ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product...

33
ABB Australia Pty Ltd 1VGA671004 – Rev. D June 10, 2022 | Slide 1 UniGear ZVC Standard Product January 2010

Transcript of ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product...

Page 1: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

ABB Australia Pty Ltd1VGA671004 – Rev. DApril 19, 2023 | Slide 1

UniGear ZVCStandard Product

January 2010

Page 2: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 2

Contents

Air Insulated Switchgear

Certifications3Internal Arc Containment 4Loss of Service Continuity5Partition Class6Current Ratings7Electrical Characteristics 8Wall Standing Solution9 Panel Dimension10Cable Entry11Flexible Applications12Basic Structure13Contactor and Cable Compartments 14The Heart of the Switchgear15Contactor

16

HRC Fuses17Earth Switch20Control Power Transformer21Instrument Transformer22Compulsory Tools23UniGear Platform24Product Value25Comparisons

26Project Savings

28The SLD of Typical Motor Starting Options30Typical Configuration of Unigear ZVC Panels31Contact32

Page 3: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 3

Air Insulated SwitchgearMotor Control Centre

Certifications:

Quality System: ISO 9001 Standards

Environmental Management System: ISO 14001 Standards

Complies with:

IEC Standards

Australian Standards

Chinese GB Standards

Back to Content

Page 4: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 4

Air Insulated SwitchgearInternal Arc Containment

Arc Flash safe according to IEC 62271-200

Classification AFLR ...50kA (...1sec)

For all the five criteria

Front, rear and sides arc resistance

Back to Content

Page 5: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 5

Air Insulated SwitchgearLoss of Service Continuity

LSC2A according to IEC 62271-200

Busbar, cable and fused contactor compartments physically and electrically segregated (Metal-Clad)

A. Circuit Breaker Compartment

B. Busbar Compartment

C. Feeder Compartment

D. Low Voltage Control Compartment

Back to Content

Page 6: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 6

Air Insulated SwitchgearPartition Class

Partition class PM to IEC 62271-200

Metallic shutters operated by the apparatus movement

Metallic segregation of all the compartments

Back to Content

Page 7: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 7

Air Insulated SwitchgearCurrent Ratings

Back to Content

Page 8: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 8

Air Insulated SwitchgearElectrical Characteristics

Rated Voltage kV 3.6 7.2

Test Voltage (50-60Hz/1 min) kV 16 20

Impulse Withstand Voltage kV 40 60

Rated Frequency Hz 50/60 50/60

Rated Short-time Withstand Current kA …50 …50

Peak Withstand Current kA …125 …125

Internal Arc Fault Containment kA …50 …50

Rated Current of the Main Busbars A 4000 4000

Rated Normal Load Current A 200 400 200 400

Fused Drawout Contactor Type VSC7/ZVC

V7/ZVC

- -

- -

Motor Switching kW 1000 2000 2000 4000

Capacitors Switching kVAR - 1000 - 2000

Transformers Switching kVA 1000 2000 2000 4000

Back to Content

Page 9: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 9

Air Insulated SwitchgearWall Standing Solution

All operations behind closed compartment doors

Maintenance and service operations performed from the front

Front access to all the compartments (apparatus, busbars, cables)

Comfortable front cables access

Back to Content

Page 10: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 10

Air Insulated SwitchgearPanel Dimension

Width (mm) 325

Height (mm) 2200 2400 2595

LV Box Height (mm) 665 865 1060

Height with Gas Duct (mm) 2530 / 2680

Back to Content

Page 11: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 11

Air Insulated SwitchgearCable Entry

Back to Content

Page 12: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 12

Air Insulated SwitchgearDesigned for Flexible Applications

Direct coupling with UniGear platform

Vacuum contactor technology

Two fuses in parallel for each phase for high load current ≥ 400A

Withdrawable truck

Back to Content

Page 13: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 13

Air Insulated SwitchgearBasic Structure

Compartments:A. Busbar compartment

B. Contactor and HRC fuses compartment

C. Cable compartment

D. Low voltage compartment

Main Components1. Busbars

2. Withdrawable fused contactor’s contacts

3. Vacuum contactor

4. HRC fuses

5. Instruments current transformer

6. Earthing switch

7. Auxiliary voltage transformer

8. Cable connection terminals

Back to Content

Page 14: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 14

Air Insulated SwitchgearContactor and Cable Compartments

Internal view detailing:

1. Metal shutter – Bus

2. Metal shutter – Circuit

3. Fixed auxiliary control connection

4. Earth switch operating slot

5. Power cables connections

6. Earth switch

1

2

4

5

3

6

Back to Content

Page 15: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 15

Air Insulated SwitchgearThe Heart of the Switchgear

Busbar Moulding Contactor Moulding BS Fuses Metallic Shutters Current Transformers Auxiliary control connection Voltage Transformer Contactor Chassis Earth Switch Cable connection Moulding Front Plate

Back to Content

Page 16: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 16

Air Insulated SwitchgearContactor

Rear ViewRear View

Upper line side disconnect contacts

Lower load side disconnect contacts

Moving auxiliarycontrol connection

Front ViewFront View

Rating plate

Mechanical Position Indicator

Truck Interlock

Contactor ON/OFF Indicator

Truck Racking Point

LeftLeft Side View.Side View.RightRight Side ViewSide View

Power fuses

Control VT fuses

Vacuum interrupters

Electronic controller

Control VT

Operation Counter

Back to Content

Page 17: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 17

Air Insulated SwitchgearHRC Fuses

Fuse selection. Service voltage 3300V

Fuse Rating (A)Transformers Motors Capacitors

F.L.C. kVA F.L.C. kW F.L.C. kVAR

63 40A 200 45A 200 40A 250

80 50A 250 60A 280 60A 300

100 65A 325 75A 350 75A 400

125 80A 400 90A 425 90A 500

160 100A 500 120A 550 120A 600

200 130A 700 150A 700 150A 800

225 150A 800 165A 750 165A 900

250 165A 900 185A 800 185A 1000

315 210A 1000 225A 1100 225A 1000

350 230A 1250 270A 1300 225A 1000

400 (2x225) 260A 1400 - - - -

400 (2x225) 300A 1500 300A 1500 - -

450 (2x250) 360A 2000 335A 1650 - -

550 (2x315) 400A 2200 400A 2000 - -

Back to Content

Page 18: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 18

Air Insulated SwitchgearHRC Fuses

Fuse selection. Service voltage 6600V

Fuse Rating (A)Transformers Motors Capacitors

F.L.C. kVA F.L.C. kW F.L.C. kVAR

63 40A 400 45A 400 40A 500

80 50A 500 60A 550 60A 600

100 65A 750 75A 710 75A 800

125 80A 800 90A 850 90A 1000

160 100A 1000 120A 1100 120A 1200

200 130A 1250 150A 1400 150A 1600

225 150A 1600 165A 1500 165A 1800

250 165A 1750 185A 1750 185A 2000

315 210A 2000 225A 2100 225A 2000

400 (2x225) 260A 2750 - - - -

400 (2x225) 300A 3050 300A 3000 - -

450 (2x250) 360A 4000 335A 3300 - -

550 (2x315) 400A 4400 400A 4000 - -

Back to Content

Page 19: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 19

Air Insulated SwitchgearHRC Fuses

Fuse Options for ZVC

ManufacturerOrder

Code/Part No.

SizeRated

Voltage (kV)

Current Range (A)

Maximum Breaking Current

(kA)

SIBA 30 269 56 TA2 3.6 50…315 50

SIBA 30 271 56 TA4 7.2 50…315 50

GEC ALSTHOM K81PEX TA2 3.6 100…350 40

GEC ALSTHOM K81SDX TA4 7.2 50…315 45

Cooper Bussman 3.6WDFHO TA2 3.6 50…125 50

Cooper Bussman 3.6WFFHO TA2 3.6 160…200 50

Cooper Bussman 3.6WKFHO TA2 3.6 250…400 50

Cooper Bussman 7.2WFNHO TA4 7.2 25…315 40

Cooper Bussman 7.2MROSA TA4 7.2 50…315 50

XiRong WFNDF TA2 3.6 50…400 50

XiRong WFNDF TA4 7.2 25…315 50

Back to Content

Page 20: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 20

Air Insulated SwitchgearEarth Switch

With full making capacity

Short time withstand current for 3 seconds

Operated from the front

Provided with secure position indicators

Visible identification of Earth Switch Position

Visible through window in front door

Back to Content

Page 21: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 21

Air Insulated SwitchgearControl Power Transformer

2 pole Power Transformer, withdrawable HV fused

Control PT

Back to Content

Page 22: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 22

Air Insulated SwitchgearInstrument Transformers

Ring type Current Transformers

Multi ratio 2-core resin encapsulated toroids. Three versions cover the full range: 400-300-200/1/1A 150-100-75/1/1A 50/1/1A

Back to Content

Page 23: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 23

Air Insulated SwitchgearCompulsory Tools

Contactor Transport Trolley

Handles and Key

Back to Content

Page 24: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 24

Air Insulated SwitchgearUniGear Platform

UniGear ZVC can be directly coupled to:

UniGear ZS1

UniGear 550

UniGear 500R

UniGear ZVC standard design utilises REM 615, but can easily integrate IEDs:

REF542 plus

REF5xx series

REM5xx series

RET5xx series

Others including 3rd party manufacture

Back to Content

Page 25: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 25

Air Insulated Switchgear Product Value

How can a product add value?

1. By reducing the total cost

2. Or by increasing revenues

UniGear ZVC adds value by:

1. Occupying minimum floor space

2. Reduced size of motor cables

3. Higher performance and availability

Back to Content

Page 26: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 26

Air Insulated SwitchgearComparisons

Comparison of performance

Evaluating UniGear ZVC Fused Vacuum Contactor technology to conventional Circuit Breaker technology for switching applications:

Back to Content

UniGear ZVC

Fault current limited due to HRC fuses.

Fault clearing time is typically <5ms at full fault current.

Reduced let through energy allows reduced cable size.

Reduced thermal stresses on motor and rapid fault clearing time minimise damage.

Up to 1,000,000 op. provides extended service life.

Small footprint totalling 0.42 sq m.

Circuit Breaker

No fault current limiting capability.

CB fault break at first natural current zero 200ms.

Cable needs to be sized to maximum system short circuit level.

Thermal stresses consistent with system short circuit level and clearing time result in severe damage.

Up to 30,000 operations service life.

Average footprint 1.05 sq m.

Page 27: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 27

Air Insulated SwitchgearComparisons

Back to Content

TYPICAL CABLE COST COMPARISON

Motor FLC (A)

31.5kA 50kAFused Contactor Panel Circuit Breaker Panel Fused Contactor Panel Circuit Breaker PanelCable

csa sq mmCable Cost

100mCable

csa sq mmCable Cost [1]

100mCable

csa sq mmCable Cost

100mCable

csa sq mmCable Cost [1]

100m45 35 €1,600 185 €4,800 35 €1,600 300 €7,50060 35 €1,600 185 €4,800 50 €2,000 300 €7,50075 35 €1,600 185 €4,800 50 €2,000 300 €7,50090 50 €2,000 185 €4,800 50 €2,000 300 €7,500

120 50 €2,000 185 €4,800 70 €2,900 300 €7,500150 50 €2,000 185 €4,800 70 €2,900 300 €7,500165 50 €2,000 185 €4,800 70 €2,900 300 €7,500185 50 €2,000 185 €4,800 70 €2,900 300 €7,500225 70 €3,800 185 €4,800 95 €3,800 300 €7,500

[1] Cable cost in yr. 2008.

TYPICAL FLOOR SPACE COMPARISON

Panel Width (mm) Panel Depth (mm) Area (sq m) Construction cost325 1300 0.42 €1,268

400 1300 0.52 €1,560

500 1300 0.65 €1,950

600 1300 0.78 €2,340

700 1300 0.91 €2,730

800 1300 1.04 €3,120

900 1300 1.17 €3,510

1000 1300 1.30 €3,900

1200 1300 1.56 €4,680

Page 28: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 28

Air Insulated SwitchgearProject Savings

Back to Content

Typical FPSO Switchboard 6.6kV, 3150A, 40kA comprising:

- 2 off Incomer panel

- 1 off Bus Riser panel

- 1 off Bus Section (Tie) panel

- 1 off Bus Metering panel

- 15 off Transformer Feeder panel

- 15 off Motor Feeder panel

Page 29: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 29

Air Insulated SwitchgearProject Savings

Back to Content

ENGINEERING DESIGN ELEMENTS

MCC Switchboard Floor Area Cable[1] Heat Loss[2] Weight Clear FaultCircuit breaker solution 32 m2 300 mm2 5.1 kW 29 tonnes 60 msCompact UniGear ZVC solution

19 m2 95 mm2 4.8 kW17 tonnes 20 ms

OVERALL PROJECT COST COMPARISON

MCC SwitchboardCost

Floor Area[3] Cable[4] Heat Loss Weight Clear FaultCircuit breaker solution € 96,000 € 225,000 5.1 kWh 29 tonnes 60 msCompact UniGear ZVC solution

€ 57,000 € 114,0004.8 kWh 17 tonnes 20 ms

Difference (Δ) with UniGear ZVC

Less 41 % Less 50 %Less 6 % Less 70 % Good 300 %

Savings in plant purchasing cost

€ 39,000 € 52,500 Varies[5] Significant[7] Negligible[8]

Savings in plant running cost - - Varies[6] - -Savings in plant spare part - - - - Significant[9]

[1] Power cables based on differences of motor and transformer feeder. Same power cable for Incomer.[2] Heat loss based on motor load 1000 kW and transformer 1000 kVA. [3] Floor space construction cost based on € 3000 /m2 (average for E-Houses – yr. 2008)[4] Cable cost based on average length 100 m each.[5] Depends on air conditioning system to cool switchgear heat loss generated.[6] Depends on energy and greenhouse cost, plant specific.[7] Depends on installations, i.e. on or off-shore, seismic (earthquake), vibration, wind loads, remoteness, etc[8] Similar manufacturing cost for fused contactor and circuit breaker technology.[9] Depends on operation and fault severity. Worst case – equipment replacement may be necessary.

Page 30: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 30

Air Insulated SwitchgearThe SLD of Typical Motor Starting Options

Key to components : Contactor with electrical

latching

Contactor with mechanical latching

Two-poles voltage transformer forsupplying the control circuit

Direct-on-line

1

2

3

A

Back to Content

Page 31: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 31

Air Insulated Switchgear Typical configuration of UniGear ZVC panels

Large number of motor starters

Large number of transformer feeders

IF IF

IF BT R IF

IF IF IFIF IF IF IF IF

Back to Content

Page 32: ABB Australia Pty Ltd 1VGA671004 – Rev. D August 7, 2015 | Slide 1 UniGear ZVC Standard Product January 2010.

© ABB Group April 19, 2023 | Slide 32

Air Insulated SwitchgearEnquiries?

Please send all enquiries to:

ZVC Team

ABB Australia Pty Limited

Bapaume Road

Moorebank NSW 2170

Australia

Ph:  + 612 9821 0111

Fax: + 612 9602 2454

Email: [email protected]

Product library:

Internal link

External link

Back to Content