ABB turnkey stations ULTRA-MVC-S770 to 3110 kW
Turnkey solutions comprising an ULTRA series inverter and a Medium Voltage Compartment (MVC-S).
The new ULTRA-MVC-S has been specifically developed for large installations made with ULTRA series inverters. The MVC-S can operate at the most extreme climatic and environmental conditions, such as desert areas or coastal, salt water saline environments.
The MVC-S solution has been designed to optimize space, transportation, installation and maintenance, thanks to the integration of medium voltage components on a single metal base (skid).
Furthermore, the MVC-S is compliant with the most stringent European standards. Thanks to the use of oil sealed transformers with reduced loss, the MVC-S ensures minimum losses and maximum return on investment.
The ease of installation and maintenance is ensured by front access to all components and the ability to completely remove the transformer grid protection.
Highlights − Developed to be used jointly with
outdoor type inverters (ULTRA Series) − Designed and built for outdoor use in
all environmental conditions − Completely removable protection
grid for simplified installation and maintenance
− Maximum efficiency guaranteed by the use of reduced-loss MT transformer
− Reduced weight and dimensions to ensure ease of transport and installation
− Front access to all components and removable grid to simplify maintenance and installation
Solar inverters
ABB solar inverters | Product flyer for ULTRA-MVC-S
ABB turnkey stations
Technical data and types
Type code ULTRA-MVC-770.0-S ULTRA-MVC-1160.0-S ULTRA-MVC-1550.0-S
Inverter 1) ULTRA-700.0-TL ULTRA-1050.0-TL ULTRA-1400.0-TL
LV distribution panel
LV connections from the inverter 1) Max 6 x 3 x 240 mm2
Low voltage AC power distribution from inverters to trafo (magnetothermic switch) Not available (an automatic breaker is available as inverter option)
Device for insulation permanent control 2) Not available (the insulation control device is available as inverter option)
Energy meters 3) Not available (the Energy meter is available as inverter option)
Medium-voltage transformer
Construction Oil-sealed
Rated power (voltage) 800 kVA 1250 kVA 1600 kVA
Tap changer 4) ± 2 x 2.5%
Number of secondary windings 1
Cooling ONAN
Charging Mineral oil
Vector group Dyn11
Short circuit voltage 6%
Losses class Refer to transformer datasheet
Environmental protection rate IP65
Mv switchgear
Configuration Single feeder (double feeder optional)
Trafo protection Switch disconnector and fuses 16 kA (1s) / 630 A
Auxiliary supply
Auxiliary supply voltage 3x400 Vac + N, 50 Hz
Low voltage distribution for auxiliary functions Yes (include dedicated and protected supply lines for: inverter, data logger, lighting, AC socket, spare)
Supply for customer devices Single-phase socket with RCD protection, 16 A/230 V/50 Hz (Id = 0,03 A)
Auxiliary supply transformer (optional)
Construction Dry
Rated power (voltage) 15 kVA (690/400 V)
Cooling Air
Vector group Dyn11
No load losses / On load losses <130 W / <460 W
Protection for AUX transformer Circuit breaker
Cooling
Cooling type (switch gear cabinet) Forced air by extractor fan
MV trafo 1600kVA
0,69kV / XXkV
L1
L2
L3
MV switchgear (single feeder)
LBS
ES1
ES2
ES
///
Inv. Aux
ULTRA-1400.0-TL(1556kW@cosφ=1)
Aux trafoUVWN
3x690V3x400V+N
Inv. Aux 1
AUX QMT
AUX QBT
LV distributionfor AUX functions
Lighting
Fan
2P Spare
VWN
U
2P Socket
Inv. Aux 2
Extractor fan
LV distributionfor AUX functions
(UPS section)
Datalogger
AUX QBT-UPS
UPS
Therm. unittrafo
AUX QMT-UPS
Aux trafoprotectionfuses
MV
LBS
ES
Electrical diagram of ULTRA-MVC-1550.0-S
Technical data and types
Type code ULTRA-MVC-770.0-S ULTRA-MVC-1160.0-S ULTRA-MVC-1550.0-S
Inverter 1) ULTRA-700.0-TL ULTRA-1050.0-TL ULTRA-1400.0-TL
Environmental parametersFull power operating temperature range -25°C...+45°CRelative humidity (non-condensing) ≤ 95%Maximum operating altitude without deranting 5) 1000Communication/user interface and system monitoringCommunication port (PC / Data logger) 1 x RS485Communication to inverter 1 x RS485Remote communication (optional) VSN700 Data LoggerUPS (optional)UPS for protection and monitoring system 2 kVA, 10’
Lighting Fluorescent lamps T8 2x18 W, electronic supplier for emergency lighting with Ni-Cd hermetic battery (1 h autonomy)
Mechanical characteristicsDimensions (W x H x D) 5200 x 2800 x 2300 mmBody material (MV switch gear cabinet) Metal housing with double metal panel insulated by polyurethanic foamOil collecting tank 110% of oil contentEnvironmental protection rate (MV switch gear cabinet) IP43 (IP54 optional)
Environmental protection rate(trafo protection grid) IP1XA
1) For further details, please refer to the specific inverter data-sheet 4) Other medium voltage levels available on request2) Available as inverter option 5) Contact ABB for application at higher altitudes3) Available as inverter option - 4 quadrant MID certifiedRemark. Features not specifically listed in the present data sheet are not included in the product
Optional ULTRA-MVC-SLV electrical panel with automatic circuit breaker -Energy meters (one for each inverter) -LV distribution panels for auxiliary functions ●Auxiliary transformer ○Single / double feeder switchgear ●/○Monitoring system VSN700 Data Logger ○UPS 2 kVA for monitoring and protection system ○Hot climate package 50°C ○IP54 ambiental protection degree ○IP54 ambiental protection degree + sand trap filter ○
Product flyer for ULTRA-MVC-S | ABB solar inverters
AA
SPILL CONTAINMET
QMT SAFE RING CCV
5000
DOUBLE DOOR1650x2400h
ONLY RING CONFIGURATION
AIR ENTRANCE LOUVER(IP 43 PROTECTION GRADE)
DOOR
OIL TRAFO..... KVA
UPS 2 kVA Q.S.
TRAFOAUX
50 KVA(OPTIONAL)Q
.TR
AU
X
PROTECTION NET IP10
REMOVABLE FRAME
Optional IP 54Optional KIT SAND TRAP
5130
5130
2720
14020
2720
2489
71
2300
300
1930
259
2276
7390
5
7263
0
4611330 192300
19743156
7676 1822
DOOR1000x2200h
SECTION A-A
FRONT VIEW RIGHT LATERAL VIEW REAR VIEW
PLANT
QMT ABB
Footprint ULTRA-MVC-3110.0-S
Technical data and types
Type code ULTRA-MVC-1940.0-S ULTRA-MVC-2330.0-S ULTRA-MVC-2720.0-S ULTRA-MVC-3110.0-S
Inverter 1)ULTRA-700.0-TL
2x ULTRA-1050.0-TLULTRA-1050.0-TL
2x ULTRA-1400.0-TLULTRA-1050.0-TL ULTRA-1400.0-TL
LV distribution panel
LV connections from the inverter 1) Max 12 x 3 x 240 mm2
Low voltage AC power distribution from inverters to trafo (magnetothermic switch) Not available (an automatic breaker is available as inverter option)
Device for insulation permanent control 2) Not available (the insulation control device is available as inverter option)
Energy meters 3) Not available (the Energy meter is available as inverter option)
Medium-voltage transformer
Construction Oil-sealed
Rated power (voltage) 2000 kVA 2500 kVA 3150 kVA 3150 kVA
Tap changer 4) ± 2 x 2.5%
Number of secondary windings 1
Cooling ONAN
Charging Mineral oil
Vector group Dyn11
Short circuit voltage 6%
Losses class Refer to transformer datasheet
Environmental protection rate IP65
Mv switchgear
Configuration Single feeder (double feeder optional)
Trafo protection Switch disconnector and fuses 16 kA (1 s) / 630 A
Auxiliary supply
Auxiliary supply voltage 3x400 Vac + N, 50 Hz
Low voltage distribution for auxiliary functions Yes (include dedicated and protected supply lines for: inverter, data logger, lighting, AC socket, spare)
Supply for customer devices Single-phase socket with RCD protection, 16 A/230 V/50 Hz (Id = 0,03 A)
Auxiliary supply transformer (optional)
Construction Dry
Rated power (voltage) 25 kVA (690/400 V)
Cooling Air
Vector group Dyn11
No load losses / On load losses <200 W / <650 W
Protection for AUX transformer Circuit breaker
Cooling
Cooling type (switch gear cabinet) Forced air by extractor fan
ABB solar inverters | Product flyer for ULTRA-MVC-S
MV trafo 3150kVA
0,69kV / XXkV
MV switchgear (single feeder)LBS
ES1
ES2
ESx
Aux trafoUVWN
3x690V3x400V+N
Inv. Aux 1
AUX QMT
AUX QBT
LV distributionfor AUX functions
Lighting
Fan
2P Spare
VWN
U
2P Socket
Inv. Aux 2Extractor fan
LV distributionfor AUX functions
(UPS section)
Datalogger
AUX QBT-UPS
UPS
Therm. unittrafo
AUX QMT-UPS
///
Aux trafoprotectionfuses
Inv. Aux1 MV
MV
ULTRA-1400.0-TL(1556kW@cosφ=1)
ULTRA-1400.0-TL(1556kW@cosφ=1)
Inv. Aux2
LBS
ES
Electrical diagram of ULTRA-MVC-3110.0-S
Product flyer for ULTRA-MVC-S | ABB solar inverters
Technical data and typesType code ULTRA-MVC-1940.0-S ULTRA-MVC-2330.0-S ULTRA-MVC-2720.0-S ULTRA-MVC-3110.0-S
Inverter 1)ULTRA-700.0-TL
2x ULTRA-1050.0-TLULTRA-1050.0-TL
2x ULTRA-1400.0-TLULTRA-1050.0-TL ULTRA-1400.0-TL
Environmental parametersFull power operating temperature range -25°C...+45°CRelative humidity (non-condensing) ≤ 95%Maximum operating altitude without deranting 5) 1000Communication/user interface and system monitoringCommunication port (PC / Data logger) 1 x RS485Communication to inverter 1 x RS485Remote communication (optional) VSN 700 Data LoggerUPS (optional)UPS for protection and monitoring system 2 kVA, 10’
Lighting Fluorescent lamps T8 2x18W, electronic supplier for emergency lighting with Ni-Cd hermetic battery (1 h autonomy)
Mechanical characteristicsDimensions (W x H x D) 5200 x 2800 x 2300 mmBody material (MV swithc gear cabinet) Metal housing with double metal panel insulated by polyurethanic foamOil collecting tank 110% of oil contentEnvironmental protection rate (MV switch gear cabinet) IP43 (IP54 optional)
Environmental protection rate(trafo protection grid) IP1XA
1) For further details, please refer to the specific inverter data-sheet 4) Other medium voltage levels available on request2) Available as inverter option 5) Contact ABB for application at higher altitudes3) Available as inverter option - 4 quadrant MID certifiedRemark. Features not specifically listed in the present data sheet are not included in the product
Optional ULTRA-MVC-SLV electrical panel with automatic circuit breaker -Energy meters (one for each inverter) -LV distribution panels for auxiliary functions ●Auxiliary transformer ○Single / double feeder switchgear ●/○Monitoring system VSN700 Data Logger ○UPS 2 kVA for monitoring and protection system ○Hot climate package 50°C ○IP54 ambiental protection degree ○IP54 ambiental protection degree + sand trap filter ○
BC
D.0
0556
R
ev.
B
EN
25.
03.2
015
Support and serviceABB supports its customers with dedicated, global service organization in more than 60 countries and strong regional and national technical partner networks providing complete range of life cycle services.
For more information please contact your local ABB representative or visit: www.abb.com/solarinverterswww.abb.com/solarwww.abb.com
© Copyright 2015 ABB. All rights reserved. The appearance of products, including safety agency certifications pictured on labels, my change depending on the data manufactured. Specifications are subject to change without notice.