Indoor Voltage Transformers KGUG
Description
The KGUG voltage, double-pole insulated transformers are casted in epoxi resin and designed mostly for insu-lation voltages of 24 kV to 36 kV.Other insulation values are to be the subject of an agreement between the manufacturer and the customer.If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the partsof the primary winding of the transformer are insulated from the earth, including the terminals, to an insulationlevel identical with the rated insulation level. When operating in a three-phase system the primary inlets of thetransformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type ofconnections. The majority of transformers is equipped with one secondary winding, intended to be used for eitherthe measurement or protection purposes. One of the terminals of each secondary winding has to be earthedduring the transformer operation.If not required other wise, the secondary winding is lead out into a casted secondary terminal board.The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 boltedearthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered witha transparent cover.
Rated primary voltages ... 15 kV; 20 kV; 22 kV; 30 kV; 33 kV; 35 kVOther primary voltages based on customer‘s request may be delivered, too.Rated secondary voltages... 100 V; 110 V – 0.2; 0.5 and 1 accuracy classes (measuring winding), or 3P; 6P(protection winding)Other secondary voltages based on customer‘s request may be delivered, too.Rated frequency ... 50 Hz; 60 HzThe transformers are manufactured and delivered conformably to the requirements and recommendations of thefollowing standards and regulations: IEC, SEV, VDE, ANSI, BS, GOST and »SN.
Highest voltage for equipment [kV] 24, 36Power frequency test voltage, 1 min. [kV] 50, 70Lightning impulse test voltage [kV] 125, 170Rated burden, classes [VA/cl] 80/0.2 - 300/0.5 - 600/1Max. thermanl output [VA] 2000
Dimensions
Double pole voltage transformers
A 3440-530-I/2001
epyT ecnadroccanituptuodetaR,EDVdnaSB,VES,CEIhtiw
sessalcni,zH06dna05AV
ecnadroccaninedrubdeaR,ISNAhtiw
sessalcni,zH06AV
mumixaMtuptuolamreht
AVni.t.vrep
zH06dna05AV2.0 5.0 1 3 3.0 6.0 2.1
42GUGK63GUGK
0808
003003
006006
00810081
ZYXWZYXW
ZZ,ZYXWZZ,ZYXW
ZZ,ZYXWZZ,ZYXW
00020002
Type A B C D E F D H J K L m/kgKGUG 24 391 202 455 376 320 200 222 215 260 179 72 approx. 60KGUG 36 443 227 505 427 348 310 248 230 300 186 72 approx. 80
KGUG 2436
KGU
2
ABB s.r.o.Videnska 117 Tel.: +420 547 152 602619 00 Brno, Czech Republic +420 547 152 604E-mail: [email protected] Fax: +420 547 152 626http://www.abb.com
The data and ilustrations in this catalogue are not binding.We reserve the right to make changes of the content, inthe course of technical development of the product.
DescriptionThe TDC 4 voltage, double-pole insulated transformers are cast in epox resin and designed mostly for insulation voltages of 3.6 kV to 12 kV.If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the parts of the primary winding of the transformer are insulated from the earth, including the terminals, to an insulation level identical with the rated insulation level. When operating in a three-phase system the primary inlets of the transformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type of connection. The majority of the transformers is equipped with one secondary winding, intended to be used for either the measurement or protection purposes. One of the terminals of each secondary winding has to be earthed during the transformer operation.If not required otherwise, the secondary winding is lead out into a cast secondary terminal board.The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 bolted earthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered with a transparent cover made of plastic material.
Rated primary voltages ... 3 kV; 3.3 kV; 6 kV; 6.6 kV; 10 kV; 11 kVOther primary voltages based on customer‘s request may be delivered, too.Rated secondary voltages... 100 V; 110 V – 0.2; 0.5; and 1 accuracy classes (measuring winding), or 3P; 6P (protection winding)Other secondary voltages based on customer‘s request may be delivered, too.Rated frequency ... 50 Hz; 60 HzDesign for two primary voltages is also possible, based on a consultancy to be conducted with the manufacturer (change over secondary side).The transformers are manufactured and delivered conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.
Highest voltage for equipment [kV] 3.6 - 12
Power frequency test voltage, 1 min. [kV] 10 -
Lightning impulse test voltage [kV] 40 - 75
Max. rated burden, classes [VA/cl] 25/0.2 - 75/0.5 - 150/1
TDC 4Indoor voltage transformers
Medium Voltage Product
2
Dimensions
100
220
20
116139
22
9
4
M10x15
M8
Pg1
6 14
(125
)
2x 11
148
27010
1196
30
82 188
110
338
Marking of the voltage transformer outlets
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.
3
Standartized transformers
Primary
voltage,V
Secondary voltage
voltage,V accuracy burden, VA
3000 100 0,2 10,15,25
3000 100 0,5 15,25,50
3000 100 1 50,75,100
3300 110 0,2 10,15,25
3300 110 0,5 15,25,50
3300 110 1 50,75,100
6000 100 0,5 15,25,50
6000 100 0,5 15,25,50
6000 100 1 50,75,100
6600 110 0,2 10,15,25
6600 110 0,5 15,25,50
6600 110 1 50,75,100
10000 100 0,2 10,15,25
10000 110 0,2 10,15,25
10000 100 0,5 15,25,50
10000 110 0,5 15,25,50
10000 100 1 50,75,100
10000 110 1 50,75,100
11000 100 0,2 10,15,25
11000 110 0,2 10,15,25
11000 100 0,5 15,25,50
11000 110 0,5 15,25,50
11000 100 1 50,75,100
11000 110 1 50,75,100
1VLC
0005
22 -
Rev
1, e
n 20
10.x
x.xxABB s.r.o.
PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.: +420 547 152 602
+420 547 152 614
Fax: +420 547 152 626
E-mail: [email protected]
www.abb.com
The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.
Description
Highest voltage for equipment [kV] 3.6 – 12
Power frequency test voltage, 1 min. [kV] 10 – 28 (42)
Lightning impulse test voltage [kV] 40 - 75
Fuse : 2 or 6,3 A(IEC)
Max. rated burden, classes [VA/cl] 25/0.2 - 50/0.5 - 100/1
Residual winding [VA/cl] 50 - 200/6P
TJP 4.0-FIndoor Voltage Transformer
Medium Voltage Product
The TJP 4.0-F epoxi insulated voltage transformers are cast in epoxi resin and designed mostly for insulation voltages of 3.6 kV to 12 kV. If no a different value is required the transformers are manufactured with a overvoltage factor of 1.9 x Un/8 hrs. One outlet of the primary winding, including the respective terminal is insulated from the earth to a level which corresponds to the rated insulation value. The other outlet of primary winding with its terminal is earthed during the operation. Most of the transformers are equipped with two secondary windings, the first one for either measuring or protection purposes, the other for being connected into an open-delta connection in a three-phase system. One terminal of each secondary winding and one of the open-delta connected terminals have to be earthed during the transformer operation. The secondary windings are lead out into a cast-type secon-dary terminal board. The secondary terminal board is covered with a sealed plastic over. The transformer can be mounted in any position. The trans-former body is fixed by four screws, the bolted M8 earthing clamp is located on the transformer base plate. The TJP 4.0-F transformer is equipped with a fuse conformably to IEC standard. The design of TJP4.0-F is suitable for AIS panels (see HV terminal and the position of the secondary terminals) and the replacement of the fuse can be done from the front (HV terminal) or after removing the upper part of the fuseholder – see „fuse replacement instruction“. There are two options for the fuseholder position : above secondary terminal box (suitable for ABB AIS, drawing number 1VL4200251R0101) or on the opposite side (drawing number 1VL4200300R0101).
Rated primary voltages ... 3/V3 kV; 3,3/V3 kV; 6/V3 kV; 6,6/V3 kV; 10/V3 kV; 11/V3 kV. Other primary voltages can also be supplied on request. Rated secondary voltages... 100/V3 V; 110/V3 V – accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P;6P(protection winding). Other secondary voltages can also be supplied on request. Rated voltages for open-delta connection: ... 100/3 V; 110/3 V- class 6P. Other voltages for open-delta connection can also be supplied based on customer requirement. Rated frequency ... 50 Hz; 60 Hz. Based on a discussion with the manufacturer the transformer can also be provided with primary winding designed for two different primary voltages (with secondary side changeover).The transformers are manufactured conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.
1VLC
0005
22, R
ev.1
, en
2011
. 02.
15
The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.
ABB s.r.o.
PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.: +420 547 152 602
+420 547 152 614
Fax: +420 547 152 626
E-mail: [email protected]
www.abb.com
Dimensions
Marking of the voltage transformer outlets
a) Single-pole insulated transformer b) Double-pole insulated transformer with a tap c) Single-pole insulated transformer with two secondary windings d) insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding e) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.
a) b) c) d) e)
KGUGIIndoor Voltage Transformers
Medium Voltage Product
Dimensions
Highest voltage for equipment
Power frequency test voltage, 1 min.
Lightning impulse test voltage
Rated burden, classes
Residual windin
[kV]
[kV]
[kV]
[ VA/cl ]
[ VA/cl ]
D
Technical parameters
escription
The KGUGI single-pole insulated voltage transformers are casted in epoxi resin and designed mostly for insu-lation voltages of 24 to 36 kV.Insulation voltages different from the above are to be the subject of an agreement between the manufacturer andthe customer.If no other value is required the transformers are manufactu-red with a overvoltage factor of 1.9 x Un/8 hrs. Oneoutlet of the primary winding, including the respective terminal is insulated from the earth to a level whichcorresponds to the rated insulation value. The other outlet of primary winding with terminal is earthed duringthe operation.The transformer is mostly equipped with two secondary windings, the first one for either measuring or protectionpur-poses, the other for being connected into an open-delta connection in a three-phase system. One terminalof each secondary winding and one of the open-delta connected terminals have to be earthed during thetransformer operation.When not required other wise the secondary windings are lead out into a casted-type secondary terminal board.The transformer can be mounted in any position. The transformers are fixed by four screws, the M8 boltedearthing clamp is located on the transformer base plate. The secondary terminal board is covered with voltagessealable cover.
Rated primary voltages ... 15/√3 kV; 20/√3 kV; 22/√3 kV; 30/√3 kV; 33/√3 kV; 35/√3 kVOther primary voltages can also be supplied on request.Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P(protection winding).Other secondary voltages can also be supplied on request.Rated voltages for open-del-ta connection: ... 100/3 V; 110/3 V- class 6POther voltages for open-delta connection can also be supplied based on customer requirement.Rated frequency ... 50 Hz; 60 HzThe transformers are manufactured confor-mably to the requirements and recommendations of the followingstandards and regulations: IEC, SEV, VDE, ANSI, BS, GOST and ČSN.
24, 36
50, 70
125, 170
80/0.2 - 250/0.5 - 500/1
up to 600/6P
1VLV
0005
31-R
ev.,
en,2
011.
02.2
5
ABB s.r.o.
PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.: +420 547 152 602
+420 547 152 614
Fax: +420 547 152 626
E-mail: [email protected]
www.abb.com
Text: The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product.
©Copyright 2011 ABBAll rights reserved
Dimensions
Single pole voltage transformers
epy eT cnadroccanituptuodetaR,EDVdnaSB,VES,CEIhtiw
sessalcni,zH06dna05
ecnadroccaninedrubdeaR,ISNAhtiw
sessalcni,zH06
mumixaMtuptuolamreht
AVni.t.vrep
zH06dna052.0 5.0 1 3 3.0 6.0 2.1
42IGUGK63IGUGK
08051
052004
005057
00010051
YXW)YY(YXW
ZYXWZZ,ZYXW
ZZ,ZYXWZZ,ZYXW
00510002
KGUGI 24
36
KGU1
Type A B C D E F D H J K L m/kg
KGUGI 24 391 202 455 376 320 100 222 215 260 179 72 approx. 60
KGUGI 36 443 227 505 427 348 155 248 230 300 186 72 approx. 80
DescriptionThe TJC 4 single-pole insulated voltage transformers are cast in epoxi resin and designed mostly for insulation voltages of 3.6 kV to 12 kV.If no other value is required the transformers are manufactured with a overvoltage factor of 1.9 x Un/8 hrs.One outlet of the primary winding, including the respective terminal is insulated from the earth to a level which corresponds to the rated insulation value. The transformer is mostly equipped with two secondary windings, the first one for either measuring or protection purposes, the other for being connected into an open-delta connection in a three-phase system. One terminal of each secondary winding and one of the open-delta connected terminals have to be earthed during the transformer operation. When not required otherwise, the secondary windings are lead out into a cast-type secondary terminal board.The transformer can be mounted in any position. The transformer ore fixed by four screws, the M8 bolted earthing clamp is located on the transformer base plate. The secondary terminal board is covered with a transparent and sealable cover made of plastic material.
Rated primary voltages ... 3/√3 kV; 3,3/√3 kV; 6/√3 kV; 6,6/√3 kV; 10/√3 kV; 11/√3 kVOther primary voltages can also be supplied on request.Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection winding).Other secondary voltages can also be supplied on request.Rated voltages for open-delta connection: ... 100/3 V; 110/3 V- class 6POther voltages for open-delta connection can also be supplied based on customer requirement.Rated frequency ... 50 Hz; 60 HzBased on a discussion with the manufacturer the transformer can also be designed for two primary voltage levels (with change over secondary side).The transformers are manufactured conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.
Highest voltage for equipment [kV] 3.6 - 12
Power frequency test voltage, 1 min. [kV] 10 -
Lightning impulse test voltage [kV] 40 - 75
Max. rated burden, classes [VA/cl] 25/0.2 - 50/0.5 - 100/1
Residual winding [VA/cl] 50 - 200/6P
TJC 4Indoor voltage transformers
Medium Voltage Product
2
Dimensions
WEIGHT: appr. 20kgCREEPAGE DISTANCE: 280mm
22 2022
0
8
174197
4
M8
Pg16 14
M10x15
125
148
11
280338
11 30
130140
96
Marking of the voltage transformer outlets
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.
3
Standard execution of the transformers
Primary
voltage,V
Secondary voltage Residual winding
voltage,V accuracy burden, VA voltage,V accuracy burden, VA3000/√3 100/√3 0,2 10,15,25 3000/√3 100/√3 0,2 10,15,25 100/3 6P 50
3000/√3 100/√3 0,2 10,15,25 100/3 6P 100
3000/√3 100/√3 0,5 15,25,50
3000/√3 100/√3 0,5 15,25,50 100/3 6P 50
3000/√3 100/√3 0,5 15,25,50 100/3 6P 100
3000/√3 100/√3 1 50,75,100
3000/√3 100/√3 1 50,75,100 100/3 6P 50
3000/√3 100/√3 1 50,75,100 100/3 6P 100
3300/√3 110/√3 0,2 10,15,25
3300/√3 110/√3 0,2 10,15,25 110/3 6P 50
3300/√3 110/√3 0,2 10,15,25 110/3 6P 100
3300/√3 110/√3 0,5 15,25,50
3300/√3 110/√3 0,5 15,25,50 110/3 6P 50
3300/√3 110/√3 0,5 15,25,50 110/3 6P 100
3300/√3 110/√3 1 50,75,100
3300/√3 110/√3 1 50,75,100 110/3 6P 50
3300/√3 110/√3 1 50,75,100 110/3 6P 100
6000/√3 100/√3 0,2 10,15,25
6000/√3 100/√3 0,2 10,15,25 100/3 6P 50
6000/√3 100/√3 0,2 10,15,25 100/3 6P 100
6000/√3 100/√3 0,5 15,25,50
6000/√3 100/√3 0,5 15,25,50 100/3 6P 50
6000/√3 100/√3 0,5 15,25,50 100/3 6P 100
6000/√3 100/√3 1 50,75,100
6000/√3 100/√3 1 50,75,100 100/3 6P 50
6000/√3 100/√3 1 50,75,100 100/3 6P 100
6600/√3 110/√3 0,2 10,15,25
6600/√3 110/√3 0,2 10,15,25 110/3 6P 50
6600/√3 110/√3 0,2 10,15,25 110/3 6P 100
6600/√3 110/√3 0,5 15,25,50
6600/√3 110/√3 0,5 15,25,50 110/3 6P 50
6600/√3 110/√3 0,5 15,25,50 110/3 6P 100
6600/√3 110/√3 1 50,75,100
6600/√3 110/√3 1 50,75,100 110/3 6P 50
6600/√3 110/√3 1 50,75,100 110/3 6P 100
10000/√3 100/√3 0,2 10,15,25
10000/√3 100/√3 0,2 10,15,25 100/3 6P 50
10000/√3 100/√3 0,2 10,15,25 100/3 6P 100
10000/√3 110/√3 0,2 10,15,25
10000/√3 110/√3 0,2 10,15,25 110/3 6P 50
10000/√3 110/√3 0,2 10,15,25 110/3 6P 100
10000/√3 100/√3 0,5 15,25,50
10000/√3 100/√3 0,5 15,25,50 100/3 6P 50
10000/√3 100/√3 0,5 15,25,50 100/3 6P 100
10000/√3 110/√3 0,5 15,25,50
10000/√3 110/√3 0,5 15,25,50 110/3 6P 50
10000/√3 110/√3 0,5 15,25,50 110/3 6P 100
10000/√3 100/√3 1 50,75,100
10000/√3 100/√3 1 50,75,100 100/3 6P 50
10000/√3 100/√3 1 50,75,100 100/3 6P 100
10000/√3 110/√3 1 50,75,100
10000/√3 110/√3 1 50,75,100 110/3 6P 50
10000/√3 110/√3 1 50,75,100 110/3 6P 100
11000/√3 100/√3 0,2 10,15,25
11000/√3 100/√3 0,2 10,15,25 100/3 6P 50
11000/√3 100/√3 0,2 10,15,25 100/3 6P 100
11000/√3 110/√3 0,2 10,15,25
11000/√3 110/√3 0,2 10,15,25 110/3 6P 50
11000/√3 110/√3 0,2 10,15,25 110/3 6P 100
11000/√3 100/√3 0,5 15,25,50
11000/√3 100/√3 0,5 15,25,50 100/3 6P 50
11000/√3 100/√3 0,5 15,25,50 100/3 6P 100
11000/√3 110/√3 0,5 15,25,50
11000/√3 110/√3 0,5 15,25,50 110/3 6P 50
11000/√3 110/√3 0,5 15,25,50 110/3 6P 100
11000/√3 100/√3 1 50,75,100
11000/√3 100/√3 1 50,75,100 100/3 6P 50
11000/√3 100/√3 1 50,75,100 100/3 6P 100
11000/√3 110/√3 1 50,75,100
11000/√3 110/√3 1 50,75,100 110/3 6P 50
11000/√3 110/√3 1 50,75,100 110/3 6P 100
1VLC
0005
20 -
Rev
1, e
n 20
11, 0
1.15ABB s.r.o.
PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.: +420 547 152 602
+420 547 152 614
Fax: +420 547 152 626
E-mail: [email protected]
www.abb.com
The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.