Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH)...

20
1. Typical Channeled Adhesive 2. Typical Application 3. Typical Application over CMU 4. Typical Application over Brick 5. Typical Aesthetic Reveal 6. Typical Corner Mesh Application with Acromesh 4, Intermediate 6 or 12 7. Typical Pipe Penetration 8. Typical Light Fixture 9. Typical Expansion Joint 10. Typical Expansion Joint at Change in Substrate 11. Typical Expansion Joint at Floorline 12. Typical Drainage at Floorline 13. Typical EIFS Abutment to Brick with Drainage at Floorline 14. Typical Termination at Foundation 15. Typical EIFS Abutment to Brick 16. Typical Termination at Foundation (Flush) 17. Typical Window Head (Flush) 18. Typical Window Head with Weep Tubes (Flush) 19. Typical Window Head with Diverter Track (Flush) 20. Typical Window Head (Recessed) 21. Typical Window Jamb (Flush) 22. Typical Window Sill (Flush) 23. Typical Window Jamb (Recessed) 24. Typical Window Sill (Recessed) 25. Typical Coping 26. Typical Parapet Cap 27. Typical Kick-Out Flashing 28. Typical Roof Edge Flashing 29. Typical Section at Fascia/Soffit 30. Typical Core Mounted Railing Attachment 31. Typical Railing Attachment 32. Typical Sign Attachment Typical Details Acrowall-ES Plus Design Water Drainage Class PB Exterior Insulation and Finish System

Transcript of Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH)...

Page 1: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

1. Typical Channeled Adhesive

2. Typical Application

3. Typical Application over CMU

4. Typical Application over Brick

5. Typical Aesthetic Reveal

6. Typical Corner Mesh Application with Acromesh 4,Intermediate 6 or 12

7. Typical Pipe Penetration

8. Typical Light Fixture

9. Typical Expansion Joint

10. Typical Expansion Joint at Change in Substrate

11. Typical Expansion Joint at Floorline

12. Typical Drainage at Floorline

13. Typical EIFS Abutment to Brick with Drainage at Floorline

14. Typical Termination at Foundation

15. Typical EIFS Abutment to Brick

16. Typical Termination at Foundation (Flush)

17. Typical Window Head (Flush)

18. Typical Window Head with Weep Tubes (Flush)

19. Typical Window Head with Diverter Track (Flush)

20. Typical Window Head (Recessed)

21. Typical Window Jamb (Flush)

22. Typical Window Sill (Flush)

23. Typical Window Jamb (Recessed)

24. Typical Window Sill (Recessed)

25. Typical Coping

26. Typical Parapet Cap

27. Typical Kick-Out Flashing

28. Typical Roof Edge Flashing

29. Typical Section at Fascia/Soffit

30. Typical Core Mounted Railing Attachment

31. Typical Railing Attachment

32. Typical Sign Attachment

Typical Details

Acrowall-ES Plus DesignWater Drainage Class PB Exterior Insulation and Finish System

Page 2: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• Apply mixed base coat to entire surface ofinsulation board using a stainless steel trowel with13 mm x 13 mm (1/2" x 1/2") notches spaced50 mm (2") apart. Ribbons of adhesive must beapplied parallel to the 610 mm (2’) dimension ofthe EPS insulation board to ensure they are verticalwhen the EPS insulation board is applied to thesubstrate.

• Set EPS insulation board into place and applypressure over entire surface of board toensure positive uniform contact and high initialgrab. Do not slide board into place.

TYPICAL CHANNELED ADHESIVE

TYPICAL APPLICATION

ESP-01 0810

ESP-02 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination.

Page 3: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL APPLICATION OVER CMU

TYPICAL APPLICATION OVER BRICK

ESP-03 0810

ESP-04 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination.

Page 4: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• Maintain a minimum 19 mm (¾”) thick EPSinsulation board behind all reveals & aestheticgrooves.

• Reinforcing mesh shall be continuous and careshall be taken to ensure reinforcing mesh is notcut during base coat application.

• Horizontal reveals shall provide for outwardpositive drainage.

• Reveals must not occur at the abutment of twopieces of EPS insulation board.

TYPICAL AESTHETIC REVEAL

TYPICAL CORNER MESH APPLICATIONWITH ACROMESH 4, INTERMEDIATE 6 OR 12

ESP-05 0810

ESP-06 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• Ensure Acromesh 4, Intermediate 6 or 12reinforcing mesh is lapped a minimum of 203 mm(8”) around corners.

Page 5: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL PIPE PENETRATION

TYPICAL LIGHT FIXTURE

ESP-07 0810

ESP-08 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced basecoat.

• Ensure all penetrations into the system areproperly sealed.

• Provide continuous air seal around perimeterof penetration prior to EPS insulation boardapplication.

• Do not apply finish to areas that will receivesealant.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure all penetrations into the system areproperly sealed.

Page 6: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Do not apply finish to areas that will receivesealant.

• Ensure drainage plane is continuous andunobstructed at expansion joint.

• Install expansion joints in the system at allchanges in substrate, through existing expansionjoints, floor lines in multi-levelwood frameconstruction, and where movement isanticipated. It is the sole responsibility of thedesign professional to determine specificexpansion joint location, placement and design.

TYPICAL EXPANSION JOINT

TYPICAL EXPANSION JOINT AT CHANGEIN SUBSTRATE

ESP-09 0810

ESP-10 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Do not apply finish to areas that will receivesealant.

• Ensure drainage plane is continuous andunobstructed at expansion joint.

• Install expansion joints in the system at allchanges in substrate, through existing expansionjoints, floor lines in multilevel wood frameconstruction, and where movement is anticipated.It is the sole responsibility of the design professionalto determine specific expansion joint location,placement and design.

Page 7: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL EXPANSION JOINT AT FLOORLINE

TYPICAL DRAINAGE AT FLOORLINE

ESP-11 0810

ESP-12 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Do not apply finish to areas that will receivesealant.

• Install expansion joints in the system at allchanges in substrate, through existing expansionjoints, floor lines in multilevel wood frameconstruction, and where movement isanticipated. It is the sole responsibility of thedesign professional to determine specificexpansion joint location, placement and design.

• It is recommended that a means for drainage isprovided at every third floor. (See Detail 12)

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Do not apply finish to areas that will receivesealant.

• Install expansion joints in the system at allchanges in substrate, through existing expansionjoints, floor lines in multilevel wood frameconstruction, and where movement is anticipated.It is the sole responsibility of the design professionalto determine specific expansion joint location,placement and design.

• It is recommended that a means for drainage isprovided at every third floor.

Page 8: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at brick.

• Brick ties not shown for clarity.• Brick must be installed per local code requirements.

TYPICAL EIFS ABUTMENT TO BRICKWITH DRAINAGE AT FLOORLINE

TYPICAL TERMINATION AT FOUNDATION

ESP-13 0810

ESP-14 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at foundation.

• Terminate system a minimum of 203 mm (8”)above grade.

• Extend system a minimum of 50 mm (2”)and a maximum of 305 mm (12”) at thesole plate foundation transition.

Page 9: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL EIFS ABUTMENT TO BRICK

TYPICAL TERMINATION AT FOUNDATION (FLUSH)

ESP-15 0810

ESP-16 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a continuous drainage plane ismaintained at system abutment to brick.

• Brick ties not shown for clarity.• Brick must be installed per local code requirements.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at foundation.

• Place weep tubes a minimum of 610 mm(24”) on center.

• Do not apply finish to areas that will receivesealant.

Page 10: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

ESP-17 0810

ESP-18 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at window head.

• Provide end-dams at flashing terminations.• Provide continuous air seal around interiorperimeter of window. Contact windowmanufacturer for specific installation instructions.

TYPICAL WINDOW HEAD (FLUSH)

TYPICAL WINDOW HEAD (FLUSH)WITH WEEP TUBES Notes:

• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at window head.

• Provide end-dams at flashing terminations.• Provide continuous air seal around interiorperimeter of window. Contact windowmanufacturer for specific installation instructions.

• Do not apply finish to areas that will receivesealant.

Page 11: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

ESP-19 0810

ESP-20 0810

TYPICAL WINDOW HEAD (FLUSH)WITH DIVERTER TRACK

TYPICAL WINDOW HEAD (RECESSED)

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Provide continuous air seal around interiorperimeter of window. Contact windowmanufacturer for specific installation instructions.

• Ensure that the diverter flashing extends 152 mm(6”) beyond opening on either side of the openingto allow potential moisture to drain down the wallto the side of the opening. Self Adhering Meshembedded in Acrostop, Sheathing Fabricembedded in Acrostop R or Acroflash mustbe extended over flange of flashing. Maintaina minimum of 19 mm (3/4”) EPS insulationthickness. Ensure the diverter track flashing issloped to provide a means for drainage.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Do not apply finish to areas that will receivesealant.

• Ensure a means for drainage is provided atsystem termination at soffit/fascia transition.

• Provide a back wrapped type joint with backerrod and sealant at system terminations todissimilar materials, ensuring that a watertight seal is achieved (width per design).

• Provide continuous air seal around interiorperimeter of interior window. Contact windowmanufacturer for specific installation instructions.

Page 12: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure water-resistive barrier is properlyapplied into the rough openings in accordancewith application guidelines and code requirementsprior to EPS insulation board application.

• Do not apply finish to areas that will receivesealant.

• Provide a back wrapped type joint with backerrod and sealant at system terminations todissimilar materials, ensuring that a watertight seal is achieved (width per design).

• Provide continuous air seal around interiorperimeter of interior window. Contact windowmanufacturer for specific installation instructions.

TYPICAL WINDOW JAMB (FLUSH)

TYPICAL WINDOW SILL (FLUSH)

ESP-21 0810

ESP-22 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure water-resistive barrier is properlyapplied into the rough openings in accordancewith application guidelines and code requirementsprior to EPS insulation board application.

• Do not apply finish to areas that will receivesealant.

• Provide a back wrapped type joint with backerrod and sealant at system terminations todissimilar materials, ensuring that a watertight seal is achieved (width per design).

• Provide continuous air seal around interiorperimeter of interior window. Contact windowmanufacturer for specific installation instructions.

Page 13: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL WINDOW JAMB (RECESSED)

TYPICAL WINDOW SILL (RECESSED)

ESP-23 0810

ESP-24 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure water-resistive barrier is properly appliedinto the rough openings in accordance withapplication guidelines and code requirementsprior to EPS insulation board application.

• Do not apply finish to areas that will receivesealant.

• Provide a back wrapped type joint with backerrod and sealant at system terminations todissimilar materials, ensuring that a watertight seal is achieved (width per design).

• Provide continuous air seal around interiorperimeter of interior window. Contact windowmanufacturer for specific installation instructions.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure water-resistive barrier is properlyapplied into the rough openings in accordancewith application guidelines and code requirementsprior to EPS insulation board application.

• Ensure that metal pan flashing extends onto thesystem a minimum of 50 mm (2”) down the faceand that end dams are provided.

• Provide continuous air seal around interiorperimeter of interior window. Contact windowmanufacturer for specific installation instructions.

Page 14: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure that metal coping/ flashing extends ontothe system a minimum of 50 mm (2”) down theface.

TYPICAL COPING

TYPICAL PARAPET CAP

ESP-25 0810

ESP-26 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• Provide a minimum 6:12 slope for all horizontalsurfaces. Acrocrete requires the use of a roofingsystem or metal cap flashing for sloped surfacesover 610 mm (24”).

• Additional layers of mesh reinforced base coat isrecommended when sloped surfaces exceed305 mm (12”).

• Ensure a means for drainage is provided atsystem termination.

• Terminate system a minimum of 203 mm (8”)above roof.

• Maintain a minimum 25 mm (1”) thick EPSinsulation board.

Page 15: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL KICK-OUT FLASHING

TYPICAL ROOF EDGE FLASHING

ESP-27 0810

ESP-28 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at roof.

• Terminate system a minimum of 50 mm (2”)above roof.

• Ensure step flashing is a minimum of 50 mm(2”) behind system.

• Kick-out flashing shall be a minimum of 102 mm(4”) in height.

• Do not apply finish to areas that will receivesealant.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure that metal coping/flashing extends ontothe system a minimum of 50 mm (2”) down theface.

Page 16: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure a means for drainage is provided atsystem termination at soffit/fascia transition.

SECTION AT FASCIA / SOFFIT

TYPICAL CORE MOUNTED RAILING ATTACHMENT

ESP-29 0810

ESP-30 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure all penetrations into the system areproperly sealed.

Page 17: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

TYPICAL RAILING ATTACHMENT

TYPICAL SIGN ATTACHMENT

ESP-31 0810

ESP-32 0810

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure all penetrations into the system areproperly sealed.

Notes:• Verify all materials are installed in accordancewith current installation instructions.

• All terminations must be fully encapsulated withmesh reinforced base coat.

• Ensure all penetrations into the system areproperly sealed.

• Blocking or other structural support required forsign attachment.

.

Page 18: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

NOTES

Page 19: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

NOTES

Page 20: Acrowall ES Plus 3D Color Details - BASF · ESP-190810 ESP-200810 TYPICALWINDOWHEAD(FLUSH) WITHDIVERTERTRACK TYPICALWINDOWHEAD(RECESSED) Notes: •Verifyallmaterialsareinstalledinaccordance

NoteBASF Wall Systems is an operating unit ofBASF Corporation (herein after referred toas “BASF Wall Systems”)

Residential PolicyApply wall systems in accordance withlocal building codes in force at the timeof construction. On one and two-familyresidential framed construction, BASF WallSystems requires that the wall systemselected be one that includes provisionsfor moisture drainage.

DisclaimerThis information and all further technicaladvice are based on BASF Wall Systems’present knowledge and experience. However,BASF assumes no liability for providing suchinformation and advice including the extent towhich such information and advice may relateto existing third party intellectual propertyrights, especially patent rights. In particular,BASF Wall Systems disclaims any and allCONDITIONS AND WARRANTIES,WHETHEREXPRESS OR IMPLIED, INCLUDING THEIMPLIED WARRANTIES OF FITNESS FOR APARTICULAR PURPOSE OR MERCHANTABILITY.BASF WALL SYSTEMS SHALL NOT BERESPONSIBLE FOR CONSEQUENTIAL,INDIRECT OR INCIDENTAL DAMAGES(INCLUDING LOSS OF PROFITS) OF ANYKIND. BASF Wall Systems reserves the rightto make any changes according to technologicalprogress or further developments. It is thecustomer’s responsibility and obligation tocarefully inspect and test any incoming goods.Performance of the product(s) describedherein should be verified by testing andcarried out only by qualified experts. It is thesole responsibility of the customer to carry outand arrange for any such testing. Referenceto trade names used by other companies isneither a recommendation, nor anendorsement of any product and does notimply that similar products could not be used.It is the responsibility of both the specifier andthe purchaser to determine if a product issuitable for its intended use. The designerselected by the purchaser shall be responsiblefor all decisions pertaining to design, detail,structural capability, attachment details, shopdrawings and the like. BASF Wall Systemshas prepared guidelines in the form ofspecifications, typical application details, andproduct bulletins to facilitate the design processonly. BASF Wall Systems is not liable for anyerrors or omissions in design, detail, structuralcapability, attachment details, shop drawingsor the like, whether based upon the informationprovided by BASFWall Systems or otherwise, orfor any changes which the purchasers, specifiers,designers or their appointed representativesmay make to BASF Wall Systems publishedcomments. For more information visit ourwebsite at www.acrocrete.basf.com.

BASF Wall Systems3550 St. Johns Bluff Road SouthJacksonville, FL 32224-2614Phone 800 • 221 • 9255Fax 904 • 996 • 6300www.acrocrete.basf.com

©2010 BASF CorporationPrinted in U.S.A. 08/10