AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W....
Transcript of AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W....
Layer 3:
90% Argon*
1/4"
0.50"
Gap 1:
Reference must be made to Report No. E6658.02-116-46, dated 08/20/15 for complete test
specimen description and data.
Condensation Resistance Factor - Frame (CRFf)
78-3/4" x 78-3/4"
1/4" PPG Solarban 60 (e=0.035*, #4)
Gap 2:
PPG Solarban 70XL (e=0.018*, #2)
Layer 2:
0.50" 90% Argon*
0.22
84
79
TS-D: Technoform TGI Wave Spacer
TS-D: Technoform TGI Wave Spacer
1/4"
Unit Size:
AAMA 1503-09 THERMAL PERFORMANCE
TEST REPORT
Rendered to:
TUBELITE, INC.
Layer 1:
SERIES/MODEL: 400TU Ultra Thermal Curtain Wall (Fiberglass Pressure Plates) -
Triple Glazed
TYPE: Glazed Wall Systems (Site-built)
Clear
Summary of Results
Condensation Resistance Factor - Glass (CRFg)
Thermal Transmittance (U-Factor)
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Report Number:
Test Date:
Report Date:
Test Sample Submitted by:
F
F
1.
2.
1. Average warm side ambient temperature
-0.40
Client
06/11/15
TU400 Ultra Thermal Curtain Wall (Fiberglass Pressure Plates) -
Triple Glazed
70.05
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT
79
Thermal transmittance due to conduction (U)
Condensation resistance factor - Frame (CRFf) 84
3. 15 mph dynamic wind applied to test specimen exterior.
0.22
Rendered to:
(U-factors expressed in Btu/hr·ft2·F)
Test Sample Identification:
Test Results Summary:
Condensation resistance factor - Glass (CRFg)
4. 0.0" +0.04" static pressure drop across specimen.
Glazed Wall Systems (Site-built)
2. Average cold side ambient temperature
Reed City, Michigan 49677
TUBELITE, INC.
4878 Mackinaw Trail
Test Procedure: The condensation resistance factor (CRF) and thermal transmittance (U) were
determined in accordance with AAMA 1503-09, Voluntary Test Method for Thermal
Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections
Type:
Series/Model:
08/20/15
E6658.02-116-46
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Test Sample Description:
*Stated per Client/Manufacturer
N/A Non-Applicable
Exterior*
*Exterior pressure plate screwed 4" O.C.
Size:
Page 2 of 9
78-3/4" x 78-3/4"
E6658.02-116-46
35-3/4" x 73-3/4" (x2) Glazing Method:Daylight Opening:
Material: AT (1.47"): Aluminum with Thermal Breaks - All Members
Frame:
Anodized
Clear Interior Finish: AnodizedInterior Color:
Corner Joinery: Square Cut / Screws / Sealed
Exterior Color: Clear Exterior Finish:
Glazing Information:
Layer 1: 1/4" PPG Solarban 70XL (e=0.018*, #2)
Desiccant: Yes
Clear
TS-D: Technoform TGI Wave SpacerGap 2:
PPG Solarban 60 (e=0.035*, #4)
90% Argon*0.50"
Gas Fill Method: Single-Probe Method*
1/4"
90% Argon*
Layer 3:
TS-D: Technoform TGI Wave Spacer0.50"
Layer 2: 1/4"
Gap 1:
Test Sample Description: (Continued)
Weatherstripping:
Hardware:
Drainage:
Aluminum face cover 7
Diameter weephole
Location
6(1.00" x 1.75") Wood block
7Four exterior horizontals, three exterior
verticalsFiberglass pressure plate
Two per head and sill, one per jamb
Quantity
0.31"
Four exterior horizontals, three exterior
verticals
One per horizontal face cover4
Size
Description
QuantityDrainage Method
Description Quantity
EPDM gasket
Location
E6658.02-116-46
Page 3 of 9
Interior and exterior glazing perimeter
Location
1 row
Test Duration:
1.
2.
Condensation Resistance Factor (CRF):
= F
= F
= F
= F
=
= F
= F
=
=
Condensation resistance factor – Glass
Condensation resistance factor – Frame
CRFf = (FT - Tc) / (Th - Tc) x 100
70.05
CRFf
55.57
-0.40
FTp(1-W) + W (FTr) = Frame Temperature
FTp
0.068
Average of roving thermocouples (4)
84
[(FTp - FTr) / (FTp - (Tc + 10))] x 0.40
Average of pre-specified frame temperatures (14)
FT
59.35
CRFg
50.95
Glass Temperature
CRFg = (GT - Tc) / (Th - Tc) x 100
W
58.78
79
GT
Cold side ambient air temperature
FTr
Page 4 of 9
E6658.02-116-46
Th Warm side ambient air temperature
The thermal performance test results were derived from 02:10 hours, 06/11/15 to 06:10
hours, 06/11/15.
The environmental systems were started at 17:25 hours, 06/10/15.
Tc
The following information, condensed from the test data, was used to determine the
condensation resistance factor:
The CRF number was determined to be 79 (on the size as reported). When reviewing this
test data, it should be noted that the glass temperature (GT) was colder than the frame
temperature (FT) therefore controlling the CRF number. Refer to the 'CRF Report' page
and the 'Thermocouple Location Diagram' page of this report.
Th = Average warm side ambient temperature F
Tc = Average cold side ambient temperature F
P = Static pressure difference across test specimen psf
15 mph dynamic perpendicular wind at exterior
Nominal sample area ft2
Total measured input to calorimeter Btu/hr
Calorimeter correction Btu/hr
Net specimen heat loss Btu/hr
U = Thermal Transmittance
Left Glazing
Ext. / Int.
Estimated center gap width upon receipt of
specimen in laboratory (after stabilization)
Glazing Deflection:
735.67
Prior to testing the specimen was sealed with silicone on the interior side and checked for air
infiltration per Section 9.3.4.
The sample was inspected for the formation of frost or condensation, which may influence the
surface temperature measurements. The sample showed no evidence of condensation/frost at
the conclusion of the test.
0.44" / 0.47"
Center gap width at test conditions
Btu/hr·ft2·F
43.07
669.07
70.05
0.22
Right Glazing
Ext. / Int.
0.50" / 0.50"
0.41" / 0.50"
0.44" / 0.47"
0.50" / 0.50"
0.38" / 0.47"
0.50" / 0.50"
Required annual calibrations for the Architectural Testing Inc. 'thermal test chamber' (ICN
000001) in York, Pennsylvania were last conducted in May 2015 in accordance with
Architectural Testing Inc. calibration procedure. A CTS Calibration verification was performed
December 2014. A Metering Box Wall Transducer and Surround Panel Flanking Loss
Characterization was performed May 2015.
Edge Gap Width
Center gap width at laboratory ambient
conditions on day of testing
Thermal Transmittance (Uc):
E6658.02-116-46
0.50" / 0.50"
Page 5 of 9
66.59
-0.40
0.00
Time: 04:10 04:40 05:10 05:40 06:10 AVERAGE
Pre-specified Thermocouples - Frame
55.83
63.75
62.36
56.98
CRF Report
52.09
52.64
47.40
55.56
55.42
55.61
47.4047.40 47.40
63.76
64.24
55.56 55.57
52.10
50.95 50.95
52.10
52.64
Warm Side - Room Ambient Air Temperature
55.43
62.33
45.53
61.63
50.30
60.30
55.57
Cold Point (Roving) Thermocouples
54.19
60.33
62.32
52.05
54.72
59.36
45.53 45.52
62.3262.32
45.53
62.32
57.7357.74
62.32
45.51 45.47
57.74
59.35
Pre-specified Thermocouples - Glass
59.34
57.72
59.35
57.7357.74
59.36FTP
54.73
64.22
52.08
62.59
62.38
54.73
60.33
60.32
60.32
62.58
62.81
61.62
62.82 62.84
52.08
54.76
60.34
60.34
52.09
61.62
54.22
52.62 52.60
54.2154.23
63.3163.33
52.64 52.63
55.43
63.31 63.3463.31 63.28
50.30
55.43 55.43
47.40
55.57
55.43
55.58
47.40
50.30
54.00
50.30
54.00
50.30
52.10
54.00
50.30
52.10
50.95
54.00 54.00
50.95
70.04
0.070.070.07
58.79 58.78
0.07
58.78
52.10
0.07
50.95
0.07
58.79
50.95
70.07 70.05
-0.40 -0.47
CRFf
-0.41
69.98
-0.33
84
70.04
79 79
84
70.04
-0.40 -0.40
Cold Side - Room Ambient Air Temperature
84
79 79 80 79
8484
16
13
18
CRFg
E6658.02-116-46
Page 6 of 9
23
24
FTR
84
55.60
55.84
55.60
55.83
22
19
7
8
21
59.35
62.81
2
4
11
14
61.62
60.29
62.80
55.60
6
62.59 62.58
63.76
62.79
12
60.33
60.3310
9 60.29
62.59
64.20 64.22
63.72
62.34
61.64
64.22
5
3
54.71
64.21
63.7563.75
62.34 62.37
61.63
62.35
52.08
60.30
54.73
54.2054.20
W
20
GT
FT
54.00
52.10
58.78 58.78
55.84
56.98
55.59 55.60
62.56
15
17
56.9856.97 56.99
55.83
56.97
55.83
1
50.30
DRAG HERE,
E6658.02-116-46
47.40
Thermocouple Location Diagram
Cold Point Locations
23.
24.
52.10
SELECT DRAWING,
AND IDENTIFY COLD POINTS
22.
21.
54.00
Page 7 of 9
21
23
24
22
22
23
24
21
For ARCHITECTURAL TESTING, INC.
Ryan P. Moser Shon W. Einsig
Senior Technician Senior Technician
Individual-In-Responsible-Charge
RPM:klb
E6658.02-116-46
Attachments (pages): This report is complete only when all attachments listed are included.
Architectural Testing, Inc. is accredited by the International Accreditation Service (IAS) under the
specific test methods listed under lab code TL-144, in accordance with the recognized
International Standard ISO/IEC 17025:2005. The laboratory’s accreditation or test report in no
way constitutes or implies product certification, approval, or endorsement by IAS.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
specimen tested. This report may not be reproduced, except in full, without the written
approval of Architectural Testing, Inc.
Page 8 of 9
Architectural Testing, Inc. will service this report for the entire test record retention period. Test
records that are retained such as detailed drawings, datasheets, representative samples of test
specimens, or other pertinent project documentation will be retained by Architectural Testing,
Inc. for the entire test record retention period. The test record retention end date for this report
is June 11, 2019.
Appendix-A:
E6658.02-116-46
Drawings (11)
Original Report Issue. Work requested by
Greg Hall of Tubelite, Inc.
Revision(s)
All.02R0
Rev. #
Page 9 of 9
08/20/15
Revision Log
Date
Page(s)
E6658.02-116-46
This report produced from controlled document template ATI 00025(c), revised 03/14/2013.
Appendix A: Drawings
E6658.02-116-46