ActivitiesCheclisto7-08_2
Transcript of ActivitiesCheclisto7-08_2
-
8/4/2019 ActivitiesCheclisto7-08_2
1/41
Checklist of E/OHS Activities for Automatic External Defibrillator
Program Contact Person: Carol Loch
School policy for use adopted in place? Yes No N/A
Brand of AED? Phillips Heart Smart Model # M5066A-ABA
Name of Medical Director? The device was purchased through the HutchinsonMedical Clinic. It is assumed the Medical Director of the clinic would serve inthat capacity.
Year device was placed into use? 2006
Location(s) of devices:Building Name Location in Building
West Elementary Foyer above fire extinguisherPark Elementary Hall by main office near water
fountain
Middle School (1)Hall by office/(2) Auditorium
High School (1)Foyer/ (2)wrestling room
Have all software updates been installed? Yes No N/A
Date of update installation: Winter 2007-2008
Expiration date of pads? 4-2008
Expiration date of batteries? 08-20(date)
Has staff been trained on operation of the device? Yes, all school nurses andEmergency responders are trained biannually.
Most recent date of training:2006(date
Provider of training: Carol Loch
Location of operators manual: School nurse office and one at each building
Are battery checks documented? Yes, a check list is available at each AEDstationNotes: The AEDs were purchased by the local medical clinic. The effort wascoordinated between the PTO and the clinic.
-
8/4/2019 ActivitiesCheclisto7-08_2
2/41
Checklist of E/OHS Activities for Asbestos Management
Program Contact Person: Jo Pyle
Is the Asbestos Management Plan in place? Yes No N/A
Is the Plan current for all buildings? Yes No N/A
Has the Plan (or Plans) been reviewed this school year? Yes No N/A
The Plan is located at affected building: the original plans along with updatesare located at each building_.
Training for Asbestos Awareness was conducted 3/3/06 .
New PT employees received training on N/A .(date)
Annual written notification has been prepared; Fall of 2007 .
(date)
Notification appeared in the following publication(s):
Name of publication DateSpotlight August 2007
Three-year re-inspection Surveillance was conducted: 7/12/07.
6-month Periodic Surveillance was conducted: 5/07(first date)
11/07(second date)
All caution labels have been posted.Label locations: Boiler room tunnels
Are supplies of repair materials adequate to meet the requirements ofmaintenance and repair of ACM? Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
3/41
Asbestos Maintenance Supplies on Hand
Bags Glove bags 6 mil
sheeting
Respirators Respirator
filters
Is documentation of Operations and Maintenance available?
Location: Yes
Status of the Asbestos repair and maintenance Work Order System: N/AEstablished, Pending
Comments:All repairs are outsourced. Repair materials are notroutinely used.
**For information regarding the medical review and questionnaire, see theRespiratory Protection Program. **
-
8/4/2019 ActivitiesCheclisto7-08_2
4/41
Checklist of E/OHS Activities for AWAIR
Program Contact Person: Jo Pyle
Is the AWAIR Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Is the Safety Committee organized? Yes No N/A
How often are meetings held?Attempt quarterly
Are minutes of the meeting maintained?
Location: teachers work rooms
Posted: District office
How is the program communicated to employees?All staff developmentmeetings
Who is the Contact Person for OSHA 300?Jeanette H.
Is the OSHA 300A Log completed for the previous calendar year? Yes
Have the Logs been maintained for five (5) years? Yes
Location:Jeanettes office and the Activities Manual
Is the Log posted from February 1 until April 30? Yes
The location/s of the posted log: Staff lounges
Is information on injuries recorded on the Log with five (5) working days? YesNo N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
5/41
Safety Committee Meeting Schedule
Date Location Time
.
.
District Safety Committee Members
Member Position Building
-
8/4/2019 ActivitiesCheclisto7-08_2
6/41
Checklist of E/OHS Activities for Bleacher safety
Program Contact Person: Jo Pyle
Is the BSM Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Has an annual survey of school bleachers been conducted? Yes No N/A
Is the five-year recertification required by December 31, 2007 complete andsubmitted to the Minnesota Department of Labor and Industry? Yes No N/A
Openings and gaps:
Openings limited to four-inch gap between the railings and between the footboardsand seat boards, starting at a height of 56 inches or more.
Retractable bleachers:
They may contain openings of 9 inches or less
If exempt from standards must have a safety management plan in place and anamortization schedule to plan for their future replacement
Approved netting:
Netting may be provided to prevent persons from falling through the bleachersbetween the seat and footboards
Chain link fencing may be used but must be secured tightly to the underside of thebleachers.
Railings:
Bleachers 55 inches and under are exempt from railing requirements
Bleachers with guardrails over 30 inches above grade must not contain openingsgreater than four inches, unless safety nets are installed.State building inspectors shall determine whether the safety nets and guardrail climbability meet the requirements of the alternate design section of the State Building
Code.
Periodic inspections:
Bleacher footboards and guardrails must at a minimum be reinspected at least everyfive years and a structural inspection at least every ten years. The equipment has norust, rot, cracks, or splinters, especially where it comes in contact with the ground
-
8/4/2019 ActivitiesCheclisto7-08_2
7/41
There are no broken or missing components on the equipment (e.g., handrails,guardrails, protective barriers, steps, or rungs on ladders) and there are no damagedfences, benches, or signs on the playground
-
8/4/2019 ActivitiesCheclisto7-08_2
8/41
Checklist of E/OHS Activities for Bloodborne Pathogens
Program Contact Person: Mary Carter
Is the Bloodborne Pathogens Written Plan in place? Yes No
Has the Plan been reviewed this school year? Yes No
List job categories that may be at risk to exposure:School nurse Playground supervisorCustodians ArtSecretaries Industrial ArtsBus drivers Special edCoaches
What is this schools policy regarding Hepatitis B vaccinations for employeesconsidered at risk versus employees considered not at risk in the ExposureControl Plan?All staff are given the opportunity to receive the 3 part HBVvaccine at no cost.
Is training provided at this school on methods and techniques to reduceexposure incidents?Annual training is provided by the school nurse.
New Employees: _within ten days of employment____
Have the employees identified as first aid responders been given at a minimumRed Cross First Aid Training? Yes No N/A
Are Exposure Control Kits available to staff? Yes No N/A
Location(s): all rooms are provided kits
Status of Declination forms: the forms are maintained by the school nurse
How are blood or bodily-fluid-containing materials handled at this facility?
Policy regarding cleanup: Custodial staff routinely clean up all fluid spills.
-
8/4/2019 ActivitiesCheclisto7-08_2
9/41
Location of biohazard bags at school: Nurses office
Approved disposal location for biohazardous waste: Tracy Hospital
-
8/4/2019 ActivitiesCheclisto7-08_2
10/41
Checklist of E/OHS Activities for Compressed Gas Safety
Program Contact Person(s) Jo Pyle
Department Contacts:
Maintenance Jo Pyle
Metals Shop John Lanoue
Industrial Tech. John Lanoue
Bus Garage Bob Bruder
Is the Compressed Gas Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Has the facility been surveyed for compressed gas inventories? Yes No N/A
Has training been conducted for affected personnel? Yes No N/ADate: summer 2008
Are records established/maintained to monitor gas inventory? Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
11/41
COMPRESSED GAS FIELD REVIEW
Compressed Gas Inventory
Date: Feb. 13, 2008 Program Contact Person : Lee Carlson
Department: Metals Shop Department Responsible Person: Paul Skoglund
Location: Metals Shop Room
Cylinders: O2 ___(5)_________ Acetyl _(2)___________
NH4 ____________
CO2 __(4)__________ Argon __(2)__________
Argon/CO2__(5)__________ Other( helium) __(1)__________
Compliance Check List
No Yes1. Are cylinders in well-ventilated area? X
2. Are cylinders stored separate from flammable by at least 20feet?
X
3. During storage are oxygen cylinders separated from fuel gas
cylinders, unless on welding cart?
X
4. Are cylinders kept away from sources of heat (below 130 F)? X
5. Are safety chains used at all times on both full and emptycylinders? (2/3rds from top of cylinder)
X
6. Are empty cylinders maintained separate from full cylinders? X
7. Are cylinders kept away from sources of ignition such aselectricity,excessive heat or oily rags?
X
8. Are carts designed specifically for gas cylinders available? X
9. Are damaged cylinders, valves/hoses removed from service? X
10. Are all cylinders properly labeled with the contents? X
-
8/4/2019 ActivitiesCheclisto7-08_2
12/41
Checklist of E/OHS Activities for Confined Space Entry
Program Contact Person: Jo Pyle
Is the Confined Space Entry Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Have confined space areas been identified? Yes No N/A
Have measurements to include CCI/ft been completed? Yes No N/A
Are permit entry forms in place? Yes No N/A
Location: Activities Manual
Are confined space labels in the proper locations? Yes No N/A
Is a list of employees eligible to enter confined spaces complete? Yes No N/A
Has training for affected employees completed? Yes No
Date of completion: 2/25/05
Note: Confined space entry at this school is limited to licensed contractorsonly.
-
8/4/2019 ActivitiesCheclisto7-08_2
13/41
Confined Space Inventory
Building: Tracy High School
Building Contact: Jo Pyle Program Contact: Lee Carlson
Date: 2-13-08
RoomIdentificationName GivenSpace
OpeningDimension
DimensionOf Confined
Space
Potential
HazardsPermit/Non-Permit/Alternate
Labeled PhotoID #
Boiler room 18 7X3X3.5 Ele.O2, Heat Permit Yes
Boiler #1Boiler Room 18 7X3X3.5 Ele.O2, Heat Permit Yes
Boiler #2
Boiler Room 4X15 100X15X4 Heat,electricity
Non-permit Yes
Tunnel
-
8/4/2019 ActivitiesCheclisto7-08_2
14/41
Checklist of E/OHS Activities for Community Right-to-Know
Program Contact Person: Jo Pyle
Is the Community Right-to-Know Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Are quantities of stored and used designated hazardous materials documentedand verified? Yes No N/A
Where are the documents stored? Custodial office /Activities Manual
Have the State Emergency Response Commission and local fire departmentbeen notified of hazardous materials on school grounds? Yes No N/A
When were they notified? Winter, 2006(date)
Has training been provided? Yes No N/A
Date: 2/25/05
Presenter: Steve Musser
-
8/4/2019 ActivitiesCheclisto7-08_2
15/41
Inventory Form
Client: Tracy Public Schools
Contact Person: Jo Pyle Date:2-13-08
HazardousMaterial Quantity Location
Reported onTier Two
InstallationDate(s)
#2 Fuel Oil 10,000 gal High School YesMid90s
#2 Fuel Oil 10,000 gal Elementary Yes02
-
8/4/2019 ActivitiesCheclisto7-08_2
16/41
Checklist of E/OHS Activities for Emergency Action Planning
Program Contact Person: Chad Anderson
Is the Emergency Action Planning program in place and as outlined in the
Minnesota Executive Order 93-27 and Model Crisis Management Plan? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Have the program and goals been approved by the School Board for the currentschool year? Yes No
Are information maps posted to indicate travel routes in the event of fire,tornado shelter locations, and procedures during lockdown? YesNo
Located where? Maps are located in each classroom.
Are all drills timed and recorded? Yes No
Responsible person: Chad Anderson, High School, Scott Lesley,Elementary School
Location of records:At the principals respective offices_______________
Forms provided: Yes No
Does this school coordinate drills with local government authorities to assuresheltering in school, evacuating to their homes or use of congregate carecenters? Yes No N/A
Has this school completed the Fire Marshall required Fire Safety and EmergencyEvacuation Plan? Yes No N/A
Training provided for affected staff? Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
17/41
Checklist of E/OHS Activities for Employee Right-to-Know/HazardCommunication
Program Contact Person: Jo Pyle
Is the Employee Right-to-Know/Hazard Communication Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Has the program been approved by the School Board for the current schoolyear? Yes No
Has the chemical inventory been completed for the following functional areas?
Location of Chemical InventoryForm
Art Instruction Yes No N/A
Custodians Yes No N/A Board room/ Custodial office
Food Service Yes No N/A Lead cooks desk
Science Rooms Yes No N/A Lab prep room
Shop (metals, wood, auto) Yes No N/A
Are MSDS available and located with the chemical inventory? Yes No
Do the MSDS concur with the chemical inventory? Yes No
Has training been provided for the following staff?
Art Instructors Yes No N/A Science Yes No N/A
Custodians Yes No N/A Shop Yes No N/A
Food Service Yes No N/A Transportation Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
18/41
Checklist of E/OHS Activities for Facilities Safety Managementand Fire Safety in Schools
Program Contact Person: Jo Pyle
Is the Facilities Safety Management program in place? Yes No
Does this school use contracted services for the Management AssistantProgram? Yes No N/A
If no, who is the designated person or persons?
Fire and Life Safety in Schools
Program Contact Person: Jo Pyle
Is the Fire Marshal approved Emergency Evacuation Plan in place for eachdistrict building? Yes No
Most recent date of sprinkler electronics inspection_________ N/A
Most recent date of alarm inspection_________ N/A
Most recent inspection of fire extinguishers__8-30-07__________ N/A
Most recent inspection of fume hoods with fire suppressant__9-06______ N/A
Are emergency lights tested at least biannually? Yes No N/A
Science safety Checklist completed? Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
19/41
Facilities Safety Review
Building:
Mock-OSHA ReviewArea Date ReviewCompleted N/A Recommendations
Art
Dark Room
Wood Shop
Kitchen
Metal Shop
Halls, Gym, etc.
Graphic Arts
Maintenance/Custodial
Transportation
Grounds/Garage
Chemistry/Life Science
Fire and Life Safety Checklist
ARTX Emergency phone numbers posted and MSDS availableX Flammable liquids and combustibles stored properly
COMPRESSED GASX Cylinders chained in place so they cannot fall overX Valve covers in place when cylinder not in use
SPRAY BOOTH
-
8/4/2019 ActivitiesCheclisto7-08_2
20/41
X Fire control sprinkler heads kept cleanX Mechanical ventilation provided when spraying is done in enclosed areaX NO SMOKING signs posted in spray areas, paint rooms, booths, and storageX Spray area at least 20 from flames, sparks, operating electrical motors
BOILER ROOMX Fire extinguisher mounted and accessibleX No combustibles stored in boiler roomX Two exits
CORRIDORS, ENTRANCES, STAIRSX All decorations, artwork in corridors limited to 25% of wall surfaceX All EXIT corridors and hallways free of obstructionsX All EXIT doors open in the direction of exit without effortX All EXIT doors posted as exits with letters 5 high and wide
X All EXIT signs visible and with working lights, if lightedX Appropriate fire extinguishers are mounted within 75 of outside areas
containing flammable liquids and within 10 of any inside storage area forsuch materials
X Buildings over two levels have doors that close automatically in stair towerX Fire extinguishers free from obstruction or blockageX Fire extinguishers provided for the types of materials in the area whereused
Class A Ordinary combustible material firesClass B Flammable liquid, gas, or grease firesClass C Energized-electrical equipment fires
X Fire extinguishers serviced, maintained, and tagged every yearX No dead-end corridor >20X Non-exit doors, passages, and stairways labeled, NOT AN EXITX Panic hardware on all exit doors and rooms with occupancy of 50 or moreX Sprinkler heads protected by metal guards, when exposed to physicaldamage
ELECTRICALX Extension cords used for permanent wiringX 36 clear access to all electrical control panels for emergency shutdown
EXTERIORX Dumpsters stored at least 5 from any combustible buildings, doors, and
windows
GYM
-
8/4/2019 ActivitiesCheclisto7-08_2
21/41
X Stage curtain must be flame retardant
HOME ECX Outlets within 6 of a water source must be GFC
KITCHENX Exhaust hood, ducts, and filters clear of any grease accumulation
X Fire extinguisher within 30 of cooking equipment (min. 40BC)X Hood with auto fire extinguishing system inspected every 6 monthsX Means to shut off gas supply to the cooking equipment for emergencyX MSDS availableX Outlets within 6 of a water source must be GFC
SCIENCE LABSCHEMICALSX Chemicals stored in open lab work area kept to a minimumX Neutralizing chemicals and spill kits readily available
FIRE SAFETYX Aisles serving work areas on 2 sides at least 42 wide; those serving workareas on one side only must be 36X Flammable liquids stored in refrigerated equipment in closed containersX Flammable/combustible liquids and chemicals must not be stored in fume
hoods or on the floor, except in original containerX Refrigerators, freezers, or coolers that store or cool flammable liquids must
be of explosion-proof construction and properly labeledX 2A-20BC or larger rated fire extinguisher for each 3,000 feet of lab; travel
distance must not exceed 50 from anywhere in room
STORAGEX Acids stored in approved cabinetsX Chemical storage area must have inventoryX Chemical storage area properly ventilatedX Chemicals properly labeled
X Chemicals stored in approved containers (original shipping package)X Flammable liquids stored in approved cabinetsX Shelves used for chemical storage should have lip or guard to prevent
chemicals from falling offX Storage cabinets and rooms locked against unauthorized entry
VENTILATION
-
8/4/2019 ActivitiesCheclisto7-08_2
22/41
X Hood tested every yearX Lab hoods achieve 100 lfmX Means provided for manually shutting down ventilation equipment
STORAGE ROOMSX Room used for storage of combustibles must have 1-hour fire-rated walls
(sheet rock or plaster) and fire-rated doors (or solid core 1.75 thick wooddoors) with self-closer (or automatic fire sprinklers in them)
TECHNICAL LAB AREASX Compressed gas cylinders (oxygen, acetylene, propane, etc.) secured so
they cannot fall overX Emergency stop buttons colored red
X Fire extinguishers located within 30 of hazardous processes (painting,welding, and woodworking)mounted and inspectedX Flammable liquids stored in approved cabinetsX Oil-soaked, greasy, or paint-soaked rags stored in metal containers with lidsX Solvent wastes and flammable liquids are kept in fire-resistant, covered
containers until they are removed from the worksiteX Worksite clean and orderly with clear paths to exit
Completed by ___________________________Date
-
8/4/2019 ActivitiesCheclisto7-08_2
23/41
Checklist of E/OHS Activities for First Aid/CPR
Program Contact Person(s): Mary Carter
Is the First Aid/CPR program in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Have the program and goals been approved by the School Board for the currentschool year? Yes No
Has the District determined a provider in the event of a medical emergency?Yes No
The local provider determined travel time was estimated to be within the 4-8minute limit. Therefore Tracy Ambulance will bethe designated emergency response provider.
The local provider determined travel time was estimated to be in excess of the4-8 minute limit. Therefore N/A will be thedesignated emergency response person located within the district.
Has training been provided for affected staff? Yes No
Note: Training is provided alternative years. One year is dedicated to first-aidand the next to CPR.
-
8/4/2019 ActivitiesCheclisto7-08_2
24/41
Checklist of E/OHS Activities for Hazardous Waste Management
Program Contact Person(s)
Primary Contact Person: Jo Pyle
Secondary Contact Person: Richard Hanson
Is the Hazardous Waste Management program in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Have the program and goals been approved by the School Board for the currentschool year? Yes No
Did this school generate ten gallons of waste per year? Yes No
Note: In Greater Minnesota, schools generating ten gallons of waste per year orless do not need a license.
Did this school generate 220 pounds or less per month hazardous waste (about drum or less liquid)? Yes No
Note: Wastes that do not count include antifreeze, cathode ray tubes,fluorescent lamps, lead acid batteries, pcb ballasts, photo fixer reclaimed onsite, used oil and oil filters.
Training for VSQGs do not have training requirements however MPCA stronglyrecommends persons handling wastes be given training on best handling andsafety risks associated.Has training been provided for affected persons? Yes No N/A
Date Conducted: N/A
Date Scheduled: N/A
Has annual report and license application sent in? Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
25/41
Checklist of E/OHS Activities for Hearing Conservation
Program Contact Person: Jo Pyle
Is the Hearing Conservation Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Has the program been approved by the School Board for the current schoolyear? Yes No
Has the school been surveyed for noise hazards? Yes No
Have sound level measurements been collected? Yes No
Have the results been documented? Yes No
Location: Activities Manual
Has training been scheduled or completed for affected individuals this schoolyear? Yes No N/A
Date:
Presenter:
Have regulatory changes occurred that may affect this program? No
-
8/4/2019 ActivitiesCheclisto7-08_2
26/41
Checklist of E/OHS Activities for Indoor Air Quality
Program Contact Person: Jo Pyle
Is the IAQ Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Has an IAQ Committee beenestablished? Yes No
Have the program and goals been approved by the School Board for the currentschool year? Yes No
Has the annual cursory walk-through been conducted? Yes No
Havethedistrictskeybuilding systems been evaluated? Yes No
When was the evaluation completed? Aug, 1999
Who conducted the evaluation? MacNeil Environmental
Wereoccupied areas of the district evaluated using the EPAs Tools For Schoolscheck list or equivalent? Yes
Teachers check list? An information fact sheet was provided all staff.# of forms distributed 30 # of Forms returned: 30
Building maintenance checklist?
Building ventilation checklist?
Training conducted(date)
Training has been scheduled for _______________. (date)
Has the District determined the mechanical ventilation rate of each occupiedspace? Yes No.
Supportive technical services were conducted on: May 15, 2000. (date)
Results of technical services are located? Activities manual
-
8/4/2019 ActivitiesCheclisto7-08_2
27/41
Checklist of E/OHS Activities for Integrated Pest Management
Program Contact Person: Jo Pyle
Is the IPM Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Has the annual monitoring been conducted to determine location and degree ofinfestation? Yes No
A map of the problem area/areas has been developed. Yes No
Has notice been given to parents regarding application activities? Yes No
Location or publication used to notify parents: Spotlight, Aug, 2007.
-
8/4/2019 ActivitiesCheclisto7-08_2
28/41
Checklist of E/OHS Activities for Laboratory Standard/ChemicalHygiene Plan
Program Contact Person: Monica Headlee , CHO
Is the Laboratory Standard/Chemical Hygiene Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Fume hood was tested on _______________.(date)
The results indicate air velocity to be: satisfactory, unsatisfactory.
Chemical inventory:
Date of most recent survey: fall, 2007
Location of inventory listing: Chemistry lab
Are Material Safety Data Sheets (MSDSs) located with inventory? Yes No N/A
Are the MSDS readily accessible? Yes No N/A
Has the DCFL Science Lab Checklist been completed? Yes No N/A
Is training for affected personnel complete? Yes No N/A
Date(s) of instruction:
Roster signed? Yes No N/A
Lesson plan outline available with roster? Yes No N/A
Status of Emergency Eye Wash/Deluge Shower:
Is flushing conducted weekly? Yes No N/A
Is descriptive signage properly posted? Yes No N/A
Is flushing activity documented? Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
29/41
Checklist of E/OHS Activities for Lead-in-Water Management
Program Contact Person: Jo Pyle
Is the Lead-in-Water Management Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
This school completed testing of water supply taps _7/13/2000.(date)
Is a map of all potable water taps available for review? Yes No N/A
Checklist of E/OHS Activities for Lead-in-Paint Management
Program Contact Person: Jo Pyle
Is the Lead-in-Paint Management Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Testing for lead in paint on playground equipment: Note: All playgroundequipment has been replaced with lead free.
Date completed: N/A
Yet to be tested: N/A
Results of evaluation for paint condition in rooms K-1:Building constructed post-1978; facility not applicableBuilding constructed prior to 1978; paint determined to be in
____good__________ condition
-
8/4/2019 ActivitiesCheclisto7-08_2
30/41
Checklist of E/OHS Activities for Lockout/Tagout
Program Contact Person: Jo Pyle
Is the Lockout/Tagout Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Is LO/TO equipment available? Yes No N/A
Is the equipment appropriate for application? Yes No N/A
If available, where is the equipment located? Custodial office
Is the equipment maintained in an orderly and readily usable condition?Yes No N/A
Have affected personnel been trained as to methods and technique of use?Yes No N/A
Are written procedures available for affected staff? Yes No N/A
If available, the procedures are located where?Activities Manual
Has the annual audit of energy control procedures been completed? Yes No
Date or dates of completion:
-
8/4/2019 ActivitiesCheclisto7-08_2
31/41
Checklist of E/OHS Activities for Machine Guarding
Program Contact Person: Jo Pyle/Mike Peterreins
Is the Machine Guarding Plan for each affected work area in place? Yes No
Is the plan/plans current? Yes No
Has the Plan been reviewed this school year? Yes No
Has a survey of all district fixed equipment been conducted?Yes No
When was the evaluation completed?_______________________
Who conducted the evaluation? _______________________
How are corrections documented? _______________________________
Is all fixed equipment safeguarded to meet OSHA criteria? Yes No
Has the alternative MDE best practices criteria used to safeguard equipment?Yes No
Has equipment determined not in compliance scheduled for repair orreplacement? Yes No
If replaced, was best practices, bid specification criteria used forprocurement? Yes No
-
8/4/2019 ActivitiesCheclisto7-08_2
32/41
Identified Fixed Equipment Locations
Location Building/Buildings Staff Affected # of itemAutomotive ShopWood Shop
Custodial/Maintenance
Welding Shop
Ag Shop
Bus Garage
Art
Scene shop
Science
Contracted technical services to review and recommend?__________________.
Name of person or contractor conducting survey? ___________________.(date)
Results of technical services located where? ________________________
Checklist for minimum requirements:
Power outage protection provided for required equipment
Emergency stops provided for required equipment
Safe work practice placards at applicable fixed tool stations
Proper guards provided and used
Color coding as prescribed by OSHA standards
Non-slip surfaces by each piece of equipment
Fixed equipment secured to prevent walking or movement
Has a log of employee accidents and near misses been established and used?
Yes No
Annual training for affected staff is provided? Yes No
Training conducted ____________. (date)
Training has been scheduled for ____________.(date)
-
8/4/2019 ActivitiesCheclisto7-08_2
33/41
Checklist of E/OHS Activities for Playground Safety
Program Contact Person: Jo Pyle
Is the Playground Safety program in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Surfacing:
The equipment has adequate protective surfacing under and around itand the surfacing materials have not deteriorated
Loose-fill surfacing materials have no foreign objects or debris
Loose-fill surfacing materials are not compacted and do not havereduced depth in heavy use areas such as under swings or at slide exits
General Hazards:
There are no sharp points, corners, or edges on the equipment
There are no missing or damaged protective caps or plugs
There are no hazardous protrusions and projections
There are no potential clothing entanglement hazards, such as open S-hooks or protruding bolts
There are no pinch, crush, and shearing points or exposed moving parts
There are no trip hazards, such as exposed footings on anchoringdevices and rocks, roots, or any other environmental obstacles in theplay area
Deterioration of the Equipment:
The equipment has no rust, rot, cracks, or splinters, especially whereit comes in contact with the ground
-
8/4/2019 ActivitiesCheclisto7-08_2
34/41
There are no broken or missing components on the equipment (e.g.,handrails, guardrails, protective barriers, steps, or rungs on ladders)and there are no damaged fences, benches, or signs on the playground
All equipment is securely anchored
Security of Hardware:
There are no loose fastening devices or worn connections, such as S-hooks
Moving components, such as swing hangers or merry-go-round bearings,are not worn
Drainage:
The entire play area has satisfactory drainage, especially in heavy useareas such as under swings and at slide exits
Leaded Paint:
The leaded paint used on the playground equipment has notdeteriorated as noted by peeling, cracking, chipping, or chalking
There are no areas of visible leaded paint chips or accumulation oflead dust
General Upkeep of Playgrounds:
The entire playground is free from miscellaneous debris or litter suchas tree branches, soda cans, bottles, glass, etc.
There are no missing or full trash receptacles
-
8/4/2019 ActivitiesCheclisto7-08_2
35/41
Checklist of E/OHS Activities for Personal Protective Equipment
Program Contact Person: Jo Pyle
Is the Personal Protective Equipment Plan in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Has a survey of potential workplace hazards been completed? Yes No N/A
Date(s) activity was conducted:__________________________
Have recommendations been completed for appropriate equipment? Yes No
Has training been completed for the following departments?
Art and Photo Yes No N/A
Custodial Yes No N/A
Grounds keeping/Garage Yes No N/A
Kitchen Yes No N/A
Maintenance Yes No N/A
Science Laboratories Yes No N/A
Technical Education Yes No N/A
Transportation Yes No N/A
-
8/4/2019 ActivitiesCheclisto7-08_2
36/41
Personal Protective Equipment AssessmentBuilding: High School_______
Location:Kitchen
Location:Boiler room
Location:Maintenance
Location:Tech Shop
Location:ScienceRooms
Employee: Employee:Jo Pyle
Employee:Joe Pyle
Employee:PaulSkoglund,MikePeterreins
Employee:MonicaHeadlee,JacobScandrett
Hand
Hot Glove X X X XLatex
Vinyl XLeather X XNeoprene X X
Face
Impact X X X
Splash X X XShieldRespirator X
EarMuffs X XPlugs
BodyNeo Apron X X XDenim X
FootSteel Toes XMetatarsal
Head Hard Hat X
Hazard(s)
Chemicals,
scaldingwater, heat,Knives,
Chemicals,
scaldingwater, heat,hotenvironment,body fluids
Chemicals,
electricity,heat
Body fluids,impact
body fluids,
gascylinders,
heat, impact
body fluids,
chemicals,open flame,
Comments onAvailability,Condition, &Storage
.
Completed by __Lee Carlson______________Date 3-25-2008
-
8/4/2019 ActivitiesCheclisto7-08_2
37/41
Checklist of E/OHS Activities for Respiratory Protection
Program Contact Person: Jo Pyle
Does this school provide respirators for voluntary use? Yes No N/AIf the school allows employees to use respirators voluntarily the following ismandatory.
1. Read and follow instructions provided by manufacturer.2. Choose respirators certified for use against contaminants of concern.3. Do not wear respirators in atmospheres containing contaminants not
designed to protect from those contaminants.4. Keep track of respirators so that you do not mistakenly wear someone
elses respirator.
Is the Respiratory Protection program in place? Yes No N/A
Is the Plan current? Yes No N/A
Has the Plan been reviewed this school year? Yes No N/A
Date of review: __2-13-08_____________
Are all employees in this program identified? Yes No N/A
Employee IntendedUse Type ofRespirator Medical Exam/Questionnaire Date ofMedical Date ofFit Test
Jo Pyle Misc.voluntary
mask N/A N/A N/A
Fit testing was completed on N/A.(date)
Type of testing protocol; Irritant Smoke (Stannic Chloride) orBitrex (Denatonium Benzoate)
-
8/4/2019 ActivitiesCheclisto7-08_2
38/41
Condition and location of respirators:
Condition:____new__________
Location(s):__custodial area__________________
Are the appropriate adequate accessories on hand? Yes No N/A
Verified by: Lee Carlson
Note: The respirators were checked on 3-25-2008 and found to be in like newcondition. The respirators are located in the gray cabinet in the boiler room.
The particulate filters are also located in the same area. LC
-
8/4/2019 ActivitiesCheclisto7-08_2
39/41
Checklist of E/OHS Activities for Underground and AbovegroundStorage Tanks
Program Contact Person: Jo Pyle
Is the Underground and Aboveground Storage Tanks Plan in place? Yes No
Is the Plan current? Yes No
Has the Plan been reviewed this school year? Yes No
Have forms for inventory tracking been provided? Yes No N/A
Do existing records accurately reflect purchase use correlation? Yes No N/A
Are all USTs registered with the Minnesota Pollution Control Agency? Yes NoN/A
Are removals or additions of tanks anticipated in this facility? Yes No N/A
Notes:
-
8/4/2019 ActivitiesCheclisto7-08_2
40/41
Underground/Aboveground Storage Tank Status
Tank No. Location Size Contents Registered Install date
#1 Bus garage 1000 gal #2 diesel fuel ? 2006
#2 Bus Garage 400 gal gasoline ? 2006
#3 High School 10,000 gal #2 fuel oil Yes 1995?
#4 ElementarySchool
10,000 gal #2 fuel oil Yes 2002
Regulated Tanks:Motor fuel tanks larger than 110 gallons
Non-regulated Tanks:Heating oil tanks
Requirements for All USTs: Tank must be registered with MPCA
Requirements for Regulated Tanks:Annual tightness testing and inventorycontrol Tank must be updated, replaced, or removed by December 22, 1998
Upgrades:--Overfill protection--Corrosion protection STPI approved
--Leak detection
Tightness Testing Results on File:
Dates of past testing:____________________
Records on file:________________________
-
8/4/2019 ActivitiesCheclisto7-08_2
41/41