ABB; Softstarters, Type PSR, PSS, PST/PSTB
Transcript of ABB; Softstarters, Type PSR, PSS, PST/PSTB
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
1/50
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
2/50
New
New
New
New
Torque controlThe latest version o the PST(B) sotstarteroers a new unctionality called Torquecontrol. With this unction enabled thevoltage o the motor is regulated so thatthe torque ollows a predefned torque curve duringstart and stop. Torque control is especially useul inpump applications where a sudden stop can causewater hammering and pressure surges.
Analog outputWith the latest version o the PST(B) sotstarter it
is possible to have analog output signals rom thesotstarter. These signals can then be used as inputto a PLC or an analog meter.
Type PSR SoftstarterThe latest addition to the ABB sotstarter range is thecompact PSR sotstarter. This new sotstarter has acompact, attractive design and is ideal or installationin places where space is limited and where there is ademand or easy installation.
Complete rangeWith the new PSR sotstarter, ABB oers a completerange o sotstarters rom 3 to 1810 A. This completerange consists o the three models PSR, PSS andPST(B).
45 515 1810 Ampe
Functionality
PST/PSTB
PSS
PSR
Advanced
Flexible
Compact
ABB Softstarters the complete range
Softstarters
News
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
3/50
SoftstartTypePSS
Low Voltage Products & Systems
Contents PageGeneral.
The.complete.range.
Softstarters,typePSROverview.6Description.Ordering.(incl.accessories).Technical.data,.UL.ratings.9
Softstarters,typePSSOverview.1Application.and.Description.12Ordering.14Accessories.1Technical.data. 1UL.ratings2
Softstarters,typePSTOverview.2Application.and.Description.24Ordering.26Accessories.3FBP.Field.Bus.Plug.3Technical.data. 3UL.ratings4
Wall.mounting.instruction.42Dimensions. 4Circuit.diagrams.46Certications.and.approvals.4Leader.in.power.and.automation.technologies,Division.Automation.Products,.Low.voltage.products.5
Softstarters
Some.inormation.about.the.catalogue:
Orderingdetails:
When.placing.an.order.please.give.either.the.Type.or.the.Order
code.Please.note.that.or.some.o.the.products.you.need.to.ll.in.
some.additional.code.letters/code.numbers.to.dene.the.complete.
Type/Order.code
Packing:
All.sotstarters.and.most.o.the.accessories.are.delivered.in.an
individual.packing.Some.o.the.accessories.are.packed.together.
in.batches.o.n.pieces.(see.ordering.Packingpieces).For.these.
items,.please.order.the.total.amount.corresponding.to.a.multiple.
o.the.number.in.the.packing.Example:.I.two.in.the.packing,.then.
please.order.minimum.two,.our,.six.etc
Note: Each Type or Order code always corresponds to only one
piece.
The.products.described.in.this.catalogue.are.subject.to.change.(design,..
dimensions,.technical.data,.etc).without.prior.notice
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
4/50
Softs
tarte
rs
Type
PSS
2 Low Voltage Products & Systems
Thesolutiontobothmechanicalandelec-
tricalproblemsAC.motors,.the.workhorse.o.the.industry,.that.are.used.to.
drive.ans,.crushers,.agitators,.pumps,.conveyors.etc,.are..
unnecessarily.causing.unwanted.load.peaks.day.in.and.day.out.
in.production.plants.all.over.the.world.These.violent.starts.cause.
damage.in.several.ways.Among.them.are:
.Electrical.problems.due.to.voltage.and.current.transients
. arising.rom.Direct-on-Line.or.Star-Delta.starts.Such.tran-
. sients.may.overload.the.local.supply.network.and.cause
. unacceptable.voltage.variations.that.interere.with.other
. electrical.equipment.connected.to.the.network
.Mechanical.problems.that.address.the.entire.drive.chain,
. rom.motor.to.driven.equipment,.to.severe.stress
.Operational.problems,.such.as.pressure.surges.in.pipelines,
. damage.to.products.on.conveyor.belts.and.uncomortable
. escalator.rides
The.nancial.consequences.are.considerable:.every.technical.
problem.and.every.breakdown,.costs.money..in.terms.o.repairs.
as.well.as.lost.production.
The.easy.solution.to.all.o.these.problems.is.to.install.an.ABB.
Sotstarter.type.PSR,.PSS.or.PST.With.ABB.Sotstarters,.it.is.
possible.to.start.and.stop.smoothly.while.keeping.mechanical.
and.electrical.stresses.to.a.minimum
Graphs showing the basic differences between direct-on-line start-
ing (DoL), star-delta starting and soft starting in terms of the motor
voltage (V), motor current (I) and motor torque (T).
Graphs showing the basic differences between direct-on-line start-
ing (DoL), star-delta starting and soft starting in terms of the motor
voltage (V), motor current (I) and motor torque (T).
DoL
Softstart
Star/Delta
Motor speed
T
Torque
DoL
Motor speed
T
Motorvoltage
Time
100.%
V
Adjustable
ramp.slope
DoL Star/Delta Softstart
70.%
58.%
30.%
SoftstartersFrom the moment the frst electrical motors appeared,
engineers have been searching a way to avoid electrical and
mechanical problems that occur using Direct-on-Line and
Star-Delta starters. ABB has been producing sotstarters
since the beginning o the 1980s. The valuable experiencegained since the early 80s has been incorporated into the
design o todays product ranges. With the latest series
named PST, ABB has taken a signifcant step urther in sot
starting technology. Matching modern power electronics
with smart circuitry and sotware, the new PST sotstarter
oers superior electronic control o the current and voltage
during motor start-up, in addition to several new design
eatures.
Softstart
I
Star/DeltaDoL
Motorcurrent
Motor speed
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
5/50
SoftstartTypePSS
Low Voltage Products & Systems
ABBsoftstartersThecompleterangeABB oers three dierent ranges o sotstarters to cover
every customer need or solutions or small to medium-
sized motor applications, rom 3 A to 1810 A. The overview
table at the bottom o this page shows the main characteris-
tics o the dierent types. For more specifc technical detailsand ordering data, see the ollowing pages.
CompactRangeTypePSR,covers.motor.currents.rom.3.to.45.A.It.is.the.latest.
addition.to.the.sotstarter.amily.and.has.an.attractive,.compact.
design.Further,.the.system.concept.includes.MMS.and.the.
sotstarters.are.available.or.remote.control.connection.using.the.
FieldBusPlug.as.an.accessory.All.sizes.include.a.Run.signal.relay,.
while.rom.sizes.25.A.the.PSR.Sotstarters.are.also.provided.with.
an.output.signal.or.TOR.(Top.O.Ramp),.ie.ull.voltage).With.
standard.perormance.the.PSR.Sotstarters.handle.ten.starts.per.
hour.When.an.auxiliary.cooling.an.is.added,.the.starting.capacity.
is.increased.to.20.starts.per.hour
.Current.ratings.39..45.A.(15.-.22.kW),.at.400.V.Motor.voltage.208..600.V
.Supply.voltage.24.V.DC.or.100-240.V.AC
.Easy.to.install.and.adjust
.DIN.rail.or.screw.mounting
.Integrated.by-pass.contacts
With.their.compact.design,.the.PSR.Sotstarters.are.ideal.or.
installation.in.places.where.space.is.limited.and.where.there.is.a.
demand.or.easy.installation
FlexibleRangeTypePSS,.covers.motor.currents.rom.18.to.300.A.and.oers.a.
fexible.solution.with.easy.installation.and.setup
.Flexible:.With.two.connection.possibilities,.either.in.line.with
. the.motor.or.inside.the.motor.delta.It.can.also.be.equipped
. with.current.limit
.Easy to set up: With.just.three.clearly.labeled.rotary
. switches.on.the.ront.o.the.unit.it.is.possible.to.adjust.the.. .
PSS.Sotstarter.or.a.wide.range.o.applications
.Solid state electrical circuit:.This.ensures.the.highest
. reliability.and.reduces.maintenance.to.a.minimum,
. even.in.applications.with.requent.starts.and.stops
AdvancedRangeTypePST(B),.covers.motor.currents.rom.30.to.1050.A.and.
provides.advanced.unctionality,.including.integrated.protections,.
programmable.signal.relays,.a.fexible.communication
system.and.an.LCD.display.Sizes.PSTB370.to.1050.A.includ
by-pass.contactor
.Advanced integrated protections :.For.the.motor;.inte-.
grated.electronic.overload.relay,.phase.monitoring.relays,..
high.current.and.PTC.protection.For.the.Sotstarter;.ad-.vanced.thyristor.protection
.Flexible bus communication system:.By.using.the.ABB
. FieldBusPlug.(FBP),.you.can.decide.at.any.time.which.bus
. system.to.select.within.the.ABB.FBP.range.The.interace
. between.the.PST.Sotstarter.and.the.ABB.FBP.is.always.th
. same,.independent.o.size.and.delivery.date
.LCD display:.With.13.languages,.a.menu.system
. similar.to.your.mobile.phone,.preprogrammed.application
. settings.and.automatic.status.and.event.logging,.it.couldn
. be.easier.to.set.up.and.operate!
.Programmable signal relays:.gives.you.several.possi-
. bilities.or.signalling.warnings,.aults.and.other.events.
.Torque control:.allows.you.to.start.and.stop.motors.with
. a.more.linear.acceleration.than.when.using.voltage.ramp
O. . . Field.bus.communication.enabled
. . . Real.time.clock
. . . Programmable.ault.supervision.unctions
. . . Programmable.warning.unctions
. . . PTC.input.or.motor.protection
. . . High.current.protection
. . . Phase.imbalance./phase.reversal.protection
. . . Locked.rotor.protection
. . . Thyristor.overtemperature.protection
. . . Motor.overload.protection
. . . Four.button.keypad.(external.keypad.available)
. . O. External.keypad
. O. . Current.limit.control
. . . In.Line.and.Inside.Delta.connection
. . . LED.indications
. . .1). Built-in.by-pass.contactor..(1).On.PSTB)
. . . Ramp.Start/Stop
. . . Torque.control
. . . Analog.output
PSR3...45
PSS18/30...300/515
PST30...PSTB1050B
StandardO. Optional
. Not.availab
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
6/50
Softs
tarte
rs
Type
PSS
Low Voltage Products & Systems
The.line.contactor.is.not.required.or.the.sotstarter.itsel.but.oten.used.to.open.i.OL.trips
The.overload.relay.is.always.required.to.protect.the.motor
Softstarter,Type
Normalstart: PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30
InLineconnected 400V
kW 1.5 3 4 5.5 7.5 11 15
A 3.9 6.8 9 12 16 25 30
InLineconnected 480V
hp 2 3 5 7.5 10 15 20 A 3.4 6.1 9 11 15.2 24.2 28
400V,40C
Manualmotorstarter, Type
MS116. MS116. MS116. MS116. MS116. MS325. MS450
Fuseprotection400V,65kA,40C, gGFuse
. . 10.A. 16.A. 25.A. 32.A. 32.A. 50.A. 63.A
Switchfuse,Type
OS32D. OS32D. OS32D. OS32D. OS32D. OS32D. OS32D
Linecontactor,Type
A9. A9. A9. A12. A16. A26. A30
Thermaloverloadrelay,Type
TA25DU. TA25DU. TA25DU. TA25DU. TA25DU. TA25DU. TA25DU
By-passcontacs
. . Built-in. Built-in. Built-in. Built-in. Built-in. Built-in. Built-in
I.using.manual.motor.starterstype.1.coordination.will.be.achieved
Using.gG.uses.type.1.coordination.will.be.achieved
Suitable.switch.use.or.the.above.gG.uses
SoftstartersType.PSROverview.
PSR3...PSR16 PSR25...PSR30
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
7/50
SoftstartTypePSS
Low Voltage Products & Systems
DescriptionPSR-Compactrange,.covers.motor.currents.rom.3.to.45.A.It.is.
latest.addition.to.the.sotstarter.amily.and.has.an.attractive,.compac
design.Further,.the.system.concept.includes.MMS.and.the.sotstart
are.available.or.remote.control.connection.using.the.FieldBusPlug.a
accessory.All.sizes.include.a.Run.signal.relay,.while.rom.sizes
25.A.the.PSR.Sotstarters.are.also.provided.with.an.output.signal.o
TOR.(Top.O.Ramp),.ie.ull.voltage.With.standard.perormance.the
Sotstarters.handle.ten.starts.per.hour.When.an.auxiliary.cooling.an
added,.the.starting.capacity.is.increased.to.20.starts.per.hour
.Current.ratings.39..45.A.(15.-.22.kW),.at.400.V
.Motor.voltage.208..600.V
.Supply.voltage.24.V.DC.or.100-240.V.AC
.Easy.to.install.and.adjust
.DIN.rail.or.screw.mounting
.Integrated.by-pass.contacts
With.their.compact.design,.the.PSR.Sotstarters.are.ideal.or.installa
in.places.where.space.is.limited.and.where.there.is.a.demand.or.ea
installation
Settings
SoftstartersType.PSROverview.and.description
3
2
1
3
21
Start Stop
Uini
U
time
Ramp.time.START.=.1..10.sec
Ramp.time.STOP.=.0..20.sec
Initial.voltage.Uini.=40..70.%.
(also.set.end.voltage)
3
2
1
PSR37...PSR45
Softstarter,Type
PSR37 PSR45
18.5 22
37 45
25 3034 46.2
400V,40C
Manualmotorstarter, Type
MS450. MS450
Fuseprotection400V,65kA,40C, gGFuse100.A. 125.A
Switchfuse,Type
OS63D. OS125D
Linecontactor,Type
A40. A50
Thermaloverloadrelay,Type
TA42DU. TA75DU
By-passcontacts
Built-in. Built-in
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
8/50
Softs
tarte
rs
Type
PSS
Low Voltage Products & Systems
SoftstartersType.PSR3..PSR45Ordering.details
. PSR16-MS116
. PSR-FAN
. PSR45-MS450
. FieldBusPlug
PSR37..PSR45
PSR-FBPA
. PSR16-MS116
. PSR-FAN
. PSR45-MS450
. FieldBusPlug
Motorpower IEC
230V 400V 500V Maxratedmotor Weight
Pe P
e P
e current,I
e kg
kW kW kW A. Type Ordercode. 1.piece
208600VAC
Supplyvoltage,Us100-240VAC
.075. 15. 22. 39. PSR3-600-70 1SFA896103R7000. 045
.15. 3. 4. 68. PSR6-600-70 1SFA896104R7000. 045
.22. 4. 4. . 9. PSR9-600-70 1SFA896105R7000. 045
. 3. 55. 55. 12. PSR12-600-70 1SFA896106R7000. 045
. 4. 75. 75. 16. PSR16-600-70 1SFA896107R7000. 045
. 55. 11. 15. 25. PSR25-600-70 1SFA896108R7000. 065
. 75. 15. 185. 30. PSR30-600-70 1SFA896109R7000. 065
. 75. 185. 22. 37. PSR37-600-70 1SFA896110R7000. 100
.11. 22. 30. 45 PSR45-600-70 1SFA896111R7000. 100
Supplyvoltage,Us24VDC
.075. 15. 22. 39. PSR3-600-81 1SFA896103R8100. 045
.15. 3. 4. 68. PSR6-600-81 1SFA896104R8100. 045.22. 4. 4. 9. PSR9-600-81 1SFA896105R8100. 045
. 3. 55. 55. 12. PSR12-600-81 1SFA896106R8100. 045
. 4. 75. 75. 16. PSR16-600-81 1SFA896107R8100. 045
. 55. 11. 15. 25. PSR25-600-81 1SFA896108R8100. 065
. 75. 15. 185. 30. PSR30-600-81 1SFA896109R8100. 065
. 75. 185. 22. 37. PSR37-600-81 1SFA896110R8100. 100
.11. 22. 30. 45 PSR45-600-81 1SFA896111R8100. 100
. . . . . . WeightDescription Type Ordercode kg
1.piece
FieldbusPlugConnectionAccessory
The.same.accessory.or.all.sizes. . PSR-FBPA. 1SFA896312R1001 . 006
ConnectionkitforPSR3-16andMS116. PSR16-MS116. 1SFA896211R1001 . 003
ConnectionkitforPSR37-45andMS450. PSR45-MS450. 1SFA896213R1001 . 003
Fan
All.sizes.can.be.equipped.with.auxiliarycooling.an.or.increased.starting.capacity. PSR-FAN 1SFA896311R1001 . 001
Suitable.or.all.sizes
ABBFieldBusPlug
Suitable.or.all.sizes
Accessories
PSR25..PSR30
PSR3..PSR16
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
9/50
SoftstartTypePSS
Low Voltage Products & Systems
SoftstartersType.PSR3..PSR45Technical.data
Ratedinsulationvoltage ,.Ui. 600.V
Ratedoperationalvoltage,Ue. 208600.V
Ratedsupplyvoltage ,.Us. 100240.V.AC.or.24.V.DC
Powerconsumption, . PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30 PSR37 PSR45
. at.100-240.V.AC. 12.VA. 12.VA. 12.VA. 12.VA. 12.VA. 12.VA. 12.VA. 10.VA. 10.VA. .
. at.24.V.DC. 5.W. 5.W. 5.W. 5.W. 5.W. 5.W. 5.W. 5.W. 5.W.
Ratedoperationalcurrent ,Ir. PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30 PSR37 PSR45
. . 39.A. 68.A. 9.A. 12.A. 16.A. 25.A. 30.A. 37.A. 45.A
StartingcapacityatIr. 4.x.I
r.or.6.sec
Numberofstartsperhour,. standard. 10.(4.x.Ie.during.6.s)
. with.aux.an. 20.(4.x.Ie.during.6.s)
Servicefactor. . 100.%
Ambienttemperature . during.operation.1). -25.C.to.+60.C
. during.storage. -40.C.to.+70.C
Maximumaltitude 2). 4000.m
Degreeofprotection ,. . PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30 PSR37 PSR45. .
. main.circuit. IP20. IP20. IP20. IP20. IP20. IP20. IP20. IP10. IP10.. control.circuit. IP20. IP20. IP20. IP20. IP20. IP20. IP20. IP20. IP20.
Connectablecablearea ,. . PSR3-PSR16. . . . P SR2 5 -P SR 30 PS R37 - P SR 45
. main.circuit. 1.x.075.-.25.mm2. . . . 1.x.25.-.10.mm2. 1.x.6.-.35.mm 2
. . 2.x.075.-.25.mm2. . . . 2.x.25.-.10.mm2. 2.x.6.-.16.mm 2
. . PSR3-PSR16. . . . PSR25-PSR45
. control.circuit. 1.x.075.-.25.mm2. . . . 1.x.075.-.25.mm2
. . 2.x.075.-.25.mm2. . . . 2.x.075.-.15.mm2
Signalrelays.. PSR3-PSR16. . . . PSR25-PSR45
. or.Run.signal
. . Resistive.load. 240.V,.2.A.. . . . 250.V,.5.A.
. . AC-15.(Contactor). 240.V,.05.A. . . . 250.V,.05.A
. or.Top.o.Ramp.signal
. . Resistive.load. -. . . . . 250.V,.2.A
. . AC-15.(Contactor). -. . . . . 250.V,.05.A
LED. or.On/Ready. Green. or.Run/Top.O.Ramp. Green
Settings
. Ramp.time.during.start. 1-10.sec
. Ramp.time.during.stop. 0-20.sec.
. Initial-.and.End.Voltage. 40-70%. .
1)..Above.40.C.up.to.max.60.C.reduce.the.rated.current.with.08.%.per.C
2)..When.used.at.high.altitudes.above.1000.meters.up.to.4000.meters.you.need.to.derate.the.rated.current.using.the.ollowing.ormula
[%.o.Ie.=..100.-..]
x.=.actual.altitude.or.the.sotstarter
x.-.1000150
ULratings
Softstarter MotorpowerP(hp)andfullloadcurrentFLA(A) Max.fuse
Ue
Ue
Ue
Ue
FLA 208V 240V 480V 600V
Type A hp hp hp hp A,Type
PSR3. 34. 05. 075. 2. 2. 40.A.J-Type
PSR6. 61. 1. 15. 3. 5. 40.A.J-Type
PSR9. 9. 2. 2. 5. 75. 40.A.J-Type
PSR12. 11. 3. 3. 75 10. 40.A.J-Type
PSR16. 152. 3. 5. 10 10. 40.A.J-Type
PSR25. 242. 75. 75. 15. 20. 60.A.J-Type
PSR30. 28. 75. 10. 20 25. 70.A.J-Type
PSR37. 34. 10. 10. 25 30. 100.A.J-Type
PSR45. 462. 15. 15. 30 40. 100.A.J-Type
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
10/50
Softs
tarte
rs
Type
PSS
8 Low Voltage Products & Systems
SoftstartersType.PSSOverview
PSS18/30...PSS44/76 PSS50...PSS72/124
Softstarter,Type
Normalstart: PSS18/30 PSS30/52 PSS37/64 PSS44/76 PSS50/85 PSS60/105 PSS72/124
InLineconnected 400V
kW 7.5 15 18.5 22 25 30 37
RatedcurrentIe, A 18 30 37 44 50 60 72
InLineconnected 480V hp 10 20 25 30 30 40 50
RatedcurrentIe, A 18 28 34 40 47 56 67
400V,40C
MCCB(50kA),Type
T2S160. T2S160. T2S160. T2S160. T2S160. T2S160. T2S160
Fuseprotection(65kA)Bussmann,Type
170M1364. 170M1366. 170M1368. 170M1369. 170M1369. 170M1370. 170M1371
Switchfuse,Type
OS160RD0380. OS160RD0380. OS160RD0380. OS160RD0380. OS160RD0380. OS160RD0380. OS160RD0380
Linecontactor,Type A26. A30. A40. A50. A50. A63. A75
Thermaloverloadrelay,Type
TA25DU. TA25DU. TA42DU. TA75DU. TA75DU. TA75DU. TA75DU
By-passcontactor,Type
. . A9. A16. A26. A26. A30. A40. A50
Currenttransformers,Type
. . PSCT-60. PSCT-40. PSCT-50. PSCT-60. PSCT-75. PSCT-75. PSCT-75
. . 2.turns. 1.turn. 1.turn. 1.turn. 1.turn. 1.turn. 1.turn
I.using.MCCB.only,.type.1.coordination.will.be.achieved
To.achieve.a.type.2.coordination,.semi-condcutor.uses.must.be.used
Suitable.switch.use.or.recommended.semi-conductor.uses
The.line.contactor.is.not.required.or.the.sotstarter.itsel.but.oten.used.to.open.i.OL.trips
The.overload.relay.is.always.required.to.protect.the.motor
Must.be.used.i.current.limit.unction.is.required
The.by-pass.contactor.can.be.used.to.reduce.the.power.loss.o.the.sotstarter.but.also.to.increase.the.number.o.starts/h.All.sotstarters.can.be.operated.without.by-pass
The.table.above.is.an.overview.o.possible.combinations.o.devices
Complete.coordination.tables.are.available.at.www.abb.com/lowvoltage.
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
11/50
SoftstartTypePSS
Low Voltage Products & Systems
SoftstartersType.PSSOverview
PSS85/147...PSS142/245 PSS175/300...PSS300/515
QuickguideforselectionNormalstartClass10 HeavydutystartClass30
Ordering..See.page.14.15. Ordering..See.page.16.17
Typicalapplications Typicalapplications Bow.thruster. Centriugal.pump. .Centriugal.an. .Conveyor.belt.(long)
.Compressor. .Conveyor.belt.(short). .Crusher. .Mill
.Elevator. .Escalator. Mixer. Stirrer
Ifmorethan10starts/hSelectonesize.larger.than.the.standard.selection!
Softstarter,Type
PSS85/147 PSS105/181 PSS142/245 PSS175/300 PSS250/430 PSS300/515
45 55 75 90 132 160
85 105 142 175 250 300
60 75 100 125 150 200
85 105 125 156 225 248
400V,40C
MCCB(50kA),Type
T2S160. T3S250. T3S250. T3S250. T4S320. T5S400
Fuseprotection(65kA)Bussmann,Type
170M1372. 170M3019. 170M3020. 170M3021. 170M5013. 170M5015
Switchfuse,Type
OS160RD0380. OESA250R03D80. OESA250R03D80. OESA250R03D80. OESA400R03D80. OESA400R03D80
Linecontactor,TypeA95. A110. A145. A185. A50. A300
Thermaloverloadrelay,Type
TA110DU. TA110DU. TA200DU. TA200DU. TA450DU. TA450DU
By-passcontactor,Type
A50. A63. A95. A145. A145. A210
Currenttransformers,TypePSCT-125. PSCT-150. PSCT-200. PSCT-250. PSCT-400. PSCT-75
1.turjdn. 1.turn. 1.turn. 1.turn. 1.turn. 1.turn
Howtoselectcorrectsize
By.using.the.guide.beside,.you.can
quickly.select.a.suitable.sotstarter.or.the.
most.common.applications
I.a.more.precise.selection.is.required,.you.
can.use.Prosot,.a.selection.sotware..
available.at.www.abb.com/lowvoltage.
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
12/50
Softs
tarte
rs
Type
PSS
0 Low Voltage Products & Systems
58.A
100.A..
Inside.Delta
100.A
100.A..
In-Line
SoftstartersType.PSS18/30..PSS300/515Application.and.Description
ApplicationThe.sotstarter.range.PSS18/30..PSS300/515.is.a.very.fexible.solution.
suitable.or.most.applications.and.or.replacements.o.Star-Delta.starters.
Since.the.unit.can.be.connected.inside.the.motor.delta.(compare.the.con-
nection.or.standard.Star-Delta.starters),.the.current.through.the.sotstarter.is.reduced.by.42.%.It.will.then.be.possible,.or.example,.to.run.a.100.A.
motor.using.a.58.A.PSS.Sotstarter
In-Line and Inside Delta connection of PSS18/30 PSS300/515
Description. Wide.main.voltage.range.208.-.690.V.AC
. Supply.voltage.range.110-120.V.AC.and.220-240.V.AC
. Current.ratings.18..300.A.(In.Line).and.30..515.A.(Inside.Delta)
. Same.unit.can.be.used.or.both.In.Line.and.Inside.Delta.connection
. Start.ramp,.Stop.ramp.and.Initial.voltage.included
. Current.limit.unction.as.option
. Solid.state.electrical.circuit. Designed.or.continuous.operation.without.by-pass
. 15.%.overcurrent.capability.during.continuous.run.(10.%.or.PSS300/515)
. Accessories.or.connection.and.installation.available:.See.the.ordering
. pages
The.PSS.Sotstarter.can.be.selected.according.to.the.rated.motor.
power.in.normal duty.applications.like.pumps,.compressors,.eleva-
tors,.escalators,.short.conveyor.belts.and.bow.thrusters.
see.page.14-15
For.heavy duty.applications.like.centriugal.ans,.crushers,.mixers,.
mills,.stirrers.and.long.conveyor.belts,.select.a.sotstarter.rom
page.16-17
Built-in.signal.relays
or.ault.and.by-pass
Transparent.lid.to
protect.the.settings
Three.rotating.switches.setting:-Start.ramp.(130.sec)
-Stop.ramp.(030.sec)
-Initial.voltage.(3070.%.o.Ue)
-Current.limit.15.4.x.Ir.
.(I.used:.Initial.voltage.xed.at.40.%.o.Ue)
Dip-switch.or.In.Line/
Inside.Delta.connection
LED.indications:
. Power.supply.on
. Completed.start.ramp
General.ault.(motor.side.or.unit)
. External.ault
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
13/50
SoftstartTypePSS
Low Voltage Products & Systems
2
3
1
3
21
Start Stop
Uini
U
time
2
3
1
SoftstartersType.PSS18/30..PSS300/515
Dierent.sizes.o.PSS,.rom.let.PSS175/300-500L,.PSS85/147-500L,.PSS50/85-500L.and.in.the.ront.PSS18/30-500L.
Settings
PSS18/30..PSS300/515
Ramp.time.START.=.1..30.sec
Ramp.time.STOP.=.0..30.sec
Initial.voltage.Uini.=40..70.%,.when.current.limit.is.
used.xed.at.40.%..(also.set.end.voltage)
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
14/50
Softs
tarte
rs
Type
PSS
2 Low Voltage Products & Systems
PSS18/30-500..44/76-500
PSS50/85-500.72/124-500
PSS18/30-690..72/124-690
PSS85/147-500.142/245-500
PSS85/147-690.142/245-690
PSS175/300-500..300/515-500
PSS175/300-690..300/515-690
ss
SoftstartersType.PSS18/30..PSS300/515Normal.starts,.class.10..In-Line,.Ordering.details
*) AddcodeletterinTypefor: Supplyvoltage,U
s
F=.110-120.V,.50/60.Hz
L=.220-240.V,.50/60.Hz
Faultsignalrelay
no.code.letter.=.
NO. C=.NC
**)AddcodenumberinOrdercodefor: Supplyvoltage,U
s
1=.110-120.V,.50/60.Hz
2=.220-240.V,.50/60.Hz
Faultsignalrelay
1.=.NO 2=.NC
PSS18/30...PSS300/515
230500VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
75. 11. -. 18. PSS18/30-500 1SFA892001R00. 230
15. 185. -. 30. PSS30/52-500 1SFA892002R00. 230
185. 22. -. 37. PSS37/64-500 1SFA892003R00. 230
22. 25. -. 44. PSS44/76-500 1SFA892004R00. 230
25. 30. -. 50. PSS50/85-500 1SFA892005R00. 360
30. 37. -. 60. PSS60/105-500 1SFA892006R00. 380
37. 45. -. 72. PSS72/124-500 1SFA892007R00. 380
45. 55. -. 85. PSS85/147-500 1SFA892008R00. 860
55. 75. -. 105. PSS105/181-500 1SFA892009R00. 1040
75. 90. -. 142. PSS142/245-500 1SFA892010R00. 1040
90. 110. -. 175. PSS175/300-500 1SFA892011R00. 2050
132. 160. -. 250. PSS250/430-500 1SFA892013R00. 2200160. 200. -. 300. PSS300/515-500 1SFA892014R00. 2200
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
75. 11. 15. 18. PSS18/30-690 1SFA893001R00. 230
15. 185. 25. 30. PSS30/52-690 1SFA893002R00. 230
185. 22. 30. 37. PSS37/64-690 1SFA893003R00. 230
22. 25. 37. 44. PSS44/76-690 1SFA893004R00. 230
25. 30. 45. 50. PSS50/85-690 1SFA893005R00. 360
30. 37. 55. 60. PSS60/105-690 1SFA893006R00. 380
37. 45. 59. 72. PSS72/124-690 1SFA893007R00. 380
45. 55. 75. 85. PSS85/147-690 1SFA893008R00. 860
55. 75. 90. 105. PSS105/181-690 1SFA893009R00. 1040
75. 90. 132. 142. PSS142/245-690 1SFA893010R00. 1040
90. 110. 160. 175. PSS175/300-690 1SFA893011R00. 2050
132. 160. 220. 250. PSS250/430-690 1SFA893013R00. 2200
160. 200. 257. 300. PSS300/515-690 1SFA893014R00. 2200
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
15/50
SoftstartTypePSS
Low Voltage Products & Systems
ss
PSS18/30-500..44/76-500
PSS50/85-500.72/124-500
PSS18/30-690..72/124-690
PSS85/147-500.142/245-500
PSS85/147-690.142/245-690
PSS175/300-500..300/515-500
PSS175/300-690..300/515-690
*) AddcodeletterinTypefor: Supplyvoltage,U
s
F=.110-120.V,.50/60.Hz
L=.220-240.V,.50/60.Hz
Faultsignalrelay
no.code.letter.=.
NO. C=.NC
**)AddcodenumberinOrdercodefor: Supplyvoltage,U
s
1=.110-120.V,.50/60.Hz
2=.220-240.V,.50/60.Hz
Faultsignalrelay
1.=.NO 2=.NC
SoftstartersType.PSS18/30..PSS300/515
Normal.starts,.class.10..Inside.Delta,.Ordering.details
PSS18/30...PSS300/515
230500VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
15. 185. -. 30. PSS18/30-500 1SFA892001R00. 230
25. 30. -. 52. PSS30/52-500 1SFA892002R00. 230
30. 37. -. 64. PSS37/64-500 1SFA892003R00. 230
37. 45. -. 76. PSS44/76-500 1SFA892004R00. 230
45. 55. -. 85. PSS50/85-500 1SFA892005R00. 360
55. 75. -. 105. PSS60/105-500 1SFA892006R00. 380
59. 80. -. 124. PSS72/124-500 1SFA892007R00. 380
75. 90. -. 147. PSS85/147-500 1SFA892008R00. 860
90. 110. -. 181. PSS105/181-500 1SFA892009R00. 1040
132. 160. -. 245. PSS142/245-500 1SFA892010R00. 1040
160. 200. -. 300. PSS175/300-500 1SFA892011R00. 2050
220. 295. -. 430. PSS250/430-500 1SFA892013R00. 2200257. 355. -. 515. PSS300/515-500 1SFA892014R00. 2200
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
15. 185. 25. 30. PSS18/30-690 1SFA893001R00. 230
25. 30. 45. 52. PSS30/52-690 1SFA893002R00. 230
30. 37. 55. 64. PSS37/64-690 1SFA893003R00. 230
37. 45. 59. 76. PSS44/76-690 1SFA893004R00. 230
45. 55. 75. 85. PSS50/85-690 1SFA893005R00. 360
55. 75. 90. 105. PSS60/105-690 1SFA893006R00. 380
59. 80. 110. 124. PSS72/124-690 1SFA893007R00. 380
75. 90. 132. 147. PSS85/147-690 1SFA893008R00. 860
90. 110. 160. 181. PSS105/181-690 1SFA893009R00. 1040
132. 160. 220. 245. PSS142/245-690 1SFA893010R00. 1040
160. 200. 257. 300. PSS175/300-690 1SFA893011R00. 2050
220. 295. 400. 430. PSS250/430-690 1SFA893013R00. 2200
257. 355. 500. 515. PSS300/515-690 1SFA893014R00. 2200
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
16/50
Softs
tarte
rs
Type
PSS
Low Voltage Products & Systems
Heavy duty
PSS30/52-500..44/76-500
PSS50/85-500.72/124-500
PSS18/30-690..72/124-690
PSS85/147-500.142/245-500
PSS85/147-690.142/245-690
PSS175/300-500..300/515-500
PSS175/300-690..300/515-690
ss
SoftstartersType.PSS30/52..PSS300/515Heavy.duty.starts,.class.30..In-Line,.Ordering.details
PSS30/52...PSS300/515
230500VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
75. 11. -. 18. PSS30/52-500 1SFA892002R00. 230
15. 185. -. 30. PSS37/64-500 1SFA892003R00. 230
185. 22. -. 37. PSS44/76-500 1SFA892004R00. 230
22. 25. -. 44. PSS50/85-500 1SFA892005R00. 360
25. 30. -. 50. PSS60/105-500 1SFA892006R00. 380
30. 37. -. 60. PSS72/124-500 1SFA892007R00. 380
37. 45. -. 72. PSS85/147-500 1SFA892008R00. 860
45. 55. -. 85. PSS105/181-500 1SFA892009R00. 1040
55. 75. -. 105. PSS142/245-500 1SFA892010R00. 1040
75. 90. -. 142. PSS175/300-500 1SFA892011R00. 2050
90. 110. -. 175. PSS250/430-500 1SFA892013R00. 2200
132. 160. -. 250. PSS300/515-500 1SFA892014R00. 2200
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
75. 11. 15. 18. PSS30/52-690 1SFA893002R00. 230
15. 185. 25. 30. PSS37/64-690 1SFA893003R00. 230
185. 22. 30. 37. PSS44/76-690 1SFA893004R00. 230
22. 25. 37. 44. PSS50/85-690 1SFA893005R00. 360
25. 30. 45. 50. PSS60/105-690 1SFA893006R00. 380
30. 37. 55. 60. PSS72/124-690 1SFA893007R00. 380
37. 45. 59. 72. PSS85/147-690 1SFA893008R00. 860
45. 55. 75. 85. PSS105/181-690 1SFA893009R00. 1040
55. 75. 90. 105. PSS142/245-690 1SFA893010R00. 1040
75. 90. 132. 142. PSS175/300-690 1SFA893011R00. 2050
90. 110. 160. 175. PSS250/430-690 1SFA893013R00. 2200
132. 160. 220. 250. PSS300/515-690 1SFA893014R00. 2200
*) AddcodeletterinTypefor: Supplyvoltage,U
s
F=.110-120.V,.50/60.Hz
L=.220-240.V,.50/60.Hz
Faultsignalrelay
no.code.letter.=.NO
. C=.NC
**)AddcodenumberinOrdercodefor: Supplyvoltage,U
s
1=.110-120.V,.50/60.Hz
2=.220-240.V,.50/60.Hz
Faultsignalrelay
1.=.NO
2=.NC
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
17/50
SoftstartTypePSS
Low Voltage Products & Systems
Heavy duty
PSS30/52-500..44/76-500
PSS50/85-500.72/124-500
PSS18/30-690..72/124-690
PSS85/147-500.142/245-500
PSS85/147-690.142/245-690
PSS175/300-500..300/515-500
PSS175/300-690..300/515-690
*) AddcodeletterinTypefor: Supplyvoltage,U
s
F=.110-120.V,.50/60.Hz
L=.220-240.V,.50/60.Hz
Faultsignalrelay
no.code.letter.=.NO
. C=.NC
**)AddcodenumberinOrdercodefor: Supplyvoltage,U
s
1=.110-120.V,.50/60.Hz
2=.220-240.V,.50/60.Hz
Faultsignalrelay
1.=.NO
2=.NC
ss
SoftstartersType.PSS30/52..PSS300/515Heavy.duty.starts,.class.30..Inside.Delta,.Ordering.details
PSS30/52...PSS300/515
230500VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
15. 185. -. 30. PSS30/52-500 1SFA892002R00. 230
25. 30. -. 52. PSS37/64-500 1SFA892003R00. 230
30. 37. -. 64. PSS44/76-500 1SFA892004R00. 230
37. 45. -. 76. PSS50/85-500 1SFA892005R00. 360
45. 55. -. 85. PSS60/105-500 1SFA892006R00. 380
55. 75. -. 105. PSS72/124-500 1SFA892007R00. 380
59. 80. -. 124. PSS85/147-500 1SFA892008R00. 860
75. 90. -. 147. PSS105/181-500 1SFA892009R00. 1040
90. 110. -. 181. PSS142/245-500 1SFA892010R00. 1040
132. 160. -. 245. PSS175/300-500 1SFA892011R00. 2050
160. 200. -. 300. PSS250/430-500 1SFA892013R00. 2200
220. 295. -. 430. PSS300/515-500 1SFA892014R00. 2200
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A. Type*) Ordercode**). kg
15. 185. 25. 30. PSS30/52-690 1SFA893002R00. 230
25. 30. 45. 52. PSS37/64-690 1SFA893003R00. 230
30. 37. 55. 64. PSS44/76-690 1SFA893004R00. 230
37. 45. 59. 76. PSS50/85-690 1SFA893005R00. 360
45. 55. 75. 85. PSS60/105-690 1SFA893006R00. 380
55. 75. 90. 105. PSS72/124-690 1SFA893007R00. 380
59. 80. 110. 124. PSS85/147-690
1SFA893008R
00. 860
75. 90. 132. 147. PSS105/181-690 1SFA893009R00. 1040
90. 110. 160. 181. PSS142/245-690 1SFA893010R00. 1040
132. 160. 220. 245. PSS175/300-690 1SFA893011R00. 2050
160. 200. 257. 300. PSS250/430-690 1SFA893013R00. 2200
220. 295. 400. 430. PSS300/515-690 1SFA893014R00. 2200
Heavy duty
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
18/50
Softs
tarte
rs
Type
PSS
Low Voltage Products & Systems
. LZ
. PSCT
LW
LE185
. LT..-AC.. LT..-AL
PSLW-44
SoftstartersAccessories.or.type.PSS18/30..PSS300/515
Ordering.details
.Currenttransformerforcurrentlimitfunction
To.be.connected.to.terminals.11.and.12.on.the.sotstarter
The.setting.range.(15..4).corresponds.to.a.multiple.o.the.transormer.ratio.
Technical.data.below.shows.transormer.ratio.and.number.o.turns.or.the.primary.winding
You.can.also.use.your.own.current.transormer.with.corresponding.transormer.ratio.and.with.minimum.1.VA Weight
Forsoftstarter Transformerratio, Packing kg
type Numberofturns Type Ordercode piece 1.piece
PSS18/30. 60/1..2.turns. PSCT-60 1SFA899001R1060 1. 030
PSS30/52. 40/1..1.turn. PSCT-40 1SFA899001R1040 1. 030
PSS37/64. 50/1..1.turn. PSCT-50 1SFA899001R1050 1. 030
PSS44/76. 60/1..1.turn PSCT-60 1SFA899001R1060 1. 030
PSS50/85. 75/1..1.turn. PSCT-75 1SFA899001R1075 1. 030
PSS60/105. 75/1..1.turn PSCT-75 1SFA899001R1075 1. 030
PSS72/124. 100/1..1.turn PSCT-100 1SFA899001R1100 1. 025
PSS85/147. 125/1..1.turn. PSC T-125 1SFA899001R1125 1. 025
PSS105/181. 150/1..1.turn. PSCT-150 1SFA899001R1150 1. 025
PSS142/245. 200/1..1.turn. PSC T-200 1SFA899001R1200 1. 025
PSS175/300. 250/1..1.turn. PSCT-250 1SFA899001R1250 1. 025
PSS250/430. 400/1..1.turn. PSCT-400 1SFA899001R1400 1. 025
PSS300/515. 400/1..1.turn. PSCT-400 1SFA899001R1400 1. 025
CableconnectorsforCucablesFor Wire Tightening Weight
softstarter range torque Packing kg
type mm2 max.Nm Type Ordercode piece 1.piece
PSS85/147142/245. 6-185. 16 1SDA023354R0001 3. 020
PSS85/147142/245. 2x(50-120).16. LZ185-2C/120 1SFN074709R1000 3. 030
PSS175/300300/515.16-240. 25 1SDA023368R0001 3. 040
CableconnectorsforAlandCucablesFor Wire Tightening Weight
softstarter range torque Packing kg
type mm2 max.Nm Type Ordercode piece 1.piece
PSS85/147142/245. 35-95. 135 1SDA023356R0001 3. 010
PSS85/147142/245. 25-150. 31. 1SDA023357R0001 3. 010
PSS175/300300/515.120-240. 43 1SDA023370R0001 3. 010
TerminalenlargementsFor Wire Weight
softstarter range Packing kg
type mm2 Type Ordercode piece 1.piece
PSS18/30-500.44/76-500. 1x635.
2x616. PSLW-44 1SFA899002R1044 1. 010
PSS50/85-50072/124-500
PSS18/30-690..72/124-690.1x1050.
. 2x1025. PSLW-72 1SFA899002R1072 1. 015
PSS85/147142/245.. . . LW185 1SFN074707R1000 1. 025
PSS175/300300/515. . . LW300 1SFN075107R1000 1. 040
TerminalnutwasherFor Weight
softstarter Packing kg
type Type Ordercode piece 1.piece
PSS85/147142/245.. . LE185 1SFN074716R1000 2. 020
PSS175/300300/515. LE300 1SFN075116R1000 2. 030
TerminalshroudsFor Weight
softstarter Packing kg
type Suitablefor Type Ordercode piece 1.piece
PSS85/147142/245. Cable.connectors LT185-AC 1SFN124701R1000 2. 010
PSS85/147142/245. Compression.lugs LT185-AL 1SFN124703R1000 2. 010
PSS175/300300/515. Cable.connectors LT300-AC 1SFN125101R1000 2. 020
PSS175/300300/515. Compression.lugs LT300-AL 1SFN125103R1000 2. 020
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
19/50
SoftstartTypePSS
Low Voltage Products & Systems
SoftstartersType.PSS18/30..PSS300/515Technical.data
PSS18/30...PSS300/515Ratedinsulationvoltage,U
i. . . 690.V
Ratedoperationalvoltage,Ue. . . 208..690.V
Startingcapacity. . . . . . . .. at.max.rated.current,.I
e. .
.4.x.I
e.or.10.sec...
Numberofstartsperhour. . . 30.3)
Overloadcapability.
. Overload.class. . . 10.
Servicefactor. . . PSS18/30...250/430 PSS300/515
. . . 115.%.. . . . 110.%
Ambienttemperature.
. During.operation. . . -25.to.+60.C.1). .
. During.storage. . . -40.to.+70.C
Maximumaltitud.4). . . 4000.m
Degreeofprotection PSS18/30-500...44/76-500 PSS50/85-500...72/124-500
. Main.circuit. . . IP.20.. . IP.10.
. . . PSS18/30-690...72/124-690 PSS85/147-690...300/515-690.
. . . IP.10. . . IP.00.
. . . PSS18/30PSS300/515
. Supply.and.control.circuit. . . IP.20.
Settings.
. Ramp.time.during.start. . . 1..30.sec. .
. Ramp.time.during.stop. . . 0..30.sec. .
. Initial.voltage.during.start. . . 30..70.%.
. Current.limit.unction. x.CT-ratio. . 15..4.2)
Switchfor.
. Inside.Delta.connection..ON/OFF. . Yes
Signalrelays.
. By-pass.signal. . . Yes. .
. Fault.signal. . . Yes.(NO.or.NC). .
. Rated.operational.voltage,.Ue. . . 250V. . .
. Rated.thermal.current,.Ith. . . 5A. .
. Rated.operational.current,.Ie. .. . .
. at.AC-15.(Ue=250.V). . . 15A.
SignalindicationLED.
. Ready.to.start/stand.by. ON. . Green.
. Ramping.up/down. . . . .
. Completed.start.ramp.. TOR. . Green.
. General.ault.. . . Red.
. External.ault. . . Red
1).. Above.40.C,.up.to.max.60.C,.reduce.the.rated.current..with.08.%.per.C2). Only.i.current.transormer.is.connected.(accessory)3). Valid.or.50.%.on.time.and.50.%.o.time.35.x.I
e.or.7.sec,.i.other.data.is.required,.contact.your.sales.oce
4). When.used.at.high.altitudes.above.1000.meters.up.to.4000.meters.you.need.to.derate.rated.current.using
. the.ollowing.ormula
.. . . x.-..1000[.%.o.I
e.=..100.-..]
. . . . 150
x.=.actual.altitude.or.the.sotstarter
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
20/50
Softs
tarte
rs
Type
PSS
8 Low Voltage Products & Systems
E1858D
17.5
8.5
5
E1859D
20
10.2
5
Crosssectionofconnectioncables
Typeofsoftstarter
PSS18/30-500 PSS50/85-500 PSS85/147-500 PSS175/300
44/76-500 72/124-500, 142/245-500, 300/515-500, 18/30-690 85/147-690 175/300
72/124-690 142/245-690 300/515-690
Maincircuit.
Connection.clamp
.
. Solid/Stranded. 1.x.mm2. 25..16. 6..50. See.accessories. See.accessories.
. Solid/Stranded. 2.x.mm2. 25..16. 6..25. See.accessories. See.accessories
. Tightening.torque.(recommended). .Nm. 26. 45. See.accessories. See.accessories
Connection.bar
. Width.and.thickness. mm. . . .
. Hole.diameter. mm. . . .
. Tightening.torque.(recommended). .Nm. . . 9. 18
Supplyandcontrolcircuit.
Connection.clamp.
. Solid/Stranded. 1.x.mm2. 25. 25. 25. 25.
. Solid/Stranded. 2.x.mm2. . . .
. Tightening.torque.(recommended). .Nm. 05. 05. 05. 05
SoftstartersType.PSS18/30..PSS300/515Technical.data
Fuseratingsandpowerlosses
Recommended Max2)
ABBOverloadprotection power Powerre-
For Current lossat Maxfuserating-maincircuit1) quirements
Softstarter range rated/e Bussmanfuses Ferrazfusescircuit ofsupply
Type Type A W A Type Holder A Type VA
PSS18/30. TA25DU. 618. 65. 50. 170M1364. 170H1007. 63. 66.URB.000.D08.V.0063. 9.
PSS30/52. TA25DU. 1030. 100. 80. 170M1366. 170H1007. 100. 66.URB.000.D08.V.0100. 9.
PSS37/64. TA42DU. 2237. 120. 125. 170M1368. 170H1007. 160. 66.URB.000.D08.V.0160. 9.
PSS44/76. TA75DU. 2944. 142. 160. 170M1369. 170H1007. 200. 66.URD.30.D08.A.0200. 9.
PSS50/85. TA75DU. 2950. 160. 160. 170M1369. 170H1007. 200. 66.URD.30.D08.A.0200. 10.
PSS60/105. TA75DU. 2960. 190. 200. 170M1370. 170H1007. 250. 66.URD.30.D08.A.0250. 10.
PSS72/124. TA75DU. 4572. 226. 250. 170M1371. 170H1007. 315.. 66.URD.30.D08.A.0315. 10.
PSS85/147. TA110DU. 6585. 291. 315. 170M1372.. 170H1007. 400. 66.URD.30.D08.A.0400. 36.
PSS105/181. TA110DU. 65105. 351. 400. 170M3019.. 170H3004. 400. 66.URD.30.D08.A.0400. 36.
PSS142/245. TA200DU. 100142. 462. 450. 170M3020.. 170H3004. 500. 66.URD.30.D08.A.0500. 36.
PSS175/300. TA200DU. 100175. 590. 500. 170M3021. 170H3004. 530. 66.URD.30.D08.A.0550. 65. .
PSS250/430. TA450DU. 130250. 815. 700. 170M5013. 170H3004. 630. 66.URD.31.D08.A.0630. 65. .
PSS300/515. TA450DU. 130300. 965. 900. 170M5015. 170H3004. 900. 66.URD.32.D11.A.0900. 65
1).For.the.supply.circuit.6.A.delayed,.or.MCB.use.C.characteristics.2).Calculated.power.loss.at.operational.current.(Iop).without.by-pass.
Ptot.=.3.x.Iop.+.VA.value.
Example: PSS 60/105 running at 52A
Ptot = 3 x 52 + 10 = 166W
When.using.bypass,.the.powerloss.is.reduced.to.the.VA.value.only
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
21/50
SoftstartTypePSS
Low Voltage Products & Systems
SoftstartersType.PSS18/30..PSS300/515UL.ratings
3-phasemotorrating-InLine
Softstarters MotorpowerP(hp)andnominalcurrentIeA
Ue
Ue
Ue
Ue
200V/208V 220V/240V 440V/480V 550V/600VType hp A hp A hp A hp A
PSS18/30 5. 18. 5. 18. 10. 18. 15. 18PSS30/52 75. 28. 10. 28. 20. 28. 25. 28PSS37/64 10. 34. 10. 34. 25. 34. 30. 34PSS44/76 10. 40. 10. 40. 30. 40. 30. 40PSS50/85 15. 47. 15. 47. 30. 47. 40. 47PSS60/105 15. 56. 20. 56. 40. 56. 50. 56PSS72/124 20. 67. 20. 67. 50. 67. 60. 67PSS85/147 25. 85. 30. 85. 60. 85. 75. 85PSS105/181 30. 105. 40. 105. 75. 105. 100. 105PSS142/245 40. 125. 40. 125. 100. 125. 125. 125PSS175/300 50. 156. 60. 156. 125. 156. 150. 156PSS250/430 75. 225. 75. 225. 150. 225. 200. 225PSS300/515 75. 248. 100. 248. 200. 248. 250. 248
. 3-phasemotorrating-InsideDelta
Softstarters MotorpowerP(hp)andnominalcurrentIeA
Ue
Ue
Ue
Ue
200V/208V 220V/240V 440V/480V 550V/600V
Type hp A hp A hp A hp A
PSS18/30. 75. 30. 10. 30. 20. 30. 25. 30
PSS30/52. 15. 48. 15. 48. 30. 48. 40. 48PSS37/64. 20. 58. 20. 58. 40. 58. 50. 58
PSS44/76. 20. 69. 25. 69. 50. 69. 60. 69
PSS50/85. 25. 81. 30. 81. 60. 81. 75. 81
PSS60/105. 30. 96. 30. 96. 75. 96. 75. 96
PSS72/124. 40. 116. 40. 116. 75. 116. 100. 116
PSS85/147. 50. 147. 50. 147. 100. 147. 150. 147
PSS105/181. 60. 181. 60. 181. 150. 181. 150. 181
PSS142/245. 75. 215. 75. 215. 150. 215. 200. 215
PSS175/300. 75. 270. 100. 270. 200. 270. 250. 270
PSS250/430. 125. 389. 150. 389. 300. 389. 400. 389
PSS300/515. 150. 429. 150. 429. 350. 429. 400. 429
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
22/50
Softs
tarte
rs
Type
PST
20 Low Voltage Products & Systems
Softstarter,Type
Normalstart: PST30 PST37 PST44 PST50 PST60 PST72 PST85 PST105 PST142
InLineconnected(400V)
kW 15 18.5 22 25 30 37 45 55 75RatedcurrentIe, A 30 37 44 50 60 72 85 105 142
InLineconnected(480V)
hp 20 25 30 40 40 50 60 75 100
RatedcurrentIe, A 28 34 42 54 60 68 80 104 130
400V,40C
MCCB(50kA),Type
T2S160 T2S160 T2S160 T2S160 T2S160 T2S160 T2S160 T3S250 T3S250
Fuseprotection(65kA)Bussmann,Type
170M1366 170M1368 170M1369 170M1369 170M1370 170M1371 170M1372 170M1319 170M1320
Switchfuse,Type
OS160RD0380 OS160RD0380 OS160RD0380 OS160RD0380 OESA250R03D8
OS160RD0380 OS160RD0380 OS160RD0380 OESA250R03D80
Linecontactor,Type
A30 A40 A50 A50 A63 A75 A95 A110 A145
Thermaloverloadrelay,Type
Built-in Built-in Built-in Built-in Built-in Built-in Built-in Built-in Built-in
By-passcontactor,Type
A9 A16 A26 A26 A30 A40 A50
Currenttransformers Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated
IusingMCCBonly,type1coordinationwillbeachieved.
Toachieveatype2coordination,semi-condcutorusesmustbeused.
Suitableswitchuseor
recommendedsemi-conductoruses.
ThelinecontactorisnotrequiredorthesotstarteritselbutotenusedtoopeniOLtrips.
Theoverloadrelayisalwaysrequiredtoprotectthemotor.
Theby-passcontactorcanbeusedtoreducethepowerlossothesotstarterbutalsotoincreasethenumberostarts/h.Allsotstarterscanbeoperatedwithoutby-pass.
Thetableaboveisanoverviewopossiblecombinationsodevices.
Completecoordinationtablesareavailableatwww.abb.com/lowvoltage.
PST85...PST142PST30...PST72
SoftstartersTypePST30...300andPSTB370...1050Overview
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
23/50
SoftstartTypePST
Low Voltage Products & Systems
PST175...PST300
QuickguideforselectionNormalstartClass10 HeavydutystartClass30
OrderingSeepage2627 OrderingSeepage2829
Typicalapplications Typicalapplications Bowthruster Centriugalpump Centriugalan Conveyorbelt(long)
Compressor Conveyorbelt(short) Crusher Mill
Elevator Escalator Mixer Stirrer
Ifmorethan10starts/hSelectonesizelargerthanthestandardselection.!
Howtoselectcorrectsize
Byusingtheguidebeside,youcan
quicklyselectasuitablesotstarterorthe
mostcommonapplications.
Iamorepreciseselectionisrequired,you
canuseProsot,aselectionsotware
availableatwww.abb.com/lowvoltage.
Softstarter,Type
PST175 PST210 PST250 PST300 PSTB370 PSTB470 PSTB570 PSTB720 PSTB840 PSTB1050
90 110 132 160 200 250 315 400 450 560175 210 250 300 370 470 570 720 840 1050
125 150 200 250 300 400 500 600 700 900
156 192 248 302 361 480 590 720 840 1062
400V,40C
MCCB(50kA),Type
T4S250 T4S250 T5S400 T5S400 T5S1630 T5S1630 S6S630 S6S800 S7S1250 S7S1600
Fuseprotection(65kA)Bussmann,Type
170M3021 170M5012 170M5013 170M5015 170M5013 170M5015 170M5015 170M5018 170M5018 170M50202)
Switchfuse,Type
OESA250R03D80 OESA400R03D80 OESA400R03D80 OESA630R03D80 1) 1)
OESA400R03D80 OESA400R03D80 OESA630R03D80 OESA800R03D80
Linecontactor,Type
A185 A210 A260 A300 A400 A580 A580 A750 A1350 A1650
Thermaloverloadrelay,Type
Built-in Built-in Built-in Built-in Built-in Built-in Built-in Built-in Built-in Built-in
By-passcontactor,Type
A145 A145 A145 A210 Built-in Built-in Built-in Built-in Built-in Built-in
Currenttransformers
Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated
PSTB570...1050PSTB370...470
1)PSTB840andPSTB1050:Switchusenotavailable,useuseholder,seepage40.2)PST1050-690-70has170M6019
SoftstartersTypePST30...300andPSTB370...1050Overview
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
24/50
Softs
tarte
rs
Type
PST
22 Low Voltage Products & Systems
SoftstartersTypePST30...300andPSTB370...1050Applicationanddescription
DescriptionWidemainvoltagerange208-690VAC
Widesupplyvoltagerange100250V,50/60Hz
Currentratings30to1050A(InLine)and52...1810A(InsideDelta)SameunitcanbeusedorbothInLineandInsideDeltaconnection
PremiumadjustableSotstarterunctionslikestart/stopramp,kick
start,jog,stepdownvoltageandsequentialstarts.
Currentlimitadjustablebetween27xIe
Thermistor(PTC)supervisionomotorwinding
Realtimeclock
Loggingolast20eventswithtimemarking
Preparedorfeldbuscommunication
Motoroverloadprotectionwithsimulatedmotortemperaturerom
measuredcurrent.Selectbetween10A,10,20and30
Lockedrotorprotection
Motorunderloadprotection
Phaseimbalanceprotection
Phasereversalprotection
Torquecontrol
Analogoutput
ApplicationThePSTrangeisamicroprocessorbasedsotstarterdesignedwiththe
latesttechnologyorsotstartandsotstopomotors.ThePSTSotstart-
erhasseveraladvancedmotorprotectioneaturesasstandard.Theour
buttonkeypadandthelogicstructureothemenumaketheinstallation,
commissioningandoperationeasy.Itispossibletochoosebetween13
dierentlanguages.
ThePSTSotstartercanbeusedwithorwithoutaby-passcontactor
exceptorthelargersizesPSTB370...PSTB1050wheretheby-pass
contactorisalreadybuilt-in.
ThePSTSotstartercanbeselectedaccordingtotheratedmotorpower
innormal dutyapplicationslikepumps,compressors,elevators,escala-
tors,shortconveyorbeltsandbowthrusters.
Seepage26-27
Forheavy dutyapplicationslikecentriugalans,crushers,mixers,mills,
stirrersandlongconveyorbelts,selectasotstarterrom
page28-29.
In-Line and Inside Delta connection of PST30 PSTB1050
58A
100A
In-Line InsideDelta
100A
100A
LCD-displaywith
plainwordsin
yourlanguage
Fourbuttonkeypad
Clearinormation
Fieldbuscommunication
LEDindications:
Poweron
Fault
Protection
Threeseparateterminalspreparedorexternalby-pass
Programmable
signalinputs
Programmable
signalrelays
TerminalsorPTCinput
andanalogueoutput
Integratedadvanced
motorprotection
Symbolor
torquecontrol
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
25/50
SoftstartTypePST
Low Voltage Products & Systems
SoftstartersTypePST30...300andPSTB370...1050
Functionaldescription
LCDdisplayThedisplayothePSTgivesyouinormationpresentedinplainwords
inrequiredlanguage.Youcanchoosebetween13dierentlanguages
includingEnglish,German,Italian,Chinese,Finnish,Swedish,French,
Spanish,Dutch,Portuguese,Russian,TurkishandPolish.Onthe
PSTdisplay,yougetalltheinormationyouneedtosetup,adjust
andtrouble-shoot.ThismakesthePSTextremelyeasytohandleand
reducestheriskomisinterpretations.
FourbuttonkeypadThePSTemploysthesamebasicuserconceptastodaysadvanced
mobiletelephones.Usingtheourbuttonsonthekeypad,youcaneas-
ilyadjustyourownstartandstopprofleandmotorprotection
unctionsoranytypeoapplication.Therearestandardsettingsor
manycommonapplicationsincludingpumps,conveyors,ans,mixers
andcompressorsorquickandeasysetup.
Youcanalsosettheadvancedwarningparameterstoallowpotential
problemstobeidentifedbeorerealproblemsoccur.Apassword
protectionunctionisavailabletopreventunauthorizedchangestotheprogramming.
StartingseveralmotorsYoucanstoreasmanyasthreedierentstartingparametersetsor
optimalsequencestartothreedierentmotors.Youcanusethis
unctionortwoorthreespeedmotorsaswell.
IntegratedadvancedmotorprotectionInsidethePSTSotstarter,youwillfnduseuleaturesoradvanced
motorandsotstarterprotection,including;programmableoverload
protection,highcurrent,underload,phaseimbalance,phasereversal,
thyristoroverloadprotection,andbypassmonitoringtoensureproper
by-passoperation
ProgrammablesignalrelaysAllPSTunitshavethreeprogrammablesignalrelayswhereeachrelay
cansignalRun,TopoRamporEvent.TheEventsettingcanbeused
tosignalprotections,aultsandwarnings.Thesupervisoryunctions
monitornotonlysotwareandcriticalsotstarterunctionalitybutalso
phaselossandoutorequencyrange.
Integratedby-passcontactorOnthelargersizes(PSTB370...PSTB1050),thereisanABBAF
contactorintegrated.Thisgivesyouadvantagesintermsocost-
saving,spacesavingandlastbutnotleastenergysaving.Witha
by-passcontactoryoucanreducethepowerlossesduringnormalrun
by90%ormore.
Thesmallerunits,PST30uptoPST300,whicharenotequippedwitha
built-inby-passcontactor,haveanextrasetothreeterminalsonthelineside.TheterminalsaremarkedB1,B2andB3andshallbeusedwhen
connectinganexternalby-passcontactor.Thiswillenabletheintegrated
protectionunctionsalsowhenthesotstarterisby-passed.
Externalkeypad(option)Anexternalkeypadisavailableasoption.Thekeypadcanbemountedonapaneldoororexampletoview/controlthesotstarterwithoutopeningthedoor.Thekeypadcanalsobeusedtocopyparame-tersbetweendierentsotstarters.
PSTB570withintegratedby-passcontactor.
FieldbuscommunicationThePSTSotstarterhasabuilt-ininteraceontherontorconnectio
otheABBFieldBusPlugusedorfeldbuscommunication.Through
interaceitispossibletocontrolthesotstarter,achievestatusinorm
tion,up-anddownloadoparameters.Theinteracebetweenthes
starterandtheFieldBusPlugisalwaysthesame.IndependentlyoP
Sotstartersizeordeliverydateitispossibletoconnecttoanyfeldb
protocollateronsincethisisdefnedintheFieldBusPlugitsel.Avali
protocolsareAS-Interace,DeviceNet,ProfbusDPandModbus-RT
ToconnectthePSTSotstartertoafeldbussystemyouneedthea
cessoriesdescribedonpage31to36aswellasspecifcsotwareo
PLCset-up,whichisavailableatwww.abb.com/lowvoltageonthe
Sotstarterpages.
TorquecontrolThedeaultsettingisanormalvoltagerampbutit
ispossibletoselecttorqueramp.Withthetorque
controlunctionitispossibletostartandstop
motorswithamorelinearaccelerationthanwhenusingthenormalvoltageramps.
Duringstartthiscanbeusedtoreducethewearontheequipmentd
bythemotor.
Duringstop,controllingthetorqueisespeciallyuseulorpumpappl
tionswherevoltagerampscanleadtoasuddentorquedropwhich
resultinwaterhammeringandpressuresurges.Torquecontrolwillk
theseproblemstoanabsoluteminimum.
TorquelimitWiththetorquelimitunctionenabled,thetorquecanneverexceed
valueduringstart.Thiswillminimizestressandwearontheequipme
drivenbythemotor.
AnalogoutputWiththePST(B)sotstarteritispossibletohaveanalogoutputsignabeusedasinputtoaPLCorananalogmeter.Theoutputsignalsca
selectedtobeorinstancethecurrentothemotor,mainvoltage,a
powerorthetemperatureothemotor.Theterminalsusedoranalo
outputarealsousedorPTCprotection,soonlyoneotheseunctio
canbeused.
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
26/50
Softs
tarte
rs
Type
PST
24 Low Voltage Products & Systems
SoftstartersTypePST30...300andPSTB370...1050Normalstarts,class10In-Line,Orderingdetails
PST30...PST300
230600VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
15 18.5 - 30 PST30-600-70 1SFA894002R7000 4.8
18.5 22 - 37 PST37-600-70 1SFA894003R7000 4.8
22 25 - 44 PST44-600-70 1SFA894004R7000 4.8
25 30 - 50 PST50-600-70 1SFA894005R7000 4.8
30 37 - 60 PST60-600-70 1SFA894006R7000 5.0
37 45 - 72 PST72-600-70 1SFA894007R7000 5.0
45 55 - 85 PST85-600-70 1SFA894008R7000 11.2
55 75 - 105 PST105-600-70 1SFA894009R7000 13.0
75 90 - 142 PST142-600-70 1SFA894010R7000 13.0
90 110 - 175 PST175-600-70 1SFA894011R7000 21.5
110 132 - 210 PST210-600-70 1SFA894012R7000 21.5
132 160 - 250 PST250-600-70 1SFA894013R7000 23.0
160 200 - 300 PST300-600-70 1SFA894014R7000 23.0
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
15 18.5 25 30 PST30-690-70 1SFA895002R7000 4.8
18.5 22 30 37 PST37-690-70 1SFA895003R7000 4.8
22 25 37 44 PST44-690-70 1SFA895004R7000 4.8
25 30 45 50 PST50-690-70 1SFA895005R7000 4.8
30 37 55 60 PST60-690-70 1SFA895006R7000 5.0
37 45 59 72 PST72-690-70 1SFA895007R7000 5.0
45 55 75 85 PST85-690-70 1SFA895008R7000 11.2
55 75 90 105 PST105-690-70 1SFA895009R7000 13.0
75 90 132 142 PST142-690-70 1SFA895010R7000 13.0
90 110 160 175 PST175-690-70 1SFA895011R7000 21.5
110 132 184 210 PST210-690-70 1SFA895012R7000 21.5
132 160 220 250 PST250-690-70 1SFA895013R7000 23.0
160 200 257 300 PST300-690-70 1SFA895014R7000 23.0
PSTB370...PSTB1050withintegratedby-pass
230600VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
200 257 - 370 PSTB370-600-70 1SFA894015R7000 31.0
250 315 - 470 PSTB470-600-70 1SFA894016R7000 31.0
315 400 - 570 PSTB570-600-70 1SFA894017R7000 52.0
400 500 - 720 PSTB720-600-70 1SFA894018R7000 55.0
450 600 - 840 PSTB840-600-70 1SFA894019R7000 60.0560 730 - 1050 PSTB1050-600-70 1SFA894020R7000 60.0
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
200 257 355 370 PSTB370-690-70 1SFA895015R7000 31.0
250 315 450 470 PSTB470-690-70 1SFA895016R7000 31.0
315 400 560 570 PSTB570-690-70 1SFA895017R7000 52.0
400 500 710 720 PSTB720-690-70 1SFA895018R7000 55.0
450 600 800 840 PSTB840-690-70 1SFA895019R7000 60.0
560 730 1000 1050 PSTB1050-690-70 1SFA895020R7000 60.0
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
PST30...PST72
PST85...PST142
PST175...PST300
PSTB370...PSTB470
PSTB570...PSTB1050
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
27/50
SoftstartTypePST
Low Voltage Products & Systems
SoftstartersTypePST30...300andPSTB370...1050Normalstarts,class10InsideDelta,Orderingdetails
PST30...PST300
230600VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
25 30 - 52 PST30-600-70 1SFA894002R7000 4.8
30 37 - 64 PST37-600-70 1SFA894003R7000 4.8
37 45 - 76 PST44-600-70 1SFA894004R7000 4.8
45 55 - 85 PST50-600-70 1SFA894005R7000 4.8
55 75 - 105 PST60-600-70 1SFA894006R7000 5.0
59 80 - 124 PST72-600-70 1SFA894007R7000 5.0
75 90 - 147 PST85-600-70 1SFA894008R7000 11.2
90 110 - 181 PST105-600-70 1SFA894009R7000 13.0
132 160 - 245 PST142-600-70 1SFA894010R7000 13.0
160 200 - 300 PST175-600-70 1SFA894011R7000 21.5
184 250 - 360 PST210-600-70 1SFA894012R7000 21.5
220 295 - 430 PST250-600-70 1SFA894013R7000 23.0
257 355 - 515 PST300-600-70 1SFA894014R7000 23.0
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
25 30 45 52 PST30-690-70 1SFA895002R7000 4.8
30 37 55 64 PST37-690-70 1SFA895003R7000 4.8
37 45 59 76 PST44-690-70 1SFA895004R7000 4.8
45 55 75 85 PST50-690-70 1SFA895005R7000 4.8
55 75 90 105 PST60-690-70 1SFA895006R7000 5.0
59 80 110 124 PST72-690-70 1SFA895007R7000 5.0
75 90 132 147 PST85-690-70 1SFA895008R7000 11.2
90 110 160 181 PST105-690-70 1SFA895009R7000 13.0
132 160 220 245 PST142-690-70 1SFA895010R7000 13.0
160 200 257 300 PST175-690-70 1SFA895011R7000 21.5
184 250 315 360 PST210-690-70 1SFA895012R7000 21.5
220 295 400 430 PST250-690-70 1SFA895013R7000 23.0
257 355 500 515 PST300-690-70 1SFA895014R7000 23.0
PSTB370...PSTB1050withintegratedby-pass
230600VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
355 450 - 640 PSTB370-600-70 1SFA894015R7000 31.0
450 600 - 814 PSTB470-600-70 1SFA894016R7000 31.0
540 700 - 987 PSTB570-600-70 1SFA894017R7000 52.0
710 880 - 1247 PSTB720-600-70 1SFA894018R7000 55.0
800 1000 - 1455 PSTB840-600-70 1SFA894019R7000 60.01000 1250 - 1810 PSTB1050-600-70 1SFA894020R7000 60.0
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
355 450 600 640 PSTB370-690-70 1SFA895015R7000 31.0
450 600 800 814 PSTB470-690-70 1SFA895016R7000 31.0
540 700 960 987 PSTB570-690-70 1SFA895017R7000 52.0
710 880 1200 1247 PSTB720-690-70 1SFA895018R7000 55.0
800 1000 1400 1455 PSTB840-690-70 1SFA895019R7000 60.0
1000 1250 1700 1810 PSTB1050-690-70 1SFA895020R7000 60.0
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
PST30...PST72
PST85...PST142
PST175...PST300
PSTB370...PSTB470
PSTB570...PSTB1050
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
28/50
Softs
tarte
rs
Type
PST
26 Low Voltage Products & Systems
Heavy dutyHeavy dutyHeavy duty
SoftstartersTypePST37...300andPSTB370...1050Heavydutystarts,class30In-Line,Orderingdetails
PST37...PST300
230600VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
15 18.5 - 30 PST37-600-70 1SFA894003R7000 4.8
18.5 22 - 37 PST44-600-70 1SFA894004R7000 4.8
22 25 - 44 PST50-600-70 1SFA894005R7000 4.8
25 30 - 50 PST60-600-70 1SFA894006R7000 5.0
30 37 - 60 PST72-600-70 1SFA894007R7000 5.0
37 45 - 72 PST85-600-70 1SFA894008R7000 11.2
45 55 - 85 PST105-600-70 1SFA894009R7000 13.0
55 75 - 105 PST142-600-70 1SFA894010R7000 13.0
75 90 - 142 PST175-600-70 1SFA894011R7000 21.5
90 110 - 175 PST210-600-70 1SFA894012R7000 21.5
110 132 - 210 PST250-600-70 1SFA894013R7000 23.0
132 160 - 250 PST300-600-70 1SFA894014R7000 23.0
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
15 18.5 25 30 PST37-690-70 1SFA895003R7000 4.8
18.5 22 30 37 PST44-690-70 1SFA895004R7000 4.8
22 25 37 44 PST50-690-70 1SFA895005R7000 4.8
25 30 45 50 PST60-690-70 1SFA895006R7000 5.0
30 37 55 60 PST72-690-70 1SFA895007R7000 5.0
37 45 59 72 PST85-690-70 1SFA895008R7000 11.2
45 55 75 85 PST105-690-70 1SFA895009R7000 13.0
55 75 90 105 PST142-690-70 1SFA895010R7000 13.0
75 90 132 142 PST175-690-70 1SFA895011R7000 21.5
90 110 160 175 PST210-690-70 1SFA895012R7000 21.5110 132 184 210 PST250-690-70 1SFA895013R7000 23.0
132 160 220 250 PST300-690-70 1SFA895014R7000 23.0
PSTB370...PSTB1050withintegratedby-pass
230600VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
160 200 - 300 PSTB370-600-70 1SFA894015R7000 31.0
200 257 - 370 PSTB470-600-70 1SFA894016R7000 31.0
250 315 - 470 PSTB570-600-70 1SFA894017R7000 52.0
315 400 - 570 PSTB720-600-70 1SFA894018R7000 55.0
400 500 - 720 PSTB840-600-70 1SFA894019R7000 60.0450 600 - 840 PSTB1050-600-70 1SFA894020R7000 60.0
400690VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
160 200 257 300 PSTB370-690-70 1SFA895015R7000 31.0
200 257 355 370 PSTB470-690-70 1SFA895016R7000 31.0
250 315 450 470 PSTB570-690-70 1SFA895017R7000 52.0
315 400 560 570 PSTB720-690-70 1SFA895018R7000 55.0
400 500 710 720 PSTB840-690-70 1SFA895019R7000 60.0
450 600 800 840 PSTB1050-690-70 1SFA895020R7000 60.0
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
PST30...PST72
PST85...PST142
PST175...PST300
PSTB370...PSTB470
PSTB570...PSTB1050
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
29/50
SoftstartTypePST
Low Voltage Products & Systems
Heavy duty
SoftstartersTypePST37...300andPSTB370...1050Heavydutystarts,class30InsideDelta,Orderingdetails
PST37...PST300
230600VMotorpower
400V 500V 690V Ratedmotor
Pe P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
25 30 - 52 PST37-600-70 1SFA894003R7000 4.8
30 37 - 64 PST44-600-70 1SFA894004R7000 4.8
37 45 - 76 PST50-600-70 1SFA894005R7000 4.8
45 55 - 85 PST60-600-70 1SFA894006R7000 5.0
55 75 - 105 PST72-600-70 1SFA894007R7000 5.0
59 80 - 124 PST85-600-70 1SFA894008R7000 11.2
75 90 - 147 PST105-600-70 1SFA894009R7000 13.0
90 110 - 181 PST142-600-70 1SFA894010R7000 13.0
132 160 - 245 PST175-600-70 1SFA894011R7000 21.5
160 200 - 300 PST210-600-70 1SFA894012R7000 21.5
184 250 - 360 PST250-600-70 1SFA894013R7000 23.0
220 295 - 430 PST300-600-70 1SFA894014R7000 23.0
400690VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
25 30 45 52 PST37-690-70 1SFA895003R7000 4.8
30 37 55 64 PST44-690-70 1SFA895004R7000 4.8
37 45 59 76 PST50-690-70 1SFA895005R7000 4.8
45 55 75 90 PST60-690-70 1SFA895006R7000 5.0
55 75 90 105 PST72-690-70 1SFA895007R7000 5.0
59 80 110 124 PST85-690-70 1SFA895008R7000 11.2
75 90 132 147 PST105-690-70 1SFA895009R7000 13.0
90 110 160 181 PST142-690-70 1SFA895010R7000 13.0
132 160 220 245 PST175-690-70 1SFA895011R7000 21.5
160 200 257 300 PST210-690-70 1SFA895012R7000 21.5184 250 315 360 PST250-690-70 1SFA895013R7000 23.0
220 295 400 430 PST300-690-70 1SFA895014R7000 23.0
PSTB370...PSTB1050withintegratedby-pass
230600VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
257 355 - 515 PSTB370-600-70 1SFA894015R7000 31.0
355 450 - 640 PSTB470-600-70 1SFA894016R7000 31.0
450 600 - 814 PSTB570-600-70 1SFA894017R7000 52.0
540 700 - 987 PSTB720-600-70 1SFA894018R7000 55.0
710 880 - 1247 PSTB840-600-70 1SFA894019R7000 60.0800 1000 - 1455 PSTB1050-600-70 1SFA894020R7000 60.0
400690VMotorpower
400V 500V 690V Ratedmotor P
e P
e P
e current,I
e Weight
kW kW kW A Type Ordercode kg
257 355 500 515 PSTB370-690-70 1SFA895015R7000 31.0
355 450 600 640 PSTB470-690-70 1SFA895016R7000 31.0
450 600 800 814 PSTB570-690-70 1SFA895017R7000 52.0
540 700 960 987 PSTB720-690-70 1SFA895018R7000 55.0
710 880 1200 1247 PSTB840-690-70 1SFA895019R7000 60.0
800 1000 1400 1455 PSTB1050-690-70 1SFA895020R7000 60.0
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
Supplyvoltage,Us100...250V,50/60Hz
PST30...PST72
PST85...PST142
PST175...PST300
PSTB370...PSTB470
PSTB570...PSTB1050
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
30/50
Softs
tarte
rs
Type
PST
28 Low Voltage Products & Systems
LX...
LZ...
LT...-AC LT...-AL
LW...
LE185
PSTEK
PSTM-2
SoftstartersAccessoriesortypePST30...300andPSTB370...1050Orderingdetails
CableconnectorsforCucables
ForPST85...300youneed9piecesialsousingtheterminalsB1,B2,B3orexternalby-passcontactor.
For Wire Tightening Weightsoftstarter range torque Packing kg
type mm2
max.Nm Type Ordercode piece 1piecePST85142 6-185 16 1SDA023354R0001 3 0.20
PST85142 2x(50-120)16 LZ185-2C/120 1SFN074709R1000 3 0.30
PST175300 16-240 25 1SDA023368R0001 3 0.40
CableconnectorsforAlandCucables
ForPST85...300youneed9piecesialsousingtheterminalsB1,B2,B3orexternalby-passcontactor.
For Wire Tightening Weightsoftstarter range torque Packing kg
type mm2 max.Nm Type Ordercode piece 1piece
PST85142 35-95 13.5 1SDA023356R0001 3 0.10
PST85142 25-150 31 1SDA023357R0001 3 0.10
PST175300 120-240 43 1SDA023370R0001 3 0.10
TerminalextensionsFor Dimensions Weightsoftstarter hole bar Packing kg
type mm2 mm Type Ordercode pieces 1piecePST85142 8.5 17.5x5 LX185 1SFN074710R1000 1 0.250
PST175300 10.5 20x5 LX300 1SFN075110R1000 1 0.350
PSTB370...470 10.5 25x5 LX460 1SFN075710R1000 1 0.500
PSTB570...1050 13 40x6 LX750 1SFN076110R1000 1 0.850
TerminalenlargementsFor Dimensions Weightsoftstarter hole bar Packing kg
type mm2 mm Type Ordercode pieces 1piece
PST3072 6.5 15x3 LW110 1SFN074307R1000 1 0.100
PST85142 10.5 17.5x5 LW185 1SFN074707R1000 1 0.250
PST175...300 10.5 20x5 LW300 1SFN075107R1000 1 0.450
PSTB370...470 10.5 25x5 LW460 1SFN075707R1000 1 0.730
PSTB570...1050 13 40x6 LW750 1SFN076107R1000 1 1.230
TerminalnutwasherFor Weightsoftstarter Packing kg
type Type Ordercode piece 1piece
PST85...142 LE185 1SFN074716R1000 2 0.20
PST175...300 LE300 1SFN075116R1000 2 0.30
TerminalshroudsFor Weightsoftstarter Packing kg
type Req.qty Type Ordercode pieces 1piece
PST85142 1pcsand LT185-AC 1SFN124701R1000 2 0.050
1pcs LT460-AC 1SFN125701R1000 2 0.100
PST85142 1pcsand LT185-AL 1SFN124703R1000 2 0.2201pcs LT460-AL 1SFN125703R1000 2 0.800
PST175...300 3pcs LT300-AC 1SFN125101R1000 2 0.070
PST175...300 3pcs LT300-AL 1SFN125103R1000 2 0.280
PSTB370...470 2pcs LT460-AC 1SFN125701R1000 2 0.100
PSTB370...470 2pcs LT460-AL 1SFN125703R1000 2 0.800
PSTB570...1050 2pcs LT750-AC 1SFN126101R1000 2 0.120
PSTB570...1050 2pcs LT750-AL 1SFN126103R1000 2 0.825
Externalkeypadincludinga3mcableFor Weightsoftstarter Packing kgtype Type Ordercode piece 1piece
PST30...300 PSTEK 1SFA899003R1000 1 0.400
PSTB370...1050
MarineKitFor Weightsoftstarter Packing kgtype Type Ordercode piece 1piece
PST85142 PSTM-2 1SFA899004R1000 1 0.24
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
31/50
Softstart
Low Voltage Products & Systems
ASD11-FBP
ASP22-FBP
SotstartersFBP FieldBusPlugAS-Interace Fieldbus Connectors
Orange cable
ASD11-FBP
ASP22-FBP
AS-Interace FieldBusPlug DirectReady-made AS-Interace slave feldbus interace with various cable lengths.
Applicable on all MSD11-FBP and terminal devices with max. 2 input and 1 output signals.
Degree o protection IP65, diagnostic LED
Weig
Designation Cable Packing k
FieldBusPlug length Type Order code pieces 1 piec
AS-Interace FBP Direct 0.25 m ASD11-FBP.025 1SAJ 210 000 R0003 1 0.0
AS-Interace FBP Direct 0.50 m ASD11-FBP.050 1SAJ 210 000 R0005 1 0.1
AS-Interace FBP Direct 1.00 m ASD11-FBP.100 1SAJ 210 000 R0010 1 0.1
AS-Interace FBP Direct 5.00 m ASD11-FBP.500 1SAJ 210 000 R0050 1 0.3
AS-Interace FieldBusPlug PerormanceReady-made AS-Interace slave feldbus interace with various cable lengths.
Applicable on all FBP motor starters and devices with max. 4 input signals and 3 output signals
Degree o protection IP65, diagnostic LED
Weig
Designation Cable Packing k
FieldBusPlug length Type Order code pieces 1 piec
AS-Interace FBP 0.25 m ASP22-FBP.025 1SAJ 220 000 R0003 1 0.0Perormance
AS-Interace FBP 0.50 m ASP22-FBP.050 1SAJ 220 000 R0005 1 0.1Perormance
AS-Interace FBP 1.00 m ASP22-FBP.100 1SAJ 220 000 R0010 1 0.1Perormance
AS-Interace FBP 5.00 m ASP22-FBP.500 1SAJ 220 000 R0050 1 0.3Perormance
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
32/50
Softs
tarte
rs
30 Low Voltage Products & Systems
ASM11-FBP.0, ASF11-FBP.0
ASX11-FBP
ASF11-FBP, ASM11-FBP
AST11-FBP.0
SotstartersFBP FieldBusPlugAS-Interace Fieldbus Accessories
Orange cable
Accessories or AS-Interace Bus ConnectionAS-Interace Round Cable or Bus Junctions
Ready-made bus cable with an M12 connector and an open cable end.
Application on bus junctions such as e.g. AS-Interace couplers or devices with an integrated AS-Interace
Weight
Cable Packing kg
Designation length Type Order code pieces 1 piece
AS-Interace Round Cablewith emale connector 0.30 m ASF11-FBP.030 1SAJ 922 002 R0003 1 0.04
AS-Interace Round Cablewith male connector 0.30 m ASM11-FBP.030 1SAJ 922 003 R0003 1 0.04
AS-Interace Round Cable or Bus Extension
Ready-made bus cable with M12 male and emale connectors
Weight
Cable Packing kg
Designation length Type Order code pieces 1 piece
AS-Interace ExtensionCable 1.00 m ASX11-FBP.100 1SAJ 922 001 R0010 1 0.08
AS-Interace ExtensionCable 3.00 m ASX11-FBP.300 1SAJ 922 001 R0030 1 0.20
AS-Interace ExtensionCable 5.00 m ASX11-FBP.500 1SAJ 922 001 R0050 1 0.31
AS-Interace ExtensionCable 100 m ASC11-FBP.999 1SAJ 922 004 R1000 1 5.60
AS-Interace Round Cable and Accessories or Bus Extension
Bus cable and coupling accessories
Weight
Packing kg
Designation Type Order code pieces 1 pieceAS-Interace Round Cable,male conn. ASM11-FBP.0 1SAJ 922 005 R0001 5 0.15
AS-Interace Round Cable,emale conn. ASF11-FBP.0 1SAJ 922 006 R0001 5 0.15
AS-Interace Flat-CableBranch Circuitwith M12 socket AST11-FBP.0 1SAJ 922 007 R0001 1 0.15
AS-Interace Addressing Device, Power Unit, miscellaneous accessories
WeightDesignation Packing kgFieldBusPlug Type Order code pieces 1 piece
AS-Interace Addr. Device, includingplug-in power unit ASA21-FBP.0 1SAJ 922 010 R0001 1 0.56
Address Signs or FieldBusPlug CAL11-FBP.0 1SAJ 929 005 R0001 400 0.15
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
33/50
Softstart
Low Voltage Products & Systems
DNP21-FBP
MRP21-FBP
SotstartersFBP FieldBusPlug/DeviceNet andMODBUS-RTU Fieldbus Connectors
Black cable
To connect the PST Sotstarter to a DeviceNet feldbus system...
you need specifc sotware or PLC set-up, (EDS fle) which is available at www.abb.com/lowvoltage
on the Sotstarter pages. Look under the documentation-link named Sotware. I you need help or advice,
please contact your local ABB ofce.
DeviceNet FieldBusPlug
Ready-made DeviceNet feldbus interace with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree o protection IP65, diagnostic LED
Weigh
Cable Packing kg
Designation length Type Order code pieces 1 piec
DeviceNet-FBP 0.25 m DNP21-FBP.025 1SAJ 230 000 R0003 1 0.09
DeviceNet-FBP 0.50 m DNP21-FBP.050 1SAJ 230 000 R0005 1 0.10
DeviceNet-FBP 1.00 m DNP21-FBP.100 1SAJ 230 000 R0010 1 0.13
DeviceNet-FBP 5.00 m DNP21-FBP.500 1SAJ 230 000 R0050 1 0.36
MODBUS-RTU FieldBusPlug
Ready-made MODBUS-RTU feldbus interace with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree o protection IP65, diagnostic LED
Weigh
Cable Packing kgDesignation length Type Order code pieces 1 piec
MODBUS-RTU-FBP 0.25 m MRP21-FBP.025 1SAJ 250 000 R0003 1 0.09
MODBUS-RTU-FBP 0.50 m MRP21-FBP.050 1SAJ 250 000 R0005 1 0.10
MODBUS-RTU-FBP 1.00 m MRP21-FBP.100 1SAJ 250 000 R0010 1 0.13
MODBUS-RTU-FBP 5.00 m MRP21-FBP.500 1SAJ 250 000 R0050 1 0.36
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
34/50
Softs
tarte
rs
32 Low Voltage Products & Systems
DNR11-FBP.120
DNF11-FBP.0
DNM11-FBP.0
DNX11-FDP
DNM-11FBP.050
DNF-11FBP.050
SotstartersFBP FieldBusPlug/DeviceNet andMODBUS-RTU Fieldbus Accessories
Black cable
To connect the PST Sotstarter to a DeviceNet feldbus system...
you need specifc sotware or PLC set-up, (EDS fle) which is available at www.abb.com/lowvoltage
on the Sotstarter pages. Look under the documentation-link named Sotware. I you need help or advice,
please contact your local ABB ofce.
Accessories or the DeviceNet and MODBUS-RTU Bus Connector
DeviceNet and MODBUS-RTU round cable or bus junctions
Ready-made bus cable with an M12 connector and an open cable end.
WeightCable Packing kg
Designation length Type Order code pieces 1 piece
Round Cablewith emale connector 0.50 m DNF11-FBP.050 1SAJ 923 002 R0005 1 0.04
Round Cablewith male connector 0.50 m DNM11-FBP.050 1SAJ 923 003 R0005 1 0.04
DeviceNet and MODBUS-RTU Round Cable or Bus Extension
Ready-made bus cable with M12 male and emale connectorsWeight
Cable Packing kg
Designation length Type Order code pieces 1 piece
Extension Cable 1.00 m DNX11-FBP.100 1SAJ 923 001 R0010 1 0.08
Extension Cable 3.00 m DNX11-FBP.300 1SAJ 923 001 R0030 1 0.20
Extension Cable 5.00 m DNX11-FBP.500 1SAJ 923 001 R0050 1 0.31
Round Cable 100 m DNC11-FBP.999 1SAJ 923 004 R0001 1 5.6
DeviceNet and MODBUS-RTU Round Cable and Accessories or Bus Extension
Bus cable and coupling accessoriesWeight
Cable Packing kg
Designation length Type Order code pieces 1 piece
Round CableMale Connector DNM11-FBP.0 1SAJ 923 005 R0001 5 0.15
Device Net Round CableFemale Connector DNF11-FBP.0 1SAJ 923 006 R0001 5 0.15
DeviceNet and MODBUS-RTU, Termination Resistor, Miscellaneous AccessoriesWeight
Packing kg
Designation Type Order code pieces 1 piece
Termination Resistor, 120 Ohm DNR11-FBP.120 1SAJ 923 007 R0001 1 0.02
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
35/50
Softstart
Low Voltage Products & Systems
PDP21-FBP
PDP22-FBP
SotstartersFBP FieldBusPlug/Profbus DP/V0, DP/V1 FieldbusConnectors
Purple cable
To connect the PST Sotstarter to a Profbus DP feldbus system...
you need specifc sotware or PLC set-up, (GSD fle) which is available at www.abb.com/lowvoltage
on the Sotstarter pages. Look under the documentation-link named Sotware. I you need help or advice,
please contact your local ABB ofce.
Profbus DP/V0 FieldBusPlug
Ready-made Profbus DP/V0 feldbus interace with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree o protection IP65, diagnostic LEDWeig
Cable Packing
Designation length Type Order code pieces 1 pie
Profbus DP/V0-FBP 0.25 m PDP21-FBP.025 1SAJ 240 000 R0003 1 0.0
Profbus DP/V0-FBP 0.50 m PDP21-FBP.050 1SAJ 240 000 R0005 1 0.1
Profbus DP/V0-FBP 1.00 m PDP21-FBP.100 1SAJ 240 000 R0010 1 0.1
Profbus DP/V0-FBP 5.00 m PDP21-FBP.500 1SAJ 240 000 R0050 1 0.3
Profbus DP/V1 FieldBusPlug
Ready-made Profbus DP/V1 feldbus interace with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree o protection IP65, diagnostic LED
Weig
Cable Packing
Designation length Type Order code pieces 1 pie
Profbus DP/V1-FBP 0.25 m PDP22-FBP.025 1SAJ 240 100 R0003 1 0.0
Profbus DP/V1-FBP 0.50 m PDP22-FBP.050 1SAJ 240 100 R0005 1 0.1
Profbus DP/V1-FBP 1.00 m PDP22-FBP.100 1SAJ 240 100 R0010 1 0.1
Profbus DP/V1-FBP 5.00 m PDP22-FBP.500 1SAJ 240 100 R0050 1 0.3
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
36/50
Softs
tarte
rs
34 Low Voltage Products & Systems
PDF11-FBP.50
PDM11-FBP.50
PDX11-FBP
PDF11-FBP.0
PDM11-FBP.0
SotstartersFBP FieldBusPlug/Profbus DP/V0, DP/V1 FieldbusAccessories
Purple cable
To connect the PST Sotstarter to a Profbus DP feldbus system...
you need specifc sotware or PLC set-up, (GSD fle) which is available at www.abb.com/lowvoltage
on the Sotstarter pages. Look under the documentation-link named Sotware. I you need help or advice,
please contact your local ABB ofce.
Accessories or the Profbus DP/V0. DP/V1 Bus Connector
Profbus DP/V0, DP/V1 Round Cable or Bus Junctions
Ready-made bus cable with an M12 connector and an open cable end.
Application on bus junctions such as e.g.Profbus DB couplers or devices with an integrated Profbus DB
interace
Weight
Cable Packing kg
Designation length Type Order code pieces 1 piece
Round Cablewith emale connector 0.50 m PDF11-FBP.050 1SAJ 924 002 R0005 1 0.04
Round Cablewith male connector 0.50 m PDM11-FBP.050 1SAJ 924 003 R0005 1 0.04
Profbus DP/V0, DP/V1 Round Cable or Bus Extension
Ready-made bus cable with M12 male and emale connectors
Weight
Cable Packing kg
Designation length Type Order code pieces 1 piece
Extension Cable 1.00 m PDX11-FBP.100 1SAJ 924 001 R0010 1 0.08
Extension Cable 3.00 m PDX11-FBP.300 1SAJ 924 001 R0030 1 0.20
Extension Cable 5.00 m PDX11-FBP.500 1SAJ 924 001 R0050 1 0.31
Round Cable 100 m PDC11-FBP.999 1SAJ 924 004 R1000 1 5.60
Profbus DP/V0, DP/V1 Accessories or Bus Extension
Weight
Packing kg
Designation Type Order code pieces 1 piece
Male Connector PDM11-FBP.0 1SAJ 924 005 R0001 5 0.03
Female Connector PDF11-FBP.0 1SAJ 924 006 R0001 5 0.03
Profbus DP/V0, DP/V1 Termination Resistor, Miscellaneous Accessories
Weight
Packing kg
Designation Type Order code pieces 1 piece
Termination resistor, 150 ohm PDR11-FBP.150 1SAJ 924 007 R0001 1 0.03
Feeding connector 24V DC PDV11-FBP.0 1SAJ 924 008 R0001 1 0,04Code B-A
Feeding connector 24V DC PDV12-FBP.0 1SAJ 924 011 R0001 1 0,04Code A-A
Adaptor M12-Dsub9-M12 PDA11-FBP.050 1SAJ 924 009 R0001 1 0,04Cable lenth 0.50m
Adaptor M12-Dsub9-M12 PDA12-FBP.050 1SAJ 924 010 R0001 1 0,04Cable lenth 2 x 0.50m
-
8/14/2019 ABB; Softstarters, Type PSR, PSS, PST/PSTB
37/50
Softstart
Low Voltage Products & Systems
PST30 300 PSTB370 ... 1050
Rated insulation voltage Ui
690 V 690 V
Rated operational voltage Ue
208 ... 690 V 208 ... 690 V
Starting capacityat max rated current Ir
3 x Iror 15 sec. 3 x I
ror 15 sec
Number o starts per hour 30 1) 10 1)
Overload capability,Overload Class 10 10
Service actor 115 % 115 % (PSTB370...PSTB840)
100 % (PSTB1050)
Ambient temperature During operation 0 +50 C 2) 0 +50 C 2)During storage -25 +70 C -25 +70 C
AltitudeMaximum altitude 4000 m 3) 4000 m 3)
Degree o protection
Main circuit IP10(PST30 ... 72)
IP00(all)
IP00 ( PST85 ... 300)Supply and Control circuit IP20 IP20
Main circuitBuilt in By-pass contactor No YesCooling system - Fan cooled(thermostat controlled) Yes Yes
Supply circuitSupply voltage one range 100 ... 250 V, 100 ... 250 V
50/60 Hz 50/60 Hz+10 %/-15 % +10 %/-15 %
HMI or settings(Human Machine Interface)
20 segment display Yes Yes
Keypad with two selection
keys and two navigating keys Yes YesPlain text in 13 languages
(English, German, Italian,Dutch, Chinese, Finnish,Swedish, French, Spanish,Russian, Portuguese,Turkish and Polish) Yes Yes
Signal relaysNumber o programmablesignal relays (Each relay can
be programmed to be Run,By-pass or Event signal) 3 3K4 Deault as Run signal Yes YesK5 Deault as By-pass signal Yes YesK6 Deault as Event signal Yes YesRated operational voltage U
e250 V 250 V
Rated thermal current Ith
5 A 5 ARated operational current I
e
at AC-15 (Ue
= 250 V) 1.5 A 1.5 A
Analog outputOutput signal reerence 0 ... 10 V, 0 ...20 mA, 4 ... 20 mA
Type o output signal I Amp, U Volt, P kW, P hp, Q kVAr,
S kVA, TmpMot, TmpSCR, cosPhi
SotstartersType PST30 ... 300 and PSTB370 ... 1050Technical data
PST30 300 PSTB370 ... 1050
Control circuit /Hardware inputsInternal 24 V DC (10 mA closed) Yes Yes
Start / Stop inputs Yes Yes
Two extra programmable inputs(Each input can be programmed
to be either; Non, Reset, Enable,
Jog, DOL- On, Start motor 2 or
Start motor 3, FB-Dis). Yes Ye
Signal indication LEDsPower on Green Yes Yes
Fault - Red Yes Yes
Protection - Yellow Yes Yes
ProtectionsElectronic overload Yes Yes
Adjustable tripping classes -Class 10 A, 10, 20 and 30 Yes Yes
Dual overload (separate overload
unction or start and run) Yes YesPTC connection Yes Yes
Locked rotor protection Yes Yes
Underload protection Yes Yes
Phase imbalance Yes Yes
High current (8 x Ie ) Yes Ye
Phase reversal protection Yes Yes
Warnings (pre-warning)High current Yes Yes
Low current (underload) Yes Yes
Overload trip Yes Yes
Overtemp. thyristors (SCR) Yes Yes
Start o several motors
Possible to set up and startthree dierent motors Yes Yes
Field bus connectionConnection orABB FieldBusPlug Yes Yes
PTC inputSwitch o resistance 2825 ohm + 20% 2825 ohm + 20%
Switch on resistance 1200 ohm + 20% 1200 ohm + 20%
External keypad
Display LCD