    Vibration of steel staircases

    The Advisory Desk has received a number of queries asking for guidance on vi-

    bration of steel staircases. In fact, guidance is already given in several parts of

    SCI publication Design of floors for vibration: A new approach (P354). This AD

    collects that guidance and adds references to other sources of information that

    may be relevant when analysing the vibration behaviour of steel staircases.

    This AD also identifies some other design considerations that may be relevant.

    General approach

    Steel staircases are, by their nature, highly susceptible to vibration as they

    combine low levels of damping (typically 0.5%), low mass and high levels

    of human-induced excitation. The general approach outlined in Chapter 6 of

    SCI P354 can be used to determine the dynamic behaviour of the staircase, but

    clearly the applied forces will be different for people travelling up and down

    staircases than for walking across floors, and acceptable levels of vibration

    also differ.

    Applied Loads

    In P354, the response is determined from the modal properties of the staircase

    (frequencies, modal masses and mode shapes) and the frequency and ampli-

    tude of the applied vertical load. The peak amplitude of the load in each mode

    is generally given in terms of Fourier coefficients, n, which represent the

    proportion of a persons weight that is acting at each harmonic of the activity

    frequency. These Fourier coefficients are given in Human induced loading

    of flexible staircases(Bishop, Willford & Pumphrey, 1995 and Kerr & Bishop,

    2001), and depend on the speed of ascent or descent. ISO 10137: 2007 (Bases

    for design of structures Serviceability of buildings and walkways against

    vibrations) reproduces the worst case of these in Table A.4, and these are also

    given in Table 3.2 of P354 :

    In P354 floors are categorised as either low-frequency or high-frequency, the

    latter case responding to impulsive excitations rather than responding reso-nantly. No specific analysis is given by Bishop et al for the impulsive loads that

    will be experienced by staircases with natural frequencies that exceed the up-

    per limits of the Fourier terms given in ISO 10137. Further Fourier coefficients

    (up to the 6th harmonic) are presented in the paper; these could be used to

    determine a more comprehensive response.

    Acceptability criteria

    Bishop et al. also give guidance on the acceptability criteria for staircases,

    and their research indicates that for multi-person excitation, a maximum mul-

    tiplying factor of 64 applies. Typically this is achieved by designing staircases

    for a limiting multiplying factor of 32 for light use (such as offices) or 24 for

    heavy use (such as public buildings and stadia) under single person excitation

    using the Fourier terms given above. The limits for staircases are higher than

    for floors because the frequency of exposure to staircase vibration is gener-

    ally significantly lower than for a floor, and the audio and visual stimuli that ac-company the movement reduce the associated level of annoyance. For narrow

    staircases with no landings, it is unlikely that there will be stationary people

    on the stairs to receive the vibration, and as vibration is, in the main, a service-

    ability issue, in these cases the level or response is less critical.

    Other design considerations

    An additional design consideration for staircases is to ensure that the interac-tion between a staircase and the floors it links is such that excessive vibration

    does not carry onto the floor plate and therefore affect nearby rooms. This can

    generally be achieved by attaching the staircase in the vicinity of columns,

    and by avoiding features such as cantilever beams which are highly suscepti-

    ble to vibration issues.

    Contact: Andy Smith

    Tel:01344 636530

    Email:[email protected]

    Activity Harmonicnumber, n

    Common range offorcing frequency,nf

    1(Hz)

    Fourier coefficientfor verticaldirection,

    n,v

    Ascending ordescending stairs

    1 1.2 to 4.5 1.1

    2 2.4 to 9.0 0.22