01
02
0809
11
13
SOUTH
ENTRY
VEST.
01
CORRIDOR
02
CLASSROOM
06
CLASSROOM
07
CLASSROOM
08
CLASSROOM
09
JANITOR
12
NOTE TO CONTRACTOR:
WALL PARTITION DIMENSIONS
ARE FROM CENTER LINE TO
CENTERLINE OF CMU, TYPICAL
AND UNLESS NOTED OTHERWISE.
8" TYP.
138'-6" OVERALL BUILDING DIMENSION
ELECTRICAL
& IDF
ROOM
13
GIRLS
REST
ROOM
11
BOYS
REST
ROOM
10
CLASSROOM
04
COMPUTER
LAB
03
76
'-0
" O
VE
RA
LL
B
UIL
DIN
G D
IM
EN
SIO
N
06
07
05
0403
10
12
CLASSROOM
05
14
SPRINKLER
ROOM
15
136'-8" CENTERLINE OF CMU TO CENTERLINE OF CMU
FD
FD
FD
Roof
access
ladder &
hatch
STORAGE
16
15
A6.0
8
6'-0" 3'-0" 8'-0" 3'-0" 6'-0"
2'-0
"
1'-0
"
12
'-1
"1
6'-8
"
SIM.
A6.0
8
21'-4" M.O.
EQ.EQ.
26'-0"
6'-0" 44'-0" 12'-0" 8'-0" 14'-0" 10'-8"6'-0"10'-0"
5'-4" 6'-2" 2'-6"12'-0" 12'-0" 44'-0" 12'-0" 22'-0"
22'-0" 22'-0"
5'-0"
2'-0" M.O.
3'-8"
6'-0" 6'-0"
6'-0" 6'-0"6'-0"
6'-4" 2'-0" M.O.
2'-0" M.O.
6'-0" 6'-0"
3'-6
"
3'-6
"
6'-4"2'-0" M.O.6'-4" 2'-0" M.O.
6'-4"
Semi-recessed fire
extinguisher cabinet.
Coordinate cabinet
with OFCI Fire
Extinguisher.
Coordinate rough
in of cabinet with
vertical rebar.
Refer to Structural.
Semi-recessed fire
extinguisher cabinet.
Coordinate cabinet
with OFCI Fire
Extinguisher.
Coordinate rough
in of cabinet with
vertical rebar.
Refer to Structural.
BBBB
B
B
B
F.E.C.
F.E.C.
5
A2.0
5
A2.0
A2.0
6
A A A
6'-0" M.O.53'-0" 22'-0" 6'-0" M.O. 6'-0" M.O.22'-0" 21'-8"
44
'-3
" O
UT
ER
F
AC
E T
O O
UT
ER
F
AC
E O
F B
RIC
K V
EN
EE
R
42
'-5
" C
EN
TE
RL
IN
E O
F C
MU
T
O C
EN
TE
RL
IN
E O
F C
MU
31
'-9
" C
EN
TE
RL
IN
E O
F C
MU
T
O C
EN
TE
RL
IN
E O
F C
MU
31
'-9
" O
UT
ER
F
AC
E T
O O
UT
ER
F
AC
E O
F B
RIC
K V
EN
EE
R
AAAA
11'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 11'-0"
112'-0" CENTERLINE OF CMU TO CENTERLINE OF CMU
113'-10" OUTER FACE TO OUTER FACE OF BRICK VENEER
138'-6" OVERALL BUILDING DIMENSION
24'-8"OUTER FACE TO OUTER FACE
OF BRICK VENEER
33
'-1
0"
4'-9
"6
'-6
" M
.O
.
74
'-2
" C
EN
TE
RL
IN
E O
F C
MU
T
O C
EN
TE
RL
IN
E O
F C
MU
3'-4
"M
.O
.
25
'-9
"
Capped,
painted 4'-0"
steel pipe
bollard,
each side.
SIM.
A2.0
6
31
'-9
"1
0'-8
"6
'-8
"2
5'-1
"
7
A4.0
1
A4.0A2.0
7,9
28
'-3
"3
'-6
"
10
'-8
"
Cn
trln
.
to
C
ntrln
.3
1'-9
"
4'x6' Entry
mat. Recess
in slab 7/8".
See Struct.
3'-6
"
NORTH
ENTRY
VEST.
14
6'-4"2'-0"M.O.6'-4" 2'-0"M.O.
3'-6
"
10
'-8
"
SIM.
A2.0
7,8
4
A2.0
NOTE: SEE ELEVATIONS FOR
LOCATIONS OF BRICK MASONRY
CONTROL JOINTS.
EDF
Hi/Lo EDF
2
A2-0
3
A2.0
1
A2.0
FD
FD
(7) downspout &
boots. See Civil.
LOCATION FOR WALL CLOCK.
SEE ELECTRICAL
16
17
1" EXPANSION
JOINT. SEE
STRUCTURAL
CONCRETE BENCH.
SEE STRUCTURAL.
1'-4"
8'-6
"1
0'-7
"
22'-0"
No. 4 Walkerducts,
recessed raceway.
Coordinate with
Electrical and
Structural for floor
slab construction.
16
A6.0
PLANTING AREA
PLANTING AREA
GRASS COVERED PLAY AREA
PLANTING
AREA
SWALE.
SEE
CIVIL
8'-0"
11
A4.0
15
A6.0
REINFORCED CONCRETE RETAINING WALL
WITH FABRICATED GUARD RAIL AT TOP.
REFER TO STRUCTURAL AND CIVIL.
LOW HEIGHT REINFORCED
CONCRETE RETAINING WALL.
SEE STRUCTURAL AND CIVIL.
EX
IS
TIN
G B
UIL
DIN
G
NEW LANDSCAPE TREES PER DIRECTION OF
ARCHITECT (REFER TO PROJECT MANUAL
SPEC SECTION 01 02 00 - ALLOWANCES)
CLASSROOM
1,157 SF
64 OCC. LOAD
64
42
SOUTH VESTIBULE
190 Occupant Load
EGRESS DOOR:
38.0" Required
66.0" Provided
190
126
LIFE SAFETY LEGEND
Path of egress travel and
Occupant Load
Maximum travel distance
42
CODE DATA
Occupancy Type: Educational
Construction Type: IIB
1 Story
BUILDING AREA
1st Floor Area: 8,768 SF
Max. Allowable Area per Floor:
14,500 SF
OCCUPANCY
for Classrooms: 20/net/person
for Non-Educ.Occupied Spaces:
100SF/person
TABLE 1005.1
Egress Components (Doors):
0.15" /occupant
Per SFM and NFPA101 7.3.3.1
Egress capacity of
doors = 0.2/person
Clearance at 36" door = 33"
4242
CLASSROOM
829 SF
42 OCC. LOAD
42
CLASSROOM
829 SF
42 OCC. LOAD
CLASSROOM
829 SF
42 OCC. LOAD
CLASSROOM
829 SF
42 OCC. LOAD
4242
NORTH VESTIBULE
126 Occupant Load
EGRESS DOOR:
25.2" Required
66.0" Provided
CLASSROOM
829 SF
42 OCC. LOAD
CLASSROOM
829 SF
42 OCC. LOAD
EXISTING
CAFETERIA
4015 SF
15 net SF / person
268 Occupant Load
4 Existing Exits
EXISTING
SOUTH EAST
EGRESS DOOR:
67 Occupant Load
EXTERIOR
ENCLOSURE
126 (new bldg)
+ 67 (cafeteria)
193 Occ. Load
63
130
EAST GATE
63 Occupant Load
EGRESS DOOR:
12.6" Required
33.0" Provided
WEST GATE
130 Occupant Load
EGRESS DOOR:
26.0" Required
33.0" Provided
EX
IS
TIN
G B
UIL
DIN
G
CLASSROOM
06
EAST
ENTRY
VEST.
01
CLASSROOM
07
CLASSROOM
08
CLASSROOM
09
JANITOR
12
ELECTRICAL
& IDF ROOM
13
GIRLS
REST
ROOM
11
BOYS
REST
ROOM
10
CLASSROOM
04
COMPUTER
LAB
03
CLASSROOM
05
SPRINKLER
ROOM
15
STOR.
16
Canopy liner panels
with recessed lighting
and exit lights at each
end. All Conduit
installation shall be
concealed from view.
Refer to Electrical.
Canopy liner panels
with recessed lighting.
See Electrical
SEE SHEET E2.1 FOR
EXTERIOR LIGHTING
AND CONTROLS
SUSPENDED MOISTURE
RESISTANT GYPBOARD CEILING
IN GROUP RESTROOMS
Ceiling Mounted
Occupancy
Sensor. See
electrical sheets to
determine whether
Low Voltage or
Line Voltage.
Ceiling mounted
exit sign. See
Electrical.
Ceiling mounted
speaker. See
Electrical.
Ceiling mounted
intercom speaker.
See Electrical.
Provide all power and
communication required
for ceiling mount Security
Cameras. See Electrical.
See Mechanical Sheets
for Unit Heater and mini
split system
5
A2.0
5
A2.0
A2.0
6
SIM.
A2.0
6
2
A4.0A2.0
7,9
SIM.
A2.0
7,812
A4.0
Provide power required
for canopy mount exit
light. See Electrical.
Provide power required for
canopy mount exit light.
See Electrical.
EX
IS
TIN
G B
UIL
DIN
G
46
'-0
" +
/- V
ER
IF
Y
WT-1
EXTERIOR, NON RATED
8" REINFORCED CMU WITH
BRICK VENEER
WT-2A
INTERIOR, NONRATED
8" REINFORCED CMU
WT-2B
INTERIOR, NON FIRE-RATED
8" REINFORCED CMU
SMOKE PARTITION
(IBC Section 710)
WT-2C
INTERIOR, 1 HOUR FIRE RATED
8" REINFORCED CMU
WALL TYPE LEGEND
SEE ELEVATIONS FOR LOCATIONS OF
BRICK VENEER CONTROL JOINTS
Exterior light, recessed in canopy
liner panel. See Electrical.
Recessed Architectural Troffer.
See Electrical Sheets.
Surface mounted light.
See Electrical Sheets.
Supply Diffuser.
See Mechanical Sheets.
Return Air Device.
See Mechanical Sheets.
Unit Heater.
See Mechanical Sheets.
Note to Contractor: The Reflected Ceiling Plan and
Symbol Legend on this Architectural Sheet are not
intended to be used independently of the whole
construction document set. Refer also to the MPE
and FP sheets for complete information.
Sprinkler Head. Semi Recessed.
See FP Sheets.
Sprinkler Head. Upright.
See FP Sheets.
Ceiling mounted occupancy
Sensor. See Electrical Sheets.
Ceiling mounted speaker. See
Sound Schedule on Electrical
Sheets.
Ceiling mounted exit sign. See
Electrical Sheets.
Ceiling mounted Security
Camera. See Electrical
RCP SYMBOL LEGEND
A1.0
FLOOR PLAN
SCALE: 1/8"=1'-0"
1
A1.0
LIFE SAFETY PLAN
SCALE: 1/16"=1'-0"
3
A1.0
REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
2
A1.0
FLOOR PLAN
REFLECTED CEILING PLAN
LIFE SAFETY PLAN
WALL TYPES AND UL DATA
N
john pruett
architects
1869 madison ave.
memphis, tn 38104
p: 901.721.9062
f: 901.721.9063
CONSULTANTS
DAVIS PATRIKIOS CRISWELL, INC
7975 Stage Hills Blvd. #1
Memphis, TN 38133
901.377.9984
HNA ENGINEERING, PLLC
11880 Cranson Dr., Ste 104
Arlington, TN 38002
901.290.6377
Ad
ditio
n
JA
CK
SO
N E
LE
ME
NT
AR
Y S
CH
OO
L
39
25
W
ale
s A
ve
., M
em
ph
is, T
N 3
81
08
N
N
TFM Review1 05/24/2019