AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W....

22
Layer 3: 90% Argon* 1/4" 0.50" Gap 1: Reference must be made to Report No. E6658.02-116-46, dated 08/20/15 for complete test specimen description and data. Condensation Resistance Factor - Frame (CRF f ) 78-3/4" x 78-3/4" 1/4" PPG Solarban 60 (e=0.035*, #4) Gap 2: PPG Solarban 70XL (e=0.018*, #2) Layer 2: 0.50" 90% Argon* 0.22 84 79 TS-D: Technoform TGI Wave Spacer TS-D: Technoform TGI Wave Spacer 1/4" Unit Size: AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. Layer 1: SERIES/MODEL: 400TU Ultra Thermal Curtain Wall (Fiberglass Pressure Plates) - Triple Glazed TYPE: Glazed Wall Systems (Site-built) Clear Summary of Results Condensation Resistance Factor - Glass (CRF g ) Thermal Transmittance (U-Factor) 130 Derry Court York, PA 17406 p. 717.764.7700 f. 717.764.4129 www.archtest.com www.intertek.com/building

Transcript of AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W....

Page 1: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Layer 3:

90% Argon*

1/4"

0.50"

Gap 1:

Reference must be made to Report No. E6658.02-116-46, dated 08/20/15 for complete test

specimen description and data.

Condensation Resistance Factor - Frame (CRFf)

78-3/4" x 78-3/4"

1/4" PPG Solarban 60 (e=0.035*, #4)

Gap 2:

PPG Solarban 70XL (e=0.018*, #2)

Layer 2:

0.50" 90% Argon*

0.22

84

79

TS-D: Technoform TGI Wave Spacer

TS-D: Technoform TGI Wave Spacer

1/4"

Unit Size:

AAMA 1503-09 THERMAL PERFORMANCE

TEST REPORT

Rendered to:

TUBELITE, INC.

Layer 1:

SERIES/MODEL: 400TU Ultra Thermal Curtain Wall (Fiberglass Pressure Plates) -

Triple Glazed

TYPE: Glazed Wall Systems (Site-built)

Clear

Summary of Results

Condensation Resistance Factor - Glass (CRFg)

Thermal Transmittance (U-Factor)

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 2: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Report Number:

Test Date:

Report Date:

Test Sample Submitted by:

F

F

1.

2.

1. Average warm side ambient temperature

-0.40

Client

06/11/15

TU400 Ultra Thermal Curtain Wall (Fiberglass Pressure Plates) -

Triple Glazed

70.05

AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT

79

Thermal transmittance due to conduction (U)

Condensation resistance factor - Frame (CRFf) 84

3. 15 mph dynamic wind applied to test specimen exterior.

0.22

Rendered to:

(U-factors expressed in Btu/hr·ft2·F)

Test Sample Identification:

Test Results Summary:

Condensation resistance factor - Glass (CRFg)

4. 0.0" +0.04" static pressure drop across specimen.

Glazed Wall Systems (Site-built)

2. Average cold side ambient temperature

Reed City, Michigan 49677

TUBELITE, INC.

4878 Mackinaw Trail

Test Procedure: The condensation resistance factor (CRF) and thermal transmittance (U) were

determined in accordance with AAMA 1503-09, Voluntary Test Method for Thermal

Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections

Type:

Series/Model:

08/20/15

E6658.02-116-46

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 3: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Test Sample Description:

*Stated per Client/Manufacturer

N/A Non-Applicable

Exterior*

*Exterior pressure plate screwed 4" O.C.

Size:

Page 2 of 9

78-3/4" x 78-3/4"

E6658.02-116-46

35-3/4" x 73-3/4" (x2) Glazing Method:Daylight Opening:

Material: AT (1.47"): Aluminum with Thermal Breaks - All Members 

Frame:

Anodized

Clear Interior Finish: AnodizedInterior Color:

Corner Joinery: Square Cut / Screws / Sealed

Exterior Color: Clear Exterior Finish:

Glazing Information:

Layer 1: 1/4" PPG Solarban 70XL (e=0.018*, #2)

Desiccant: Yes

Clear

TS-D: Technoform TGI Wave SpacerGap 2:

PPG Solarban 60 (e=0.035*, #4)

90% Argon*0.50"

Gas Fill Method: Single-Probe Method*

1/4"

90% Argon*

Layer 3:

TS-D: Technoform TGI Wave Spacer0.50"

Layer 2: 1/4"

Gap 1:

Page 4: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Test Sample Description: (Continued)

Weatherstripping:

Hardware:

Drainage:

Aluminum face cover 7

Diameter weephole

Location

6(1.00" x 1.75") Wood block

7Four exterior horizontals, three exterior

verticalsFiberglass pressure plate

Two per head and sill, one per jamb

Quantity

0.31"

Four exterior horizontals, three exterior

verticals

One per horizontal face cover4

Size

Description

QuantityDrainage Method

Description Quantity

EPDM gasket

Location

E6658.02-116-46

Page 3 of 9

Interior and exterior glazing perimeter

Location

1 row

Page 5: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Test Duration:

1.

2.

Condensation Resistance Factor (CRF):

= F

= F

= F

= F

=

= F

= F

=

=

Condensation resistance factor – Glass

Condensation resistance factor – Frame

CRFf = (FT - Tc) / (Th - Tc) x 100

70.05

CRFf

55.57

-0.40

FTp(1-W) + W (FTr) = Frame Temperature

FTp

0.068

Average of roving thermocouples (4)

84

[(FTp - FTr) / (FTp - (Tc + 10))] x 0.40

Average of pre-specified frame temperatures (14)

FT

59.35

CRFg

50.95

Glass Temperature

CRFg = (GT - Tc) / (Th - Tc) x 100

W

58.78

79

GT

Cold side ambient air temperature

FTr

Page 4 of 9

E6658.02-116-46

Th Warm side ambient air temperature

The thermal performance test results were derived from 02:10 hours, 06/11/15 to 06:10

hours, 06/11/15.

The environmental systems were started at 17:25 hours, 06/10/15.

Tc

The following information, condensed from the test data, was used to determine the

condensation resistance factor:

The CRF number was determined to be 79 (on the size as reported). When reviewing this

test data, it should be noted that the glass temperature (GT) was colder than the frame

temperature (FT) therefore controlling the CRF number. Refer to the 'CRF Report' page

and the 'Thermocouple Location Diagram' page of this report.

Page 6: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Th = Average warm side ambient temperature F

Tc = Average cold side ambient temperature F

P = Static pressure difference across test specimen psf

15 mph dynamic perpendicular wind at exterior

Nominal sample area ft2

Total measured input to calorimeter Btu/hr

Calorimeter correction Btu/hr

Net specimen heat loss Btu/hr

U = Thermal Transmittance

Left Glazing

Ext. / Int.

Estimated center gap width upon receipt of

specimen in laboratory (after stabilization)

Glazing Deflection:

735.67

Prior to testing the specimen was sealed with silicone on the interior side and checked for air

infiltration per Section 9.3.4.

The sample was inspected for the formation of frost or condensation, which may influence the

surface temperature measurements. The sample showed no evidence of condensation/frost at

the conclusion of the test.

0.44" / 0.47"

Center gap width at test conditions

Btu/hr·ft2·F

43.07

669.07

70.05

0.22

Right Glazing

Ext. / Int.

0.50" / 0.50"

0.41" / 0.50"

0.44" / 0.47"

0.50" / 0.50"

0.38" / 0.47"

0.50" / 0.50"

Required annual calibrations for the Architectural Testing Inc. 'thermal test chamber' (ICN

000001) in York, Pennsylvania were last conducted in May 2015 in accordance with

Architectural Testing Inc. calibration procedure. A CTS Calibration verification was performed

December 2014. A Metering Box Wall Transducer and Surround Panel Flanking Loss

Characterization was performed May 2015.

Edge Gap Width

Center gap width at laboratory ambient

conditions on day of testing

Thermal Transmittance (Uc):

E6658.02-116-46

0.50" / 0.50"

Page 5 of 9

66.59

-0.40

0.00

Page 7: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Time: 04:10 04:40 05:10 05:40 06:10 AVERAGE

Pre-specified Thermocouples - Frame

55.83

63.75

62.36

56.98

CRF Report

52.09

52.64

47.40

55.56

55.42

55.61

47.4047.40 47.40

63.76

64.24

55.56 55.57

52.10

50.95 50.95

52.10

52.64

Warm Side - Room Ambient Air Temperature

55.43

62.33

45.53

61.63

50.30

60.30

55.57

Cold Point (Roving) Thermocouples

54.19

60.33

62.32

52.05

54.72

59.36

45.53 45.52

62.3262.32

45.53

62.32

57.7357.74

62.32

45.51 45.47

57.74

59.35

Pre-specified Thermocouples - Glass

59.34

57.72

59.35

57.7357.74

59.36FTP

54.73

64.22

52.08

62.59

62.38

54.73

60.33

60.32

60.32

62.58

62.81

61.62

62.82 62.84

52.08

54.76

60.34

60.34

52.09

61.62

54.22

52.62 52.60

54.2154.23

63.3163.33

52.64 52.63

55.43

63.31 63.3463.31 63.28

50.30

55.43 55.43

47.40

55.57

55.43

55.58

47.40

50.30

54.00

50.30

54.00

50.30

52.10

54.00

50.30

52.10

50.95

54.00 54.00

50.95

70.04

0.070.070.07

58.79 58.78

0.07

58.78

52.10

0.07

50.95

0.07

58.79

50.95

70.07 70.05

-0.40 -0.47

CRFf

-0.41

69.98

-0.33

84

70.04

79 79

84

70.04

-0.40 -0.40

Cold Side - Room Ambient Air Temperature

84

79 79 80 79

8484

16

13

18

CRFg

E6658.02-116-46

Page 6 of 9

23

24

FTR

84

55.60

55.84

55.60

55.83

22

19

7

8

21

59.35

62.81

2

4

11

14

61.62

60.29

62.80

55.60

6

62.59 62.58

63.76

62.79

12

60.33

60.3310

9 60.29

62.59

64.20 64.22

63.72

62.34

61.64

64.22

5

3

54.71

64.21

63.7563.75

62.34 62.37

61.63

62.35

52.08

60.30

54.73

54.2054.20

W

20

GT

FT

54.00

52.10

58.78 58.78

55.84

56.98

55.59 55.60

62.56

15

17

56.9856.97 56.99

55.83

56.97

55.83

1

Page 8: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

50.30

DRAG HERE,

E6658.02-116-46

47.40

Thermocouple Location Diagram

Cold Point Locations

23.

24.

52.10

SELECT DRAWING,

AND IDENTIFY COLD POINTS

22.

21.

54.00

Page 7 of 9

21

23

24

22

22

23

24

21

Page 9: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

For ARCHITECTURAL TESTING, INC.

Ryan P. Moser Shon W. Einsig

Senior Technician Senior Technician

Individual-In-Responsible-Charge

RPM:klb

E6658.02-116-46

Attachments (pages): This report is complete only when all attachments listed are included.

Architectural Testing, Inc. is accredited by the International Accreditation Service (IAS) under the

specific test methods listed under lab code TL-144, in accordance with the recognized

International Standard ISO/IEC 17025:2005. The laboratory’s accreditation or test report in no

way constitutes or implies product certification, approval, or endorsement by IAS.

This report does not constitute certification of this product nor an opinion or endorsement by

this laboratory. It is the exclusive property of the client so named herein and relates only to the

specimen tested. This report may not be reproduced, except in full, without the written

approval of Architectural Testing, Inc.

Page 8 of 9

Architectural Testing, Inc. will service this report for the entire test record retention period. Test

records that are retained such as detailed drawings, datasheets, representative samples of test

specimens, or other pertinent project documentation will be retained by Architectural Testing,

Inc. for the entire test record retention period. The test record retention end date for this report

is June 11, 2019.

Appendix-A:

E6658.02-116-46

Drawings (11)

Page 10: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Original Report Issue. Work requested by

Greg Hall of Tubelite, Inc.

Revision(s)

All.02R0

Rev. #

Page 9 of 9

08/20/15

Revision Log

Date

Page(s)

E6658.02-116-46

This report produced from controlled document template ATI 00025(c), revised 03/14/2013.

Page 11: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or

Appendix A: Drawings

E6658.02-116-46

Page 12: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
rmoser
New Stamp
Page 13: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
rmoser
New Stamp
Page 14: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Painted or Anodized Aluminum
agoodyear
Rejected
agoodyear
Rejected
agoodyear
Rejected
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
agoodyear
Rejected
Page 15: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Painted or Anodized Aluminum
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 16: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Painted or Anodized Aluminum
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 17: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Painted or Anodized Aluminum
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 18: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Fiberglass
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 19: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Polyamide
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 20: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: Painted or Anodized Aluminum
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 21: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Text Box
Material: EPDM
rmoser
New Stamp
rmoser
Oval
rmoser
Oval
rmoser
Oval
Page 22: AAMA 1503-09 THERMAL PERFORMANCE - … 21. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Shon W. Einsig Senior Technician Senior Technician Individual-In-Responsible-Charge. ... or
agoodyear
Rectangle
agoodyear
Line
agoodyear
Line
rmoser
New Stamp