Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1....

39

Transcript of Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1....

Page 1: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9
Page 2: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

2 ABB

UniswitchContent

1. Design philosophy ............................... 32. Applications ......................................... 53. Switchgear construction ....................... 64. Cubicle types ........................................ 9

5. Components & accessories ............... 21

7. Ordering example ................................. 38

6. Technical data / dimensions ................ 30

4.1 Cubicle program ................................... 94.2 Cubicle type SDC ..................................... 114.3 Cubicle with fuse, type SDF .................

12

4.4 Cubicle type ZS8.X ...............................13

4.5 Cubicle type DBC ................................14

4.6 Cubicle type SEC ................................15

4.7 Cubicle type SMC ...............................16

4.8 Cubicle type BRC ...............................17

5.1 Mechanism,types single and double spring ...............18

5.2 Switch disconnector , type SFG ............. 195.3 Busbar arrangement .............................. 205.4 Motor operation of switch disconnector .....215.5 Earthing switches................................... 225.6 Vacuum Circuit Breaker VD4-S ..............235.75.8

Fuse link type CEF ................................ 24

5.95.10

Low voltage compartment .....................26

5.1 1

Voltage presence indicating system ......27Control cable entries .............................. 28Arc gas channel ..................................... 29

6.1 Cubicle dimensions .............................. 306.2 Floor plan ............................................. 316.3 Cable arrangement .............................. 346.4 Technical data / Dimensions ................. 36

Page 3: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

3ABB

1.Uniswitch, need to say more?

Uniswitch

Design Philosophy

Uniswitch, the light flexible switchgear developed as a modular, simpleto apply design, with fewer components, providing a high reliable,quality and safe product for you, our Customer.

By reducing the number of components, uti-lising modern materials correctly, we havedeveloped an environmentally and userfriendly product. The simple design andconstruction of Uniswitch will stand the testof time for generations to come.

Uniswitch is an air insulated (AIS), metalenclosed, switchgear cubicle design of thenext generation developed through conti-nuous innovation and vision to meet thechanging market needs. The standard cubicleis powder pointed light gray (RAL 7035) onvisible parts.

Uniswitch provides long-term technical solu-tions for various applications. Safety, userfriendliness and environmental concerns havebeen the driving force in the development ofthe switchgear.

Uniswitch switchgear is a compact solutionfor a fully automated power distribution net-work. Supported by sensor technology andthe latest in protection relays, it meets even themost demanding requirements in hospitalsand airports.

Uniswitch is a worldwide switchgear deve-lopment utilising the global experience of ABBto incorporate the needs of Customers fromall over the world. Uniswitch switchgear isavailable from the ABB worldwide networkof Companies.

Page 4: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

4 ABB

Uniswitch market segment

Uniswitch

Light compactdistribution switchgear

Ring Main Unit forapplications like:

Residential suburbanElectrical distributionCompact secondary

substation

Heavy switchgearfor demanding

applications including:Primary substations

Power plantsRailwaysMarine

Secondary substationsManufacturing industry

Shopping centresAirports

MetroWindmills

Small/medium sizepower plants

HospitalsSportcenters

Etc.

Switchgear for electricitydistribution application such as:

Uniswitch product provides our Medium Voltage Customer with the best solution for heavy dutyswitchgear in a size only a little than a single tank Ring Main Unit while including:ñ the flexibility in meeting our Customers specification and accomodating on future change and upgradingñ the options include complete control, measuring and protection systems

Page 5: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

Uniswitch

Applications2.

1. Airport2. Utility3. Hospital4. Power Plants, Diesel/gas engine (built by W‰rtsil‰)

5. Industry6. Windmills7. Sports center (Botnia Hall, Vaasa)

8. Metro9. Shopping center

5ABB

Page 6: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

6 ABB

3.

1

2

3

4

Metal enclosed, cubicle type switchgear

Uniswitch

Switchgear Construction

1. Busbar compartmentThe busbar compartment is located on the top of the cubicle. Thiscompartment contains the main busbars that intreconnect betweenswitchgear cubicles.

2. Switching compartmentA 3-position SF6 switch disconnector with epoxy cast resin housingis provided with inspection windows and available also with gasdensity indicator.

3. Cable compartment75 % of the space in the switch disconnector cubicle is reserved forpower cable connection making it possible to use both 1- and 3-phasecables with most simple unscreened terminations. Space is alsoadequate for cubicle accessories such as surge arresters, currenttransformers, second earthing switch etc. The door has an inspectionwindow and safety interlocking as standard. For cable entry there are3 individual cable gland plates in the bottom with support for a suitabledimensioned cable clamp. The bottom and the threshold of the cubiclecan be removed for ease of cable installation.

Busbar compartment

Switching compartment

Cable compartment

Mechanism, interlocking andlow voltage compartment

4. Mechanism, Interlocking andLow Voltage compartment

Behind a hinged door (which serves as control panel) are located thespring operating mechanism with position indicator and the mechani-cal interlocking unit. There are also facilities for cubicle accessoriessuch as: auxiliary contacts, tripping coil, emergency tripping mecha-nism, capacitive voltage presence indicating system, key interlocks andmotor operating device. Space is also provided for control circuits andmeasuring instruments as well as a protection relay. In the 750 widecubicles there is also a second indentical compartment for furtheraccessories.

The upper part of the cubicle, including the busbar compartment, theswitch disconnector and the mechanism and LV compartment isseparated from the lower part and the cable compartment. Because ofthis it is possible to carry out maintenance, repair and upgrading ofthe unit in the lower module while the switchgear is in service.

41

2

3

Page 7: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

7ABB

1

2

Primary part

1 Top unit- 3-position switch disconnector SFG- Operating mechanism with mechanical

position indication- Enclosure of busbar compartment- Integrated low voltage compartment for

secondary components- Interlocking unit- Busbars- Control cable ducts

Uniswitch

Switchgear Construction

2 Bottom unit- Enclosure- Current transformers- Earthing switches- Voltage transformers- Cable entry with cable support

3.

Page 8: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

8 ABB

Switch Disconnector Cubicle, type SDC

Width: 375 or 500 mmHeight: 1635 or 1885 mm

Uniswitch

Cubicle Program

Width: 500 mmHeight: 1635 or 1885 mm

4.1

Switch Disconnector with fuse Cubicle, type SDF

Width: 375 or 500 mmHeight: 1635 or 1885 mm

Width: 500 mmHeight: 1885 mm

Circuit Breaker Cubicle, type CBC

Width: 650 mmHeight: 1885 mm

Page 9: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

9ABB

Sectionalizing Cubicle, type SEC

Width: 750 mmHeight: 1635 or 1885 mm

Width: 750 mmHeight: 1635 or 1885 mm

Uniswitch

Cubicle Program

Direct Busbar connection Cubicle, type DBC

Width: 375 or 500 mmHeight: 1635 or 1885 mm

Width: 500 mmHeight: 1635 or 1885 mm

4.1

Page 10: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

11 ABB

Uniswitch

Cubicle Program

Width: 750 mmHeight: 1635 or 1885 mm

Width: 750 mmHeight: 1635 or 1885 mm

Sectionalizing Metering Cubicle, type SMC

4.1Bus Riser Cubicle, type BRC

Width: 375 or 500 mmHeight: 1635 or 1885 mm

Width: 500 mmHeight: 1635 or 1885 mm

Page 11: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

11ABB

Switch Disconnector Cubicletype SDC

Uniswitch

Cubicle Types4.2Basic equipmentTop unit, including- 3-position switch disconnector- operating mechanism with mechanical

position indication- enclosure of busbar compartment- integrated low voltage compartment- interlocking unit- busbars- earthing bar

Bottom unit, including- enclosure of cable compartment- cable entry with cable support

Cubicle Accessories- integrated voltage indicators or socket

interface for portable indicators- auxiliary contacts for each position,

2NO+2NC- gas density indication with alarm

contact- motor operation device- current transformers- arc-gas channel- channel for control cables- surge arresters- anti condensation heater- through-going earthing bar- apparatus earthing bar

Data SDCRated voltage [kV]Rated current [A]Rated short-time withstand current [kA]Max. rated duration of short circuit [s]Cubicle dimensions

- width [mm]- depth [mm]- height [mm]

12630252

375/500940+60

1635/1885

24630203

375/500940+60

1635/1885

Switch disconnector cubicle type SDC, ismainly used as an incoming, ring or branchcubicle. The basic unit is equipped with anSF6-insulated, 3-position switch disconnectortype SFG with its operation mechanism. The3-position switch disconnector may be in oneof three positions, "closed", "open" or "earthed",therefore preventing incorrect operation.Access to the cable compartment is possiblein earthed position. The position indicator ofthe switch disconnector (SFG) fulfils therequirements of the standards IEC 129 A2(1996), which determine the requirementsfor such an indicator. "Open" and "earthed"positions are "visible" through the inspectionwindows placed behind the low voltagecompartment door. Inspection of cableconnections and fault indicators, when used,is easily carried out through the front-doorwindow.

For safe cable testing a unique interlockingmechanism is included as standard feature.

Page 12: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

12 ABB

Switch Disconnector Cubicle,with fuse type SDF

Data SDFRated voltage [kV] 24Rated current (max. fuse) [A] 80Rated short-time withstand current [kA] 20Max. rated duration of short circuit [s] 3Fuse length [mm] 442Cubicle dimensions

- width [mm] 375/500- depth [mm] 940+60- height [mm]

12125252

292/442

375/500940+60

1635/1885 1635/1885

Uniswitch

Cubicle Types4.3Fused switch disconnector cubicle type SDF,is primarily used for transformer protectionvoltage metering. The cubicle is equippedwith a SF6-insulated, 3-position switchdisconnector and with earthing switch. Forfuse earthing, the integrated earthing switchoperates on the upstream side and separateearthing switch operates on the downstreamside of the fuses.The mechanism used is adouble spring mechanism with automaticfuse-tripping. Access to cable compartmentis possible in earthed-position. The positionindicator of the switch disconnector (SFG)fulfils the requirements of the standards IEC129 A2 (1996), which determine the require-ments for such an indicator. “Open” and“earthed” positions are “visible” throughinspection windows placed behind the lowvoltage compartment door. Inspection ofcable connections and fault indicators whenused, is easily carried out through the front-door window.

Basic equipmentTop unit, including– 3-position switch disconnector– operating mechanism with mechanical

position indication– enclosure of busbar compartment– integrated low voltage compartment– interlocking unit– fuse tripping with indication– busbars– earthing bar

Bottom unit, including– earthing switch type EF– fuse base– enclosure of cable compartment– cable entry with cable support

Cubicle Accessories– integrated voltage indicators or socket

interface for portable indicators– auxiliary contacts for each position,

2NO+2NC– gas density indication with alarm

contact– emergency tripping– tripping coil– motor operation device– voltage transformers– arc-gas channel– channel for control cables– anti condensation heater– through-going earthing bar– apparatus earthing bar

Page 13: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

13ABB

Circuit Breaker Cubicletype ZS8.X

Data ZS8.X

Uniswitch

Cubicle Types4.4Basic equipmentTop unit , including– low voltage room– shell body of busbar room– busbar

Middle unit , including– breaker room

moveable VD4 vacuum breaker––

enclosure of busbar compartment

Bottom unit, including– enclosure of cable compartment– inlet of cable, with cable support– grounding busbar plate

Cubicle Accessories– current mutual-inductor– voltage mutual-inductor– displayer with electricity– pressure releasing channel– insulated partition

ZS8.X type circuit breaker is used for the leading-in of Uniswitch cabinet, with rated current 1250A.The cabinet is equipped with moveable VD4 vacuum breaker. Operator can obs-erve the handcart position of breaker th-rough the window on the door of breaker room, or observe the connecting of cable through the window on the door of cable room. The breaker cabinet could also be equipped with current mutual-inductor and voltage mutual-inductor.

Rated voltage [kV] 12Rated frequency voltage endurance(1 min)[kV] 42Rated impulse voltage endurance [kV] 75Frequency [Hz] 50Rated main busbar current [A] 1250Rated peak value current [kA] 80Rated resistance current in short time [kA] 31.5Rated continuous time in short circuit [s] 3Auxiliary power supply voltage [V] AC: 110, 220 DC: 24, 48, 60, 110, 220Overall dimension- Width [mm] 650- Depth [mm] 1257- Height [mm] 1885

Page 14: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

14 ABB

Direct Busbar Cubicletype DBC

Uniswitch

Cubicle Types4.5Basic equipmentTop unit, including– busbar supports– enclosure of busbar compartment– interlocking unit, but only when using

earthing switch (EM)– integrated low voltage compartment– busbars– earthing bar

Bottom unit, including– enclosure of cable compartment– parallel cable connection possibility– cable entry with cable support

Cubicle Accessories– integrated voltage indicators or socket

interface for portable indicators– current transformers– earthing switch for CT’s (EM)– arc-gas channel– channel for control cables– surge arresters– anti condensation heater– through-going earthing bar

Data DBCRated voltage [kV] 12Rated current [A] 1250Rated short-time withstand current [kA] 25Max. rated duration of short circuit [s] 2Cubicle dimensions

- width [mm] 375/500- depth [mm] 940+60- height [mm] 1635/1885

24630203

375/500940+60

1635/1885

To connect cables to the busbars, a busbarconnection cubicle is available. This cubicleis equipped with connection lugs for fixing thecables. CT's can be installed in the 500 mmcubicle.

The front door is fixed and can only beopened with a tool when earthing switch is notincluded.

Page 15: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

15ABB

Data SECRated voltageRated currentRated short-time withstand currentMax. rated duration of short circuitCubicle dimensions

- width- depth- height

[kV][A][kA][s]

[mm][mm][mm]

12630252

375/500940+60

1635/1885

24630203

375/500940+60

1635/1885

Sectionalizing Cubicletype SEC

4.6 Uniswitch

Cubicle Types

Basic equipmentTop unit, including– 3-position switch disconnector– operating mechanism with mechanical

position indication– enclosure of busbar compartment– integrated low voltage compartment– interlocking unit– earthing bar

Bottom unit, including– enclosure with sectionalizing busbars– bottom cover

Cubicle Accessories– integrated voltage indicators or socket

interface for portable indicators– auxiliary contacts for each position,

2NO+2NC– gas density indication with alarm

contact– motor operation device– current transformers– arc-gas channel– channel for control cables– anti condensation heater– through-going earthing bar– apparatus earthing bar– voltage transformers

The sectionalizing cubicle is always usedtogether with the bus riser cubicle. The stan-dard version with 375 mm width is equippedwith a SF6-insulated, 3-position switchdisconnector for sectionalizing the busbars.Earthing facility is provided always as astandard.

Page 16: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

Upper part of the right side including units: 3 station-type loading switch Operated mechanism equipped with mechanical position indicator Integrated low-voltage chamber Interlocking device BusbarUpper part of the left side including units: 3 station-type loading switch Operated mechanism equipped with mechanical position indicator Interlocking device BusbarLower part including units: Shell body of cable roomOptional components of cabinet: Insert interface of integrated electricity displayer or portable electricity displayer Auxiliary contacting point of each position, with 2 always open and 2 always closed. Gas density meter or gas density device with alarming contact. Emergency tripping mechanism Breaking coil Power operated device Voltage mutual-inductor Current mutual-inductor Pressure releasing channel Control cable channel Grounding busbar

16 ABB

Sectional measuring cabinettype SMC

Technical data

Uniswitch

Cubicle Types4.7Basic equipment

––

–––

–––

––

Two independent operated SFG type 3 station-type loading switches can be installed in the SMC type sectional measuring cabinet. The two loading switches are placed at both ends of the sectional busbar.There is interlock between the loading switch and the front door of cabinet. The front door can't be opened unless both loading switches at the grounding positions.

––

–––

––

––

Rated current [A]630Rated resistance current in short time[kA]25Rated continuous time in short circuit[s]2Overall dimension- Width[mm]750- Depth[mm]1000- Height[mm]1635, 1885

Page 17: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

17ABB

Bus Riser Cubicletype BRC

Data BRCRated voltage [kV] 12 24Rated current [A] 630/1250 630/1250Rated short-time withstand current [kA] 25 20Max. rated duration of short circuit [s] 2 3Cubicle dimensions

- width [mm] 375/500 375/500- depth [mm] 940+60 940+60- height [mm] 1635/1885 1635/1885

Uniswitch

Cubicle Types4.8Basic equipmentTop unit, including– switch substitute– enclosure of busbar compartment– integrated low voltage compartment– earthing bar

Bottom unit, including– enclosure with bus riser bars– bottom cover

Cubicle Accessories– current transformers– voltage transformers– earthing switch with position indication– auxiliary contacts for earthing switch,

2NO+2NC– arc-gas channel– channel for control cables– anti condensation heater– through-going earthing bar– integrated voltage indicators

Bus riser cubicle, type BRC, connects thebusbar to the bottom of a sectionalizingcubicle with circuit breaker or switchdisconnector. This 500 mm width cubicle canbe used as a metering cubicle with space for3 CTs and 3 VTs. The front cover is fixed tothe cubicle and has to be released with a tool.The front door has a window for inspection.

Page 18: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

18 ABB

Uniswitch

Components & Accessories5.1Mechanism

UES-A3/2 double springoperating deviceThe UES-A3/2 is used together with the switchdisconnector type SFG and the cubicles ofSDF.

The same mechanism is used to operate theswitch positions between OPEN ñ CLOSEand OPEN ñ EARTH. The UES-A3/2 is alsoused to operate the earthing switch EF. Therehas to be always the central interlockingmodule 1VFJ220001R2 fully assembledin the front of the UES-A3/2 during theoperation.

The UES-A3/2 uses the energy stored in 2 flatsprings. One (K-spring) to close and open theswitch disconnector and another (A-spring)to rapidly open the switch-disconnector.The A-spring charges the K-spring. The Aspring is charged during the manual or motoroperation from the open to the close positiononly once. During the operation the A-springwill be locked and not released before theimpulse from the fuse, shunt trip-coil ormechanical push button. Before that theUES-A3/2 can be used similarly to UES-K3/2.The operation shaft has to be returned to theopen position after the tripping.

The total manual operation angle is approxi-mately 180° (90°+ 90°). The switch iscon-nector is closed by a clockwise operation andthe earthing switch is closed by an anti-clockwise operation.

The mechanism is maintenance free duringthe whole lifetime (i.e. 30 years) in normalconditions. Mechanical endurance is 2000C/O (5000 C/O in a motor use only) and 1000O/Earth.

The UES-A3(M)/2 can be equipped with– Shunt trip-coil type

- 24VDC =1VFJ120007R2 -24VDC- 48VDC =1VFJ120007R2 -48VDC- 60VDC =1VFJ120007R2 -60VDC

- 110VDC =1VFJ120007R2 -110VDC- 220VDC =1VFJ120007R2 -220VDC- 110VAC =1VFJ120007R2 -110VAC- 230VAC =1VFJ120007R2 -230VAC

– Mechanical push button for a rapidopening, type 1VFJ120042R2

– For motor operation device UES-A3M/2

UES-K3/2 single springoperating mechanismThe UES-K3/2 is used together with the switchdisconnector type SFG and the cubicles of– SDC– SEC– SMC

The same mechanism is used to operate theswitch positions between OPEN ñ CLOSEand OPEN ñ EARTH. There has to be alwaysthe central interlocking module 1VFJ220001R2fully assembled in the front of the UES-K3/2during the operation.

The UES-K3/2 uses the energy stored in aflat spring to close and open the switchdisconnector. The total operation angle isabout 180° (90° + 90°). The switch disconnectoris closed by a clockwise operation and theearthing switch is closed by an anti-clockwiseoperation.

The mechanism is maintenance free duringwhole lifetime (i.e. 30 years) in normal condi-tions. Mechanical endurance is 5000 C/Oand 1000 O/Earth.

The UES-K3/2 can be equipped with motoroperating device UEMC40K8-U/1.The opening time from the impulse is about40 ms.

Central interlocking moduleThere is a new central interlocking moduletype 1VFJ220001R2 used in Uniswitch. Themodule is used to avoid any incorrectoperations and to give more alternatives tointerlock. Padlocks can be used to interlock.Can be equipped with a fast lock.

Position indication andoperator interface moduleDifferent colors of position indication labelsare available.As a standard white color has been used inthe module type 1VFJ120005R2.

Manual operation handleTo avoid any incorrect operations use themanual control handle type 2183-2720CNTHBR1only.

Single spring mechanism

Single spring mechanismwith motor

Double spring mechanismwith motor

Page 19: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

19ABB

Switch disconnector, type SFGThe switch disconnector, type SFG, has thefollowing 3 positions:– CLOSE– OPEN– EARTHING

The switch disconnector is using SF6 asextinguishing and insulation medium. Theswitch housing is equipped with two thermoplastic windows to allow visual inspection.Each switch is sealed for life (i.e. 30 years)and maintenance free. SF6 gas pressure is1.4 bar and the SFG switch incorporates acapacitive divider for voltage indication.Mechanical endurance is 5000 C/O and 1000O/Earth.The switch and operation mechanism areinstalled in a removable top unit, making iteasy to convert SDF to a SDC cubicle, or viceversa.

Switch types– SFG with UES-K3 operating mechanism– SFG with UES-A3 operating mechanism

Optional equipmentAuxiliary contacts:– closed position 2NO-2NC– earth position 2NO-2NC

Shunt trip coil:For SFG with UES-A3 operating mechanism.

Push-button for mechanical tripping of SFGwith UES-A3 operating mechanism.

Motor operation: See item 5.4.

Uniswitch

Components & Accessories5.2

oRated v ltage Ur 24

Rated lightning impulse withstand voltage UpCommon value 125Across the isolating distance 145

Rated short-duration power-frequency withstand voltage UdCommon value 50Across the isolating distance 60

Rated frequency 50/60Rated current Ir 630

Rated short-time withstand current 20Max. rated duration of short circuit 3Rated peak withstand current 50

Breaking capacity (IEC 60265-1)Mainly active load 630Closed-loop distribution circuit current 630Cable-charging current 50/10Line-charging current 20Cable and line charging current under earth faults 87

Making capacity (IEC 60265-1) 50

Making and breaking capacity (IEC 60420)Withstanding and making the cut-off current of the fuse 20Breaking test with long prearcing time of fuse okBreaking capacity at rated transfer current 920

Mechanical endurance of switch c/o 5000Mechanical endurance of earthing switch c/o 1000

Ambient temperatureMaximum value + 40Maximum value of 24 h-mean + 35Minimum value - 5 3)

Altitude above sea level

[kV]

[kV][kV]

[kV][kV][Hz][A]

[kA][s]

[kA]

[A][A][A][A][A]

[kA]

[kA]

[A]

[˚C]

[m]

12

85110

4249

50/60800

252

62,5

630/800630

50/102087

62,5

25ok

1500

50001000

+ 40+ 35- 5 3)

<1000 2) <1000 2)

1) Highest values in accordance with national standards.2) Adjustment is necessary for greater altitudes.3) Lower ambient temperature on request.

Page 20: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

20 ABB

Busbar arrangementThe copper busbars are located in the TopUnits in their own compartment. The busbarsare provided in sections and connect thecubicles together. This arrangement makesit easy to extend the switchgear.

Busbar set 12/kV,630/1250 APanel width 375 mmPanel width 500 mmPanel width 750 mm

Busbar set 24 kV, 630 A(Insulated with heat shrink sleeve)Panel width 375 mmPanel width 500 mmPanel width 750 mm

Field control caps for 24 kV

Uniswitch

Components & Accessories5.3

Data busbarRated voltage [kV] 12 24Rated current [A] 630/1250 630Rated short-time withstand current [kA] 25 20Max. rated duration of short circuit [s] 2 3Material Cu CuInsulation no yesDimension [mm] 40x8 40x8

Page 21: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

21ABB

Motor operation ofswitch disconnector

For single spring mechanism

Uniswitch

Components & Accessories5.4For electrical or remote operation of the switchdisconnector type SFG a motor operationdevice and a control unit are available for allcubicles.

The motor operating devices and the controlunit are mounted in the low voltage compart-ment. They can be mounted without anyadditional parts.

The motor operating devices are DC ope-rated and a rectifier is used when AC supply.For control of motor operating device 2NO+ 2NC aux. contacts on switch disconnectorare required.

The motor operation device types whenmechanism UES-K3/2 is used

Type

UEMC 40 K8-24 VDC/3UEMC 40 K8-48 VDC/3UEMC 40 K8-60 VDC/3UEMC 40 K8-110 VDC/3UEMC 40 K8-125 VDC/3UEMC 40 K8-220 VDC/3

Includes:– Motor– Position limit switches

The operating device type UES-A3M/2 has tobe chosen instead of type UES-A3/2 when adouble spring device is needed.

Control push buttonsIncludes:– I-button with text CLOSE– O-button with text OPEN– On/Off selector switch with

text REMOTE ON/OFF

For double spring mechanism

Type

1VFU 12003R2-24VDC1VFU 12003R2-48VDC1VFU 12003R2-60VDC1VFU 12003R2-110VDC1VFU 12003R2-125VDC1VFU 12003R2-220VDC

Includes:– Motor + double spring device– Position limit switches

The operation shaft has to be returned tothe open position after the motorized openoperation if a manual closing is to be exe-cuted.

Page 22: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

22 ABB

Earthing Switches

Technical Data IEC 129/265-1Rated voltage 12 kV 24 kVMaking capacity

EF - 210 [kA] 5 5EM - 210 [kA] 62,5 50

The main earthing switch is incorporated inthe switch disconnector SFG. The earthingswitch has 3 double bladed moving knives.The fixed contacts are connected togetherto a common earthing bar inside the switchhousing.

The earthing switch, type EF, has reducedmaking capacity due to the fact that no fullshort circuit current can occur (Fuse down-stream).

Earthing switch, type EM, is used for earthingcurrent transformers and circuit breaker.

All earthing switches have true position indi-cators through the front door and are ope-rated by the main operating shaft in the frontof the panel.

For fuse base (down-stream)EF - 210

For current transformers (down-stream)EM - 210

Optional equipment– auxiliary contacts 2NO-2NC

+ extension 2NO-2NC

Different configurations

EM

EF

SFG

Uniswitch

Components & Accessories5.5

Page 23: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

23ABB

Vacuum Circuit Breaker

Uniswitch

Components & Accessories5.6CBC-D type breaker cabinet adopts the VD4 vacuum breaker, which technology and main components are provided by CALOR-EMAG Company, Germany, and assembled and man-ufactured in CNDMX. The breaker is fully conforming to the IEC60056 and GB1984.

VD4 vacuum breaker can be operated freque-ntly in the scope of working current, open and close short circuit current many times. It app-lies to reclosing operation, with extreme high reliability of operation.

As for detailed technical parameter of VD4 vacuum breaker, refer to product specification of the breaker.

Page 24: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

24 ABB

Fuse link type CEFThe Uniswitch system is designed forHRC-fuses according to IEC Publication 282-1.The dimensions are in accordance to DIN43625 with length «e» 292 mm for 12 kV and442 mm for 24 kV. To select and orderfuse for the transformer protection see tablebelow.

The lower fuse contacts are mounted on theinsulators. These insulators can be selectedwith or without capacitive voltage trans-mitters.The upper fuse contact with fuse trippingrelease is fixed directly on the switch-disconnector.

Medium voltage - HRC fuse links

Selection of fuses: According to IEC 60420

Uniswitch

Components & Accessories5.7

1) Unique ratings on request

Type Rated Rated e/d Ident. No.voltage current

kV A mmCEF 12 6 292/65 NHPL052721R1

10 292/65 NHPL052723R116 292/65 NHPL052724R125 292/65 NHPL052725R140 292/65 NHPL052726R150 292/65 NHP241036R1263 292/65 NHPL052727R180 292/87 NHPL052703R1

100 292/87 NHPL052728R1125 442/87 NHPL052704R1

CEF 24 6 442/65 NHPL052741R110 442/65 NHPL052743R116 442/65 NHPL052744R125 442/65 NHPL052745R140 442/65 NHPL052746R150 442/87 NHP241038R663 442/87 NHPL052747R180 442/87 NHP200473R2

Transformer rating [kVA]57 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500

Fuse selection (ratings in Amps)3 25 25 40 40 63 63 63 80 100 1005 16 25 25 25 40 40 63 63 63 80 100 1006 16 16 25 25 25 40 40 63 63 63 80 100 10010 10 16 16 16 25 25 25 40 40 63 63 63 80 100 10012 10 16 16 16 16 25 25 25 40 40 63 63 63 80 100 12515 10 10 16 16 16 16 25 25 25 40 40 63 63 63 100 10020 10 10 10 16 16 16 16 25 25 25 40 40 63 63 63 80 1)24 10 10 10 10 16 16 16 16 25 25 25 40 40 63 63 63 80

Ope-ratingvoltage kV

Page 25: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

S L J series of fuse

25ABB

The product, manufactured by Xian Fuse Plant, is suitable for indoor AC 50 Hz, rated voltage 12KV system. Length of 12KV is 292mm. The type of specification as follows:

S L J

Choose and order for the fuse with transformer protection, see the table below:

Uniswitch

Components & Accessories5.7

Transformer rating [kVA]

Insert type

N: none; A: power type; D: spring type

Length of fuse piece: 292mm

Diameter of fuse piece: D=51mm, F,K=76mm

New type fuse with transformer protection

Transformer preliminary voltage 10kV

Type of fuse Rated current of fuse [A]

100 12KVSDLDJ 16

125 12KVSDLDJ 16

160 12KVSDLDJ 16

200 12KVSDLDJ 20

250 12KVSDLDJ 25

300/315 12KVSDLDJ 31.5

400 12KVSDLDJ 40

1250 12KVSDLDJ 100

1250 12KVSDLDJ 125

500 12KVSDLDJ (SFLDT) 50

630 12KVSDLDJ (SFLDT) 63

750/800 12KVSDLDJ 80

1000 12KVSDLDJ 80

Page 26: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

26 ABB

Low Voltage CompartmentThe Uniswitch system contains an integratedlow voltage compartment whitch is segre-gated from the high voltage side by a metalpartition.

For 750 mm wide cubicles the LV compart-ment consists of two 375 mm compartments.In 750 mm cubicles the left compartment isreserved for meters, switches & push but-tons (front door) and terminal blocks, mcb¥s& auxiliary relays (rear plate). The right sidecompartment's upper side is reserved for pro-tection relays (SPACOM 100 or 300 series)and the lower side for the SFG switchdisconnector's operating device.

For 375 mm and 500 mm wide cubicles the LVcompartments upper side is reserved for ter-minals. The lower side for the SFG switchdisconnector¥s operating device.

Uniswitch

Components & Accessories5.8

Front view750 mm (CBC) cubicle

750 mm (CBC) cubicle(one part)

375 mm (SDF) cubicle

Cable inlet from cable channel, panel andbetween different panels are shown in item5.13.

The pictures on the left show examples ofhow the components can be arranged in thelow voltage compartment.

Other arrangements and special applicationsare available on request.

Protection relay

LV compartment

Measurements375/500 x 580 x 120 mm(width x hight x depth)

Page 27: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

27 ABB

Uniswitch

Components & Accessories5.9 Condenser-type displayer with electricity

It applies to middle voltage(°› 6kV) switch cabinet with high capacity-resistance display system with electricity (VIS), conforming to IEC61243-5.Choose of electricity displaying system:- DXN-T Suggesting style indicator Transfer signal to indicator from three high voltage electrification sensors.Press the key of indicator to indicate high voltage electrification.- DXN-Q Locking style Transfer signal to indicator from three high voltage electrification sensors.Press the key of indicator to indicate high voltage electrification. When there is high voltage electrification signal,the indicator forces the electromagnetic relay to lock the high voltage electrical equipment.

Specificattion

StyleMinimum input Maximum input Secondary power Electromagnetic current current Relay capacityDXN-T 40uA 5000uADXN-Q 40uA 5000uA AC 220V/110V 7A/250V AC DC 220V/110V 7A/30V DC

High voltage capacitance sensor fits: High voltage capacitive senson produced by production of KUVAG,JORDAN and RISHO.

Page 28: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

28 ABB

Uniswitch

Components & Accessories5.10Control cable entriesIn the basic cubicle the control cable entryis in the bottom (1). An internal cable duct30 x 60 mm is supporting the cable fromthe bottom up to the upper part (TopUnit).Internal wiring between cubicles (5) is easilydone through openings in side walls.

Several options are available (2, 3, 4, 6) forcontrol cable inlet.

(2) At both ends of the switchgear, it ispossible to have side ducts mounted.

(3) A duct can also be placed on top of theswitchgear supportning cables coming frome.g. overhead cable ladder (4).

..

5

43

2

1

2 6 1

5 5

115

Page 29: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

29ABB

Uniswitch

Components & Accessories5.11Arc gas channel

To ventilate the arc-gas out in a certain direc-tion, arc-gas channels are available for theUniswitch system. Vertical channel (1) on therear of each cubicle has been connected toa common horizontal channel (2) on the top ofthe switchgear. The horizontal channel hasbeen connected to an opening (3) in the wall

of the switchgear room. The connecting pointfrom channel (2) to the opening will be locatedin the rear or in the end of the top channel (2).The opening (3) has been equipped with inpressure relief flap.

Page 30: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

30 ABB

Cubicle dimensions

Uniswitch

Technical data / Dimensions6.1

Main dimensions and the need of space of circuitbreaker cubicle without arc channel

Main dimensions and the need of space of cubicleswithout circuit breaker and with arc gas channel

940

H =

163

5Al

t H

= 1

885

40

35

1000

250

1190

Page 31: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

31ABB

Uniswitch

Technical data / Dimensions6.2Floor plan

Page 32: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

32ABB

Uniswitch

Technical data / Dimensions6.2Floor plan

Page 33: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

33ABB

Uniswitch

Technical data / Dimensions

�Connect with CBC ��

CBC -- UniSwitch installation form

CBC -- UniSwitch dimension of channel steel

��

6.2wall

channel steel

channel steel

secondary cable hole

channel steel channel steel

Page 34: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

34 ABB

Cable arrangement

Uniswitch

Technical data / Dimensions6.3

Further information regarding cable arrangement is available in installation manual.

188

By H

/163

5 = 98

0 mm

By H

/188

5 = 12

30 m

m

288

By H

/163

5=46

mm

By H

/188

5=71

0mm

M12Hexagonal bolt

M12Hexagonal bolt

Page 35: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

35ABB

Cable arrangement

Uniswitch

Technical data / Dimensions

Further information regarding cable arrangement is available in installation manual.

188

By H

/163

5

12/

17,5

kV

= 60

5

24

kV

=

455

By H

/188

5

12/

17,5

kV

= 85

5

24

kV

=

705

M12Hexagonal bolt

Page 36: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

36 ABB

Rated voltage Ur [ kV] 12 24

Width / circuit breaker cubicle [mm] 750 750

Width / other cubicles [mm] 375/500 375/500

Height [mm] 1635/1885 1635/1885

Depth [mm] 940+60 940+60

Height / LV-compartment [mm] 450 450

Dimensions

Technical data

Uniswitch

Technical data / Dimensions6.4

1) Higher values in accordance with national standards on request2) Adjustment is necessary for greater altitudes3) Lower ambient temperature on request.

Rated voltage Ur [ kV] 12 24

Rated lightning impulse withstand voltage UpCommon value [kV] 75 125Across the isolating distance 85 145

Rated short-duration power-frequency withstand voltage UdCommon value [kV] 28 1) 50Across the isolating distance 32 1) 60

Rated frequency [Hz] 50/60 50/60

Rated current IrBusbar [A] 630/1250 630Feeder 630 630

Rated short-time withstand currentMain circuit [kA] 25 20Earthing circuit [kA] 25 20

Max. rated duration of short circuit [s] 2 3Rated peak withstand current [kA] 62,5 50Arc-fault current, 1s [kA] 20 20

Degree of protection (IP-code)For the enclosure IP2XC IP2XCFor the partitions IP 2X IP 2X

Mechanical endurance of switch c/o 5000 5000Mechanical endurance of earthing switch c/o 1000 1000

Ambient temperatureMaximum value [oC] +40 +40Maximum value of 24 h-mean +35 +35Minimum value -5 3) -5 3)

Altitude above sea level [m] <1000 2) <1000 2)

Page 37: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

37ABB

Weights (without packing)

Tests and CertificatesType test according to IEC 60298 and certificated by SATSRoutine test IEC 60298Quality certificate ISO 9001Environmental certificate ISO 14001.

Uniswitch

Technical data / Dimensions

Note: Circuit breaker belonging to breaker cubicle is delivered in a separate packing.

1) without CT's and VT's2) without fuses3) without circuit breaker4) including CT's and VT's

Dimensions: (W x H mm) SDC 1) SDF 2) DBC 1) SEC 1) BRC 1) BMC 4)

- 375 x 1635 [kg] 130 140 110 140 140 -- 375 x 1885 [kg] 140 150 120 150 150 -

- 500 x 1635 [kg] 140 150 120 150 150 -- 500 x 1885 [kg] 150 160 130 16 0 160 -

- 750 x 1635 [kg] - - - - - 420- 750 x 1885 [kg] - - - - - 440

Page 38: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

SDC SDF DBC SEC BRC SMC PT

38 ABB

Uniswitch

Ordering example7.

Mainoptions

Standardcubicletypes

Voltage indicators

Current transformers

Surge arresters

Voltage transformers

Height Width

1635 375

1635 500

1635 750

1885 375

1885 500

1885 750

[mm] [mm]

FusedSwitchDisconn.Cubicle

The standard range of cubicles and the main options

SwitchDisconn.Cubicle

PTCubicle

DirectBusbarConnectionCubicle

Sectional.CubiclewithLBS

BusRiserCubicle

Sectional.MeteringCubicle

Page 39: Uniswitchfs1.gongyeku.com/data/default/201210b/20121030020536714.pdf2 ABB Uniswitch Content 1. Design philosophy 3 2. Applications 5 3. Switchgear construction 6 4. Cubicle types 9

ABB High Voltage Switchgear Co. Ltd., Beijing

Add: No 12 Jingyuan Street,Beijing Economic-Technological Development Area,Beijing, 100176, P. R. China