A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

download A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

of 23

Transcript of A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    1/23

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    2/23

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    3/23

    Insert the other end of the ground wire into the receptacle on the ground buss of the panel. Tighten the

    holding screw.

    Earthing Systems

    Published on January 23, 2012, by admin in Electrical.

    What is Earthing? Earthing is the green and yellow insulated cable that runs throughout your property.

    The earthing system is a special system designed to protect you from the faults that frequently develop

    with electrical systems.

    The earthing wire defines the electrical potential of the conductors relative to the earths conductive

    surface a (PE) for short. To put it very simply it stops you from getting an electric shock when a live

    cable touches things it shouldnt be. The issue is almost instantly read by your residual current device

    and your power is then tripped off by your circuit breaker.

    This clever earthing system plays a crucual role in the health and safety aspect of electricity systems.

    http://www.candnpropertysolutions.co.uk/blog/electrical/earthing-systems.html.10th july

    How to Detect a Short in Electrical Wiring in a House

    By G.K. Bayne, eHow Contributor

    Detecting a short in electrical wiring is a simple task once you understand what it means and how it was

    caused. An electrical short can be caused by two wires coming in contact with each other. Another cause

    may be a defective receptacle outlet or light fixture. An electrical short will show itself by fuses being

    repetitively blown or the circuit breaker tripping out constantly. Following the steps below should allow

    you to troubleshoot the problem.

    Other People Are Reading

    How Does a Safety Switch in a House Work?

    How to Ground Your Home Electrical Panel

    http://www.candnpropertysolutions.co.uk/blog/electrical/earthing-systems.html.10thhttp://www.candnpropertysolutions.co.uk/blog/electrical/earthing-systems.html.10thhttp://www.candnpropertysolutions.co.uk/blog/electrical/earthing-systems.html.10th
  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    4/23

    Print this article

    Things You'll Need

    Volt ohmmeter

    Screwdrivers: Philips and slotted

    Wire pliers

    Instructions

    1

    Unplug the device--toaster, microwave or lamp--that is connected to the circuit. Reset the breaker or

    replace the fuse. You want to eliminate any device that may be defective before proceeding. Energize

    the circuit; if the breaker or fuse does not blow, then the device is bad and should be repaired or

    replaced. If the circuit still trips out or blows the fuse, then there is a possible short in the wiring or the

    receptacle.

    2

    Switch off the circuit that keeps tripping or remove the fuse from the troubled circuit. Take the volt

    ohmmeter and switch it to volts. Insert the metal probe ends into the troubled receptacle and test for

    voltage to be sure the circuit is off. The voltage should read zero volts. Remove the receptacle or fixture

    from the box with the screwdriver. Pull the wires from the sides of the receptacle or fixture using the

    screwdriver and wire pliers.

    Sponsored Links

    Oscilloscope Calibration

    Fully-Automated Oscilloscope Calibration Solutions by Fluke!

    flukecal.com/Get_Free_Quote

    3

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    5/23

    Use the volt ohmmeter and switch it to ohms. Test the wires for a short condition by placing each lead

    to one of the bare ends of the insulated wires. Touch one lead of the ohmmeter to the black wire and

    the other lead to the white wire. The meter should show infinite ohms or an O.L. if its a digital meter. If

    it does, the receptacle or fixture is defective and needs to be replaced. If the meter reading does show

    continuity, the short could be in the wire or the circuit breaker.

    4

    Remove the cover from the circuit breaker box after first shutting off the main breaker that controls the

    power. Remove the wires from the troubled breaker or fuse connection and the corresponding white

    wire. This white wire will be enclosed in the same insulated jacket as the black wire.

    5

    Test the wires for a short condition. The meter should read wide-open, infinite ohms or O.L.. If it does,

    the breaker is defective; replace the bad circuit breaker with an original replacement. If the wire shows

    a short condition, reading zero ohms or any resistance reading at all, the wire is shorted in the circuit.

    The wire will have to be replaced.

    Sponsored Links

    AutoCAD is a software application for computer-aided design (CAD) and drafting. The software supports

    both 2D and 3D formats. The software is developed and sold by Autodesk, Inc.,[1] first released in

    December 1982 by Autodesk in the year following the purchase of the first form of the software by

    Autodesk founder, John Walker. http://en.wikipedia.org/wiki/AutoCADn july10th

    snappybob

    Aug 8, 2005, 10:16 AM

    I am re-wiring an old house. It is a small 2 bedroom, 1 bath house. We put in a 200 amp service and

    need to run a sevice entrance cable about 20 -25 ft to the inside breaker panel. My question is how big

    of a gauge wire should we run for the sevice entance cable. #? 3 conductor with ground in copper. We

    have 18 -110v outlets, 3 - 220V outlets (Window AC, Kitchen Stove and clothes dryer), 3 ceiling fans with

    lights, Electric bathroom heater in ceiling. Etc.

    Thanks

    kp2171

    Aug 8, 2005, 12:07 PM

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    6/23

    I'm really not trying to be a snot when I say this, but if you have to ask in this case, you may not be

    qualified.

    I think its one thing to work within a panel. To run service to the panel is another. Don't tighten that

    connection correctly and you're certain to have a fire eventually.

    I'd personally hire a licensed and qualified electrician to run service to the panel.

    I know the guys in the know will have some advice....

    snappybob

    Aug 8, 2005, 02:45 PM

    Acually KP I'm helping an electrician wire my house. I do the grunt work, he does the real wiring. The

    reason for the post was to just check and see if important things like the service are being done

    correctly.

    kp2171

    Aug 8, 2005, 03:17 PM

    I'm sure one of the pros here can confirm the demand need.

    tkrussell

    Aug 8, 2005, 04:30 PM

    First off, a 200 amp service with a panel 20-25 feet away shall have a disconnect outside at the meter

    location. This can be either a 200 amp breaker, or fuses, in a NEMA 3R Raintite enclosure. Some meter

    trim come with a disconnect built in together.

    Agai, due to the distance, the cable can be a #4/0 XHHW insulation Aluminum 4 wire cable. Thsi is called

    SER cable. This is a very popular cable. Even thou some aluminum cable is listed to be connected

    without an anitoxident treatment, "grease" treatment similar to gray lotion, most electricans still use it.

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    7/23

    Another important issue is grounding at the panel. The neutral must be isolated from the backbox of

    the panel and no green or bare grounds shall be connected to it, only branch circuit neutrals. A separate

    ground bar (terminal strip) shall be bolted to the panel backbox and this is for all the greens and the

    bare wires, including the bare in the SER cable. Connected in any other way can cause various problems

    to detailed to go through here.

    If you chose copper, and keep in mind, aluminum feeder cable is fine providing it is installed per

    manufacturers instructions, cable similar to SER cable is not very common, but is available usually by

    special order.

    You may be able to wrestle 2 inch PVC conduit in , and you can use #3/0 copper wire with THHN/THWN

    insulation, three for the feeders, and a #6 copper ground green wire.

    By the way, again due to the distance and the main breaker located outside, the system ground must

    connect to the neutral out at the meter/disconnect.

    This system is usually two eight foot ground rods , spaced 6 foot or more apart, and a wire going the

    water system. If you have a water meter, the #6 wire may need to connect to both sides of the water

    meter to jump out the meter, so to speak.

    Hope this answers your question.

    Friend has a permit,right?

    snappybob

    Aug 8, 2005, 05:29 PM

    Yes, we have a permit. I'm putting the house up for sale when all of the renovations are complete so the

    electrical has to be inspected by the city. One thing that has me concerned is the fact that the service

    cable that the electricians are having me locate and get is #1-3 w/ground copper. None of the supply

    houses stock this cable. A 200A service is what is required by the city. I would think it would be readily

    available. In my mind this raises a red flag. Also, the electricians are saying that you size the service cable

    to the panel inside the house which is under 200A and there will be a 100A breaker on the primary panel

    outside so that the house can only draw 100A. Thanks for all your input. This is a really great website

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    8/23

    tkrussell

    Aug 9, 2005, 12:53 PM

    Well #1 copper has a ampacity of 150 amps , when used for residential service.

    I do need to make a correction, you can use #2/0 copper for 200 amp residential service, I gave you

    #3/0, which is for all applications other than residential.

    Whoever signs the permit, even if the inspector does not catch the mistake, will be held liable for any

    problems that occur later. So if the #1 does get installed, the permittee will own it.

    You as the seller, may be doubly responsible, as the seller of a property with a faulty condition, that you

    were knowledgeable of and possibly installed or party to.

    You may want to check with an attorney for the exact liability exposure.

    Make this go away, and install either #2/0 copper or #4/0 aluminum.

    The #4/0 Al SER cable is readily avaialbe at every electrical supply house, and every big box home

    improvement store. So simple to make this all go away.

    I am trying to follow what is being installed. City wants a minimum[ of 200 amps, but the main panel is

    less than 200, then you do not have a 200 amp service. A little difficult to determine exactly what you

    are installing. I hope I have cleared up any question you still may have.

    snappybob

    Aug 10, 2005, 06:30 AM

    TK and others, thanks again for your input. Let me try and clarify the situation. The city code requires

    200A service at the primary panel outside on new consruction and re-wires so that all residential home

    are upgraded. I suspect this is driven by the fact that the people that write the city codes are mostly

    electricians and enfluenced by local electrical contractors and electrical equipment suppliers.

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    9/23

    I guess my real question here is, what parameters do you use to determine the size of wire used that

    feeds the secondary interior panel:

    A) the rating of the primary outside panel regardless of any breakers or fuses that would limit it's

    potential. In this case 200A

    B) the rating of the inside secondary panel regardless of any breakers or fuses that would limit it's

    potential. In this case I believe 150A

    C) The potential of the inside panel after concidering it's potential that would be limited by the number

    and size of breakers installed for the circuits installed in the house.

    I hope this is a little clearer.

    Thanks

    tkrussell

    Aug 11, 2005, 04:01 PM

    Having a little trouble following this. What do you mean by primary panel outside? Does this mean you

    will have a 200 amp breaker panel outside? Will this contain branch circuit breakers, and then you will

    have a subpanel in the basement which will be 100 amp?

    The inside panel will have an amp rating, I get from your post 100 amp rated. This panel must be

    protected by a circuit breaker, 100 amp in the outside panel, the wire can be # 3 copper THHN or XHHW

    insulation or # 2 aluminum XHHW insulation, three wires each plus a ground, lets just keep this at #8

    copper to keep it simple.

    The outside panel needs to have a 200 amp breaker protectng it.

    Is my understanding correct? Does any of this make sense?

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    10/23

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    11/23

    I hope this helps explain the situation. If not get back with more questions.

    labman

    Aug 19, 2005, 12:50 PM

    In a few fires I witnessed, the fireman went ahead and pulled the meter.

    tkrussell

    Aug 19, 2005, 03:38 PM

    Pulling the meter is clever, and will shut down power to the building, however still dangerous. This will

    leave the two live line jaws of the meter socket exposed wide open to all personel in the vincinity.

    They may do it in certain cases, where a structure is only partially involved, and they deterimine the

    structure can be saved by flooding that area with water. Hopefully the fire is on the opposite side away

    from the meter.

    Most firemen, I believe, religiously respect electricity. They say it does not mix well with water, another

    perspective is that electricity mixes all too well with water.

    I have had to respond to sites with firemen on site, standing off to the side, waiting for me to make

    something safe before they would proceed with their task, of course never been a raging fire.

    teacha

    Aug 19, 2005, 04:00 PM

    Thanks!

    I appreciate the use the main has on the outside by the fire department. Certainly even a home owner

    or renter could also throw it if an emergency happened inside without any danger to themselves from

    the electricity. I think it ought to be in the code, if for no other reason than what you have said.

    Tom

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    12/23

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    13/23

    because it is illegal to have only one grounded wire on feeder circuit.You need a properly sized

    equipment grounding wire too on a feeder.To prevent ground loop current one must INSULATE the

    neutral conductor from the bare ground wire inside the secondary panel..This is a must.It is also a good

    idea to drive a ground rod at the disconnect socket and tie the neutral and ground wires at the

    disconnect meter socket terminals to the rod and any other grounding electrodes that might be

    present.Okay now snappybob:this is how we do it..We use NEC Article 220 Branch Circuit and Feeder

    Calculations.Okay you say you have a 200 amp required by the city.That pretty much tells you what size

    feeder cable you are going to use period.4/0 Aluminum SER style cable or 2/0 copper SER style cable or

    THHN wire in conduit.What we usually do derate the neutral wire (which must be white!)one size down

    so a nunk of 1/0 wire if you are going to usecopper.You will need #4 bare wire from the service

    disconnect breaker/meter socket combination to the ground rod but you and use #6 bare copper to the

    interior panel.Can you tell I have done my share of services?No matter what the panel all panelboards

    are limited to 42 circuits only.You will never find one with more tyhan 42 circuits,again that an NEC

    article.YOur interior panel is rated for 200 amperes and the rating shall not exceed 125% of 200 amperes

    continuous load.

    stanfortyman

    Oct 25, 2011, 06:33 PM

    No I think he means a disconnect style meter socket.There is no real Code article that tells you when a

    situation requires a disconnect at the socket,I do know that we always used a disconnect type meter

    socket when the interior panel was located more than 8 feet from the socket.We also used disconnect

    sockets when the AHJ(the inspector)for the locality required it.Some do and some dont.OK using a

    disconnect style socket requires you to use SER style cable or 3 conductors and a ground wire conduit

    because it is illegal to have only one grounded wire on feeder circuit.You need a properly sized

    equipment grounding wire too on a feeder.To prevent ground loop current one must INSULATE the

    neutral conductor from the bare ground wire inside the secondary panel..This is a must.It is also a good

    idea to drive a ground rod at the disconnect socket and tie the neutral and ground wires at the

    disconnect meter socket terminals to the rod and any other grounding electrodes that might be

    present.Okay now snappybob:this is how we do it..We use NEC Article 220 Branch Circuit and Feeder

    Calculations.Okay you say you have a 200 amp required by the city.That pretty much tells you what size

    feeder cable you are going to use period.4/0 Aluminum SER style cable or 2/0 copper SER style cable or

    THHN wire in conduit.What we usually do derate the neutral wire (which must be white!)one size down

    so a nunk of 1/0 wire if you are going to usecopper.You will need #4 bare wire from the service

    disconnect breaker/meter socket combination to the ground rod but you and use #6 bare copper to the

    interior panel.Can you tell I have done my share of services?No matter what the panel all panelboards

    are limited to 42 circuits only.You will never find one with more tyhan 42 circuits,again that an NEC

    article.YOur interior panel is rated for 200 amperes and the rating shall not exceed 125% of 200 amperes

    continuous load.

    Well, you may have done your share of these, but much of what you write is incorrect.

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    14/23

    There is a code telling that an outside disco is required. The one that says if the panel is too far into the

    structure, or a local code amendment. The inspector cannot request what has not been written. It's not

    his call.

    "Ground loops" are not an issue in AC building wiring. Not sure where you got that one from.

    It is not just a good idea to drive an electrode at a main disconnect. It is a requirement.

    You do not need #4cu to a ground rod. A connection to just a ground rod requires no larger than #6cu.

    Also the correct size equipment ground from a 200A main disconnect to panel is #4cu.

    The 42 circuit limit was lifted for the 2011 NEC cycle.

    A continuous load is ABSOLUTELY NOT 125% of the panel rating.

    A 200A panel is rated for 200A, and 80% of that for a continuous load, or 160A.

    And lastly, you are addressing the OP like he is around to read and apply your advice. This thread is

    from 2005. I think it is a safe bet that this is all done by now. :rolleyes:

    Riders3627

    Jan 11, 2012, 04:24 PM

    Tk Russel wrote "This system is usually two eight foot ground rods , spaced 6 foot or more apart, and a

    wire going the water system. If you have a water meter, the #6 wire may need to connect to both sides

    of the water meter to jump out the meter, so to speak."

    This is incorrect.... Sorry tk but the NEC requires that anything within 2/0-3/0 Copper or 4/0-500 kcmil

    requires a # 4 Copper wire for a grounding electrode to the water main only if such pipe is copper and in

    direct contact with the earth no less that 25'( usually you would just hook it up anyways and always

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    15/23

    jump the meter). Now the ground rods are okay to use with #6 copper wire and must be green or

    reidentified inside the panel or meter box.

    Now to the service question a 2 bedrm house with 1 bath seems quite small for a 200A service. Now i

    dont know the demand of the house and maybe you want a Hot tub outside (which requires a 200a

    service) oR you have a lot of electric heat... But 9 times out of 10 an electrician will suggest a 200 a

    service to get the 17-1800 dollars (Massachusetts price) but in reality 100 or 150 a service will do just

    fine and also the sizing of the wire tk got it right a 4/0 SER aluminum cable is great and it depends on the

    disconnect. If it is 25' on the exterior of the wall and penetrating through the house the wire goes

    directly to the panel ( Usually 10' in wire length) there is no disconnect required. Copper for residential

    wiring is not needed considering we up here in mass feed 5 unit bldgs with 125 A Panles each with 500

    KCMIL Aluminum wires and lasted for 10 years thus far no problems. Hope this helps

    stanfortyman

    Jan 11, 2012, 06:18 PM

    ... But 9 times out of 10 an electrician will suggest a 200 a service to get the 17-1800 dollars....

    No, they will suggest it because it makes little sense in today's world to install a new 100A service, or

    replace an old 100A with another 100A. Unless of course it is some kind of 800 sq/ft bungalow.

    And it makes absolutely no sense to install a 150 when a 200 is only a few dollars more in material and

    NO different in labor.

    Lastly, I feel sorry for you if you can only get $1700 for a 200A upgrade in MA. You are selling yourself

    short.

    SparkyyKcK

    Apr 26, 2012, 03:53 PM

    so i take it the meter can is 200 amp ready, the riser wire should be 4/O the se cable can probally be

    2/O, a 150 amp breaker in the disconnect, and then 100 amp breaker in the pannel. thats a really weird

    code to retro-fit up too a 200 amp meter, but the city wants their moneys i guess... btw dont forget your

    water ground!!

    stanfortyman

    Apr 26, 2012, 04:41 PM

    Why don't people read all the posts???

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    16/23

    This thread has gone from originally 2005, to 2008, to 2011, to Jan of this year. All with the OP not

    returning since 2005!

    Copyright 2005-, Ask Me Help Desk

    How to do Electrical Testing

    By Jerry Walch, eHow Contributor

    There are many tools and procedures involved in electrical testing. The techniques covered here will

    allow you to solve 90 percent of your electrical troubleshooting issues. The testing procedures will not

    only help you locate almost any electrical problem, but they will help you ensure the electrical safety ofyour home and loved ones. Does this Spark an idea?

    Other People Are Reading

    How to Test a Wall Socket

    How to Test the Wiring in a House

    Print this article

    Things You'll Need

    Plug-in GFCI (Ground Fault Current Interrupter) receptacle tester

    DMM (Digital Multimeter)

    Clamp-On Ammeter

    Instructions

    Receptacles and GFCI Receptacle Circuits

    1

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    17/23

    Unplug everything on the circuit for a general-purpose receptacle that appears to be working normally,

    then plug the GFCI receptacle tester into each receptacle on the circuit in succession. Depending on the

    number of lights lit and their pattern, you will know instantly if the receptacle is properly wired and

    functioning correctly. You will know if the "hot" and "neutral" conductors--the black and white wires--

    are reversed, or if the "grounding" and "neutral" conductors--green or bare and white wires--are

    reversed. This will also show if the "neutral" or the "grounding" conductors/circuits are open. An open

    grounding conductor is very dangerous.

    2

    Locate any nonfunctioning receptacles. If there are a number of dead receptacles on the same branch

    circuit, begin your testing at the one closest to the service panel. More often than not, the problem will

    be found in that device box or the last functioning one just ahead of it. Most of the time, the culprit is a

    wire splice that's come undone.

    Sponsored Links

    Manufacturing Software

    Award Winning MRP Systems. Download Our Free MRP Info Pack!

    www.Epicor.com/MRP

    3

    Follow the same process to test GFCI receptacles as for testing general-purpose, except that you'll press

    the test button on the GFCI plug-in tester to simulate a ground-fault condition on the circuit. Pressing

    the "Test" button should cause the GFCI receptacle/breaker combination to trip or cause the GFCI circuit

    breaker in the service panel to trip, shutting off all power to the receptacle being tested. A

    malfunctioning GFCI poses a serious safety threat and needs to be repaired immediately.

    Circuit Breakers That Trip Inexplicably

    4

    Remove the cover to the service panel. Clamp the jaws of the clamp-on ammeter around the conductor

    attached to the circuit breaker. Note the reading.

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    18/23

    5

    Figure out 80 percent of the circuit breaker's rating. For example, 80 percent of 20 is 16. If the load on a

    20A circuit breaker exceeds 16A, the nuisance tripping is caused by an excessive load on the circuit. A

    circuit breaker is like a thermostat and operates off heat, which can build up in the breaker's case and

    cause it to open, even if the current flowing is less than its full rating.

    6

    Check if the circuit breaker is loaded at 80 percent or less and still trips randomly. You have either an

    intermittent overload, intermittent short circuit or bad circuit breaker. Intermittent overloads and shorts

    can be extremely difficult to trace, but are more likely than a bad circuit breaker.

    Definition for service entrance cable:Web definitions: The conductors that connect the service

    conductors (drop or lateral) to the service equipment of the building..

    www.qvsdirect.com/technical/electrical_terms.html July 10, 2012

    ectrical conductivity is a physical property that indicates how well a given material conducts electricity.

    A current originates when electrical charges flow in response to a difference in electrical potential. The

    conductivity is defined as the ratio of the density of this current to the strength of the electric field. Theelectrical conductivity can be calculated measuring the resistance, area and length of the test material.

    The test material typically has a box-like shape for ease of measuring.

    Other People Are Reading

    How to Determine Conductivity

    How to Test the Conductivity of Metal

    Print this article

    Things You'll Need

    http://www.qvsdirect.com/technical/electrical_terms.htmlhttp://www.qvsdirect.com/technical/electrical_terms.htmlhttp://www.qvsdirect.com/technical/electrical_terms.html
  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    19/23

    4 terminal ohmmeter

    test material

    Instructions

    1

    Use a four-terminal ohmmeter for greater accuracy. This type of ohmmeter is more accurate because

    one pair of terminals measures current, while the other pair measures voltage. This allows the

    ohmmeter to ignore the resistance of the first pair of terminals.

    2

    Measure the resistance of the test material with a four-terminal ohmmeter by placing each pair of

    terminals on opposite ends of the test material.

    Sponsored Links

    Cable Trays and Ladders

    Complete solutions for construction and electricity industries.

    www.tekom-puk.com

    3

    Record the resistance of the test material. The ohmmeter automatically performs the calculation R = V/I

    where R is the resistance in ohms, V is the voltage in volts and I is the current in amperes.

    4

    Measure the dimensions of the test material in meters. The length is the distance between the

    ohmmeter terminals. The area is the area of the surface that the ohmmeter is measuring current across.

    5

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    20/23

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    21/23

    Switch the dial on the face of the meter to VAC or it may be labeled only as "volts." If the face is labeled

    as VAC on the switch, the display should read "0.0 VAC." If the switch is labeled as only volts, then the

    display may read "0.0." The meter is ready to use.

    Sponsored Links

    connectors-Amphenol LTW

    Largest Range IP67-IP68 Connectors For Widest Applications, Condition

    www.ltw-tech.com

    3

    Insert the red lead into the right vertical slot of the wall outlet. Place the black lead into the left vertical

    slot of the wall outlet. The meter should be displaying either "110 VAC" or "120 VAC" depending on the

    utility companies supplied electrical power. If there is no reading or "0.0" on the meter display try

    jiggling the leads inside the slots. If there is still no voltage being read, the wall outlet may have an

    electrical problem.

    4

    Withdraw the black lead from the vertical slot. Insert the black lead into the lower oval slot which is the

    electrical ground. The meter should be displaying a voltage reading. If it is not, the circuit breaker may

    be tripped or the fuse is blown.

    How to Test if an Outlet Is Grounded

    By Mike Johnson, eHow Contributor

    An outlet with three prongs can be tested.

    There might be a lot going on with your home's electrical system and outlets that you're not aware of.

    However, when you want to introduce a new electrical component, such as a surge protector, knowing

    more about how the system works can be helpful. For example, a surge protector cannot work properly

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    22/23

    and will be much more efficient if the outlet that you plug it into is properly grounded. A simple test will

    help you determine whether the outlet is grounded. Does this Spark an idea?

    Other People Are Reading

    How to Loosen Ground Soil With Detergent

    Prenatal Testing

    Print this article

    Things You'll Need

    Circuit tester

    Instructions

    1

    Purchase a circuit tester. You need a circuit tester to test whether the outlet is grounded. You can find

    them at hardware stores and similar retail establishments.

    2

    Examine your outlet to get a better idea of what it entails. Outlets that can be grounded have three

    slots. One short and one long next to each other, and a rounded hole beneath those two.

    Sponsored Links

    Find Socket Adapters Here

    Enable The Use Of Standard Line And Trace Spacing. Place Your Order Now

    www.AriesElec.com

    3

  • 7/31/2019 A Fish Tape is Used to Pull Stranded or Solid Wire Through Metal or PVC Conduit

    23/23

    Follow the instructions of the circuit tester to test whether the outlet is grounded. The instructions can

    vary slightly, but you will likely need to insert one probe into the shorter slot and one into the rounded

    hole.

    4

    Watch for the indicator light on the circuit tester. If your outlet is grounded, the indicator light should

    come on. If the outlet is not grounded, the light will not come on.