AC Drive VFD - Allen Bradley Powerflex 4M
-
Upload
nfi-industrial-automation-training-academy -
Category
Technology
-
view
2.716 -
download
19
description
Transcript of AC Drive VFD - Allen Bradley Powerflex 4M
Allen Bradley Adjustable
Frequency AC Drive
Powerflex 4M
400 W
Wire Program
Operate
Wiring the Drive
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
I/O Wiring Examples
AB Powerflex 4M
Parameter Organization
AB Powerflex 4M
Parameter Organization - Display
AB Powerflex 4M
d001 – Output FrequencyOutput frequency present at T1, T2 & T3 (U, V & W).
d002– Commanded FrequencyValue of the active frequency command. Displays the
commanded frequency even if the drive is not running.
d003 - Output CurrentThe output current present at T1, T2 & T3 (U, V & W).
d004 - Output VoltageThe output voltage present at T1, T2 & T3 (U, V & W).
d005 – DC Bus VoltagePresent DC bus voltage level.
d006 – Drive StatusPresent operating condition of the
drive.
Parameter Organization
AB Powerflex 4M
d010 – Process DisplayThe output frequency scaled by A440 [Process Factor] or by A438 [Process Time Lo] and
A439 [Process Time Hi].
d012 – Control SourceDisplays the active source of the Start
Command and Speed Command.
Parameter Organization
AB Powerflex 4M
d012 – Control In StatusStatus of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control
terminal block.
d018 - Elapsed Run TimeAccumulated time drive is outputting power. Time is displayed in 10-hour increments.
Parameter Organization
AB Powerflex 4M
d020 - Analog In 0-10VThe present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).
d021 - Analog In 4-20mAThe present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
d022 - Drive TemperaturePresent operating temperature of the drive power section.
Parameter Organization - Program
AB Powerflex 4M
P101 – Motor NP VoltageStop drive before changing this parameter.
Set to the motor nameplate rated voltage.
P102 – Motor NP HertzStop drive before changing this parameter.
Set to the motor nameplate rated frequency.
P103 – Motor OL CurrentSet to the maximum allowable motor current.
P104 – Minimum FrequencySets the lowest frequency the drive will output
continuously. Min/Max: 0.0/400.0 Hz
P105 – Maximum FrequencySets the highest frequency the drive will output
continuously. Min/Max: 0.0/400.0 Hz
Parameter Organization - Program
AB Powerflex 4M
P106 – Start SourceStop drive before changing this parameter.
Sets the control scheme used to start the drive.
P107 – Stop ModeActive stop mode for all stop sources
0“Ramp, CF”(1) (Default)
Ramp to Stop. “Stop” command clears
active fault.
1“Coast, CF”(1)
Coast to Stop. “Stop” command clears
active fault.
Parameter Organization - Program
AB Powerflex 4M
P108 – Speed ReferenceSets the source of the speed reference to the drive.
P109 – Acc. timeSets the rate of acceleration for all speed increases.
Parameter Organization - Program
AB Powerflex 4M
P110 – Dec. TimeSets the rate of deceleration for all speed decreases.
P112 – Reset to DefaultResets all parameter values to factory defaults.
Parameter Organization - Terminal
AB Powerflex 4M
t201 – Digital In1 Sel(I/O Terminal 5)
T202 – Digital In2 Sel(I/O Terminal 6)
Parameter Organization - Terminal
AB Powerflex 4M
t201 – Digital In1 Sel(I/O Terminal 5)
T202 – Digital In2 Sel(I/O Terminal 6)
Parameter Organization - Terminal
AB Powerflex 4M
t211 – Analog In 0 ~ 10 V LoSets the analog input level that corresponds to P104 [Minimum Freq] if a 0-
10V input is used by P108
Analog inversion can be accomplished by setting this value larger than
t212 [Anlg In 0-10V Hi] or by setting t201 - t202 [Digital Inx Sel] to option
15 “Anlg Invert”.
t212 – Analog In 0 ~ 10 V HiSets the analog input level that corresponds to P105 [Maximum Freq] if a 0-10V input is
used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than t211 [Anlg In 0-
10V Lo] or by setting t201 - t202 [Digital Inx Sel] to option 15 “Anlg Invert”.
Parameter Organization - Terminal
AB Powerflex 4M
t213 – Analog In 4 ~ 20mA LoSets the analog input level that corresponds to P104 [Minimum Freq] if a 4-
20mA input is used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value larger than t214
[Anlg In4-20mA Hi] or by setting t201 - t202 [Digital Inx Sel] to option 15
“Anlg Invert”.
t214 – Analog In 4 ~ 20mA HiSets the analog input level that corresponds to P105 [Maximum Freq] if a 4-
20mA input is used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than
t213 [Anlg In4-20mA Lo] or by setting t201 - t202 [Digital Inx Sel] to option
15 “Anlg Invert”.
Parameter Organization - Terminal
AB Powerflex 4M
t221 – Relay Out SelectionSets the condition that changes the state of the output relay contacts.
Parameter Organization - Terminal
AB Powerflex 4M
t221 – Relay Out SelectionSets the condition that changes the state of the output relay contacts.
t222 – Relay Out LevelSets the trip point for the digital output relay if the value
of t221 [Relay Out Sel] is 6, 7, 8, 10 or 11.
Learn 4 PLC’s in a Day100+ Video Tutorials
Life time Access
nfipresents
Lea
rn t
o C
od
e |
Co
de
to
Le
arn
Coupon Code https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare
in $99 $49
For more courses visit www.nfiautomation.org
Course Outline
• 100+ PLC Video Tutorials
• Doubt Clearing Complementary LIVE Sessions on Team Viewer
• Ladder Logic Programming
• PLC Presentations, PLC Circuits, PLC Codes
• FREE PLC Simulation Software for Practice
PLC – Programmable Logic Controller
Delta DVP 14 SS + 16 SP
Allen Bradley M1000
Siemens S7 200
Schneider
Analog Cards Programming
04 AD – Analog to Digital
04DA- Digital to Analog
PLC & VFD Advanced
Course4 PLC’s Training
Platforms
For more courses visit www.nfiautomation.org
Course Highlights:
• 30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD
• 100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator
• FREE Circuits Diagram
$149
Course Link:http://www.wiziq.com/course/28882-plc-and-ac-drives-online-certificate-trainaing-course
Thankswww.nfiautomation.org
nfi