01 02 08 09 11 13 SOUTH ENTRY VEST. 01 CORRIDOR 02 CLASSROOM 06 CLASSROOM 07 CLASSROOM 08 CLASSROOM 09 JANITOR 12 NOTE TO CONTRACTOR: WALL PARTITION DIMENSIONS ARE FROM CENTER LINE TO CENTERLINE OF CMU, TYPICAL AND UNLESS NOTED OTHERWISE. 8" TYP. 138'-6" OVERALL BUILDING DIMENSION ELECTRICAL & IDF ROOM 13 GIRLS REST ROOM 11 BOYS REST ROOM 10 CLASSROOM 04 COMPUTER LAB 03 76'-0" OVERALL BUILDING DIMENSION 06 07 05 04 03 10 12 CLASSROOM 05 14 SPRINKLER ROOM 15 136'-8" CENTERLINE OF CMU TO CENTERLINE OF CMU FD FD FD Roof access ladder & hatch STORAGE 16 15 A6.0 8 6'-0" 3'-0" 8'-0" 3'-0" 6'-0" 2'-0" 1'-0" 12'-1" 16'-8" SIM. A6.0 8 21'-4" M.O. EQ. EQ. 26'-0" 6'-0" 44'-0" 12'-0" 8'-0" 14'-0" 10'-8" 6'-0" 10'-0" 5'-4" 6'-2" 2'-6" 12'-0" 12'-0" 44'-0" 12'-0" 22'-0" 22'-0" 22'-0" 5'-0" 2'-0" M.O. 3'-8" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-4" 2'-0" M.O. 2'-0" M.O. 6'-0" 6'-0" 3'-6" 3'-6" 6'-4" 2'-0" M.O. 6'-4" 2'-0" M.O. 6'-4" Semi-recessed fire extinguisher cabinet. Coordinate cabinet with OFCI Fire Extinguisher. Coordinate rough in of cabinet with vertical rebar. Refer to Structural. Semi-recessed fire extinguisher cabinet. Coordinate cabinet with OFCI Fire Extinguisher. Coordinate rough in of cabinet with vertical rebar. Refer to Structural. B B B B B B B F.E.C. F.E.C. 5 A2.0 5 A2.0 A2.0 6 A A A 6'-0" M.O. 53'-0" 22'-0" 6'-0" M.O. 6'-0" M.O. 22'-0" 21'-8" 44'-3" OUTER FACE TO OUTER FACE OF BRICK VENEER 42'-5" CENTERLINE OF CMU TO CENTERLINE OF CMU 31'-9" CENTERLINE OF CMU TO CENTERLINE OF CMU 31'-9" OUTER FACE TO OUTER FACE OF BRICK VENEER A A A A 11'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 11'-0" 112'-0" CENTERLINE OF CMU TO CENTERLINE OF CMU 113'-10" OUTER FACE TO OUTER FACE OF BRICK VENEER 138'-6" OVERALL BUILDING DIMENSION 24'-8"OUTER FACE TO OUTER FACE OF BRICK VENEER 33'-10" 4'-9" 6'-6" M.O. 74'-2" CENTERLINE OF CMU TO CENTERLINE OF CMU 3'-4"M.O. 25'-9" Capped, painted 4'-0" steel pipe bollard, each side. SIM. A2.0 6 31'-9" 10'-8" 6'-8" 25'-1" 7 A4.0 1 A4.0 A2.0 7,9 28'-3" 3'-6" 10'-8" Cntrln. to Cntrln. 31'-9" 4'x6' Entry mat. Recess in slab 7/8". See Struct. 3'-6" NORTH ENTRY VEST. 14 6'-4" 2'-0"M.O. 6'-4" 2'-0"M.O. 3'-6" 10'-8" SIM. A2.0 7,8 4 A2.0 NOTE: SEE ELEVATIONS FOR LOCATIONS OF BRICK MASONRY CONTROL JOINTS. EDF Hi/Lo EDF 2 A2-0 3 A2.0 1 A2.0 FD FD (7) downspout & boots. See Civil. LOCATION FOR WALL CLOCK. SEE ELECTRICAL 16 17 1" EXPANSION JOINT. SEE STRUCTURAL CONCRETE BENCH. SEE STRUCTURAL. 1'-4" 8'-6" 10'-7" 22'-0" No. 4 Walkerducts, recessed raceway. Coordinate with Electrical and Structural for floor slab construction. 16 A6.0 PLANTING AREA PLANTING AREA GRASS COVERED PLAY AREA PLANTING AREA SWALE. SEE CIVIL 8'-0" 11 A4.0 15 A6.0 REINFORCED CONCRETE RETAINING WALL WITH FABRICATED GUARD RAIL AT TOP. REFER TO STRUCTURAL AND CIVIL. LOW HEIGHT REINFORCED CONCRETE RETAINING WALL. SEE STRUCTURAL AND CIVIL. EXISTING BUILDING NEW LANDSCAPE TREES PER DIRECTION OF ARCHITECT (REFER TO PROJECT MANUAL SPEC SECTION 01 02 00 - ALLOWANCES) CLASSROOM 1,157 SF 64 OCC. LOAD 64 42 SOUTH VESTIBULE 190 Occupant Load EGRESS DOOR: 38.0" Required 66.0" Provided 190 126 LIFE SAFETY LEGEND Path of egress travel and Occupant Load Maximum travel distance 42 CODE DATA Occupancy Type: Educational Construction Type: IIB 1 Story BUILDING AREA 1st Floor Area: 8,768 SF Max. Allowable Area per Floor: 14,500 SF OCCUPANCY for Classrooms: 20/net/person for Non-Educ.Occupied Spaces: 100SF/person TABLE 1005.1 Egress Components (Doors): 0.15" /occupant Per SFM and NFPA101 7.3.3.1 Egress capacity of doors = 0.2/person Clearance at 36" door = 33" 42 42 CLASSROOM 829 SF 42 OCC. LOAD 42 CLASSROOM 829 SF 42 OCC. LOAD CLASSROOM 829 SF 42 OCC. LOAD CLASSROOM 829 SF 42 OCC. LOAD 42 42 NORTH VESTIBULE 126 Occupant Load EGRESS DOOR: 25.2" Required 66.0" Provided CLASSROOM 829 SF 42 OCC. LOAD CLASSROOM 829 SF 42 OCC. LOAD EXISTING CAFETERIA 4015 SF 15 net SF / person 268 Occupant Load 4 Existing Exits EXISTING SOUTH EAST EGRESS DOOR: 67 Occupant Load EXTERIOR ENCLOSURE 126 (new bldg) + 67 (cafeteria) 193 Occ. Load 63 130 EAST GATE 63 Occupant Load EGRESS DOOR: 12.6" Required 33.0" Provided WEST GATE 130 Occupant Load EGRESS DOOR: 26.0" Required 33.0" Provided EXISTING BUILDING CLASSROOM 06 EAST ENTRY VEST. 01 CLASSROOM 07 CLASSROOM 08 CLASSROOM 09 JANITOR 12 ELECTRICAL & IDF ROOM 13 GIRLS REST ROOM 11 BOYS REST ROOM 10 CLASSROOM 04 COMPUTER LAB 03 CLASSROOM 05 SPRINKLER ROOM 15 STOR. 16 Canopy liner panels with recessed lighting and exit lights at each end. All Conduit installation shall be concealed from view. Refer to Electrical. Canopy liner panels with recessed lighting. See Electrical SEE SHEET E2.1 FOR EXTERIOR LIGHTING AND CONTROLS SUSPENDED MOISTURE RESISTANT GYPBOARD CEILING IN GROUP RESTROOMS Ceiling Mounted Occupancy Sensor. See electrical sheets to determine whether Low Voltage or Line Voltage. Ceiling mounted exit sign. See Electrical. Ceiling mounted speaker. See Electrical. Ceiling mounted intercom speaker. See Electrical. Provide all power and communication required for ceiling mount Security Cameras. See Electrical. See Mechanical Sheets for Unit Heater and mini split system 5 A2.0 5 A2.0 A2.0 6 SIM. A2.0 6 2 A4.0 A2.0 7,9 SIM. A2.0 7,8 12 A4.0 Provide power required for canopy mount exit light. See Electrical. Provide power required for canopy mount exit light. See Electrical. EXISTING BUILDING 46'-0" +/- VERIFY WT-1 EXTERIOR, NON RATED 8" REINFORCED CMU WITH BRICK VENEER WT-2A INTERIOR, NONRATED 8" REINFORCED CMU WT-2B INTERIOR, NON FIRE-RATED 8" REINFORCED CMU SMOKE PARTITION (IBC Section 710) WT-2C INTERIOR, 1 HOUR FIRE RATED 8" REINFORCED CMU WALL TYPE LEGEND SEE ELEVATIONS FOR LOCATIONS OF BRICK VENEER CONTROL JOINTS Exterior light, recessed in canopy liner panel. See Electrical. Recessed Architectural Troffer. See Electrical Sheets. Surface mounted light. See Electrical Sheets. Supply Diffuser. See Mechanical Sheets. Return Air Device. See Mechanical Sheets. Unit Heater. See Mechanical Sheets. Note to Contractor: The Reflected Ceiling Plan and Symbol Legend on this Architectural Sheet are not intended to be used independently of the whole construction document set. Refer also to the MPE and FP sheets for complete information. Sprinkler Head. Semi Recessed. See FP Sheets. Sprinkler Head. Upright. See FP Sheets. Ceiling mounted occupancy Sensor. See Electrical Sheets. Ceiling mounted speaker. See Sound Schedule on Electrical Sheets. Ceiling mounted exit sign. See Electrical Sheets. Ceiling mounted Security Camera. See Electrical RCP SYMBOL LEGEND A1.0 FLOOR PLAN SCALE: 1/8"=1'-0" 1 A1.0 LIFE SAFETY PLAN SCALE: 1/16"=1'-0" 3 A1.0 REFLECTED CEILING PLAN SCALE: 1/8"=1'-0" 2 A1.0 FLOOR PLAN REFLECTED CEILING PLAN LIFE SAFETY PLAN WALL TYPES AND UL DATA N john pruett architects 1869 madison ave. memphis, tn 38104 p: 901.721.9062 f: 901.721.9063 [email protected] CONSULTANTS DAVIS PATRIKIOS CRISWELL, INC 7975 Stage Hills Blvd. #1 Memphis, TN 38133 901.377.9984 HNA ENGINEERING, PLLC 11880 Cranson Dr., Ste 104 Arlington, TN 38002 901.290.6377 Addition JACKSON ELEMENTARY SCHOOL 3925 Wales Ave., Memphis, TN 38108 N N TFM Review 1 05/24/2019 1 1

Transcript of A1 · 2020-05-18 · A1.0.\ra Referencing all construction documents, delete all references to...

Page 1: A1 · 2020-05-18 · A1.0.\ra Referencing all construction documents, delete all references to recessed floor and thickened edge slabs at\rComputer Lab Walker Ducts / recessed raceways.

01

02

0809

11

13

SOUTH

ENTRY

VEST.

01

CORRIDOR

02

CLASSROOM

06

CLASSROOM

07

CLASSROOM

08

CLASSROOM

09

JANITOR

12

NOTE TO CONTRACTOR:

WALL PARTITION DIMENSIONS

ARE FROM CENTER LINE TO

CENTERLINE OF CMU, TYPICAL

AND UNLESS NOTED OTHERWISE.

8" TYP.

138'-6" OVERALL BUILDING DIMENSION

ELECTRICAL

& IDF

ROOM

13

GIRLS

REST

ROOM

11

BOYS

REST

ROOM

10

CLASSROOM

04

COMPUTER

LAB

03

76

'-0

" O

VE

RA

LL

B

UIL

DIN

G D

IM

EN

SIO

N

06

07

05

0403

10

12

CLASSROOM

05

14

SPRINKLER

ROOM

15

136'-8" CENTERLINE OF CMU TO CENTERLINE OF CMU

FD

FD

FD

Roof

access

ladder &

hatch

STORAGE

16

15

A6.0

8

6'-0" 3'-0" 8'-0" 3'-0" 6'-0"

2'-0

"

1'-0

"

12

'-1

"1

6'-8

"

SIM.

A6.0

8

21'-4" M.O.

EQ.EQ.

26'-0"

6'-0" 44'-0" 12'-0" 8'-0" 14'-0" 10'-8"6'-0"10'-0"

5'-4" 6'-2" 2'-6"12'-0" 12'-0" 44'-0" 12'-0" 22'-0"

22'-0" 22'-0"

5'-0"

2'-0" M.O.

3'-8"

6'-0" 6'-0"

6'-0" 6'-0"6'-0"

6'-4" 2'-0" M.O.

2'-0" M.O.

6'-0" 6'-0"

3'-6

"

3'-6

"

6'-4"2'-0" M.O.6'-4" 2'-0" M.O.

6'-4"

Semi-recessed fire

extinguisher cabinet.

Coordinate cabinet

with OFCI Fire

Extinguisher.

Coordinate rough

in of cabinet with

vertical rebar.

Refer to Structural.

Semi-recessed fire

extinguisher cabinet.

Coordinate cabinet

with OFCI Fire

Extinguisher.

Coordinate rough

in of cabinet with

vertical rebar.

Refer to Structural.

BBBB

B

B

B

F.E.C.

F.E.C.

5

A2.0

5

A2.0

A2.0

6

A A A

6'-0" M.O.53'-0" 22'-0" 6'-0" M.O. 6'-0" M.O.22'-0" 21'-8"

44

'-3

" O

UT

ER

F

AC

E T

O O

UT

ER

F

AC

E O

F B

RIC

K V

EN

EE

R

42

'-5

" C

EN

TE

RL

IN

E O

F C

MU

T

O C

EN

TE

RL

IN

E O

F C

MU

31

'-9

" C

EN

TE

RL

IN

E O

F C

MU

T

O C

EN

TE

RL

IN

E O

F C

MU

31

'-9

" O

UT

ER

F

AC

E T

O O

UT

ER

F

AC

E O

F B

RIC

K V

EN

EE

R

AAAA

11'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 22'-0" 6'-0" M.O. 11'-0"

112'-0" CENTERLINE OF CMU TO CENTERLINE OF CMU

113'-10" OUTER FACE TO OUTER FACE OF BRICK VENEER

138'-6" OVERALL BUILDING DIMENSION

24'-8"OUTER FACE TO OUTER FACE

OF BRICK VENEER

33

'-1

0"

4'-9

"6

'-6

" M

.O

.

74

'-2

" C

EN

TE

RL

IN

E O

F C

MU

T

O C

EN

TE

RL

IN

E O

F C

MU

3'-4

"M

.O

.

25

'-9

"

Capped,

painted 4'-0"

steel pipe

bollard,

each side.

SIM.

A2.0

6

31

'-9

"1

0'-8

"6

'-8

"2

5'-1

"

7

A4.0

1

A4.0A2.0

7,9

28

'-3

"3

'-6

"

10

'-8

"

Cn

trln

.

to

C

ntrln

.3

1'-9

"

4'x6' Entry

mat. Recess

in slab 7/8".

See Struct.

3'-6

"

NORTH

ENTRY

VEST.

14

6'-4"2'-0"M.O.6'-4" 2'-0"M.O.

3'-6

"

10

'-8

"

SIM.

A2.0

7,8

4

A2.0

NOTE: SEE ELEVATIONS FOR

LOCATIONS OF BRICK MASONRY

CONTROL JOINTS.

EDF

Hi/Lo EDF

2

A2-0

3

A2.0

1

A2.0

FD

FD

(7) downspout &

boots. See Civil.

LOCATION FOR WALL CLOCK.

SEE ELECTRICAL

16

17

1" EXPANSION

JOINT. SEE

STRUCTURAL

CONCRETE BENCH.

SEE STRUCTURAL.

1'-4"

8'-6

"1

0'-7

"

22'-0"

No. 4 Walkerducts,

recessed raceway.

Coordinate with

Electrical and

Structural for floor

slab construction.

16

A6.0

PLANTING AREA

PLANTING AREA

GRASS COVERED PLAY AREA

PLANTING

AREA

SWALE.

SEE

CIVIL

8'-0"

11

A4.0

15

A6.0

REINFORCED CONCRETE RETAINING WALL

WITH FABRICATED GUARD RAIL AT TOP.

REFER TO STRUCTURAL AND CIVIL.

LOW HEIGHT REINFORCED

CONCRETE RETAINING WALL.

SEE STRUCTURAL AND CIVIL.

EX

IS

TIN

G B

UIL

DIN

G

NEW LANDSCAPE TREES PER DIRECTION OF

ARCHITECT (REFER TO PROJECT MANUAL

SPEC SECTION 01 02 00 - ALLOWANCES)

CLASSROOM

1,157 SF

64 OCC. LOAD

64

42

SOUTH VESTIBULE

190 Occupant Load

EGRESS DOOR:

38.0" Required

66.0" Provided

190

126

LIFE SAFETY LEGEND

Path of egress travel and

Occupant Load

Maximum travel distance

42

CODE DATA

Occupancy Type: Educational

Construction Type: IIB

1 Story

BUILDING AREA

1st Floor Area: 8,768 SF

Max. Allowable Area per Floor:

14,500 SF

OCCUPANCY

for Classrooms: 20/net/person

for Non-Educ.Occupied Spaces:

100SF/person

TABLE 1005.1

Egress Components (Doors):

0.15" /occupant

Per SFM and NFPA101 7.3.3.1

Egress capacity of

doors = 0.2/person

Clearance at 36" door = 33"

4242

CLASSROOM

829 SF

42 OCC. LOAD

42

CLASSROOM

829 SF

42 OCC. LOAD

CLASSROOM

829 SF

42 OCC. LOAD

CLASSROOM

829 SF

42 OCC. LOAD

4242

NORTH VESTIBULE

126 Occupant Load

EGRESS DOOR:

25.2" Required

66.0" Provided

CLASSROOM

829 SF

42 OCC. LOAD

CLASSROOM

829 SF

42 OCC. LOAD

EXISTING

CAFETERIA

4015 SF

15 net SF / person

268 Occupant Load

4 Existing Exits

EXISTING

SOUTH EAST

EGRESS DOOR:

67 Occupant Load

EXTERIOR

ENCLOSURE

126 (new bldg)

+ 67 (cafeteria)

193 Occ. Load

63

130

EAST GATE

63 Occupant Load

EGRESS DOOR:

12.6" Required

33.0" Provided

WEST GATE

130 Occupant Load

EGRESS DOOR:

26.0" Required

33.0" Provided

EX

IS

TIN

G B

UIL

DIN

G

CLASSROOM

06

EAST

ENTRY

VEST.

01

CLASSROOM

07

CLASSROOM

08

CLASSROOM

09

JANITOR

12

ELECTRICAL

& IDF ROOM

13

GIRLS

REST

ROOM

11

BOYS

REST

ROOM

10

CLASSROOM

04

COMPUTER

LAB

03

CLASSROOM

05

SPRINKLER

ROOM

15

STOR.

16

Canopy liner panels

with recessed lighting

and exit lights at each

end. All Conduit

installation shall be

concealed from view.

Refer to Electrical.

Canopy liner panels

with recessed lighting.

See Electrical

SEE SHEET E2.1 FOR

EXTERIOR LIGHTING

AND CONTROLS

SUSPENDED MOISTURE

RESISTANT GYPBOARD CEILING

IN GROUP RESTROOMS

Ceiling Mounted

Occupancy

Sensor. See

electrical sheets to

determine whether

Low Voltage or

Line Voltage.

Ceiling mounted

exit sign. See

Electrical.

Ceiling mounted

speaker. See

Electrical.

Ceiling mounted

intercom speaker.

See Electrical.

Provide all power and

communication required

for ceiling mount Security

Cameras. See Electrical.

See Mechanical Sheets

for Unit Heater and mini

split system

5

A2.0

5

A2.0

A2.0

6

SIM.

A2.0

6

2

A4.0A2.0

7,9

SIM.

A2.0

7,812

A4.0

Provide power required

for canopy mount exit

light. See Electrical.

Provide power required for

canopy mount exit light.

See Electrical.

EX

IS

TIN

G B

UIL

DIN

G

46

'-0

" +

/- V

ER

IF

Y

WT-1

EXTERIOR, NON RATED

8" REINFORCED CMU WITH

BRICK VENEER

WT-2A

INTERIOR, NONRATED

8" REINFORCED CMU

WT-2B

INTERIOR, NON FIRE-RATED

8" REINFORCED CMU

SMOKE PARTITION

(IBC Section 710)

WT-2C

INTERIOR, 1 HOUR FIRE RATED

8" REINFORCED CMU

WALL TYPE LEGEND

SEE ELEVATIONS FOR LOCATIONS OF

BRICK VENEER CONTROL JOINTS

Exterior light, recessed in canopy

liner panel. See Electrical.

Recessed Architectural Troffer.

See Electrical Sheets.

Surface mounted light.

See Electrical Sheets.

Supply Diffuser.

See Mechanical Sheets.

Return Air Device.

See Mechanical Sheets.

Unit Heater.

See Mechanical Sheets.

Note to Contractor: The Reflected Ceiling Plan and

Symbol Legend on this Architectural Sheet are not

intended to be used independently of the whole

construction document set. Refer also to the MPE

and FP sheets for complete information.

Sprinkler Head. Semi Recessed.

See FP Sheets.

Sprinkler Head. Upright.

See FP Sheets.

Ceiling mounted occupancy

Sensor. See Electrical Sheets.

Ceiling mounted speaker. See

Sound Schedule on Electrical

Sheets.

Ceiling mounted exit sign. See

Electrical Sheets.

Ceiling mounted Security

Camera. See Electrical

RCP SYMBOL LEGEND

A1.0

FLOOR PLAN

SCALE: 1/8"=1'-0"

1

A1.0

LIFE SAFETY PLAN

SCALE: 1/16"=1'-0"

3

A1.0

REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

2

A1.0

FLOOR PLAN

REFLECTED CEILING PLAN

LIFE SAFETY PLAN

WALL TYPES AND UL DATA

N

john pruett

architects

1869 madison ave.

memphis, tn 38104

p: 901.721.9062

f: 901.721.9063

[email protected]

CONSULTANTS

DAVIS PATRIKIOS CRISWELL, INC

7975 Stage Hills Blvd. #1

Memphis, TN 38133

901.377.9984

HNA ENGINEERING, PLLC

11880 Cranson Dr., Ste 104

Arlington, TN 38002

901.290.6377

Ad

ditio

n

JA

CK

SO

N E

LE

ME

NT

AR

Y S

CH

OO

L

39

25

W

ale

s A

ve

., M

em

ph

is, T

N 3

81

08

N

N

TFM Review1 05/24/2019

1

1

JPA
Callout
From Addendum 1, 05/08/2019 ITEM 15. A1.0. a Referencing all construction documents, delete all references to recessed floor and thickened edge slabs at Computer Lab Walker Ducts / recessed raceways. See additional items in this addendum regarding use of power poles. Coordinate installation of power poles with ceilings as designed and specified. b Replace the carpet scheduled for the floor in Computer Lab 03 with VCT as specified in the other classrooms. c At the exterior of Door 01, delete pointer note that says “Concrete Bench See Structural”. There is no concrete bench.
JPA
Cross-Out
JPA
Text Box
Bench deleted in ITEM 15 c Addendum 1, 05/08/2019
JPA
Highlight
JPA
Callout
From Addendum 1, 05/08/2019 ITEM 16. A1.0 - CLARIFICATION OF CANOPY DIMENSIONS. North Canopy - Refer to Drawing 2/A1.0 Reflected Ceiling Plan for the dimension and configuration of the new canopy at the north end of the building. The 46'-0” +/- dimension shall be field verified per exact locations of door and window of the existing building. Coordinate with the installation of the new gates. The canopy is typically 9'-6” wide. The leg that runs perpendicular to the existing building shall center on the existing cafeteria door's centerline as illustrated.