A Guide to Fire Alarm System Design BS 5839 Part 1:2002
Transcript of A Guide to Fire Alarm System Design BS 5839 Part 1:2002
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
1/20
Fire Alarm Systems Design
BS5839Part1:2002incorporating Amendment No.2
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
2/202
Legally you must comply!
What is the RRO?
Fire authorities no longer issue irecertiicates and those previouslyin orce will have no legal status.The Regulatory Reorm (Fire Saety)Order (RRO) replaces most ire saetylegislation with one new order. It
means that any person who has somelevel o control in premises must takesteps to reduce the risk rom ire,consider how to contain a ire shouldone break out and then also makesure people can saely escape i thereis a ire.
All fire alarm designs should bebasedonaFireRiskAssessment
AllFireRiskAssessmentsshouldbe carried out by a competentperson
FireRiskassessmentsmustbereviewed annually
What constitutes a Fire Risk
Assessment?Identifyingfirehazardssuchas
sources o ignition, uel or oxygen
Identifyingallpeopleatriskinand around the premises
Evaluatingtheriskofafirestartingor the risk to people rom a ire
Removingorreducingfirehazardsor risks to people rom a ire
Protectingpeoplebyproviding ire precautions
Recordinganymajorfindings
Preparinganemergencyplan
Informingandinstructingany relevant people
ProvidingtrainingforstaffandguestsReviewingthefirerisk
assessment regularly and makechanges where necessary
Keepingaccuratefireriskassessment records
The Regulatory Reform (Fire Safety) Order (RRO)became law on 1 October 2006
AllfirealarmdesignsshouldbebasedonaFireRiskAssessment
Where does the order apply?
Virtually all premises and nearly every type o building structure and open space.
I you would like to ind out more about how Apollo products can helpyou comply with the RRO please contact us on 023 9249 2412 or visit ourwebsite on www.apollo-fire.co.uk
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
3/203
Property Protection Fire Systems
P1 AFDinstalledthroughoutallareas
P2 AFDinstalledonlyindefinedareas
Life Protection Fire Systems
L AFDdesignedtoprimarilyprotectHuman Lie
L1 AFDinstalledthroughoutallareas
L2 AFDinstalledindefinedareasinaddition to L3
L3 AFDinstalledinescaperoutesandrooms opening onto these routes
L4 AFDinstalledinescaperoutescomprising circulation areas andspaces such as corridors and stairways
L5 A non-prescriptive system in whichprotected area(s) and/or the locationo detectors is designed to satisy
aspecificfireriskobjective(otherthan that o L1 to L4)
M System design to be operatedmanually(noAFD)
*AFDAutomaticFireDetection
FireAlarmandDetectionsystemsare
categorised in the following way:
P1 P2
L1 L2L4 L3
This guide is intended to be an aid to designers and installers of firedetection systems. It is not to be used as a substitute for BS5839 whichshould be read in full. In order to help identify the relevant sections, eachdiagram includes a reference to BS5839 Part 1.
BS5839Section5
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
4/20
BS5839
Section
13.
2.
3
BS5839
Section
22.
3
Opticalchamber
SMOKE DETECTOR
>600mmX
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
5/205
BS5839Sec
tion22.3
BS5839Section35.2.3
Thermistor
HEAT DETECTOR
>150mmX
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
6/206
BS5839S
ection
22.
3
BS5839
Section
22.
3
SMOKE DETECTORS
7.5m
5.3m 10.6m
10.6m x 10.6m = 112m2
5.3m
3.8m 7.5m
7.5m x 7.5m = 56.3m2
HEAT DETECTORS
When mounted on a fat ceiling, smoke detection devices have an individualcoverage o 7.5m radius. However these radii must overlap to ensure there areno blind spots. Thereore individual coverage can be represented by a squaremeasuring 10.6x10.6m giving an actual area coverage o 112m2 per device.
When mounted on a fat ceiling, heat detection devices have an individual
coverage o 5.3m radius. However these radii must overlap to ensure there areno blind spots. Thereore individual coverage can be represented by a squaremeasuring 7.5x7.5m giving an actual area coverage o 56.3m2 per device.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
7/20
7
BS5839Sec
tion22.3
SMOKE DETECTOR
Apex >150mm Apex >600mm
HEAT DETECTORSMOKE DETECTOR
Apex
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
8/208
BS5839S
ection
22.
3SMOKE DETECTORS
7.5m
15m
7.5m
15m
7.5m
2m
Incorridorslessthan2mwidethehorizontalspacingofdetectorsmaybeincreased, the areas o coverage need not overlap as in the case o a room.Any corridor over 2m wide is deemed a room and device spacing shouldollow the standard or rooms (see page 6).
Pleasenote,heatdetectorsarenot recommended or use in corridors thatare escape routes.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
9/209
BS5839Sec
tion22.3
BS5839Section22.3
1m
AIR VENT/
AIR CON
PARTITION
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
10/2010
BS5839S
ection
22.
3
BS5839
Section
22.
2
X
D250mm
(Max)
800mm
Nevermountdevicescloserthantwicethedepthoflightttingsorotherobstructions on the ceiling.
Voids less than 800mm in height need not have independent coverage,
unlessreorsmokeisabletospreadfromoneareatoanotherthroughthevoidorriskassessmentshowsAFD(AutomaticFireDetection)tobenecessary.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
11/2011
BS5839Sec
tion22.2
BS5839Section22.2
1.5m
LIFT SHAFT LIFT SHAFTSIFT HAFTL IFT H FTL
1.5m
X
Vertical shats like lits and stairways should have a device mountedwithin 1.5m o any opening.
Enclosedstairwaysshouldhaveadetectoratthetopofthestairwayand
on each main landing.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
12/2012
BS5839S
ection
20.
2
BS5839
Section
20.
2
45m MAX
A person should not have to travel more than 45m along an escape routetoreachaManualCallPoint(25mifdisabledpersontooperate,orrapidredevelopmentislikely).ManualCallPointsshouldbesitedatallstairwells and exits rom the building.
1.4m
(+/200mm)
The centre o the rangible element o the manual call point should be
positioned 1.4m (+/-200mm) rom foor level. (Unless a wheelchair userislikelytobetherstpersontoraisethealarm).
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
13/2013
BS5839Sec
tion16.2.1
BS5839Section1
6.2.1
65dB(A)
@ 500Hz to 1,000Hz
+5dB(A)
@ 500Hz to 1,000Hz
The minimum sound level should be 65dB(A) or 5dB(A) above abackground noise which is louder than 60dB(A) (i lasting more than30seconds)andatafrequencyofbetween500Hzand1000Hz.Themaximum sound level should not be greater than 120dB(A) at anynormally accessible point. May be reduced to 60dB(A) in stairways,enclosures up to 60m2andspecicpointsoflimitedextent.
Sounder device cabling should be arranged so that in the event o a aultatleastonesounderwillremainoperationalduringarecondition.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
14/2014
BS5839
Section
16.2.1
BS5839
Section
16.
2.
1
75dB(A)
30dB(A)20dB(A)
FIREDOOR
For areas where people are sleeping, sounder devices should producea minimum 75dB(A) at the bed-head with all doors shut. In buildingsprovidingsleepingaccomodationforasignicantnumberofpeople,allbedrooms should have both audible and visual alarms.
Decibellossoccursthroughdoors:approximately20dB(A)througha
normaldoor,andapproximately30dB(A)througharedoor.Unlessasounderisinstalledinabedroom,itisunlikelythat75dB(A)willbeachieved.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
15/2015
>2.1m
BS5839Sec
tion17
BS5839Section26.2
Visual alarms such as beacons should always be mounted at a minimumheight o 2.1m rom foor level.
2m
Unless MICC cable is used, all cabling should be mechanically protected
rom foor level up to a height o 2m. In relatively benign areas, such asshops,ofcesandsimilar,cablingcanbeclippedtorobustwallsetc.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
16/2016
BS583
9
Section
26
BS5839
Section
12.2.2
Mains supply
EOL BUILT IN
Short circuit isolators limit the eect o one ault to 2000m2. 2 simultaneous
aults on a circuit should not disable protection within an area greaterthan 10,000m2.
Fireresistantcablingisnowrequiredwithinthewholerealarmsystemincludingthemainssupplycables.Theuseofnon-reresistingcableswhethermechanicallyprotectedbyre-resistingconstructionornot,willnolongercomplywithBS5839Part1.
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
17/2017
Installation Considerations and Key Points
Allmainssupplyisolatorsmustbedoublepoleandsuitablymarked.(25.2c&f)
Allcablestobefireresistingwithaminimumcross-sectionalareaof1mm.(26.2j)
Alljointstobefireresisting,junctionboxestobelabelledFIREALARM.(26.2)
Enhancedcabletobeusedwheremorethan4zonesofphasedevacuationrequired, or in multi storey systems. (un-sprinklered over 30m) or risk assessmentrequires enhanced cable. (26.2)
CableusingtrunkingasameansofcontainmentmustbeclippedusingfireresistantsupportsWITHINTHETRUNKING.(26.2)
FireAlarmcontrolpanel(s)areinstalledatalocationappropriateforstaffand
ire-ighters. (23.2)Callpointsarerequiredatallexitstotheopenair-whetherornottheexitsare
speciically designed to be ire exits. (20.2c)
COfiredetectorsshouldbespacedaspersmokedetectors,butcannotbeusedwithout smoke detectors on escape routes. (28.1.8)
Multisensors,ifusedascombinedtype/spaceassmokedetectors,ifusedasindividualtypesieheatintheday&smokeatnightthenspaceasperheat
detectors. (26.1.6)Linearheatdetectioncablespaceasheatdetectors.(22.3)
Unusualceilings:Cellularceiling,perforatedceilingsorceilingswithcloselyspacedbeamshavespecialspacing&installationrequirements,refertosection.(22.3&tables1&2)
Bells&Electronicsounderscannotbemixed(16.2.1c)
Soundlevelscanbereducedto60dB(A)instairs,smallcellularofficesor
enclosuresofnomorethanAPPROXIMATELY60sqmBedheadlevelsremains 75dB(A). (16.2.1)
Iftheambientbackgroundnoiselevelisover90dBvisualalarms(beacons)arerequired. (17.2a)
Disabledtoiletsshouldbefittedwithsoundersandbeacons.(18.1)
Aminimumofonesounderisrequiredineachfirecompartment.(16.2.1i)
Fulldocumentationrequired,testresultsasfitteddrawingsetc.(Section40)
Aninstallationcertificatewillberequired.(41.2)
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
18/2018
3 Installation and Handover Checklist
1 The system complies with the original speciication / design
2 Any changes to original speciication/design have been reerred to thesystem designer or approval
3 System has been installed to meet requirements o category L1, L2, L3, L4,
L5,P1,P2,M,other 4 Variations to the deined category have been identiied and the schedule o
variations agreed with the client
5 Cables meet requirements or standard/enhanced/mixed
6 Cables are segregated as required and suitably supported (no plastic clips,cable ties or trunking used as sole means o support)
7 Cables are mechanically protected as required.
8 Junction boxes are correctly labelled and identiied on drawings.
Connector blocks are ire resistant. 9 All cable insulation and continuity resistance measurements are logged
10 All cable penetrations are sleeved and ire stopped
11 Mains supply is dedicated, non-switched, correctly used and labelled
12 Mains supply is correctly identiied at all distribution boards
13 Standby battery veriication has been carried out or all power supplies
14 All batteries are clearly marked and labelled with date o installation
15 Field wiring is labelled and correctly terminated in all control and ancillary
equipment16 Isolators are itted as appropriate, operate correctly and are marked on
drawings
17 There are a minimum o two sounder circuits installed
18 Sound pressure levels have been checked and recorded and meet theminimum requirements.
19 Detectortypeandspacingisappropriatetothesystemcategory
20 MCPsarelocatedcorrectlyandtraveldistanceisappropriatetothesystem
category21 Remote signalling has been checked or correct operation to Alarm
Receiving Centre
22 Zonechartshavebeenfittedinallappropriatelocations(adjacenttocontrol equipment and repeaters)
23 As itted drawings are complete and have been updated where required,includingcablesizeandrouting
24 Log book and operating instructions have been issued to the responsibleperson
25 The responsible person has been adequately trained in the use o the irealarm system
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
19/2019
-
7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002
20/20
ApolloFireDetectorsLimited36 Brookside Road, Havant,Hampshire,PO91JR,UK.
Tel: +44 (0)23 9249 2412Fax: +44 (0)23 9249 2754
Email:[email protected]: www.apollo-ire.co.uk
PP2328/2013/Issue6
By Appointment toHerMajestyTheQueen
ManufacturersofFireDetection&AlarmProducts
ApolloFireDetectorsLimitedHampshire
Inormation in this guide is given in good aith, butApolloFireDetectorscannotbeheldresponsibleforany omissions or errors. The company reserves theright to change speciications o products at any timeand without prior notice.