McKee and Associates Architecture and Interior Design Addendum No. THREE Date: 04.23.19 631 South Hull Street – Montgomery, Alabama 36104 334-834-9933 Project: A NEW AG SHOP / HOME ECONOMICS BUILDING & ALTERATIONS TO EXISTING BAND BUILDING FOR FALKVILLE HIGH SCHOOL FOR THE MORGAN COUNTY BOARD OF EDUCATION DECATUR, ALABAMA MCKEE PROJECT NO. 18-227 ALABAMA BUILDING COMMISSION NO. 2018501 The following changes and/or substitutions to the plans and specifications are hereby made a part of same and are incorporated in full force as part of the contract. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form. A3.1 GENERAL MODIFICATIONS: A. Procedures for scheduling a site visit shall be as follows: Contact John Hitt (256) 476-6826 and/or Shane Bagwell (205) 915-4298 with Volkert. A3.2 SPECIFICATION MODIFICATIONS: A. None A3.3 DRAWING MODIFICATIONS: A. See attached drawings as follows: C4.0 (dated 04.22.19) M1 (dated 04.22.19) M3 (dated 04.22.19) B3.1 CLARIFICATIONS & RESPONSES: A. See the following responses to RFI questions received from Contractor’s Question: Please clarify location of welding booths, In the drawings, pages A1.1 and M2 show a different location for the booths than page P2. Pages A1.1 show a booth bumped out which effects the design of the booths. Please clarify which layout to use. Answer: Follow A1.1. END OF ADDENDUM THREE

Transcript of A NEW AG SHOP / HOME ECONOMICS BUILDING & … · SSMH TOP: 594.54 INV: 587.88 10" DIP FL 10":...

Page 1: A NEW AG SHOP / HOME ECONOMICS BUILDING & … · SSMH TOP: 594.54 INV: 587.88 10" DIP FL 10": 587.6± PROPOSED BUILDING FFE: 593.50 REQ'D 3/4" WATER SERVICE SEE PLUMBING PLAN FOR

McKee and Associates

Architecture and Interior Design Addendum

No. THREE Date: 04.23.19

631 South Hull Street – Montgomery, Alabama 36104 334-834-9933

Project:

A NEW AG SHOP / HOME ECONOMICS BUILDING &

ALTERATIONS TO EXISTING BAND BUILDING FOR

FALKVILLE HIGH SCHOOL FOR THE

MORGAN COUNTY BOARD OF EDUCATION

DECATUR, ALABAMA

MCKEE PROJECT NO. 18-227

ALABAMA BUILDING COMMISSION NO. 2018501

The following changes and/or substitutions to the plans and specifications are hereby made a part of same and are incorporated in full force as part of the contract.

Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.

A3.1 GENERAL MODIFICATIONS:

A. Procedures for scheduling a site visit shall be as follows:Contact John Hitt (256) 476-6826 and/or Shane Bagwell (205) 915-4298 with Volkert.

A3.2 SPECIFICATION MODIFICATIONS:

A. None

A3.3 DRAWING MODIFICATIONS:

A. See attached drawings as follows:

C4.0 (dated 04.22.19)M1 (dated 04.22.19)M3 (dated 04.22.19)

B3.1 CLARIFICATIONS & RESPONSES:

A. See the following responses to RFI questions received from Contractor’s

Question:

Please clarify location of welding booths, In the drawings, pages A1.1 and M2 show a different location for the booths than page P2. Pages A1.1 show a booth bumped out which effects the design of the booths. Please clarify which layout to use.

Answer: Follow A1.1.

END OF ADDENDUM THREE

Page 2: A NEW AG SHOP / HOME ECONOMICS BUILDING & … · SSMH TOP: 594.54 INV: 587.88 10" DIP FL 10": 587.6± PROPOSED BUILDING FFE: 593.50 REQ'D 3/4" WATER SERVICE SEE PLUMBING PLAN FOR

Com

pre

ssor

18-227

SHEET TITLE :

MCKEE JOB # :

DRAWN BY :

DATE:

SHEET NO. :

M c K

E

E

a n d A

S

S

O

C

I A

T

E

S

A R

C

H

I T

E

C

T

U

R

E

a n d I N

T

E

R

I O

R

D

E

S

I G

N

63

1 S

OU

TH

H

UL

L S

TR

EE

T M

ON

TG

OM

ER

Y , A

LA

BA

MA

3

61

04

(3

34

) 8

34

-9

93

3

- M

on

da

y, A

pril 2

2, 2

01

9 1

1:1

8:5

4 A

M

RWH

REVISED DATE:

REVISED DATE:

REVISED DATE:

NE

W A

G S

HO

P / H

OM

E E

CO

NO

MIC

S F

AC

IL

IT

Y

TO

FA

LK

VIL

LE

H

IG

H S

CH

OO

L

FO

R T

HE

MO

RG

AN

C

OU

NT

Y B

OA

RD

O

F E

DU

CA

TIO

N

DE

CA

TU

R, A

LA

BA

MA

SITE UTILITY PLAN

C4.0

310 8th AVENUE NE -- PO BOX 2419 -- DECATUR, AL -- (256) 353-3937Pugh Wright McAnally, Inc. www.pughwrightmcanally.comPWM JOB No. 521-19

03-13-19

03-13-19

04-22-19

AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
WM
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WM
AutoCAD SHX Text
LP
AutoCAD SHX Text
24" RCP
AutoCAD SHX Text
GR
AutoCAD SHX Text
GAS SIGN
AutoCAD SHX Text
WATER VAULT
AutoCAD SHX Text
WV & SSCO
AutoCAD SHX Text
GR
AutoCAD SHX Text
EXISTING BUILDING
AutoCAD SHX Text
EXISTING BUILDING
AutoCAD SHX Text
GV
AutoCAD SHX Text
EOP
AutoCAD SHX Text
EOP
AutoCAD SHX Text
EOP
AutoCAD SHX Text
GR
AutoCAD SHX Text
W 1ST STREET
AutoCAD SHX Text
FFE: 598.14
AutoCAD SHX Text
FFE: 593.42
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
GI TOP: 593.06 FL: 589.71
AutoCAD SHX Text
SMH TOP: 593.75 FL: 589.86
AutoCAD SHX Text
SMH TOP: 593.37 FL (24"): 589.84 FL (S): 590.42
AutoCAD SHX Text
SMH TOP: 592.00 IN(N): 588.67 IN(W): 588.84 OUT: 588.66
AutoCAD SHX Text
SMH TOP: 592.03 IN: 588.71 OUT: 588.68
AutoCAD SHX Text
OTI TOP: 591.75 THRT: 590.53 FL: 589.53
AutoCAD SHX Text
18"RCP
AutoCAD SHX Text
45"X27" RCPA
AutoCAD SHX Text
FL: 590.98
AutoCAD SHX Text
JUNCTION BOX (BURIED)
AutoCAD SHX Text
45"X27" RCPA
AutoCAD SHX Text
22"X13" RCPA
AutoCAD SHX Text
45"X27" RCPA
AutoCAD SHX Text
FL: 594.15
AutoCAD SHX Text
CHAIN LINK FENCE
AutoCAD SHX Text
45"X27" RCPA
AutoCAD SHX Text
CHAIN LINK FENCE
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
CHAIN LINK FENCE
AutoCAD SHX Text
OVERHEAD COMMUNICATIONS
AutoCAD SHX Text
8"CONC. PIPE
AutoCAD SHX Text
ENDS NOT LOCATED
AutoCAD SHX Text
END NOT LOCATED
AutoCAD SHX Text
PROPOSED BUILDING FFE: 595.50
AutoCAD SHX Text
REQ'D 2" WATER SERVICE TIE TO EXISTING SERVICE LINE SEE PLUMBING PLAN FOR CONTINUATION
AutoCAD SHX Text
REQ'D 4" PVC SEWER LATERAL TIE TO EXISTING SEWER MAIN SEE PLUMBING PLAN FOR CONTINUATION
AutoCAD SHX Text
REQ'D SSCO FL: 589.0
AutoCAD SHX Text
CONTROL POINT #1 N: 1589090.63 E: 2146284.90 ELEV: 593.64
AutoCAD SHX Text
CONTROL POINT #2 N: 1588919.39 E: 2146294.86 ELEV: 592.46
AutoCAD SHX Text
CONTROL POINT #3 N: 1589030.97 E: 2146170.44 ELEV: 593.42
AutoCAD SHX Text
REQ'D GRATE INLET TOP: 593.25 INV: MATCH CMP
AutoCAD SHX Text
SSMH TOP: 594.54 INV: 587.88
AutoCAD SHX Text
10" DIP
AutoCAD SHX Text
FL 10": 587.6±
AutoCAD SHX Text
PROPOSED BUILDING FFE: 593.50
AutoCAD SHX Text
REQ'D 3/4" WATER SERVICE SEE PLUMBING PLAN FOR CONTINUATION
AutoCAD SHX Text
%%uLEGEND
AutoCAD SHX Text
EOP BOC EOC SW WM WV GV GR PP LP OHT
AutoCAD SHX Text
W
AutoCAD SHX Text
OHE
AutoCAD SHX Text
SMH SSCO OTI GI THRT RCP CMP CMPA RCPA FL FFE N W
AutoCAD SHX Text
EDGE OF PAVEMENT BACK OF CURB EDGE OF CONCRETE SIDE WALK WATER METER WATER VALVE GAS VALVE GAS REGULATOR POWER POLE LIGHT POLE OVER HEAD TELEPHONE OVER HEAD ELECTRIC BURIED ELECTRIC GAS LINE WATER LINE FENCE
AutoCAD SHX Text
STORM MAN HOLE SANITARY SEWER CLEAN OUT OPEN THROAT INLET GRATE INLET THROAT REINFORCED CONCRETE PIPE REINFORCED CONCRETE PIPE ARCH CORRIGATED METAL PIPE CORRIGATED METAL PIPE ARCH FLOW LINE FINISHED FLOOR ELEVATION NORTH WEST
AutoCAD SHX Text
Scale 1" = 10'
AutoCAD SHX Text
30
AutoCAD SHX Text
20
AutoCAD SHX Text
10
AutoCAD SHX Text
0
AutoCAD SHX Text
10
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
M
AutoCAD SHX Text
A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
NO. 22738
AutoCAD SHX Text
R
AutoCAD SHX Text
I
AutoCAD SHX Text
C
AutoCAD SHX Text
H
AutoCAD SHX Text
A
AutoCAD SHX Text
R
AutoCAD SHX Text
D
AutoCAD SHX Text
W
AutoCAD SHX Text
.
AutoCAD SHX Text
H
AutoCAD SHX Text
U
AutoCAD SHX Text
M
AutoCAD SHX Text
P
AutoCAD SHX Text
H
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
Y
AutoCAD SHX Text
L
AutoCAD SHX Text
I
AutoCAD SHX Text
C
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
Page 3: A NEW AG SHOP / HOME ECONOMICS BUILDING & … · SSMH TOP: 594.54 INV: 587.88 10" DIP FL 10": 587.6± PROPOSED BUILDING FFE: 593.50 REQ'D 3/4" WATER SERVICE SEE PLUMBING PLAN FOR

Metal

Band Saw

Iron

Worker

Bench

Grinder

Belt

Sander

Lathe

Table Saw

Planer

CNC Router

Drill P

re

ss

Compressor

Wood Rack

Welding 8

Welding 1

Welding 2 Welding 3 Welding 4

Dust

Collector

System

Bench

Grinder

Abrasive

Cutoff

Safety Glass

Sanitizing

Station

Future Table Saw

Future

Belt

Sander

Future

Lathe

Future

Lathe

Future

Lathe

Future

Lathe

Future

Lathe

Future

Lathe

Future

Radial Arm

Saw

Table

Router

Future

Table

Router

Miter

Saw

Future

Miter

Saw

Miter

Saw

Scroll

Saw

Future

Miter

Saw

Miter

Saw

Future

Collector

System

Welding 5

Welding 6 Welding 7

DATA

120

COVERED AREA

119

SHOP AREA

118

STORAGE

116

OFFICE

115

STORAGE

114

AQUACULTURE

112

SEWING LAB

105

MECHANICAL

110

HOME

ECONOMICS

106

INSTRUCTION

113

STORAGE

107

STORAGE

109

OFFICE

108

MALE

102

FEMALE

103

JAN

104

ENTRY

101

STORAGE

117

ELECTRICAL

111

44x20 RISE HIGH

AS POSSIBLE

MAU-1 CONTROL

PANEL

EXH. FAN TYPE EF-C

HIGH AS POSSIBLE

(12,000 CFM)

*

EXHAUST FAN TYPE EF-D

SEE DETAIL & SPECS FOR VIB.

ISOLATION (4800 CFM)

6"Ø METAL DUCT AND MAN. DAMPER -

TERMINATE 8"-0" A.F.F. - PROVIDE

MIN. 6'-0" 6"Ø FLEX. DUCT WITH

SPECIFIED ACCESSORIES - COORDINATE

FINAL LENGTH OF FLEX DUCT IN FIELD

TO PROVIDE PROPER LENGTH FOR WELDING

ANYWHERE ON WELDING BENCH (600 CFM EA.)

12x12 DOUBLE FACE WALL

GRILLE LOCATE (1) 8" BELOW

CEILING AND (1) 8" A.F.F.

45° CONICAL

TAKE-OFF

FITTING (TYP.)

MAKE-UP AIR UNIT

MAU-1 ON CONC.

PAD - PAD BY GEN.

CONTR.

* * *

*

T

T

64x64 O.A. LVR. WITH

CONCEALED MOTOR &

LINKAGE 8" A.F.F.

INTERLOCK TO OPEN

WHEN EF-C OPERATES

MAKE-UP AIR UNIT

MAU-2 SUSPENDED

FROM STRUCTURE

BOTTOM OF UNIT

MAX. 14'-0" A.F.F.

(900 CFM)

32x14 LVR. BY

GEN. CONTR.

MOTORIZED DAMPER

16x14

FULL SIZE EXPANDED

METAL GRILLE OVER

FAN INLET

SMOKE

DETECTOR

ELECTRIC UNIT HEATER

EUH-A HIGH AS

POSSIBLE (8KW)

ELECTRIC UNIT HEATER

EUH-A HIGH AS

POSSIBLE (8KW)

(3) 46x18 WALL S.A.

REG. (1600 CFM EA.)

34

x2

0

20x20

44x20

SMOKE DETECTOR

24"Ø RISE EXPOSED

HIGH AS POSSIBLE

24"Ø

22"Ø

20"Ø

14"Ø

64x64 O.A. LVR. WITH

CONCEALED MOTOR &

LINKAGE 8" A.F.F.

INTERLOCK WITH

EF-C

16x14

B

24x24 RELIEF AIR LVR.

HIGH AS POSSIBLE WITH

FULL SIZE EXPANDED

METAL GRILLE ON INTERIOR

SIDE OF WALL LOUVER

42x42 EXH. UP

THRU ROOF

W/ CAP

HP-1

HP-1

26x16 WALL R.A.

REG. ABOVE BASE

14x12

T H

PACKAGED HEAT PUMP

UNIT PHP-1 ON CONC.

PAD - PAD BY GEN. CONTR.

PACKAGED HEAT PUMP

UNIT PHP-2 ON CONC.

PAD - PAD BY GEN. CONTR.

8x12

16x16

10x12

8x12

30x24 WALL R.A.

REG. ABOVE BASE

12x6

T

H C30x24 R.A.

26x16 S.A. RISE

IN CHASE TO

ABOVE CLG.

14x6

3

3

100

200

3

2

575

6

575

6

2

130

2

3

240

130

2

2

2

8x12

2

2

8x12

10x12

(2) 18x10 WALL S.A.

REG. (400 CFM EA.)

EXH. FAN TYPE

EF-A (140 CFM)

8"Ø EXH. UP

THRU ROOF

W/ CAP

30x16 R.A. RISE

IN CHASE TO

ABOVE CLG.

48x24 CLG.

R.A. REG.

26x16 S.A. RISE IN

CHASE TO ABOVE

CLG.

27 CU. FT.

DRYWELL

27 CU. FT.

DRYWELL

2" COND. DRAIN LINE

UNDERGROUND TO DRYWELL

2" COND. DRAIN LINE

UNDERGROUND TO DRYWELL

26x16 24x16 24x16

18x16 16x12

10x12

OUTDOOR SECTION OF

DUCTLESS TYPE HEAT

PUMP DHP-A ON CONC. -

PAD BY GEN. CONTR.

1" COND. DRAIN

LINE DN. TO HUB

DRAIN IN CORNER

REFRIG. PIPING - RISE IN

WALL TO ABOVE CLG.

EXTEND AND CONN. TO

DHP-A

DUCTLESS HEAT PUMP

UNIT DHP-A MOUNTED

ABOVE DOOR

EXH. FAN TYPE

EF-B W/ 6"Ø EXH.

UP THRU ROOF

(70 CFM)

75

1

125

2

100

2

3004

3004

3004

2003

2003

200

3

200

3

REFRIG. PIPING - RISE IN

CHASE TO ABOVE CLG.

EXTEND AND CONN. TO

INDOOR SECTION OF

HEAT PUMP HP-1

OUTDOOR SECTION OF

HEAT PUMP HP-1 ON CONC.

PAD - PAD BY GEN. CONTR.

4"Ø DRYER VENT &

WALL CAP ASSEMBLY

T

T

H

C

30x12 WALL S.A.

GRILLE (900 CFM)

*

PORTABLE DUST

COLLECTOR- SEE

SPECS

PORTABLE DUST

COLLECTOR- SEE

SPECS

PORTABLE DUST

COLLECTOR- SEE

SPECS

SMOKE DETECTOR

MOTORIZED DAMPER (MD)

MANUAL VOLUME DAMPER (MVD)

MOTORIZED R.A. DAMPER

LEGEND

CEILING DIFFUSER

RETURN AIR GRILLE/REGISTER

EXHAUST AIR GRILLE/REGISTER

CEILING DIFFUSER DESIGNATOR

RETURN AIR GRILLE/REGISTER

EXHAUST AIR GRILLE/REGISTER

4

4

4

DENOTES LOCATION OF VERTICAL

ACTION FIRE DAMPER

DENOTES LOCATION OF HORIZONTAL

ACTION FIRE DAMPER

BAROMETRIC DAMPER

B

DUCT W/ RECTANGULAR SIZE12x12

THERMOSTATT

H HUMIDISTAT

ABOVE FINISH FLOORA.F.F.

CEILING DIFFUSERC.D.

FIRE DAMPERF.D.

GENERAL CONTRACTORG.C.

OUTSIDE AIRO.A.

S.A. SUPPLY AIR

R.A. RETURN AIR

CLG. CEILING OR COOLING

CONNECT OR CONNECTIONCONN.

AD AUXILIARY DRAIN

C CO2 SENSOR

RECTANGULAR SUPPLY AIR DUCT TURNING DOWN

RECTANGULAR RETURN AIR OR EXHAUST

RECTANGULAR SUPPLY DUCT TURNING UP

RECTANGULAR RETURN AIR OR EXHAUST

RECTANGULAR SUPPLY AIR DUCT

RECTANGULAR RETURN OR EXHAUST AIR DUCT

FLOOR OR ROOF PENETRATION

FLOOR OR ROOF PENETRATION

DUCT TURNING UP

DUCT TURNING DOWN

EXISTING DUCTWORK

EXISTING DUCT TO BE REMOVED

X X

X X

REVISED

0422-19

(3) 48x48 AUTOMATIC MOTORIZED

SHUTTERS EQUIVALENT TO AMERICAN

COOLAIR - REFER TO ARCH. ELEVATIONS

FOR LOCATIONS - INTERLOCK TO OPEN

ANY TIME ANY EXH. FAN OPERATES

(2) SLANT WALL EXH. FANS

EQUIVALENT TO AMERICAN

COOLAIR NBF30G, 30" FAN,

1/2" HP, 6,000 CFM, 0.10 S.P.,

120V., 1PH., 60HZ, REFER TO

ARCH. ELEVATIONS FOR

LOCATION OF FANS

IGROW 400 GREENHOUSE

CONTROLLER BY COOLAIR

OR EQUIVALENT

(2) 3-BLADE HORIZONTAL AIRFLOW FANS (HAF)

EQUAL TO AMERICAN COOLER FH18G11, 18" RADIUS,

1/4" HP., 120V., 1PH., 60HZ., 1400 RPM & 2,000 CFM WITH

PEDESTAL SECURED TO STRUCTURE ABOVE

GAS FIRED UNIT HEATER

SUSPENDED FROM STRUCTURE

ABOVE - EQUAL TO ADP SERIES

SEP230, SEALED COMBUSTION, 145

MBH OUTPUT, 82% AFUE, 1/8 HP.,

2,000 CFM, WITH VENTING PER

MANUFACTURER

HVAC FLOOR PLAN

SCALE: 1/8" = 1'-0"

18-227

03-11-19

SHEET TITLE :

MCKEE JOB # :

CHECKED BY :

DATE:

SHEET NO. :

M c K

E

E

a

n

d

A

S

S

O

C

I A

T

E

S

A R

C

H

I T

E

C

T

U

R

E

a n

d

I N

T

E

R

I O

R

D

E

S

I G

N

63

1 S

OU

TH

H

UL

L S

TR

EE

T M

ON

TG

OM

ER

Y , A

LA

BA

MA

3

61

04

(3

34

) 8

34

-9

93

3

T. ZGOUVAS

REVISED DATE:

REVISED DATE:

REVISED DATE:

NE

W A

G S

HO

P / H

OM

E E

CO

NO

MIC

S F

AC

ILIT

Y

TO

FA

LK

VILLE

H

IG

H S

CH

OO

L

FO

R T

HE

MO

RG

AN

C

OU

NT

Y B

OA

RD

O

F E

DU

CA

TIO

N

DE

CA

TU

R, A

LA

BA

MA

DRAWN BY :C. WARD

MONTGOMERY, AL. 36104800 S McDONOUGH STREET

334.263.4406

ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS

THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 19-33

04-05-19

04-05-19

M1

HVAC FLOOR PLAN

GREEN HOUSE HEATING AND VENTILATION PLAN

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text
"A"
AutoCAD SHX Text
"A"
AutoCAD SHX Text
"B"
AutoCAD SHX Text
"B"
AutoCAD SHX Text
"C"
AutoCAD SHX Text
"C"
AutoCAD SHX Text
I
AutoCAD SHX Text
R
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
R.
AutoCAD SHX Text
J.
AutoCAD SHX Text
E
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
No. 23369
AutoCAD SHX Text
M
AutoCAD SHX Text
A
AutoCAD SHX Text
R
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
C
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
E
Page 4: A NEW AG SHOP / HOME ECONOMICS BUILDING & … · SSMH TOP: 594.54 INV: 587.88 10" DIP FL 10": 587.6± PROPOSED BUILDING FFE: 593.50 REQ'D 3/4" WATER SERVICE SEE PLUMBING PLAN FOR

NOT TO SCALE

TYPICAL EXPOSED RECTANGULAR DUCT

15°

RECTANGULAR DUCTS SIMILAR

THREADED ROD AS REQUIRED

FOR WEIGHT OF DUCT -

MINIMUM 3/8" RODS REQ'D

PROVIDE SUPPLEMENTAL

STEEL SUPPORTS BETWEEN

WELDED STRUCTURAL MEMBERS,

AS REQUIRED - PROVIDE AS

REQUIRED BY THE STRUCTURAL

ENGINEER

WHERE BTM. OF S.A. DUCT IS

LOCATED GREATER THAN

15'-0" A.F.F., S.A. DISCHARGE

SHALL BE AT 15° ANGLE

WHERE BTM. OF S.A. DUCT IS

LOCATED 15'-0" OR LESS A.F.F.,

S.A. DISCHARGE SHALL BE AT

A 90° ANGLE

FACTORY FABRICATED AND

INSULATED DOUBLE WALL

DUCTWORK - SEE SPECS

UNISTRUT DUCT SUPPORT

AS REQUIRED FOR WEIGHT

OF DUCT

6 FT. 316 STAINLESS

STEEL STACKHEAD

GUY WIRE (TYPICAL)

STAINLESS STEEL

STACK HEAD

ROUND TYPE 316

STAINLESS STEEL

DUCT

STAINLESS STEEL

TRANSITION

EXHAUST FAN

FLEX. CONNECTION

FAN DRAIN COUPLING

VIBRATION ISOL. SPECS.

SECTION 15700, PART 4

WELDING EXHAUST FAN DETAIL

NOT TO SCALE

6" CONC. PAD

4,800EF-D 60

60

60

60

WALL SWITCH32087.5 hp5.40197419.5PAD MOUNTED, UTILITY SET, BELT DRIVEN

12,000 WALL SWITCH32083 hp.4153833.0IN-LINE, BELT DRIVEN, CENTRIFUGAL

LIGHTING CIRCUIT112077w.3010508.070

HERTZPH.

LIGHTING CIRCUIT112077w.301050N/A8.0CEILING MOUNTED, CENTRIFUGAL, DIRECT DRIVEN140

REMARKS

INTERLOCK

CONTROL

VOLTS

POWER

H.P./

MIN.

IN. WTR. COL.

STATIC PRESS.

APPROX. EXT. FAN MOTOR

RPM

FAN SPEED

MAXIMUM

-INCHES

OPENING

ROOF

WALL/

APPROX.

INCHES

FAN SIZE

MINIMUMDESCRIPTIONFAN CFMFAN TYPE

FANS SCHEDULE

EF-A

EF-B

EF-C

WATTS

IN. OF WATER KW STEPS

MAU-1

MAU-2 900

4800

.57

.66

1/2

3.0

208

208

3

3

60

60

15.0

75.0

TWO

SCR

PACKAGED MAKE-UP AIR UNIT SCHEDULE (ELECTRIC HEAT)

APPROXIMATE

EXTERNAL

STATIC PRESS.

UNIT

NUMBER

AIR

CFM

TOTAL

FAN

FAN MOTOR

VOLTSH.P. PHASE

MINIMUM

HEATING

CAPACITY

ELECTRIC HEATER

HERTZ

NUMBER

CONTROL

OF

REMARKS

OF CONTROL

HERTZ

ELECTRIC UNIT HEATER SCHEDULE

HEATER

TYPE

EUH-A

DESCRIPTION MINIMUM

CAPACITY-QUANTITY-

CFM

AIR

KW

FAN

HP

POWER

RPM

MAX.

FAN

VOLTS PHASE

REMARKSNUMBER

STEPS

HORIZONTAL, PROPELLER 800 8.0 1/50 1550 208 3 ONE60

20

20

20

20

20

2015" ROUND

14" ROUND

12" ROUND

10" ROUND

8" ROUND

15"Ø

14"Ø

12"Ø

10"Ø

8"Ø

6"Ø

24x24

24x24

24x24

24x24

24x24

535 - 625

405 - 530

275 - 400

185 - 270

100 - 180

24x246" ROUND10 - 95

CEILING DIFFUSER SCHEDULE

1

2

3

4

5

6

TITUS TMS

TITUS TMS

TITUS TMS

TITUS TMS

TITUS TMS

TITUS TMS

NOTES

1.) RUNOUTS/BRANCH DUCTS SHALL BE AS SCHEDULED ABOVE UNLESS NOTED OTHERWISE ON THE PLANS

2.) CONTRACTOR SHALL INSULATE THE EXTERIOR (BACK SIDE OF DIFFUSER PANEL) WITH 2" THICKNESS

EXTERNAL DUCT INSULATION WITH CHARACTERISTICS SPECIFIED FOR EXTERNAL DUCT INSULATION.

SYMBOL CFM RANGE NECK SIZE

INCHES

FACE SIZE

INCHES

BRANCH

DUCT SIZE

MAXIMUM

NC VALUE

BASIS OF

DESIGN

941 - 1200

1201 - 1400

8

9

9

8

36x24

30x24CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

20

20 28x14

24x14

EXHAUST/RETURN AIR REGISTER SCHEDULE

1

9x90 - 140

1

761 - 940

601 - 760

461 - 600

341 - 460

241 - 340

141 - 240

7

6

5

7

6

5

4

3

2

4

3

2

16x16

24x24

20x20

18x18

14x14

12x12

RANGE

R.A.

SYMBOL

EXH.

CFM

IN. x IN.

SIZE -

CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

CEILING EXH. OR RETURN REG.

DESCRIPTION

20 9x6

20

20

20

20

20

20

16x9

24x12

20x12

18x10

14x7

12x7

MAXIMUM

NC

RATING

DUCT

SIZE

BRANCH

988 9

NOTES

1.) RUNOUTS/BRANCH DUCTS SHALL BE AS SCHEDULED ABOVE UNLESS NOTED OTHERWISE ON THE

PLANS.

2.) & SHALL BE IN INTEGRAL 48x24 METAL CEILING PANEL AS SPECIFIED. ALL OTHERS

SHALL BE IN INTEGRAL 24x24 METAL CEILING PANEL AS SPECIFIED.

WALL MOUNTED DUCTLESS HEAT PUMP UNIT SCHEDULE

INDOOR UNIT MCA - POWER

INDOOR FAN CFM AT HIGH SPEED

MINIMUM HEATING CAP. (COMPRESSOR ONLY) AT 70°F INDOOR & 17°F AMBIENT - BTU/HR

MINIMUM TOTAL COOLING CAP. AT A.R.I. CONDITIONS - BTU/HR

MINIMUM HSPF AT ARI 210/240 CONDS.

OUTDOOR UNIT MOP (COMPRESSOR AND COND. FAN) - POWER

UNIT TYPE

OUTDOOR UNIT MCA (COMPRESSOR AND COND. FAN) - POWER

MINIMUM S.E.E.R. AT ARI 210/240 CONDS

10.0

1.5A - 208V, 1 PH. , 60 HZ.

9,000

230

6,700

DHP-A

9.0A - 208V, 1 PH., 60 HZ.

18.0

15.0A - 208V., - 1PH., 60HZ.

BASIS OF DESIGN MITSUBISHI MSZ / MUZ

LOW AMBIENT HEAD PRESS. CONTROL TO MIN. DEGREES F (COOLING ONLY)45

1/2 HP - 208V., 1PH., 60HZ.APPROXIMATE INDOOR FAN MOTOR HP-POWER

14.0 SEER

1.5 - 208V., 1PH., 60HZ.

11.0 - 208V, 1PH., 60HZ.

208V., 1PH., 60HZ.

ONE

6.0

14,000

24,000

320 / NA / NA

800

HP-1

MINIMUM HSPF

MINIMUM ENERGY EFFICIENCY RATING AT A.R.I. CONDITIONS

APPROXIMATE OUTDOOR SECTION FAN MOTOR(S) F.L.A. - POWER

APPROXIMATE COMPRESSOR MOTOR(S) F.L.A. - POWER

POWER

NUMBER OF CONTROL STEPS

MINIMUM AUXILIARY ELECTRIC RESISTANCE HEAT - KW

INDOOR TEMPERATURE AND 22°F OUTDOOR TEMPERATURE-BTU/HR

MINIMUM HEATING CAPACITY (COMPRESSOR ONLY) AT 70°F

MINIMUM TOTAL COOLING CAPACITY AT A.R.I. CONDITIONS-BTU/HR

MINIMUM OUTSIDE AIR SETPOINT/MAX. CO2 SETPOINT/MAX. O.A. (ECONOMIZER) CFM

MINIMUM TOTAL AIR CFM

UNIT NUMBER OR TYPE

SPLIT SYSTEM HEAT PUMP UNITS SCHEDULE

APPROXIMATE EXTERNAL STATIC PRESSURE - IN. WATER COLUMN .62

9.0

NOTES:

1. ALL INDOOR UNITS SHALL BE FACTORY WIRED FOR SINGLE POINT POWER CONNECTIONS (FAN AND HEATER).

2. 208 VOLT, 1 PHASE POWER IS BEING PROVIDED BY ELECTRICAL TO THE INDOOR HEAT PUMP UNIT SECTIONS. UNIT MANUFACTURER SHALL PROVIDE FACTORY

INSTALLED RELAYS, TRANSFORMERS, ETC., AS REQUIRED TO OPERATE EQUIPMENT AT POWER REQUIREMENTS SPECIFIED ABOVE.

3. SEER RATINGS BASED ON ARI 210/240

4. HSPF RATING BASED ON ARI 210/240

.84

PHP-2

2000

150 / 660 / 2000

LOW AMBIENT HEAD PRES. CONTROL TO DEGREES F (COOLING ONLY)45

1.0 HP - 208V., 3PH., 60HZ.APPROXIMATE INDOOR FAN MOTOR HP-POWER

14.0 SEER

3.5 - 208V., 3PH., 60HZ.

20.0 - 208V, 3PH., 60HZ.

208V., 3PH., 60HZ.

TWO

15.0

38,000

60,000

150 / 640 / 2000

2000

PHP-1

MINIMUM HSPF

MINIMUM ENERGY EFFICIENCY RATING AT A.R.I. CONDITIONS

APPROXIMATE OUTDOOR SECTION FAN MOTOR(S) F.L.A. - POWER

APPROXIMATE COMPRESSOR MOTOR(S) F.L.A. - POWER

POWER

NUMBER OF CONTROL STEPS

MINIMUM AUXILIARY ELECTRIC RESISTANCE HEAT - KW

INDOOR TEMPERATURE AND 22°F OUTDOOR TEMPERATURE-BTU/HR

MINIMUM HEATING CAPACITY (COMPRESSOR ONLY) AT 70°F

MINIMUM TOTAL COOLING CAPACITY AT A.R.I. CONDITIONS-BTU/HR

MINIMUM OUTSIDE AIR SETPOINT/MAX. CO2 SETPOINT/MAX. O.A. (ECONOMIZER) CFM

MINIMUM TOTAL AIR CFM

UNIT NUMBER

PACKAGED PAD MOUNTED HEAT PUMP UNITS SCHEDULE

APPROXIMATE EXTERNAL STATIC PRESSURE - IN. WATER COLUMN .70

9.0

1.0 HP - 208V., 3PH., 60HZ.

NOTES:

1. ALL UNITS SHALL BE FACTORY WIRED FOR SINGLE POINT POWER CONNECTIONS (FAN AND HEATER).

2. 208 VOLT, 3 PHASE POWER IS BEING PROVIDED BY ELECTRICAL TO THE INDOOR HEAT PUMP UNIT SECTIONS. UNIT MANUFACTURER SHALL PROVIDE FACTORY

INSTALLED RELAYS, TRANSFORMERS, ETC., AS REQUIRED TO OPERATE EQUIPMENT AT POWER REQUIREMENTS SPECIFIED ABOVE.

3. SEER RATINGS BASED ON ARI 210/240

4. HSPF RATING BASED ON ARI 210/240

5. EACH UNIT SHALL BE PROVIDED WITH A REFRIGERANT HOT GAS REHEAT COIL COMPLETE WITH REFRIGERANT PIPING, PIPE INSULATION, VALVES, CONTROLS, ETC.

REQUIRED FOR HUMIDITY CONTROL - PROVIDE MANUAL REFRIGERANT ISOLATION VALVES FOR HOT GAS AND LIQUID LINES - FURNISH FOR APPROVAL DETAILED

REFRIGERANT PIPING CONN. DIAGRAM AND CONTROL WIRING DIAGRAM - PRIOR TO SUBMITTING THE DIAGRAM OBTAIN EQUIPMENT MANUFACTURER'S APPROVAL. SEE

SPECS FOR ADDITIONAL REQUIREMENTS

45

14.0 SEER

3.5 - 208V., 3PH., 60HZ.

20.0 - 208V, 3PH., 60HZ.

208V., 3PH., 60HZ.

TWO

15.0

38,000

60,000

9.0

CEILING MOUNTED, CENTRIFUGAL, DIRECT DRIVEN N/A

N/A

N/A

NOTES:

1. MAU-1 SHALL BE PROVIDED WITH FACTORY INSTALLED VARIABLE FREQUENCY DRIVE (VFD)

INTERNALLY

INSULATED

DUCTWORK

BOLT TO WALL WITH ANCHOR

PLATE AND ANGLE IRON 6'-0"

O.C. - COORDINATE ANCHORING

WITH STRUCTURAL ENGINEER'S

REQUIREMENTS PRIOR TO

INSTALLING

TERMINATE STACK HEAD

MINIMUM 6'-0" ABOVE EAVE

HEIGHT

NOTES:

1. EF- C AND EF-D SHALL BE PROVIDED FACTORY INSTALLED VFD'S

2. EF-C VFD SHALL BE PROVIDED WITH NEMA 1 ENCLOSURE

3. EF-D VFD SHALL BE PROVIDED WITH NEMA 4X ENCLOSURE

REVISED

0422-19

18-227

03-11-19

SHEET TITLE :

MCKEE JOB # :

CHECKED BY :

DATE:

SHEET NO. :

M c K

E

E

a

n

d

A

S

S

O

C

I A

T

E

S

A R

C

H

I T

E

C

T

U

R

E

a n

d

I N

T

E

R

I O

R

D

E

S

I G

N

63

1 S

OU

TH

H

UL

L S

TR

EE

T M

ON

TG

OM

ER

Y , A

LA

BA

MA

3

61

04

(3

34

) 8

34

-9

93

3

T. ZGOUVAS

REVISED DATE:

REVISED DATE:

REVISED DATE:

NE

W A

G S

HO

P / H

OM

E E

CO

NO

MIC

S F

AC

ILIT

Y

TO

FA

LK

VILLE

H

IG

H S

CH

OO

L

FO

R T

HE

MO

RG

AN

C

OU

NT

Y B

OA

RD

O

F E

DU

CA

TIO

N

DE

CA

TU

R, A

LA

BA

MA

DRAWN BY :C. WARD

MONTGOMERY, AL. 36104800 S McDONOUGH STREET

334.263.4406

ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS

THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 19-33

04-05-19

04-05-19

M3

HVAC SCHED. AND

DETAILS

04-22-19

AutoCAD SHX Text
I
AutoCAD SHX Text
R
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
R.
AutoCAD SHX Text
J.
AutoCAD SHX Text
E
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
No. 23369
AutoCAD SHX Text
M
AutoCAD SHX Text
A
AutoCAD SHX Text
R
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
C
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
I
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
E