KRIWAN Industrie-Elektronik GmbH · Allmand 11 · D-74670 Forchtenberg · phone ++49-7947-822-0 · fax ++49-7947-1288 · e-mail: [email protected] · home: www.kriwan.com Technical changes reserved Product group A Edition: 710.00071.1 INT69 VSY-II ® Protection module INT69 VSY-II ® Function table INT69 VSY-II Wiring diagram Dimensions in mm Temperature Phase sequenz Contact D1 Alarm Status < Trip value / Inactiv Good Phase sequenz is not elevated > Trip value / Inactiv Fault Trip due to PTC- fault, phase sequenz is not elevated < Trip value Clockwise or inactiv Activ Good Normal condition > Trip value Clockwise or inactiv Activ Fault Trip due to PTC- fault < Trip value Anti-clockwise Activ Fault Trip due to phase sequenz > Trip value Anti-clockwise Activ Fault Trip due to PTC- fault and phase sequenz L INT69 VSY-II Supply Run signal BK BN BU OG OG N D1 12 14 11 L1 L2 L3 PTC 40 4.5 6 58 3.5 87 2.5 72 250 +15 Application The KRIWAN INT69 VSY-II protection module complements the convential temperature monitoring function of the well-known switching device INT69 VS with phase sequence monitoring (Y) for screw and scroll compressors. Functional description If the response temperature of any of the connected thermistors is exceeded, the module trips and locks out. The phase sequence monitor on the three-phase supply is active when the supply voltage is also present on terminal D1 (typically via contactor auxiliary contact). An anticlockwise phase sequence also results in a trip and lockout. The D1 input allows the user to suppress reverse rotation tripping due to pres- sure equalisation after shutdown on screw compressors. The lockout can be cancelled by interrupting mains supply for approx. 5 seconds. Technical specifications Order data The mounting, maintenance and operation are to be carried out by an electrician. The valid European and national standards for connecting electrical equipment and cooling installations have to be observed. Connected sensors and connection lines that extend from the terminal box have to feature at least a basic insu- lation. No galvanic isolation between sensor and supply circuits for direct current units. Supply voltage or or or AC 115V 50/60Hz ±10% 3VA AC 230V 50/60Hz ±10% 3VA AC 24V 50/60Hz -15...+10% 3VA DC 24V ±20% 1W Permitted ambient temperature -20...+60°C Temperature measuring circuits - Type - R25,total - Rtrip, static - Rreset 1-9 PTC acc. to DIN 44081/082 in series <1,8kΩ >11,4kΩ ±20% <2,95kΩ ±20% - Thermistor connection Orange leads, with ferrules length approx. 300mm Phase sequence monitoring - Operating recognition L-potential on terminal D1 - Motor voltage AC 20-80Hz 200-400V Sinus - L1, L2, L3 connection AWG20-leads (BK/BN/BU) length approx. 250mm with 6,3mm flat plug sleeves - Recognition time phase sequence <0,5s Relay AC 240V max.2,5A C300 Mechanical service life Approx. 1 million switching cycles Protection class acc. to EN 60529 With terminal cover: IP20 Without terminal cover: IP00 Housing material PA glass-fibre-reinforced Mounting To snap open to 35mm standard rail as under EN 50022 or screw moun- ting Dimensions [mm] 87x40x58 (LxWxH) Weight Approx. 210g Manufactory setting Jumper between L and D1 INT69 VSY-II 52 A 125 S33 (AC 230V) INT69 VSY-II 41 A 125 S33 (AC 115V) INT69 VSY-II 31 A 125 S33 (AC 24V) INT69 VSY-II 13 A 125 S33 (DC 24V) INT69 VSY-II Phase sequenz monitoring for 10s 13 A 125 S35 (DC 24V)

description

rELAY FOR INVERTER

Transcript of A125S33_INT69 VSY-II_710000071_0-Ebook

Page 1: A125S33_INT69 VSY-II_710000071_0-Ebook

KRIWAN Industrie-Elektronik GmbH · Allmand 11 · D-74670 Forchtenberg · phone ++49-7947-822-0 · fax ++49-7947-1288 · e-mail: [email protected] · home: www.kriwan.com

Technical changes reserved

Pro

duc

t g

roup

AE

ditio

n: 7

10.0

0071

.1

INT69 VSY-II® Protection moduleINT69 VSY-II®

Function table

INT69 VSY-II

Wiring diagram

Dimensions in mm

Temperature Phase sequenz

Contact D1

Alarm Status

< Trip value / Inactiv Good Phase sequenz is not elevated

> Trip value / Inactiv Fault Trip due to PTC-fault, phase

sequenz is not elevated

< Trip value Clockwise or inactiv

Activ Good Normal condition

> Trip value Clockwise or inactiv

Activ Fault Trip due to PTC-fault

< Trip value Anti-clockwise Activ Fault Trip due to phase sequenz

> Trip value Anti-clockwise Activ Fault Trip due to PTC-fault and phase

sequenz

L

INT69 VSY-II

Supp

ly

Run s

ignal BK BN BU OG OG

N D1 12 14 11L1 L2 L3 PTC

404.5 6

583.5

87

2.572

250 +15

ApplicationThe KRIWAN INT69 VSY-II protection module complements theconvential temperature monitoring function of the well-known switchingdevice INT69 VS with phase sequence monitoring (Y) for screw andscroll compressors.

Functional descriptionIf the response temperature of any of the connected thermistors isexceeded, the module trips and locks out. The phase sequencemonitor on the three-phase supply is active when the supply voltage isalso present on terminal D1 (typically via contactor auxiliary contact). Ananticlockwise phase sequence also results in a trip and lockout. The D1input allows the user to suppress reverse rotation tripping due to pres-sure equalisation after shutdown on screw compressors. The lockoutcan be cancelled by interrupting mains supply for approx. 5 seconds.

Technical specifications

Order data

The mounting, maintenance and operation are to be carried outby an electrician. The valid European and national standards forconnecting electrical equipment and cooling installations have tobe observed. Connected sensors and connection lines thatextend from the terminal box have to feature at least a basic insu-lation.

No galvanic isolation between sensor and supply circuits for directcurrent units.

Supply voltageororor

AC 115V 50/60Hz ±10% 3VAAC 230V 50/60Hz ±10% 3VAAC 24V 50/60Hz -15...+10% 3VADC 24V ±20% 1W

Permitted ambient temperature -20...+60°CTemperature measuring circuits- Type

- R25,total

- Rtrip, static

- Rreset

1-9 PTC acc. to DIN 44081/082 in series<1,8kΩ>11,4kΩ ±20%<2,95kΩ ±20%

- Thermistor connection Orange leads, with ferrules length approx. 300mm

Phase sequence monitoring- Operating recognition L-potential on terminal D1- Motor voltage AC 20-80Hz 200-400V Sinus- L1, L2, L3 connection AWG20-leads (BK/BN/BU) length

approx. 250mm with 6,3mm flat plug sleeves

- Recognition time phase sequence <0,5s

Relay AC 240V max.2,5A C300Mechanical service life Approx. 1 million switching cyclesProtection class acc. to EN 60529

With terminal cover: IP20Without terminal cover: IP00

Housing material PA glass-fibre-reinforcedMounting To snap open to 35mm standard rail

as under EN 50022 or screw moun-ting

Dimensions [mm] 87x40x58 (LxWxH)Weight Approx. 210gManufactory setting Jumper between L and D1

INT69 VSY-II 52 A 125 S33 (AC 230V)INT69 VSY-II 41 A 125 S33 (AC 115V)INT69 VSY-II 31 A 125 S33 (AC 24V)INT69 VSY-II 13 A 125 S33 (DC 24V)INT69 VSY-II Phase sequenz monitoring for 10s 13 A 125 S35 (DC 24V)