A Guide to Fire Alarm System Design BS 5839 Part 1:2002

download A Guide to Fire Alarm System Design BS 5839 Part 1:2002

of 20

Transcript of A Guide to Fire Alarm System Design BS 5839 Part 1:2002

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    1/20

    Fire Alarm Systems Design

    BS5839Part1:2002incorporating Amendment No.2

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    2/202

    Legally you must comply!

    What is the RRO?

    Fire authorities no longer issue irecertiicates and those previouslyin orce will have no legal status.The Regulatory Reorm (Fire Saety)Order (RRO) replaces most ire saetylegislation with one new order. It

    means that any person who has somelevel o control in premises must takesteps to reduce the risk rom ire,consider how to contain a ire shouldone break out and then also makesure people can saely escape i thereis a ire.

    All fire alarm designs should bebasedonaFireRiskAssessment

    AllFireRiskAssessmentsshouldbe carried out by a competentperson

    FireRiskassessmentsmustbereviewed annually

    What constitutes a Fire Risk

    Assessment?Identifyingfirehazardssuchas

    sources o ignition, uel or oxygen

    Identifyingallpeopleatriskinand around the premises

    Evaluatingtheriskofafirestartingor the risk to people rom a ire

    Removingorreducingfirehazardsor risks to people rom a ire

    Protectingpeoplebyproviding ire precautions

    Recordinganymajorfindings

    Preparinganemergencyplan

    Informingandinstructingany relevant people

    ProvidingtrainingforstaffandguestsReviewingthefirerisk

    assessment regularly and makechanges where necessary

    Keepingaccuratefireriskassessment records

    The Regulatory Reform (Fire Safety) Order (RRO)became law on 1 October 2006

    AllfirealarmdesignsshouldbebasedonaFireRiskAssessment

    Where does the order apply?

    Virtually all premises and nearly every type o building structure and open space.

    I you would like to ind out more about how Apollo products can helpyou comply with the RRO please contact us on 023 9249 2412 or visit ourwebsite on www.apollo-fire.co.uk

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    3/203

    Property Protection Fire Systems

    P1 AFDinstalledthroughoutallareas

    P2 AFDinstalledonlyindefinedareas

    Life Protection Fire Systems

    L AFDdesignedtoprimarilyprotectHuman Lie

    L1 AFDinstalledthroughoutallareas

    L2 AFDinstalledindefinedareasinaddition to L3

    L3 AFDinstalledinescaperoutesandrooms opening onto these routes

    L4 AFDinstalledinescaperoutescomprising circulation areas andspaces such as corridors and stairways

    L5 A non-prescriptive system in whichprotected area(s) and/or the locationo detectors is designed to satisy

    aspecificfireriskobjective(otherthan that o L1 to L4)

    M System design to be operatedmanually(noAFD)

    *AFDAutomaticFireDetection

    FireAlarmandDetectionsystemsare

    categorised in the following way:

    P1 P2

    L1 L2L4 L3

    This guide is intended to be an aid to designers and installers of firedetection systems. It is not to be used as a substitute for BS5839 whichshould be read in full. In order to help identify the relevant sections, eachdiagram includes a reference to BS5839 Part 1.

    BS5839Section5

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    4/20

    BS5839

    Section

    13.

    2.

    3

    BS5839

    Section

    22.

    3

    Opticalchamber

    SMOKE DETECTOR

    >600mmX

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    5/205

    BS5839Sec

    tion22.3

    BS5839Section35.2.3

    Thermistor

    HEAT DETECTOR

    >150mmX

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    6/206

    BS5839S

    ection

    22.

    3

    BS5839

    Section

    22.

    3

    SMOKE DETECTORS

    7.5m

    5.3m 10.6m

    10.6m x 10.6m = 112m2

    5.3m

    3.8m 7.5m

    7.5m x 7.5m = 56.3m2

    HEAT DETECTORS

    When mounted on a fat ceiling, smoke detection devices have an individualcoverage o 7.5m radius. However these radii must overlap to ensure there areno blind spots. Thereore individual coverage can be represented by a squaremeasuring 10.6x10.6m giving an actual area coverage o 112m2 per device.

    When mounted on a fat ceiling, heat detection devices have an individual

    coverage o 5.3m radius. However these radii must overlap to ensure there areno blind spots. Thereore individual coverage can be represented by a squaremeasuring 7.5x7.5m giving an actual area coverage o 56.3m2 per device.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    7/20

    7

    BS5839Sec

    tion22.3

    SMOKE DETECTOR

    Apex >150mm Apex >600mm

    HEAT DETECTORSMOKE DETECTOR

    Apex

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    8/208

    BS5839S

    ection

    22.

    3SMOKE DETECTORS

    7.5m

    15m

    7.5m

    15m

    7.5m

    2m

    Incorridorslessthan2mwidethehorizontalspacingofdetectorsmaybeincreased, the areas o coverage need not overlap as in the case o a room.Any corridor over 2m wide is deemed a room and device spacing shouldollow the standard or rooms (see page 6).

    Pleasenote,heatdetectorsarenot recommended or use in corridors thatare escape routes.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    9/209

    BS5839Sec

    tion22.3

    BS5839Section22.3

    1m

    AIR VENT/

    AIR CON

    PARTITION

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    10/2010

    BS5839S

    ection

    22.

    3

    BS5839

    Section

    22.

    2

    X

    D250mm

    (Max)

    800mm

    Nevermountdevicescloserthantwicethedepthoflightttingsorotherobstructions on the ceiling.

    Voids less than 800mm in height need not have independent coverage,

    unlessreorsmokeisabletospreadfromoneareatoanotherthroughthevoidorriskassessmentshowsAFD(AutomaticFireDetection)tobenecessary.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    11/2011

    BS5839Sec

    tion22.2

    BS5839Section22.2

    1.5m

    LIFT SHAFT LIFT SHAFTSIFT HAFTL IFT H FTL

    1.5m

    X

    Vertical shats like lits and stairways should have a device mountedwithin 1.5m o any opening.

    Enclosedstairwaysshouldhaveadetectoratthetopofthestairwayand

    on each main landing.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    12/2012

    BS5839S

    ection

    20.

    2

    BS5839

    Section

    20.

    2

    45m MAX

    A person should not have to travel more than 45m along an escape routetoreachaManualCallPoint(25mifdisabledpersontooperate,orrapidredevelopmentislikely).ManualCallPointsshouldbesitedatallstairwells and exits rom the building.

    1.4m

    (+/200mm)

    The centre o the rangible element o the manual call point should be

    positioned 1.4m (+/-200mm) rom foor level. (Unless a wheelchair userislikelytobetherstpersontoraisethealarm).

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    13/2013

    BS5839Sec

    tion16.2.1

    BS5839Section1

    6.2.1

    65dB(A)

    @ 500Hz to 1,000Hz

    +5dB(A)

    @ 500Hz to 1,000Hz

    The minimum sound level should be 65dB(A) or 5dB(A) above abackground noise which is louder than 60dB(A) (i lasting more than30seconds)andatafrequencyofbetween500Hzand1000Hz.Themaximum sound level should not be greater than 120dB(A) at anynormally accessible point. May be reduced to 60dB(A) in stairways,enclosures up to 60m2andspecicpointsoflimitedextent.

    Sounder device cabling should be arranged so that in the event o a aultatleastonesounderwillremainoperationalduringarecondition.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    14/2014

    BS5839

    Section

    16.2.1

    BS5839

    Section

    16.

    2.

    1

    75dB(A)

    30dB(A)20dB(A)

    FIREDOOR

    For areas where people are sleeping, sounder devices should producea minimum 75dB(A) at the bed-head with all doors shut. In buildingsprovidingsleepingaccomodationforasignicantnumberofpeople,allbedrooms should have both audible and visual alarms.

    Decibellossoccursthroughdoors:approximately20dB(A)througha

    normaldoor,andapproximately30dB(A)througharedoor.Unlessasounderisinstalledinabedroom,itisunlikelythat75dB(A)willbeachieved.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    15/2015

    >2.1m

    BS5839Sec

    tion17

    BS5839Section26.2

    Visual alarms such as beacons should always be mounted at a minimumheight o 2.1m rom foor level.

    2m

    Unless MICC cable is used, all cabling should be mechanically protected

    rom foor level up to a height o 2m. In relatively benign areas, such asshops,ofcesandsimilar,cablingcanbeclippedtorobustwallsetc.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    16/2016

    BS583

    9

    Section

    26

    BS5839

    Section

    12.2.2

    Mains supply

    EOL BUILT IN

    Short circuit isolators limit the eect o one ault to 2000m2. 2 simultaneous

    aults on a circuit should not disable protection within an area greaterthan 10,000m2.

    Fireresistantcablingisnowrequiredwithinthewholerealarmsystemincludingthemainssupplycables.Theuseofnon-reresistingcableswhethermechanicallyprotectedbyre-resistingconstructionornot,willnolongercomplywithBS5839Part1.

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    17/2017

    Installation Considerations and Key Points

    Allmainssupplyisolatorsmustbedoublepoleandsuitablymarked.(25.2c&f)

    Allcablestobefireresistingwithaminimumcross-sectionalareaof1mm.(26.2j)

    Alljointstobefireresisting,junctionboxestobelabelledFIREALARM.(26.2)

    Enhancedcabletobeusedwheremorethan4zonesofphasedevacuationrequired, or in multi storey systems. (un-sprinklered over 30m) or risk assessmentrequires enhanced cable. (26.2)

    CableusingtrunkingasameansofcontainmentmustbeclippedusingfireresistantsupportsWITHINTHETRUNKING.(26.2)

    FireAlarmcontrolpanel(s)areinstalledatalocationappropriateforstaffand

    ire-ighters. (23.2)Callpointsarerequiredatallexitstotheopenair-whetherornottheexitsare

    speciically designed to be ire exits. (20.2c)

    COfiredetectorsshouldbespacedaspersmokedetectors,butcannotbeusedwithout smoke detectors on escape routes. (28.1.8)

    Multisensors,ifusedascombinedtype/spaceassmokedetectors,ifusedasindividualtypesieheatintheday&smokeatnightthenspaceasperheat

    detectors. (26.1.6)Linearheatdetectioncablespaceasheatdetectors.(22.3)

    Unusualceilings:Cellularceiling,perforatedceilingsorceilingswithcloselyspacedbeamshavespecialspacing&installationrequirements,refertosection.(22.3&tables1&2)

    Bells&Electronicsounderscannotbemixed(16.2.1c)

    Soundlevelscanbereducedto60dB(A)instairs,smallcellularofficesor

    enclosuresofnomorethanAPPROXIMATELY60sqmBedheadlevelsremains 75dB(A). (16.2.1)

    Iftheambientbackgroundnoiselevelisover90dBvisualalarms(beacons)arerequired. (17.2a)

    Disabledtoiletsshouldbefittedwithsoundersandbeacons.(18.1)

    Aminimumofonesounderisrequiredineachfirecompartment.(16.2.1i)

    Fulldocumentationrequired,testresultsasfitteddrawingsetc.(Section40)

    Aninstallationcertificatewillberequired.(41.2)

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    18/2018

    3 Installation and Handover Checklist

    1 The system complies with the original speciication / design

    2 Any changes to original speciication/design have been reerred to thesystem designer or approval

    3 System has been installed to meet requirements o category L1, L2, L3, L4,

    L5,P1,P2,M,other 4 Variations to the deined category have been identiied and the schedule o

    variations agreed with the client

    5 Cables meet requirements or standard/enhanced/mixed

    6 Cables are segregated as required and suitably supported (no plastic clips,cable ties or trunking used as sole means o support)

    7 Cables are mechanically protected as required.

    8 Junction boxes are correctly labelled and identiied on drawings.

    Connector blocks are ire resistant. 9 All cable insulation and continuity resistance measurements are logged

    10 All cable penetrations are sleeved and ire stopped

    11 Mains supply is dedicated, non-switched, correctly used and labelled

    12 Mains supply is correctly identiied at all distribution boards

    13 Standby battery veriication has been carried out or all power supplies

    14 All batteries are clearly marked and labelled with date o installation

    15 Field wiring is labelled and correctly terminated in all control and ancillary

    equipment16 Isolators are itted as appropriate, operate correctly and are marked on

    drawings

    17 There are a minimum o two sounder circuits installed

    18 Sound pressure levels have been checked and recorded and meet theminimum requirements.

    19 Detectortypeandspacingisappropriatetothesystemcategory

    20 MCPsarelocatedcorrectlyandtraveldistanceisappropriatetothesystem

    category21 Remote signalling has been checked or correct operation to Alarm

    Receiving Centre

    22 Zonechartshavebeenfittedinallappropriatelocations(adjacenttocontrol equipment and repeaters)

    23 As itted drawings are complete and have been updated where required,includingcablesizeandrouting

    24 Log book and operating instructions have been issued to the responsibleperson

    25 The responsible person has been adequately trained in the use o the irealarm system

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    19/2019

  • 7/22/2019 A Guide to Fire Alarm System Design BS 5839 Part 1 2002

    20/20

    ApolloFireDetectorsLimited36 Brookside Road, Havant,Hampshire,PO91JR,UK.

    Tel: +44 (0)23 9249 2412Fax: +44 (0)23 9249 2754

    Email:[email protected]: www.apollo-ire.co.uk

    PP2328/2013/Issue6

    By Appointment toHerMajestyTheQueen

    ManufacturersofFireDetection&AlarmProducts

    ApolloFireDetectorsLimitedHampshire

    Inormation in this guide is given in good aith, butApolloFireDetectorscannotbeheldresponsibleforany omissions or errors. The company reserves theright to change speciications o products at any timeand without prior notice.