Agency Listings
100 Series
Low-Profle Plug-inSmoke Detectors
System Sensor 100 Series Plug-in Smoke Detectors oer
superb perormance and reliability in a profle which is
just 2 (5.1 cm) deep.
Features
Sleek,low-profiledesign
Compatiblewith400Seriesproduct
TwoLEDsblinkinstandby,providing360visibility
Broadrangeofadapterbasesavailablewithbuilt-inshortingspring
Hand-heldsensitivityreaderavailable
Model 2151(photoelectricsensor)andmodel2151T(photoelectric
sensorwiththermal)canbeusedwithavarietyofadapterbasesin
severalwiringcongurationsandvoltages.Otherfeaturesinclude:
lowcurrentdraw,stableperformanceinhighairvelocities,built-in
tamperresistantbasedesign,remoteLEDoption,removablecover
andbuilt-intestswitch.
The100seriesisdesignedtomeettheperformancecriteria
designatedbyUL. Thesensingchamberissealedagainstback
pressureairow. Thechambertopiscoveredbyaonepiece
moldedscreenwhichminimizestheentryofdirtandinsects. Thisscreencanberemovedforcleaning. Additionalkeyfeaturesinclude
avarietyofmountingbasesandafulllineofaccessories.
All100Seriesphotoelectricsmokedetectorscontainaunique
opticalsensingchamberdesignedtosensesmokeparticles
producedbyawiderangeofcombustionsources.Acustom
integratedcircuitincorporatessignalprocessingtoreducefalse
alarms.
Model2151photoelectricdetectorsuniqueopticalsensingchamber
isengineeredtosensesmokebyawiderangeofcombustion
sources.Dualelectronicthermistorsadd135Fxedtemperature
thermalsensingonmodel2151T.
CS308 7272-1653:0122 21803025009S911
-
7/31/2019 a05 0182system Sensor
2/2
3825OhioAvenueSt.Charles,IL60174
Phone:800-SENSOR2Fax:630-377-6495
2011SystemSensor.
Productspecicationssubjecttochangewithoutnotice.Visitsystemsensor.comfor
currentproductinformation,includingthelatestversionofthisdatasheet.
A05-0182-01511/11#2709
100 Series Plug-in Smoke Detector SpeciicationsOperating Voltage/Alarm Current SeeAdapterBaseSelectionGuidefollowing
Standby Current 120AStandby(whenmountedinaB110LPbase)
Sensitivity 13.18%/ft.
Height 2.0inB401
Diameter 4.1installedinB401;6.2installedinB110LP
Shipping Weight 5.2oz
Construction Flameretardantthermoplastic
Temperature Photo:32Fto120F(0to49C);Photo/thermal:32Fto100F(0to38C)
UL Listed Velocity Range Photo:03000fpm(015.2m/s)
Humidity Range 10%93%RHnon-condensing
Smoke Detector Spacing Onsmoothceilings(asdenedinNFPA72),spacingof30feet(900sq.ft.)maybeusedasaguide.Otherspacingmay
beuseddependingonceilingheight,highairmovements,andotherconditionsorresponserequirements.
Adapter Base Selection Guide
Base Model Number Loop Type Current Limit Resistor Contact Type Nominal Voltage Current Draw on
Alarm (mA)
B110LP 2-wire* No 12/24VDC 10130
B110RLP 2-wire* Yes 24VDC 1062
B112LP 4-wire Yes FormA&C 24VDC 1736
B114LP 4-wire Yes FormA&C+ASupervisory 120VAC 75mAACMax
B116LP 2-wire* No FormC 24VDC 20100
B401 2-wire* No 12/24VDC 10130
*FunctionalitycontingentonpanelcompatibilityMustbelimitedbycontrolpanelFlangelessbase
RelayContactRatings: ResistiveorInductive(60%powerfactor)load.
FormA: 2.0Aat30VAC/DC
FormC: 0.6Aat110VDC,2.0Aat30VDC
1.0Aat125VAC,2.0Aat30VAC
Ordering InormationPart No. Description
2151 Low-prolephotoelectricdetector.MustbemountedtooneoftheB100SeriesorB400SeriesbaseslistedintheAdapterBaseSelectionGuide.
2151T Low-profilephotoelectricdetectorwiththermal.MustbemountedtooneoftheB100SeriesorB400SeriesbaseslistedintheAdapterBase
SelectionGuide.
Accessories
F110 AccessoryFlangeRingfor6Base
RA100Z Remoteannunciatorfor2or4wiresystems,332V.Fitsstandardsinglegangelectricalbox.
SENS-RDR Hand-heldsensitivityreader.
SMB600 Surfacemountingkit(anged)
EOLR-1 Endoflinerelayforpowersupervision,12/24VDCsystems.
M02-04-01 Testmagnet.
M02-09-00 Testmagnetwith32telescopinghandle.
XR-2B Detectorremovaltool.Allowsinstallationand/orremovalof100SeriesdetectorheadsfrombaseinhighceilinginstallationswhenusedwithXP-4.
XP-4 ExtensionpoleforXR-2B.Comesinthree5ft.sections.
C58-227-01 Replacementdustcoverfor100Seriessmokedetectors.
Junction Box Selection Guide*
Base Model Number Single Gang 3Octagon 4Octagon 4Square 50 mm 60 mm 75 mm
B401 No No No No Yes Yes No
B110LP/RLP Yes Yes Yes Yes No No No
B112LP/B116LP Yes Yes Yes Yes Yes Yes Yes
B114LP No No Yes Yes No No No
*Boxdepthcontingentonbaseandwiresize.RefertoNationalElectricalCodeorlocalapplicablecodesforappropriaterecommendations.