PROJECT NO.

KEYPLANPLAN NORTH

Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401

17220004

FEB 21 2016

A100

LOCATION PLAN/SPECS

0000

ISSUE FORCONSTRUCTION

CARDIOLOGY EXPANSION

1/32" = 1'-0"1

LOCATION PLAN - SECOND FLOOR

MARK DATE DESCRIPTION1 4/28/16 Addendum 1

1

Page 5: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

CARDIACREHABILITATION

2E037

CONFERENCEROOM

2E038

EKG EXAM 1

E288

EKG EXAM 2

E280

EKG EXAM 3

E287

EKG EXAM 4

E281

SUPPLY

E286-1

A101

1

1

2

4

HOLTEREQUIPMENT

PROCEDURE

E282

A1014

A2.1

ALIGN

A101

6

5

5

3 5

5

APPROX. LOCATION OF TEMP. WALL

APPROX. LOCATIONOF TEMP WALL

5

6

5' -

2"

10' - 7"

9' -

8"

6' - 0 1/2"

1

7

EQ EQ EQ

3' -

0"

1' -

8"

4' - 2 1/4"

1' - 9"

7

6

5

3

2' -

6"

11/4"

2

A101

TYP

11

7

7

3

A101

TYP

1

A000 2

3

4

XX

ARCHITECTURAL SYMBOLS LEGEND

NEW COLUMN LINE

SECTION INDICATOR

DETAIL INDICATORAREA OFDETAIL

DETAIL NUMBER

SHEET NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

PLAN NOTE DESIGNATION

EQUIPMENT DESIGNATION. REFERTO EQUIPMENT SCHEDULE.

CORNER GUARD (REFER TOFINISH PLANS)

ELEVATION TAG

FIRE EXTINGUISHER CABINETF.E.C.

CG

GENERAL ARCHITECTURAL NOTES

A101

1 SIM SIMILAR

1

A101

SIM

000

ROOM

000

1

A. PROVIDE 18" MINIMUM ADA REQUIRED CLEARANCE ADJACENTTO STRIKE OF DOOR.

B. WORK AT DOORWAYS MUST BE COORDINATED WITH THEOWNER. DOORS MUST BE IN PLACE DURING BUSINESS HOURS

C. CONTRACTOR WILL COORDINATE ACCESS TO WORK AREASWITH THE OWNER AND SHALL NOT LEAVE WORK AREAUNPROTECTED DURING BUSINESS HOURS.

D. CONTRACTOR SHALL CONFIRM FINAL LOCATIONS OFTEMPORARY WALLS WITH OWNER.

SOLID 2XWOOD BLOCKING

WALL BASE. REFER TO INTERIORFINISH NOTES

SOLID SURFACE (SS-1 U.N.O.) SCRIBEDTO WALL WITH EASED EDGE ON 3/4"PLYWOOD.1

1/2"

ADA ACCESSIBLE LAMINATE ENCLOSUREPANEL. PROVIDE REMOVABLE ACCESSPANEL AT SINK LOCATIONS FOR PLUMBING.USE CONCEALED FASTENERS WHEREPOSSIBLE.

2' -

10"

1"

UNDER MOUNTED SINK FIXTURE.REFER TO PLUMBING DRAWINGS

9"1'

- 6

"

5 1/

2"

HATCHED AREA INDICATES ADACLEARANCE.

ADA TOE CLEARANCE.

CABINET PULL

ADJUSTABLE SHELF WITHPLASTIC LAMINATE ON ALLSURFACES.

CABINET DOOR. LOCKABLE WHEREINDICATED ON INTERIOR ELEVATIONS.

SOLID 2X6WOOD BLOCKING

HARDWOOD MOUNTING STRIPS

6" 1/2"

1 1/

2"

TY

P.

4"

CABINET PULL

CABINET DOOR

DRAWER

SOLID 2XWOOD BLOCKING

HARDWOOD MOUNTING STRIPS

WALL BASE. REFER TO INTERIORFINISH DRAWINGS.

SOLID SURFACE (SS1) (U.N.O.) WITHDOUBLE EASED EDGE ON 3/4" PLYWOODWITH INTEGRAL BACKSPLASH AND SINKWHERE INDICATED. PROVIDE SIDESPLASHWHERE SURFACE ABUTS A WALL

3' -

0"

A.F

.F. (

TY

P.)

TO

P O

F C

AB

INE

T:

7' -

2"

A.F

.F. (

TY

P.)

2' - 1" OR 2' - 6"

GENERAL WALL TYPE NOTES

A. DIMENSIONS IN PLAN AND ELEVATION ARE TAKEN TO THE FACE OF FINISHDRYWALL, FACE OF EXPOSED MASONRY, CONCRETE, OR CENTER LINE OFCOLUMN, UNLESS NOTED OTHERWISE.

B. ALL INTERIOR WALLS SHALL BE TYPE 'B2.1' UNLESS NOTED OTHERWISE.

1. INDICATES ENTIRE WALL CONSTRUCTION TO STOP 6" ABOVE FINISHEDCEILING.

WALL TYPE SYMBOL

X1.1x

INDICATES CONSTRUCTION TYPE

NUMERICAL INDICATION OF STUD/MASONRY SIZE

SUFFIX INDICATES MODIFICATIONS TO WALLCONSTRUCTION HEIGHT

SUFFIX INDICATES HORIZONTALMODIFICATIONS

WALL TYPES SUFFIX

A2 WALL PARTITION1 1/2" = 1'-0"

BASE SECTION

PLAN SECTION

HEAD SECTION

A2-2 1/2" METAL STUDS

BASE: REFER TO FINISHDRAWINGS

FLOOR: REFER TO FINISHDRAWINGS

1/2" SEALANT SPACE

STEEL STUD RUNNER TRACK.STUDS SCREWED AT BOTTOM

FLOOR SLAB

5/8" GYPSUM WALL BOARD

METAL STUDS (REFERTO CHART BELOW)

TRACK

FASTEN GYPSUM BOARDTO STUDS NOT TO THETOP TRACK

NON-RATED

SOUND ATTENUATIONBATTS

16 GAUGE HORIZONTALSTEEL STRAPS AT 32"O.C. VERTICALLY.ANCHOR TO EACH STUD.

5/8"

FINISH CEILING. REFERTO REFLECTED CEILINGPLAN.

6" M

IN

2 1/2"

ELEVATION SYMBOL LEGEND

GENERAL ELEVATION NOTES

A. ALL DIMENSIONS ARE TAKEN TO THE FACE OF FINISHED MATERIAL.B. INSTALL WOOD BLOCKING TO STUDS TO SUPPORT ALL WALL-MOUNTED

CABINETRY AND EQUIPMENT AS REQUIRED.C. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO

CONSTRUCTING CABINETRY.D. ALL BASE CABINETS SHALL BE 2'-0" DEEP UNLESS NOTED OTHERWISE.E. ALL CASEWORK SHALL BE FINISHED IN PLASTIC LAMINATE UNLESS

NOTED OTHERWISE.F. PROVIDE FILLER PANELS AT ALL LOCATIONS WHERE CABINETRY ABUTS

A WALL.G. PROVIDE A 4" HIGH INTEGRAL BACK SPLASH ON ALL COUNTERS WITH

RECESSED SINKS. INSTALL SIDE SPLASHES WHERE THESE COUNTERSABUT A WALL.

H. PROVIDE ADJUSTABLE SHELVING WITHIN ALL WALL AND BASECABINETRY AS SHOWN BY DASHED LINE.

I. PROVIDE 12" CLEAR INTERIOR DIMENSION ON ALL UPPER WALLCABINETS UNLESS NOTED OTHERWISE.

J. CONSTRUCT GYPSUM DRYWALL BULKHEADS ABOVE UPPER CABINETRYTO BE 1" DEEPER AND LONGER THAN CABINETRY BELOW UNLESSINDICATED OTHERWISE.

K. COORDINATE ALL WALL OUTLETS TO AVOID CONFLICT WITH CASEWORK.L. PAINTING CONTRACTOR IS TO STENCIL WALL RATING ON WALLS

INDICATED AS RATED ABOVE THE CEILING ON 20'-30' INTERVALS.

XX NEW COLUMN LINE

SECTION INDICATOR

DETAIL INDICATORAREA OFDETAIL

DETAIL NUMBER

SHEET NUMBER

ELEVATION NOTE DESIGNATION

A101

1 SIM SIMILAR

1

A101

SIM

1

1

A000 2

3

4 ELEVATION TAG

6"3"

8"3'

- 7

"2'

- 9

"9

10

6

1

3

7

12

12

VIF

2' - 5 3/4"

3

A101

TYP

Newcomb&&&&Boyd

www.bsalifestructures.com

3340 Peachtree Road NE, Suite 1800

Atlanta, GA 30326

ph 404.814.9090

DATE

COORD

DRAWN

APPROVED

CLIENT NO.PROJECT NO.

PLAN NORTH

Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401

17220004

FEB 21 2016

A101

ARCH PLAN/ ELEVATIONS/DETAILS

0000

ISSUE FORCONSTRUCTION

CARDIOLOGY EXPANSION

NOTES- ARCHITECTURAL PLAN** NOT ALL NOTES APPEAR ON EACH SHEET

1 NEW WALL HUNG SINK. SEE PLUMBING DRAWINGS

2 LOCATION OF NEW CARD READER. SEE ELECTRICAL DRAWINGS

3 NEW CASEWORK AND SINK. SEE ELEVATION

4 NEW GLASS VISION SLIT IN EXISTING DOOR

5 REPAINT ALL DISTURBED WALL SURFACES TO MATCH EXISTING

6 REMOVE ONLY CABINETS NEEDED FOR ADA ACCESSIBLE BASE. NEW SINKWITH ADA ACCESSBILITY.

7 REMOVE EXISTING COUNTER TOP. REPLACE WITH NEW SOLID SURFACECOUNTERTOP

NOTES- INTERIOR ELEVATION** NOT ALL NOTES APPEAR ON EACH SHEET

1 4" RESILIENT BASE

2 25" DEEP (UNO) PLASTIC LAMINATE (PL1 UNO) COUNTERTOP WITH SIDEAND BACK SPLASHES, AS INDICATED.

3 25" DEEP (UNO) SOLID SURFACE (SS1 UNO) COUNTERTOP WITH SIDE ANDBACK SPLASHES, AS INDICATED.

4 24" DEEP (PL-1 UNO) BASE CABINET; CONFIGURE DOOR(S), DRAWER(S),AND SHELVE(S) AS INDICATED.

5 15" DEEP (PL-1 UNO) WALL CABINET; CONFIGURE DOOR(S), SHELVE(S)AND LIGHT SKIRT(S) AS INDICATED.

6 ACESSIBLE (BARRIER FREE) SINK SKIRT ASSEMBLY.

7 FINISHED END PANEL.

8 COUNTER SUPPORT BRACKET @ 48" O.C. MAXIMUM.

9 EXISTING DOOR

10 NEW 1/4" CLEAR TEMPERED GLASS

11 LAMINATE CASEWORK BULKHEAD. TO MATCH CABINETS

12 EXISTING CASEWORK TO REMAIN

1/8" = 1'-0"1

SECOND FLOOR ARCHITECTURAL PLAN(EKG)

1/4" = 1'-0"4

CASEWORK RM. E282

3/4" = 1'-0"3

ADA SINK DETAIL

3/4" = 1'-0"2

CABINET DETAIL

INTERIORS- FINISH SPECIFICATIONS

MARK:MANUFACTU

RER: STYLE: NUMBER: COLOR: SIZE: COMMENTS: CONTACT:

PL-1

SS-1

Wilsonart 7935-7 Shaker Cherry

Corian WhitecapN/A

1/4" = 1'-0"6

EXISTING DOORRB-1 Johnsonite Stone80 4"

N/A

N/AN/A

N/A

N/A

MARK DATE DESCRIPTION1 4/28/16 Addendum 1

1/4" = 1'-0"5

CASEWORK RM 2E307

1

1

Page 6: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

ADDENDUM NO. 1

April 28, 2016

EKG EXPANSION

Notice to Contractors

This Addendum has become a part of the drawings and specifications for the above project dated

04/28/2016.

Failure for a bidder to acknowledge receipt of this Addendum on the Proposal may be sufficient

cause for rejection of the Bid.

Addendum 1 includes the following documents:

DRAWING CHANGES

1. Sheet E101 - ELECTRICAL POWER SECOND FLOOR PLAN, added power and data in

Cardiac Rehabilitation 2E037.

2. Sheet P101 - PLUMBING SECOND FLOOR PLAN, relocated sink in Cardiac

Rehabilitation 2E037.

END ADDENDUM NO.1

Page 7: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

PLUMBING SPECIFICATIONSPLUMBING LEGEND

PLUMBING NOTES AND SPECIFICATIONS:

1. FURNISH ALL LABOR, MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH

ALL NATIONAL, STATE AND LOCAL CODES.

2. FURNISH AND INSTALL ALL SYSTEMS OF SOIL, WASTE, AND VENT PIPING, HOT & COLD WATER PIPING, AND DRAINAGE

PIPING INCLUDING ALL FITTINGS, VALVES, ETC. AS REQUIRED.

3. FURNISH AND INSTALL ALL PLUMBING FIXTURES AND EQUIPMENT AS SHOWN ON THE DRAWINGS.

4. ALL PLUMBING WORK SHALL BE DONE UNDER THE SUPERVISION OF AND BY LICENSED AND QUALIFIED PLUMBERS, PER

ALL LOCAL, STATE, AND NATIONAL CODES, AND TO THE COMPLETE SATISFACTION OF THE PLUMBING INSPECTOR.

5. SUBMISSION OF A BID OR PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED

HIMSELF WITH THE PLANS, SPECIFICATIONS, AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO BIDS FOR MATERIALS

AND/OR LABOR DUE TO DIFFICULTIES ENCOUNTERED, WILL NOT BE RECOGNIZED, UNLESS DIFFICULTIES COULD NOT HAVE

BEEN FORESEEN EVEN THOUGH PROPER EXAMINATION HAD BEEN MADE.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL UTILITY CONNECTIONS.

7. ALL MATERIALS SHALL BE NEW, CLEAN, AND WITHOUT DEFECTS. ANY DEFECTIVE MATERIALS SHALL BE REMOVED FROM

THE JOB SITE.

8. ALL PLUMBING PIPING SHALL BE CONCEALED WITHIN THE BUILDING STRUCTURE AND ABOVE DROP CEILINGS.

9. ALL HOT AND COLD WATER PIPING, 0.5" TO 2.5", WITH SUPPLY SERVICE TO FIXTURES, SHALL BE COPPER TUBING, TYPE L,

HARD DRAWN, ASTM B88-2009 WITH WROUGHT COPPER SWEAT TYPE FITTINGS, ASME B16.22-2013.

10. ALL HOT WATER PIPING SHALL BE INSULATED WITH 1" THICK PRE-FORMED FOAM PIPE INSULATION, IMCOLOCK OR EQUAL.

INSULATE FITTINGS WITH MITERED SECTIONS.

11. SANITARY, WASTE AND VENT PIPING AND FITTINGS ABOVE GRADE SHALL BE NO HUB CAST IRON, TAR COATED INSIDE AND

OUT, CISPI 301-2012. COUPLINGS SHALL BE HEAVY DUTY MECHANICAL COMPRESSION TYPE; ANACO HUSKY, CLAMP ALL,

OR MG COUPLING.

12. FIXTURE ARMS AND CONNECTIONS SHALL BE COPPER TUBING, TYPE DWV, HARD DRAWN, ASTM B88-2009.

13. CLEANOUT PLUGS SHALL BE INSTALLED IN ACCORDANCE WITH THE PLUMBING CODE REQUIREMENTS, AT EACH CHANGE

OF DIRECTION AND AT THE BASE OF EACH SANITARY STACK. CLEANOUTS SHALL BE PLACED IN READILY ACCESSIBLE

LOCATIONS.

14. INSULATE ALL EXPOSED PIPING UNDER HANDICAPPED LAVATORIES WITH TRU-BRO OR EQUAL.

15. FIRESTOPS SHALL BE PROSET "FIRESTOP PENETRATORS" OR APPROVED EQUAL.

16. PROVIDE WATTS MODEL 15 WATER HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED. INSTALL PER

MANUFACTURERS SPECIFICATIONS. MODEL 15 ARRESTORS MEET ASSE STANDARD 1010.

17. UPON COMPLETION OF THE WORK, TEST ALL PIPING SYSTEMS AS FOLLOWS:

A. DRAINAGE SYSTEMS INCLUDING SANITARY SEWERS AND SANITARY VENTS: PLUG LOW POINTS OF

SYSTEM AND FILL WITH WATER TO UPPERMOST OUTLET UP TO TWELVE (12) FEET HIGH, WHICHEVER IS

LOWER. LET SYSTEM STAND FULL OF WATER WITH NO INDICATIONS OF LEAKS FOR 12 HOURS.

B. DOMESTIC HOT AND COLD WATER: 150 PSIG HYDROSTATIC TEST. HOLD HYDROSTATIC TESTS FOR A

MINIMUM OF EIGHT (8) HOURS WITHOUT LOSS OF PRESSURE. HOLD AIR TESTS FOR A MINIMUM OF ONE

HOUR WITHOUT SIGNIFICANT LOSS OF PRESSURE.

18. RETESTING: RETEST PIPING FAILING INITIAL TESTS FOLLOWING CORRECTION OF DEFECTIVE WORK. REQUIREMENTS OF

INITIAL TESTS SHALL APPLY.

19. DISINFECT WATER SYSTEM AS OUTLINED BY SECTION 610 IN THE INTERNATIONAL PLUMBING CODE.

20. PROVIDE FULL-OPEN VALVES IN ACCORDANCE WITH SECTION 606.1 OF THE INTERNATIONAL PLUMBING CODE.

PLUMBING FIXTURES:

F2 LAVATORY (ADA) - VITREOUS CHINA LAVATORY, 20"x18", WITH 8" CENTERS AND FITTED WITH FAUCET,

SUPPLIES WITH STOP VALVES, GRID DRAIN, P-TRAP, WASTE TO WALL, ESCUTCHEONS, ADA INSULATION AND FLOOR

MOUNTED CARRIER WITH CONCEALED ARM SUPPORTS - AMERICAN STANDARD 0356-015 ; FAUCET SHALL BE DUAL

HANDLE TYPE, POLISHED CHROMIUM-PLATED BRASS BODY WITH GOOSENECK SPOUT, 4" BRASS BLADE HANDLES,

COLOR CODED INDEXES, QUARTER TURN CERAMIC CARTRIDGES, 0.5" RIGID BRASS INLET SHANKS ON 8" CENTERS,

AND 0.5 GPM VANDAL RESISTANT AERATOR FLOW CONTROL - MOEN 8248 ; FLOOR MOUNTED CARRIER SHALL BE

SMITH OR EQUAL BY JOSAM, WADE OR ZURN.

F6 SINK (ADA) - UNDERMOUNT 18 GAUGE TYPE 304 STAINLESS STEEL ONE BOWL SINK, 16"x20"x5.5", FAUCET, SUPPLIES

WITH STOP VALVES, REAR DRAIN, P-TRAP WITH OFFSET, WASTE TO WALL, ADA INSULATION AND ESCUTCHEONS -

ELKAY ELUHAD1418 OR EQUAL BY JUST; FAUCET SHALL BE DUAL HANDLE TYPE, POLISHED CHROMIUM-

PLATED BRASS BLADE HANDLES, COLOR CODED INDEXES, QUARTER TURN CERAMIC CARTRIDGES, O.5" RIGID BRASS

INLET SHANKS ON 8" CENTERS, AND 1.5 GPM VANDAL RESISTANT AERATOR FLOW CONTROL - MOEN 8248 .

ABBREVIATIONS

ABOVEABV

ABOVE CEILINGAC

ARCH ARCHITECT/ARCHITECTURAL

BEL BELOW

BF BELOW FLOOR

CLG CEILING

CONC CONCRETE

CONN CONNECT/CONNECTION

CONT CONTINUATION/CONTINUOUS

DOWNDN

DWG DRAWING

ELEC ELECTRICAL/ELECTRIC

EXP EXPOSED

FL FLOOR

GR GRADE

LV LAVATORY

MECH MECHANICAL

PDI PLUMBING AND DRAINAGE INSTITUTE

SPEC SPECIFICATION

SSTL STAINLESS STEEL

TEMP TEMPERATURE

TS TIGHT TO STRUCTURE

UC UNDERCOUNTER

VB VACUUM BREAKER

ABOVE FINISHED FLOOR/GRADEAFF/AFG

WC WATER CLOSET

R

A-ATMOSPHERIC TYPE; D-DOUBLE CHECK VALVE TYPE).BACKFLOW PREVENTER (R-REDUCED PRESSURE TYPE;

TYPE INDICATED ON SCHEDULE).

PRV-X PRESSURE REDUCING VALVE (X INDICATES THE PRV NUMBER;

A

AS INDICATED ON THE DRAWINGS).

WATER HAMMER ARRESTER (PDI SIZE A, B, C OR D

PRESSURE GAUGE.

THERMOMETER (SEE SPECIFICATIONS FOR TYPE).

TEMPERATURE AND PRESSURE RELIEF VALVE.

CHECK VALVE.

BALL VALVE.

REDUCER - CONCENTRIC.

STRAINER.

BASE CLEANOUT

D INDIRECT DRAIN.

HOT WATER (HW).

COLD WATER (CW).

VENT (V).

SOIL (S) OR WASTE (W) BELOW FLOOR OR GRADE.

SOIL (S) OR WASTE (W) ABOVE FLOOR OR GRADE.

GLOBE VALVE.

CONNECT TO EXISTING.

WM WATER MACHINE

6. INSTALL PIPE I.D. WITH FLOW ARROWS AND INSULATION ON ALL DOMESTICWATER PIPING SYSTEMS THROUGHOUT. LABEL ALL OTHER SYSTEMSCOMPLETE WITH PIPE I.D. AND FLOW ARROWS.

GENERAL NOTES:

THESE DRAWINGS DO NOT PURPORT TO SHOW ALL EXISTING UTILITIES.

ALL EXISTING PIPING THAT IS TO BE CONNECTED INTO OR MODIFIED SHALLBE FIELD CONFIRMED AND VERIFIED BEFORE COMMENCING WORK.

INSULATE ALL DOMESTIC WATER PIPING THROUGHOUT THIS RENOVATION.

MAKE ALL VALVES ACCESSIBLE THROUGHOUT THIS RENOVATION; INSTALLVALVE TAGS.

ANCHOR AND SECURE ALL PIPING IN CHASES AND WALLS THROUGHOUTSO THAT NO MOTION OCCURS AFTER FINISHED WALLS ARE INSTALLED.

5.

4.

3.

2.

1.

7. WHERE THE EXISTING STRUCTURE OR SURROUNDING INTERIOR IS DAMAGEDDURING THIS RENOVATION, THE CONTRACTOR IS RESPONSIBLE TO MAKE ALLNECESSARY REPAIRS TO MATCH THE EXISTING AND SURROUNDINGSURFACES.

8. CONTRACTOR SHALL VERIFY THAT EXISTING WASTE AND WATER PIPINGSHALL BE OF AMPLE SIZE AT NEW WASTE AND WATER CONNECTION POINTSTO EXISTING.

SYMBOLS

9. PROVIDE AND INSTALL ESCUTCHEONS ON ALL VISIBLE PIPE PENETRATIONS

THROUGHOUT THIS PROJECT.

10. PROVIDE AND INSTALL ISOLATION BETWEEN DISSIMILAR METALS, SUCH AS

COPPER TO CAST IRON PIPING.

PLUMBING FIXTURE SCHEDULENO.

F1

F6

FIXTURE TYPE

NOT USED

PIPING CONNECTION SIZE

HW-

CW S OR W

F2 LAVATORY, WALL TYPE, ADA

STAINLESS STEEL SINK, ONE BOWL, UNDERMOUNT, ADA 0.5" 0.5" 1.5"

0.5 1.250.5

0.5" 120°F HW SUPPLY

0.5" CW SUPPLY

3/8" FLEXIBLE RISER

MIXING VALVE, MV-1

0.5" 109°F HWTO LAVATORY

3/8" FLEXIBLE RISER

COUPLING

LAVATORY AND FAUCET (FAUCETDESIGN MAY VARY FROM SPEC)

NOTES:

1. MV-1 FOR SINGLE FIXTURE PER MANUFACTURER'S REQUIREMENTS.

MIXING VALVE SCHEDULE

NO.

MV-1

TYPE

(NOTE 1)SERVICE

DESIGN

GPM

MINIMUM CIRCULATING

FLOW RATE, GPM

PRESSURE DROP,

PSIG

TEMPERATURE

SETTING, °F

T,S FIXTURES 0.5 10 109° POWERS LF e480

NOTES

SINGLE VALVE

THERMOSTATICALLY CONTROLLED1. TYPE:

S

T

NOTES:

0.5

2. MANUFACTURER NOTED FOR BASIS OF DESIGN ONLY.

F3-F5 NOT USED

--

- --

11. CONTRACTOR SHALL PROVIDE ALL TEMPORARY OPENINGS, PENETRATIONS

AND REPAIRS REQUIRED TO COMPLETE THE SCOPE OF WORK, TO INCLUDE

BUT NOT LIMITED TO CEILING REMOVAL, PATCHING AND REPLACEMENT

AND INSTALLATION OF DAMAGED TILES.

1

P001 NO SCALE

PUBLIC LAVATORY/SINK MIXING VALVE

Newcomb&Boyd

9365 Counselors RowIndianapolis, IN 46240-1478

ph 317.819.7878 fx 317.819.7288

www.bsalifestructures.com

DATE

COORD

DRAWN

APPROVED

CLIENT NO.PROJECT NO.

Copyright © 2016Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401Contact:Kidane AbebeN&B PROJECT:15N254

17220004

FEB 21 2016

P001

PLUMBINGSPECIFICATIONS ANDLEGEND

0000

ISSUE FORCONSTRUCTION

JAN 3, 201?JAN 4, 201?JAN 5, 201?JAN 6, 201?JAN 7, 201?

EKG EXPANSION

MARK DATE DESCRIPTION

Page 8: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

CARDIAC

REHABILITATION

2E037

CONFERENCE

ROOM

2E038

Room

Room

Room

EKG EXAM 1

E288

EKG EXAM 2

E280

EKG EXAM 3

E287

EKG EXAM 4

E281

SUPPLY

E286-1

HOLTER

EQUIPMENT PROCEDURE

E282

5

F2

F2

F6

F6

5

7

7

4

4

66

0.5"

0.5" AC

0.5"

0.5"

AC

1

CARDIAC

REHABILITATION

2E037

CONFERENCE

ROOM

2E038

Room

Room

Room

EKG EXAM 1

E288

EKG EXAM 2

E280

EKG EXAM 3

E287

EKG EXAM 4

E281

SUPPLY

E286-1

HOLTER

EQUIPMENT PROCEDURE

E282

3

3

1

1

F2

F2

F6

F6

4"

3"

EX

W

EX

V

EX

W

2"3"

BF

2

W

BF

ACBF

4

4

2"

AC

3"

2"

1

Newcomb&Boyd

9365 Counselors RowIndianapolis, IN 46240-1478

ph 317.819.7878 fx 317.819.7288

www.bsalifestructures.com

DATE

COORD

DRAWN

APPROVED

CLIENT NO.PROJECT NO.

Copyright © 2016Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401Contact:Kidane AbebeN&B PROJECT:15N254

17220004

FEB 21 2016

VZJ

VZJ P101

PLUMBING SECONDFLOOR PLAN

0000

ISSUE FORCONSTRUCTION

EKG EXPANSION

1/8" = 1'-0"1

PLUMBING PRESSURE SECOND FLOOR PLAN 1/8" = 1'-0"

2PLUMBING WASTE SECOND FLOOR PLAN

1 2" WASTE AND VENT.

2 ROUTE 2" VENT PIPING AND CONNECT TO EXISTINGVENT PIPING IN TOILET ROOM CHASE.

3 ROUTE 1.25" WASTE ARM AT NEW LAVATORY ANDCONNECT TO EXISTING WASTE AND VENT PIPING INCHASE FROM EXISTING LAVATORY; ALLOW WASTEARMS IN CHASE TO OFFSET AND CONNECT ATSEPARATE HEIGHTS FOR EASE OF MAINTENANCE;MAINTAIN ADA CLEARANCE FOR WASTE PIPINGBELOW LAVATORY.

4 EXISTING LAVATORY.

REFERENCE NOTES:

5 0.5" HOT AND COLD WATER DROP TO FIXTURE ANDMIXING VALVE MV-1.

6 0.5" HOT AND COLD WATER PIPING SUPPLY TOFIXTURE AND MIXING VALVE MV-1; ROUTE ANDCONNECT TO EXISTING HOT AND COLD WATERSUPPLY PIPING IN CHASE.

7 ROUTE AND CONNECT TO MINIMUM EXISTING 0.75"HOT AND COLD WATER SUPPLY PIPING IN CEILINGSPACE.

MARK DATE DESCRIPTION1 4/28/2016 Addendum 1

Page 9: ADDENDUM NUMBER ONE Dated: 23 May 2016 Entitled: GRADY ... · mech elev elev p-1 p-2 elevator lobby cafeteria serving cafeteria serving credit union pipe space corridor ... ada toe

2D

2D 2D

CARDIAC

REHABILITATION

2E037

CONFERENCE

ROOM

2E038

Room

Room

Room

EKG EXAM 1

E288

EKG EXAM 2

E280

EKG EXAM 3

E287

EKG EXAM 4

E281

SUPPLY

E286-1

HOLTER

EQUIPMENT PROCEDURE

E282

1

1

1

Newcomb&Boyd

9365 Counselors RowIndianapolis, IN 46240-1478

ph 317.819.7878 fx 317.819.7288

www.bsalifestructures.com

DATE

COORD

DRAWN

APPROVED

CLIENT NO.PROJECT NO.

Copyright © 2016Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401Contact:Kidane AbebeN&B PROJECT:15N254

17220004

FEB 21 2016

MBE

ROW E101

ELECTRICAL POWERSECOND FLOOR PLAN

0000

ISSUE FORCONSTRUCTION

EKG EXPANSION

1/8" = 1'-0"1

ELECTRICAL POWER SECOND FLOOR PLAN

1

KEYNOTE: (THIS DRAWING ONLY)

PROVIDE NEW CARD READER. MATCH EXISTING MANUFACTURER AND TYPE.COORDINATE WITH GRADY APPROVED SUB CONTRACTOR. PROVIDE ALLNECESSARY WORK NEEDED TO COORDINATE THE INSTALL OF WIRING, DOORCONTROLS, MAGNETIC LOCK, PROXIMITY SENSOR AND CONNECTION WITH SMOKEDETECTOR AND FIRE ALARM SYSTEMS. DOORS SHALL RELEASE UPON ACTIVATIONOF CARD READER, FIRE ALARM, SMOKE DETECTOR OR PROXIMITY SENSOR.

NEW SINK LOCATION. ALL EXISTING RECEPTACLE OUTLETS INSTALLED WITHIN 6FTOF THE OUTSIDE EDGE OF THE SINK LOCATION SHALL BE REPLACED WITHHOSPITAL GRADE GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLES.RECEPTACLES SHALL BE UL 943-2011 COMPLIANT, 20A, SELF-TESTING, TAMPERRESISTANT, FEED THROUGH TYPE, INDUSTRY MARKED AS "HOSPITAL GRADE".

MANUFACTURER: HUBBELL GF8300SG, LEVITON GFWT2-HG, OR P&S 2097HGTR.

PROVIDE NEW ABOVE THE COUNTER GFCI RECEPTACLE OUTLET. RECEPTACLEOUTLETS SHALL BE HOSPITAL GRADE GROUND FAULT CIRCUIT INTERRUPTER(GFCI) RECEPTACLES. RECEPTACLES SHALL BE UL 943-2011 COMPLIANT, 20A, SELF-TESTING, TAMPER RESISTANT, FEED THROUGH TYPE, INDUSTRY MARKED AS"HOSPITAL GRADE".

MANUFACTURER: HUBBELL GF8300SG, LEVITON GFWT2-HG, OR P&S 2097HGTR.

PROVIDE NEW WALL-MOUNTED HOSPITAL DUPLEX RECEPTACLE OUTLET.RECEPTACLE OUTLETS SHALL BE RATED 20A AND INDUSTRY MARKED AS"HOSPITAL GRADE". MOUNTING STRAP, GROUND CONTACTS, AND POWERCONTACTS SHALL BE NICKEL-PLATED.

MANUFACTURER: HUBBLE HBL8300, LEVITION 8300, OR P&S 8300.

2

1

2

2

2

2

ELECTRICAL LEGEND

CARD READER.

EXISTING RECEPTACLE, REPLACED WITH HOSPITAL GRADEGFCI DUPLEX RECEPTACLE OUTLET, WALL-MOUNTED.

NEW GFCI DUPLEX RECEPTACLE OUTLET, WALL-MOUNTED, ABOVE COUNTER.

HOSPITAL GRADE DUPLEX RECEPTACLE OUTLET, WALL-MOUNTED 18" ABOVEFINISHED FLOOR.

TELECOMMUNITION OUTLET - SINGLE GANG CUT IN RING MOUNTED 18" ABOVEFINISHED FLOOR. ROUTE (2) CATEGORY 6 CABLES TO COMM ROOM.PROVIDE 4 PORT FACEPLATE WITH LABELS.

CR

CR

2

3

3

3

GENERAL NOTES:(THIS DRAWING ONLY)

1. EXISTING WORK SHOWN WITH HALF-TONE LINE WEIGHT

2. NEW WORK SHOWN WITH HEAVIER LINE WEIGHT.

3. SERVE ALL NEW RECEPTACLES FROM EXISTING CIRCUITSERVING THE ROOM.

4. COORDINTATE INSTALLTION OF TELECOMMUNICATION OUTLETS WITHGRADY IT DEPARTMENT. ROUTE CABLES TO COMMUNICATIONSCLOSET DIRECTED BY GRADY IT. PROVIDE ALL EQUIPMENT ANDDEVICES NEEDED FOR A COMPLETE SYSTEM.

MARK DATE DESCRIPTION1 4/28/2016 Addendum 1

4

44

4