A 15 / 30 FLUSH EAVE WITH EXTERNAL GUTTER BRACKET 2.0 28 ... · - 3 degree min pitch residential...
Transcript of A 15 / 30 FLUSH EAVE WITH EXTERNAL GUTTER BRACKET 2.0 28 ... · - 3 degree min pitch residential...
MetalcraftRoofing
DETAIL LIST DateRevision
KAHU - 3 degree min pitch
RESIDENTIAL ROOFING
RRKA
A 15 / 30 FLUSH EAVE WITH EXTERNAL GUTTER BRACKET 2.0 28.02.2019A 16 / 30 BARGE WITH PROFILED CLADDING 2.0 28.02.2019A 17 / 30 BARGE OVERHANG 2.0 28.02.2019A 18 / 30 PARAPET WITH TRANSVERSE APRON 2.0 28.02.2019A 19 / 30 TRANSVERSE APRON 2.0 28.02.2019A 20 / 30 PARALLEL APRON 2.0 28.02.2019A 21 / 30 PIPE PENETRATION DIRECT FIXED BOOT FLASHING 2.0 28.02.2019A 22 / 30 PIPE PENETRATION BACKTRAK BOOT FLASHING 2.0 28.02.2019A 23 / 30 3D RIDGE TO BARGE JUNCTION 2.0 28.02.2019A 24 / 30 3D DUTCH GABLE 2.0 28.02.2019A 25 / 30 3D APRON 2.0 28.02.2019A 26 / 30 3D OVER 85mm DIAMETER PIPE PENETRATION 2.0 28.02.2019A 27 / 30 3D CHIMNEY PENETRATION 2.0 28.02.2019A 28 / 30 3D RIDGE/BARGE FLASHINGS 2.0 28.02.2019A 29 / 30 3D DUTCH GABLE FLASHINGS 2.0 28.02.2019
A 00 / 30 COVER SHEETA 01 / 30 ROOF RIDGE 2.0 28.02.2019A 02 / 30 ROOF RIDGE (ROUND) 2.0 28.02.2019A 03 / 30 SAWTOOTH RIDGE 2.0 28.02.2019A 04 / 30 SAWTOOTH EAVE 2.0 28.02.2019A 05 / 30 ROOF VALLEY 2.0 28.02.2019A 06 / 30 ROOF VALLEY BAFFLE 2.0 28.02.2019A 07 / 30 INTERNAL GUTTER 2.0 28.02.2019A 08 / 30 PARALLEL HIDDEN GUTTER 2.0 28.02.2019A 09 / 30 PARALLEL HIDDEN GUTTER (2 PART FLASHING) 2.0 28.02.2019A 10 / 30 ROOF - CHANGE PITCH 2.0 28.02.2019A 11 / 30 MANSARD 2.0 28.02.2019A 12 / 30 EAVE WITH METALLINE FASCIA 2.0 28.02.2019A 13 / 30 EAVE WITH SNOW STRAP 2.0 28.02.2019A 14 / 30 FLUSH EAVE WITH INTERNAL GUTTER BRACKET 2.0 28.02.2019
PRE-FINISHED RIDGE CAP FLASHING
STOPENDS TO ROOF CLADDING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY, SHOWN DASHED
NOTCHED DRESSED OVER KAHU™ RIBS
X
* KAHU MIN. ROOF PITCH = 3°
5mm
GAP
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. FOR ALL ROOF PITCHES IN EXTRA HIGH WIND ZONES
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. FOR ALL ROOF PITCHES IN EXTRA HIGH WIND ZONES
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0ROOF RIDGE
A 01 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
PRE-FINISHED ROUND RIDGE CAP FLASHING
STOPENDS TO ROOF CLADDING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY, SHOWN DASHED
NOTCHED DRESSED OVER KAHU™ RIBS
X
* KAHU MIN. ROOF PITCH = 3°
5mm
GAP
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. FOR ALL ROOF PITCHES IN EXTRA HIGH WIND ZONES
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. FOR ALL ROOF PITCHES IN EXTRA HIGH WIND ZONES
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0ROOF RIDGE (ROUND)
A 02 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM COP
NOTCHED DRESSED OVER KAHU™ RIBS
STOPENDS TO ROOF CLADDING
PERMEABLE UNDERLAY SHOWN DASHED
PURLIN
PRE-FINISHED 8g WAFER-TEK SCREW BEDDED IN SILICONE
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
ROOF OR WALL FRAMING
TIMBER PACKER
FASCIA BOARD
TIMBER PACKER
WEATHERBOARDS ON CAVITY
PERMEABLE UNDERLAY, SHOWN DASHED
METALCRAFT KAHU™ ROOFING5 GAP
20
15
ALTERNATIVE OPTIONBIRDS BEAK EDGE
Z
X
HEMMED EDGE
SAWTOOTH RIDGE CAP FLASHING
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES INVERY HIGH WIND ZONE2. LOW, MEDIUM AND HIGH WINDZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mm
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
X
Z
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES INVERY HIGH WIND ZONE2. LOW, MEDIUM AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mm
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
X
Z
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0SAWTOOTH RIDGE
A 03 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM COP
TIMBER FASCIA
SOFFIT LINING
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
PURLIN
SAWTOOTH RIDGE CAP FLASHING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
ROOF FRAMING
X
Z
PRE-FINISHED 8g WAFER-TEK SCREW BEDDED IN SILICONE
5 GAP
20
15
ALTERNATIVE OPTIONBIRDS BEAK EDGE
STOPENDS TO ROOF CLADDING
HEMMED EDGE
NOTCHED DRESSED OVER KAHU™ RIBS
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES INVERY HIGHWIND ZONE2. LOW, MEDIUM AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mm
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
X
Z
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES INVERY HIGHWIND ZONE2. LOW, MEDIUM AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mm
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
X
Z
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0SAWTOOTH EAVE
A 04 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY CONTINUOUS UNDER GUTTER IF COPPER BASED TREATMENTS ARE USED, SHOWN DASHED
VALLEY BOARD
VALLEY GUTTER, MATERIAL AS PER E2/AS1
VALLEY RAFTER
MIN
. 50m
m
MIN
. 20mm
C C
B : CLEARANCE BETWEEN ROOFING
A : OVERALL VALLEY GUTTER WIDTH
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
MAX. CATCHMENT 25m²MIN. ROOF PITCH 8°
MIN. 250mm
MIN. 50mm
MIN. 80mm
SITUATION 2
MAX. CATCHMENT 16m²MIN. ROOF PITCH 12.5°
160mm - 249mm
MIN. 40mm
MIN. 60mm
A
B
C
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
ROOF PITCH
8 - 12°
12 - 35°
> 35°
TYPE B
MIN. 75mm
MIN. 50mm
MIN. 50mm
TYPE C
MIN. 75mm
MIN. 70mm
MIN. 70mm
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
MAX. CATCHMENT 25m²MIN. ROOF PITCH 8°
MIN. 250mm
MIN. 50mm
MIN. 80mm
SITUATION 2
MAX. CATCHMENT 16m²MIN. ROOF PITCH 12.5°
160mm - 249mm
MIN. 40mm
MIN. 60mm
A
B
C
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
ROOF PITCH
8 - 12°
12 - 35°
> 35°
TYPE B
MIN. 75mm
MIN. 50mm
MIN. 50mm
TYPE C
MIN. 75mm
MIN. 70mm
MIN. 70mm
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0ROOF VALLEY
A 05 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY CONTINUOUS UNDER GUTTER IF COPPER BASED TREATMENTS ARE USED, SHOWN DASHED
VALLEY BOARD
VALLEY GUTTER, MATERIAL AS PER E2/AS1
VALLEY RAFTER
MIN
. 70m
m MIN
. 20mm
A : OVERALL VALLEY GUTTER WIDTH
B : CLEARANCE BETWEEN ROOFING
CC
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
MAX. CATCHMENT 25m²MIN. ROOF PITCH 8°
MIN. 250mm
MIN. 50mm
MIN. 80mm
SITUATION 2
MAX. CATCHMENT 16m²MIN. ROOF PITCH 12.5°
160mm - 249mm
MIN. 40mm
MIN. 60mm
A
B
C
ROOF VALLEY BAFFLE TO BE USED WITH ROOF PITCHES OVER 35° AS PER MRM CODE OF PRACTICE
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
MAX. CATCHMENT 25m²MIN. ROOF PITCH 8°
MIN. 250mm
MIN. 50mm
MIN. 80mm
SITUATION 2
MAX. CATCHMENT 16m²MIN. ROOF PITCH 12.5°
160mm - 249mm
MIN. 40mm
MIN. 60mm
A
B
C
ROOF VALLEY BAFFLE TO BE USED WITH ROOF PITCHES OVER 35° AS PER MRM CODE OF PRACTICE
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0ROOF VALLEY BAFFLE
A 06 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY CONTINUOUS UNDER GUTTER IF COPPER BASED TREATMENTS ARE USED, SHOWN DASHED
GUTTER BOARD
INTERNAL GUTTER, MATERIAL AS PER E2/AS1 (BY OTHERS)
VALLEY RAFTER
MIN
. DEP
TH
70m
m
MIN. 300mm
OVERALL GUTTER WIDTH
MIN. 50mm
TIMBER FILLET
MIN. 100mm
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0INTERNAL GUTTER
A 07 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY CONTINUOUS UNDER GUTTER IF COPPER BASED TREATMENTS ARE USED. SHOWN DASHED
HIDDEN GUTTER, MATERIAL AS PER E2/AS1
MIN
. 20m
m
MIN. 80mm MIN. 80mm
75m
m
MIN
. CO
VER
FIXINGS AS PER E2/AS1
35m
m
MIN
. GAP
110m
m
MIN
. TO
TAL
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0PARALLEL HIDDEN GUTTER
A 08 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
ROOF FRAMING
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SCREW WITH RUBBER WASHER
PERMEABLE UNDERLAY CONTINUOUS UNDER GUTTER IF COPPER BASED TREATMENTS ARE USED, SHOWN DASHED
HIDDEN GUTTER, MATERIAL AS PER E2/AS1
MIN. 80mm MIN. 80mm
75m
m M
IN. W
ITH
OU
T H
EM E
DG
E
SUG
GES
T 50
mm
MIN
.
75m
m
MIN
. CO
VER
35m
m
MIN
. GAP
FIXINGS AS PER E2/AS1
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0PARALLEL HIDDEN GUTTER (2 PART FLASHING)
A 09 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM COP
MIN. ROOF PITCH AS PER MRM COP
PURLIN
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
PURLIN
ROOF FRAMING
STOPENDS TO ROOF CLADDING
PRE-FINISHED CHANGE OF ROOF PITCH FLASHING
PERMEABLE UNDERLAY CONTINUOUS OVER FLASHING, SHOWN DASHED
PERMEABLE UNDERLAY CONTINUOUS UNDER FLASHING, SHOWN DASHED
MIN. 250mm
CLEARANCE
MIN. 10mm
X
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
FIXINGS AS PER E2/AS1
NOTCHED DRESSED OVER KAHU™ RIBS
METALCRAFT KAHU™ ROOFING
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. NOT PERMITTED UNDER E2/AS1
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. NOT PERMITTED UNDER E2/AS1
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0ROOF - CHANGE PITCH
A 10 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM COP
MIN. ROOF PITCH AS PER MRM COP
PURLIN
METALCRAFT KAHU™ ROOFING
PURLIN
ROOF FRAMING
STOPENDS TO ROOF CLADDING
PRE-FINISHED CHANGE OF ROOF PITCH FLASHING
PERMEABLE UNDERLAY CONTINUOUS OVER FLASHING, SHOWN DASHED
PERMEABLE UNDERLAY CONTINUOUS UNDER FLASHING, SHOWN DASHED
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
FIXINGS AS PER E2/AS1
NOTCHED DRESSED OVER KAHU™ RIBS
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
5mm G
AP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. NOT PERMITTED UNDER E2/AS1
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 130mm (EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 200mm(EXCLUDDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. NOT PERMITTED UNDER E2/AS1
X
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
MIN. 130mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
MIN. 200mmX
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0MANSARD
A 11 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM
COP
FIXINGS AS PER E2/AS1
METALCRAFT KAHU™ ROOFING
PRE-FINISHED EAVE FLASHING
PERMEABLE UNDERLAY, SHOWN DASHED
METALLINE™ FASCIA
FASCIA BRACKET
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
METALLINE™ QUAD GUTTER
METALLINE™ QUAD GUTTER OVERSTRAP
TIMBER ROOF FRAMING
OVE
RLA
P
MIN
. 35m
m
MIN. 125 mm
SPRING CLIP
TIMBER PURLIN
SOFFIT LINING
FOAM CLOSURE USED AS REQUIRED
>35° = 40mm
<10° = 70mm10-35° = 50mm
EAVE FLASHING REQUIRED WHEN ALL OF THE FOLLOWING CONDITIONS ARE MET:ROOF PITCH ≤ 10°SOFFIT WIDTH ≤ 100mmWIND ZONES = VERY HIGH OR EXTRA HIGHENGINEER SPECIFIC DESIGN MRM RECOMMENDS TO USE IN AREAS EXPOSED TO CONTAMINATORS SUCH AS SEA SALT OR INDUSTRIAL POLLUTANTS
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0EAVE WITH METALLINE FASCIA
A 12 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM
COP
TIMBER FASCIA
METALLINE™ QUAD GUTTER
METALLINE™ QUAD GUTTER INTERNAL BRACKET
TIMBER ROOF FRAMING
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
OVE
RLA
P
MIN
. 35m
m
TIMBER PURLIN
PRE-FINISHED EAVE FLASHING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
FIXINGS AS PER E2/AS1
MIN. 125 mm
SNOW STRAP AS REQUIRED
PRE-FINISHED POP RIVET BEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
PRE-FINISHED 8g WAFER-TEK SCREW
SOFFIT LINING
FOAM CLOSURE AS REQUIRED
>35° = 40mm
<10° = 70mm10-35° = 50mm
EAVE FLASHING REQUIRED WHEN ALL OF THE FOLLOWING CONDITIONS ARE MET:ROOF PITCH ≤ 10°SOFFIT WIDTH ≤ 100mmWIND ZONES = VERY HIGH OR EXTRA HIGHENGINEER SPECIFIC DESIGN MRM RECOMMENDS TO USE IN AREAS EXPOSED TO CONTAMINATORS SUCH AS SEA SALT OR INDUSTRIAL POLLUTANTS
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0EAVE WITH SNOW STRAP
A 13 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM
COP
TIMBER PACKER
FASCIA BOARD
TIMBER PACKER
WEATHERBOARDS ON CAVITY
PERMEABLE UNDERLAY, SHOWN DASHED
ROOF FRAMING
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
OVE
RLA
P
MIN
. 35m
m
TIMBER PURLIN
PRE-FINISHED EAVE FLASHING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
FIXINGS AS PER E2/AS1
MIN. 125 mm
QUARTER ROUND GUTTER
QUARTER ROUND GUTTER INTERNAL BRACKET
PRE-FINISHED 8g WAFER-TEK SCREW
FOAM CLOSURE USED AS REQUIRED
>35° = 40mm
<10° = 70mm10-35° = 50mm
EAVE FLASHING REQUIRED WHEN ALL OF THE FOLLOWING CONDITIONS ARE MET:ROOF PITCH ≤ 10°SOFFIT WIDTH ≤ 100mmWIND ZONES = VERY HIGH OR EXTRA HIGHENGINEER SPECIFIC DESIGN MRM RECOMMENDS TO USE IN AREAS EXPOSED TO CONTAMINATORS SUCH AS SEA SALT OR INDUSTRIAL POLLUTANTS
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0FLUSH EAVE WITH INTERNAL GUTTER BRACKET
A 14 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM
COP
TIMBER PURLIN
PRE-FINISHED EAVE FLASHING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
TIMBER PACKER
FASCIA BOARD
TIMBER PACKER
WEATHERBOARDS ON CAVITY
PERMEABLE UNDERLAY, SHOWN DASHED
ROOF FRAMING
OVE
RLA
P
MIN
. 35m
m
FIXINGS AS PER E2/AS1
MIN. 125 mm
QUARTER ROUND GUTTER
QUARTER ROUND GUTTER EXTERNAL BRACKET
PRE-FINISHED 8g WAFER-TEK SCREW
FOAM CLOSURE USED AS REQUIRED
>35° = 40mm
<10° = 70mm10-35° = 50mm
EAVE FLASHING REQUIRED WHEN ALL OF THE FOLLOWING CONDITIONS ARE MET:ROOF PITCH ≤ 10°SOFFIT WIDTH ≤ 100mmWIND ZONES = VERY HIGH OR EXTRA HIGHENGINEER SPECIFIC DESIGN MRM RECOMMENDS TO USE IN AREAS EXPOSED TO CONTAMINATORS SUCH AS SEA SALT OR INDUSTRIAL POLLUTANTS
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0FLUSH EAVE WITH EXTERNAL GUTTER BRACKET
A 15 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
TIMBER PACKER
BARGE BOARD
PRE-FINISHED BARGE FLASHING
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
PURLIN
WEATHERBOARDS ON CAVITY
PERMEABLE UNDERLAY, SHOWN DASHED
PRE-FINISHED 8g WAFER-TEK SCREW BEDDED IN SILICONE
ROOF FRAMING
TIMBER PACKER
5 GAP
20
15
ALTERNATIVE OPTIONBIRDS BEAK EDGEHEMMED EDGE
Z
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
Y
5mm
GAP
NOTCHED DRESSED OVER KAHU™ RIBS
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≥ 10°
AT LEAST TWO CRESTS
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM AND HIGH WND ZONES WHERE ROOF PITCH ≤ 10°
AT LEAST TWO CRESTS
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE.
AT LEAST TWO CRESTS
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
X
Z
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≥ 10°
AT LEAST TWO CRESTS
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM AND HIGH WND ZONES WHERE ROOF PITCH ≤ 10°
AT LEAST TWO CRESTS
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE.
AT LEAST TWO CRESTS
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
X
Z
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0BARGE WITH PROFILED CLADDING
A 16 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
PRE-FINISHED BARGE FLASHING
METALCRAFT KAHU™ ROOFING
FLY RAFTER
BARGE BOARD
PERMEABLE UNDERLAY, SHOWN DASHED
PURLIN
SOFFIT LINING
PRE-FINISHED 8g WAFER-TEK SCREW BEDDED IN SILICONE
Z
5 GAP
20
15
ALTERNATIVE OPTIONBIRDS BEAK EDGE
HEMMED EDGE
Y
5mm
GAP
NOTCHED DRESSED OVER KAHU™ RIBS
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≥ 10°
AT LEAST TWO CRESTS
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM AND HIGH WND ZONES WHERE ROOF PITCH ≤ 10°
AT LEAST TWO CRESTS
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE.
AT LEAST TWO CRESTS
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
X
Z
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES WHERE ROOF PITCH ≥ 10°
AT LEAST TWO CRESTS
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM AND HIGH WND ZONES WHERE ROOF PITCH ≤ 10°
AT LEAST TWO CRESTS
MIN. 70mm
SITUATION 3
1.ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE.
AT LEAST TWO CRESTS
MIN. 90mm
X
Z
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
X
Z
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0BARGE OVERHANG
A 17 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM COP
MIN
. 5.0
0°
L
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
TIMBER PACKER
BARGE BOARD
WEATHERBOARDS ON CAVITY
PERMEABLE UNDERLAY, SHOWN DASHED
PRE-FINISHED PARAPET CAP FLASHING
TIMBER PACKER
DPC TO PROVIDE SEPARATION OF METAL CAPPING AND TIMBER, SHOWN DASHED
TIMBER PURLIN
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
WALL FRAMING ROOF FRAMING
PRE-FINISHED APRON FLASHING
TIMBER NOG FOR FIXING APRON FLASHING
CONTINUOUS TIMBER PACKING
FIXINGS AS PER E2/AS1
PRE-FINISHED SELF DRILLING / TAPPING SCREW WITH RUBBER WASHER
PRE-FINISHED 8g WAFER-TEK SCREW BEDDED IN SILICONE
Z
NOTCHED DRESSED OVER KAHU™ RIBS
STOPENDS TO ROOF CLADDING
NG
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, & HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 35mm
MIN. 75mm
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 70mm
SITUATION 3
1. ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE
MIN. 35mm
MIN. 75mm
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 90mm
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
MIN. 150mm
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
25mm
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
MIN. 200mm
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
G
N
L
Z
G
N
L
Z
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONE2. LOW, MEDIUM, & HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 35mm
MIN. 75mm
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 70mm
SITUATION 3
1. ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE
MIN. 35mm
MIN. 75mm
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
MIN. 90mm
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
MIN. 150mm
MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
25mm
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
MIN. 200mm
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
G
N
L
Z
G
N
L
Z
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0PARAPET WITH TRANSVERSE APRON
A 18 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM COP
GN
L
STOPENDS TO ROOF CLADDING
ROOF FRAMING
WALL FRAMING
PVC CAVITY CLOSER
WEATHERBOARDS ON CAVITY
CANT STRIP PACKER
NOG FOR FIXING APRON FLASHING
FIXINGS AS PER E2/AS1
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
METALCRAFT KAHU™ ROOFING
PERMEABLE UNDERLAY, SHOWN DASHED
PRE-FINISHED APRON FLASHING
PERMEABLE UNDERLAY OVER FLASHING, SHOWN DASHED
PERMEABLE UNDERLAY SHOWN DASHED
PURLIN
NOTCHED DRESSED OVER KAHU™ RIBS
5mm
GAP
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONES2. LOW, MEDIUM, AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 35mm
MIN. 75mm
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE
MIN. 35mm
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
G
N
L
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
MIN. 150mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
25mm
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
MIN. 200mm
G
N
L
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
MIN. 130mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 2
1. ALL ROOF PITCHES IN VERY HIGH WIND ZONES2. LOW, MEDIUM, AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 35mm
MIN. 75mm
MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
SITUATION 3
1. ALL ROOF PITCHES IN EXTRA HIGH WIND ZONE
MIN. 35mm
MIN. 200mm (EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)
G
N
L
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
MIN. 150mm
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
25mm
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
MIN. 200mm
G
N
L
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0TRANSVERSE APRON
A 19 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
PURLIN
GNPRE-FINISHED
APRON FLASHING
WEATHERBOARDS ON CAVITY
CANT STRIP PACKER
PERMEABLE UNDERLAY OVER FLASHING, SHOWN DASHED
FIXINGS AS PER E2/AS1
NOG FOR FIXING APRON FLASHING
PVC CAVITY CLOSER
METALCRAFT KAHU™ ROOFING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
M
WALL FRAMING
PERMEABLE UNDERLAY, SHOWN DASHED
ROOF FRAMING
5 m
m G
AP
NOTCHED
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
AT LEAST TWO CRESTS
SITUATION 2
1. ALL ROOF PITCHES INVERY HIGH WIND ZONE2. LOW, MEDIUM, AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 35mm
MIN. 75mm
AT LEAST TWO CRESTS
SITUATION 3
1. ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE
MIN. 35mm
MIN. 75mm
AT LEAST TWO CRESTS
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS (KAHU)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
25mm
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS (KAHU)
G
N
M
G
N
M
ACCEPTABLE SOLUTION AS PER E2/ASI
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES, WHERE ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
AT LEAST TWO CRESTS
SITUATION 2
1. ALL ROOF PITCHES INVERY HIGH WIND ZONE2. LOW, MEDIUM, AND HIGH WIND ZONES WHERE ROOF PITCH ≤ 10°
MIN. 35mm
MIN. 75mm
AT LEAST TWO CRESTS
SITUATION 3
1. ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE
MIN. 35mm
MIN. 75mm
AT LEAST TWO CRESTS
ACCEPTABLE SOLUTION AS PER MRM CODE OF PRACTICE
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS (KAHU)
CATEGORY B
1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°
25mm
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS (KAHU)
G
N
M
G
N
M
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 2
2.0PARALLEL APRON
A 20 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM
COP
*MIN 10 FOR PIPE PENETRATION. DIRECT FIX BOOT FLASHING IS APPLICABLE FOR WHEN LESS THAN 50% BLOCKAGE OCCURS. WHEN EXCEEDING 50% BLOCKAGE, REFER TO BACKTRAY BOOT FLASHING.
METALCRAFT KAHU™ ROOFING
EPDM FLEXIBLE CONE SLEEVE MALLEABLE FLANGE, SCREW OR RIVET FIXED, AND SEALED TO ROOFING PROFILE. FIT NEOPRENE WASHERS TO ALL SCREW FIXINGS. FITTED ON 45° ANGLE IN PLAN. REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019.
PERMEABLE UNDERLAY, SHOWN DASHED
METALCRAFT KAHU™ ROOFING
PIPE
EPDM FLEXIBLE CONE SLEEVE
PERMEABLE UNDERLAY, SHOWN DASHED
MALLEABLE FLANGE, SCREW OR RIVET FIXED, AND SEALED TO ROOFING PROFILE. FIT NEOPRENE WASHERS TO ALL SCREW FIXINGS. FITTED ON 45° ANGLE IN PLAN. REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019.
TIMBER PURLIN
ROOF FRAMINGPRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
TIMBER PURLIN
ROOF FRAMING
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 5
2.0PIPE PENETRATION DIRECT FIXED BOOT FLASHING
A 21 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. ROOF PITCH AS PER MRM
COP
*MIN. 3° FOR PIPE PENETRATION WITH A BACKTRAY BOOT FLASHING MUST BE FIXED DIAGONALLY BELOW 10°. BACK TRAY BOOT FLASH ING IS APPLICABLE FOR WHEN MORE THAN 50% BLOCKABLE OCCURS. WHEN LESS THAN 50% BLOCKABLE OCCURS, REFER TO DIRECT FIX BOOT FLASHING.
L
PRE-FINISHED SOAKER FLASHING UNDER PRE-FINISHED ROOF RIDGE CAP FLASHING
PIPE (PIPE DIAMETER OVER 85mm AND MAX. 500mm)
EPDM FLEXIBLE CONE SLEEVE
METALCRAFT KAHU™ ROOFING
MALLEABLE FLANGE, SCREW OR RIVET FIXED, AND SEALED TO ROOFING PROFILE. FIT NEOPRENE WASHERS TO ALL SCREW FIXINGS. FITTED ON 45° ANGLE IN PLAN. REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019. PRE-FINISHED SOAKER FLASHING WITH
PRE-FINISHED POP RIVET BEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
METALCRAFT KAHU™ ROOFING
PURLINROOF FRAMING
PRE-FINISHED ROOF RIDGE CAP FLASHING
PRE-FINISHED SELF DRILLING/TAPPING SCREW WITH RUBBER WASHER
EPDM FLEXIBLE CONE SLEEVE
PURLIN
PERMEABLE UNDERLAY, SHOWN DASHED
NOGS BETWEEN PURLINS FOR PENETRATION
5mm
GAP
M
X
ROOF FRAMING
5mm
GAP
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev.
1 : 5
2.0PIPE PENETRATION BACKTRAK BOOT FLASHING
A 22 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D RIDGE TO BARGE JUNCTION
A 23 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
PRE-FINISHED RIDGE CAP FLASHING
METALCRAFT KAHU™ ROOFING
PRE-FINISHED BARGE FLASHING
FASCIA BOARD
* PLEASE REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019 AND BRANZ HOW TO ON-SITE GUIDE METAL ROOF FLASHING FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
PRE-FINISHED BARGE FLASHING
PRE-FINISHED HIP FLASHING
PRE-FINISHED APRON FLASHING
METALCRAFT KAHU™ ROOFING TURN DOWN INTO GUTTER. REFER TO EAVE DETAILS FOR MINIMUM ROOF OVERHANG
GUTTER
FASCIA BOARD
WALL CLADDING ON CAVITY
* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 3.0/2019 AND BRANZHOW TO ON-SITE GUIDE METAL ROOFFLASHING FOR FURTHER INFORMATIONON FLASHING COVER WIDTHS.
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D DUTCH GABLE
A 24 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D APRON
A 25 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
WALL CLADDING ON CAVITY
PRE-FINISHED APRON DIVERTER
PRE-FINISHED APRON FLASHING WITH HEMMED EDGE
METALCRAFT KAHU™ ROOFING. TURN DOWN INTO GUTTER REFER TO EAVE DETAILS FOR MINIMUM ROOF OVERHANG
GUTTER
FASCIA BOARD
WALL CLADDING ON CAVITY* PLEASE REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019 AND BRANZ HOW TO ON-SITE GUIDE METAL ROOF FLASHING FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
WEATHERBOARDS REMOVED FOR CLARITY
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D OVER 85mm DIAMETER PIPE PENETRATION
A 26 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
* PLEASE REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019 AND BRANZ HOW TO ON-SITE GUIDE METAL ROOF FLASHING FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
PRE-FINISHED ROOF RIDGE FLASHING
PRE-FINISHED SOAKER FLASHING LINE UNDER PRE-FINISHED ROOFRIDGE FLASHING
PRE-FINISHED ROOF BARGE FLASHING
PIPE
METALCRAFT KAHU™ ROOFING
EPDM FLEXIBLE CONE SLEEVE
MALLEABLE FLANGE, SCREW OR RIVET FIXED, AND SEALED TO ROOFING PROFILE. FIT NEOPRENE WASHERS TO ALL SCREW FIXINGS. FITTED ON 45° ANGLE IN PLAN. REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019
PRE-FINISHED SOAKER FLASHING
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D CHIMNEY PENETRATION
A 27 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
MIN. 110mm UPSTAND PRE-FINISHED 1.6mm ALUMINIUM WELDED SOAKER FLASHING
PRE-FINISHED SOAKER FLASHING
PREFINISHED VALLEY GUTTER
VALLEY BOARD
ROOF FRAMING
WALL CLADDING ON CAVITY
PRE-FINISHED APRON FLASHING
METALCRAFT KAHU™ ROOFING TURN DOWN INTO GUTTER
PURLIN
* PLEASE REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019 AND BRANZ HOW TO ON-SITE GUIDE METAL ROOF FLASHING FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
DIVERTER FLASHING ON UPPER SIDE OF CHIMNEY
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D RIDGE/BARGE FLASHINGS
A 28 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
BARGE FLASHING
ADDITIONAL SADDLE FLASHING
RIDGE CAP FLASHING
BARGE FLASHING
ADDITIONAL SADDLE FLASHING
RIDGE CAP FLASHING
OPTION 1 OPTION 2
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM code of practice version 3.0 / 2019, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a single line for simplicity and is indicative only. Building paper type and method of installation should comply with underlay manufacturers recommendations and NZBC regulations.
ScaleDate SheetMetalcraftRoofing
Rev. 2.03D DUTCH GABLE FLASHINGS
A 29 / 3028.02.2019
KAHU
RRKA
RESIDENTIAL ROOFING
* PLEASE REFER TO MRM CODE OF PRACTICE VERSION 3.0/2019 AND BRANZ HOW TO ON-SITE GUIDE METAL ROOF FLASHINGS FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
(1) PRE-FINISHED HIP FLASHING
(2) PRE-FINISHED APRON FLASHING
(3) PRE-FINISHED 3D SADDLE FLASHING
(4) PRE-FINISHED BARGE FLASHING