9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

16
product Information on compact burners Digital combustion technology Weishaupt gas burners, WG10 to WG40 (12.5 – 550 kW)

Transcript of 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

Page 1: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

productInformation on compact burners

Digital combustion technologyWeishaupt gas burners, WG10 to WG40 (12.5 – 550 kW)

Page 2: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

Hot for quality

2

Our motivation is technological progress, which has been driving us formore than 50 years to set new standards for the combustion industry.

Weishaupt’s own Research and Development Centre is constantly working on both new developments andthe optimisation of exisitng products.

It is our goal and our responsibility to goabove and beyond current legislative requirements in developing combustionsystems which produce fewer and fewer emissions, save more and moreenergy, and in so doing combine ecology and economy in a practicalmanner.

Therefore, not only do we invest in research and technology but we alsoonly ever work on the best materials withmodern tools and we carry out meticulous quality control checks.

It has been proven over a million timesin the field that heating specialists and customers hold Weishaupt burners tobe reliable, long lasting, environmentallyfriendly and technoloically advanced. Afact also documented by numerous design and innovation prizes.

Over 600 burners are manufactureddaily at our ultra-modern production facilities in Schwendi. Every single burner is subjected to a mechanical andelectrical function test. The combinationof technology with an effective qualitycontrol system safeguards Weishaupt’sreknowned reputation for quality.

A new burner is always an investment inthe future. Cost needs to be well balanced against use, but the final deciding factors for long term sucessare quality, technology and safety. Deciding for Weishaupt burners is therefore a safe investment in the future.

Ultra-modern research and production methodsand rigourous quality control ensures the qualityfor which Weishaupt is reknowned

Page 3: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

3

Page 4: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG
Page 5: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

A hallmark of practical combustion technology

5

A safe investment in the futureReliable and economical: The miilionfoldsucess of the Weishaupt compact burners is the result of orienting withoutcompromise towards quality and the customer. The technology has beenconstantly developed and improved overdecades.

The latest production methods and stringent quality checks of all products ensure Weishaupt’s reputationfor quality. You are making a safeinvestment in the future.

Large capacity rangeThe large capacity range of 12.5 to550 kW makes the burners suitable forthe widest range of heat exchangers.

Electronic ignitionThe W-ZG 01 ignition unit used on allWeishaupt W burners is particularlyenergy efficient and extremely reliable.

Digital combustion management forsafety and ease of useWeishaupt is a pioneer in this field. Digital combustion management offers greater ease of use and simple servicing, even greater relaibility in operation, and, last but not least, an extremely attractive price/capacity relationship. Furthermore, this intelligent technology enables the burner to be integrated with complexautomation systems.

Valve proving as standard withW-FM10 and W-FM20 combustionmanagersThe low gas pressure switch is used tocheck the tightness of the gas valves,thus providing valve proving without theneed for any additional components orcosts.

Gas multifunction assemblyThe newly concieved gas multifunctionassembly incorporates the followingcomponents/functions:• Servo-controlled gas pressure

governor for continual gas pressure• 2 solenoid valves (Class A)• Filter• Gas pressure switchIf the gas pressure falls too low, a lowgas pressure program is started. Thegas pressure switch also provides forautomatic valve proving.

Outstanding serviceWeishaupt has an extensive sales andsevice network worldwide. Customerservice is available around the clock.Optimal in-house training at Weishauptensures our service engineers are ofthe highest calibre.

Proven quality All burners are tested by an independent body and conform to thefollowing standards and EU directives:

• EN 676• Gas Appliance Directive

90/396/EEC• Machinery Directive 98/37/EC• Electromagnetic Compatability

Directive 89/336/EEC• Low Voltage Directive 73/23/EEC• Boiler Efficiency Directive

92/42/EEC

WG30 and WG40 also comform to:• Pressure Equipment Directive

97/23/EC

Coded plugs for safe electrical connection All components are easily accessible Simple commissioning and diagnosis

The right size Weishaupt burner for every situation

Page 6: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

Digital combustion management:safe and easy to use

6

All Weishaupt W series burners are fittedwith digital combustion managers asstandard, whose microprocessors controland monitor all burner functions. The result: Weishaupt burners are easy touse, precise and safe.

The digital combustion managers alsooffer the possibility of communicatingwith other systems via an integratedeBUS port. This enables the heatingengineer to monitor the opration of theburner and remotely diagnose any errors.

The key points:

• The utilisation of identical units forgas and oil burners simplifies commissioning and reduces thenumber of spares required.

• Non-interchangeable plug connections ensure the correct electrical connection of all components

• Electrical remote reset is possible

• Safety ensured with the use of twomicroprocessors (reciprocal monitoring)

• Vari-coloured LED lamp to indicateburner operational stage and faultconditions (WG10, WG20 versionsLN and Z-LN)

• LCD display with interrogation, servicing and parameter functions.the burner can be set directly via theoperating keys (WG10 – WG40 version ZM-LN)

• Suitable for continuous operation ofhot water plant (controlled shutdownand restart every 24 hours)

• Suitable for air heaters and Group IIIII, and IV steam boilers (W-FM 21optional)

• The integrated eBUS interface offersthe following functions:

– Connection to a PC for display ofthe operational sequence and thesetting of function parameters

– Remote monitoring and diagnosisvia a self dialling modem

– Connection to modern building ma-nagement systems

– Prepurge time can be set from aPC via the eBUS interface

System overviewDigital combustion management W-FM 05 W-FM 10 W-FM 20 W-FM 21

Combustion manager for intermittent operation ● ● ● ●

Combustion manager for continuous operation ●

Flame sensor Ion Ion Ion Ion

Electronic compound regulation Air and gas ● ●

Stepping motor Air ●

Removable control unit (max. distance) 10 m 10 m

Valve proving ● ● ●

Fuel consumption meter available ● ● ●

eBUS interface ● ● ● ●

Available on burner models WG 10-D WG 10-D WG 10 – WG 40 WG 10 – WG 40WG 20-C WG 20-C modulating modulating

single stage single stage WG 30 – WG 40 WG 30 – WG 40without servomotor with servomotor with speed control with speed control

and two stage TRD execution

Page 7: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

7

The right mode of operationfor every heating need

Gas burnersSingle and two stageWith mechanical compound regulation andintegral gas valve proving

W-FM 10 combustion managerAir stepping motor

(with linkage to gas butterfly valve)

Gas butterfly valve Gas multifunctionassembly

Gas burners Sliding two stage / modulatingWith electronic compound regulation and integral gas valve proving

W-FM 20 combustion manager Air stepping motor

Gas stepping motor Gas multifunctionassembly

Mode of operationF = Full loadP = Partial loadI = Ignition load

G

Z

G

KZ

G

KZ

G

K

Z

On Off

On Off

On Off

On Off

Single stage without servomotor Sliding two stage

Two stage with servomotor Modulating

F F

FF

I I

IIP P

P

Page 8: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

Trustworthy technology

8

Even the visual impression after removing the burner cover is convincing.All components are clearly arranged,the electrical connections are obviousand non-interchangeable. The technology makes a good impressionbecause it is typical Weishaupt.

Compact constructionThe WG burners’ compact constructionmeans they can be easily installed byone person. Commissioning costs havebeen reduced to a minimum.

Low NOx executionAll WG burners are Low NOx executionas standard. A specially designed mixing head produces an intensive internal flue gas recirculation, resultingin exemplary emission levels.

Sound attenuated air inletThe transverse fan is sound attenuatedon the suction side. These burners therefore operate particularly quietly.

Electronically controlled air damperThe electronically controlled air dampercloses at burner shutdown to hinder thecooling-down of the combustion chamber.

Sevicing positionA special bracket enables the burner tobe put into a servicing position, whichenabling easy access to the burner andmixing assembly.

Common platformThe common platform principle usedwith W burners simplifies the provisionand storage of spare parts.

Diagnosis via laptopA special software package andconnection cables are available for interrogating the combustion manager.Combustion optimisation and fault analysis can thus be carried out easilyvia a laptop computer.

Speed control (WG 30 and WG 40)Whereas normally a burner motor isoperated at a constant speed, speedcontrolled burners vary the speed of theburner motor dependent on the burnerload. The process is controlled by the digital combustion manager. The equipment assures the gas/air compound such that no additionalspeed monitoring is required.

Speed controls offers the advantages ofreduced electrical consumption and aconsiderable reduction in noise levels atpartial load.

The reduced noise levels can be of particular benefit in the field. A 10 dBreduction in the sound level can beachieved at 50% burner load, whichequates to a halving of noise emissions.

Page 9: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

9

Example: WG40 with speed control

W-FM 20combustion manager

Variable speedmotor

Fan pressure impulse line

Frequency convertor

Digital-analogue convertor

Double solenoid valvewith ratio controller

Combustion chamber pressureimpulse line

Page 10: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

10

Model overview

Burner type Version Mode of operation Valve train Rating Product OrderBSP / DN kW Ident-Number No.

WG 10

Natural gas

WG 10 N/0-D ZM-LN sliding two stage or modulating 1/2˝ 3 12,5 – 50 CE-0085 AU 353 232 136 14

WG 10 N/1-D LN single stage with manually set air damper 3/4˝ 40 – 110 CE-0085 BM 0481 232 110 24

WG 10 N/1-D Z-LN single or two stage 3/4˝ 25 – 110 CE-0085 BM 0481 232 123 24

WG 10 N/1-D ZM-LN sliding two stage or modulating 3/4˝ 25 – 110 CE-0085 BM 0481 232 126 24

LPG

WG 10 F/0-D ZM-LN sliding two stage or modulating 1/2˝ 3 12,5 – 50 CE-0085 AU 353 233 136 14

WG 10 F/1-D LN single stage with manually set air damper 3/4˝ 40 – 110 CE-0085 BM 0481 233 110 24

WG 10 F/1-D Z-LN single or two stage 3/4˝ 25 – 110 CE-0085 BM 0481 233 113 24

WG 10 F/1-D ZM-LN sliding two stage or modulating 3/4˝ 25 – 110 CE-0085 BM 0481 233 126 24

WG 20

Natural Gas

WG 20 N/1-C LN single stage with manually set air damper 1˝ 1 80 – 200 CE-0085 BM 0216 232 210 34

WG 20 N/1-C Z-LN single or two stage 1˝ 1 35 – 200 CE-0085 BM 0216 232 213 34

WG 20 N/1-C ZM-LN sliding two stage or modulating 1˝ 1 35 – 200 CE-0085 BM 0216 232 216 34

WG 20 N/1-C LN single stage with manually set air damper 1˝ 2 80 – 200 CE-0085 BM 0216 232 210 44

WG 20 N/1-C Z-LN single or two stage 1˝ 2 35 – 200 CE-0085 BM 0216 232 213 44

WG 20 N/1-C ZM-LN sliding two stage or modulating 1˝ 2 35 – 200 CE-0085 BM 0216 232 216 44

LPG

WG 20 F/1-C LN single stage with manually set air damper 3/4˝ 1 80 – 200 CE-0085 BM 0216 233 210 24

WG 20 F/1-C Z-LN single or two stage 3/4˝ 1 35 – 200 CE-0085 BM 0216 233 213 24

WG 20 F/1-C ZM-LN sliding two stage or modulating 3/4˝ 1 35 – 200 CE-0085 BM 0216 233 216 24

WG 30

WG 30N/1-C ZM-LN sliding two stage or modulating 3/4˝ 40 – 350 CE-0085-AU 0064 232 326 211˝ 232 326 311 1/2˝ 232 326 51

WG 30F/1-C ZM-LN sliding two stage or modulating 3/4˝ 60 – 350 CE-0085-AU 0064 233 326 21

WG 40

WG 40N/1-A ZM-LN sliding two stage or modulating 3/4˝ 55 – 550 CE-0085-AS 0311 232 416 211˝ 232 426 311 1/2˝ 232 416 512˝ 232 406 61DN65 232 416 31DN80 232 416 41

WG 40F/1-A ZM-LN sliding two stage or modulating 3/4˝ 80 – 550 CE-0085-AS 0311 233 416 21

1 with gas multifunction assembly type 5072 with gas multifunction assembly type 5123 for supply pressure pa ≤ 50 mbar only

(pa > 50 mbar to 300 mbar at extra cost)

See price list for special equipment

Note:Valve trains are supplied without thermal shut offs.

See Weishaupt accessories list for thermal shut off prices, Print No. 83021201.

Page 11: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

11

Burner capacities in relation tocombustion chamber resistance

Capacity graphs in accordance with EN 676. The ratingsare based on an installation altitude of 0 m. An altitude-based reduction in capacity of approx. 1 % per 100 mabove sea level should be taken into consideration.

Speed control is available for natural gas burners only.The minimum rating is limited to 60 kW for WG30 and 80 kW for WG 40 burners.

1,5

0kW

1,0

0,5

0

-0,510 30 40 50 6020

Burner type WG 10. . . /0-DVers. ZM-LN

Combustion head WG 10/0-DRating 12.5 – 50 kW

mbarCapacity graph WG 10

3,0

0kW

2,5

2,0

1,5

1,0

0,5

0

-0,5

-1,020 60 80 100 12040

Burner type WG 10. . . /1-DVers. LN

Combustion head WG 10-DRating 40 – 110 kW

mbarCapacity graph WG 10

3,0

0kW

2,5

2,0

1,5

1,0

0,5

0

-0,5

-1,020 60 80 100 12040

Burner type WG 10 . . . /1-DVers. Z-LN / ZM-LN

Combustion head WG 10-DRating 25 – 110 kW

mbarCapacity graph WG 10

3,0

20kW

2,5

2,0

1,5

1,0

0,5

0

-0,5

-1,0100 140 18060

Burner type WG 20 . . . /1-CVers. LN

Combustion head WG 20-CRating 80 – 200 kW

mbarCapacity graph WG 20

3,0

20kW

2,5

2,0

1,5

1,0

0,5

0

-0,5

-1,0100 140 18060

Burner type WG 20 . . . /1-CVers. Z-LN / ZM-LN

Combustion head WG 20-CRating 35 – 200 kW

mbarCapacity graph WG 20

3,5

0kW

3,02,52,01,51,00,5

0

-1,5

-0,5-1,0

200 300100 400

Burner type WG 30N/1-CVers. ZM-LN

Combustion head WG 30Rating 40 – 350 kW

mbarCapacity graph WG 30

3,5

0kW

3,02,52,01,51,00,5

0

-1,5

-0,5-1,0

200 300100 400

Burner type WG 30F/1-CVers. ZM-LN

Combustion head WG 30Rating 60 – 350 kW

mbarCapacity graph WG 30

8

0kW

7654321

-2

0-1

200 300100 400 500

Burner type WG 40N/1-AVers. ZM-LN

Combustion head WG 40Rating 55 – 550 kW

mbarCapacity graph WG 40

8

0kW

7654321

-2

0-1

100 200 300 400 500

Burner type WG 40F/1-A, Vers. ZM-LN

Combustion head WG 40Rating 80 – 550 kW

mbarCapacity graph WG 40

Mixing head “open” Mixing head “closed”

Do not select firing rate below 80 kW.

1.5

1.5

1.0

1.0

2.0

2.53.0

0.5

0.5

-0.5

-0.5

-1.0

1.51.0

2.0

2.53.0

0.5

-0.5

-1.0

1.51.0

2.0

2.53.0

0.5

-0.5

-1.0

1.51.0

2.0

2.53.0

3.03.5

0.5

1.51.0

2.02.5

0.5

-0.5

-1.0

-0.5-1.0-1.5

3.03.5

1.51.0

2.02.5

0.5

-0.5-1.0-1.5

Page 12: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

12

Valve train selection

1 with gas multifunction assembly type 5072 with gas multifunction assembly type 5123 additional FRS governor required when

pa > 50 mbar (to max 300 mbar)

Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax = 300 mbar

[kW] 3/4˝

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

40 1050 1060 1070 1080 1090 11

100 12110 13

WG 10 . . . /1-D with W-MF 507 SE / SLEBurner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax = 300 mbar

[kW] 3/4˝

LPG B/P, Hi = 93.20 MJ/mn3 (25.89 kWh/mn

3), d = 1.555, Wi = 74.73 kWh/mn

3

40 850 860 970 980 1090 11

100 12110 12

Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax = 300 mbar

[kW] 3/4˝

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

40 1250 1260 1270 1280 1390 14

100 15110 16

Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax pemax ≤ 50 mbar > 50, ≤ 300 mbar

[kW] 1/2˝ 1/2˝ 3

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

25 15 1830 15 1835 16 1940 16 1945 17 2050 18 21

WG 10 . . . /0-D with W-MF 055Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax pemax ≤ 50 mbar > 50, ≤ 300 mbar

[kW] 1/2˝ 1/2˝ 3

LPG B/P, Hi = 93.20 MJ/mn3 (25.89 kWh/mn

3), d = 1.555, Wi = 74.73 kWh/mn

3

25 13 1630 13 1635 13 1640 14 1745 14 1750 15 18

Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax pemax ≤ 50 mbar > 50, ≤ 300 mbar

[kW] 1/2˝ 1/2˝ 3

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

25 15 1830 16 1935 17 2040 18 2145 19 2250 20 23

Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax = 300 mbar

[kW] 1˝ 1 1˝ 2

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

80 13 1190 13 11

100 13 11110 14 12120 14 13130 15 13140 15 13150 16 14160 16 15170 16 15180 16 15190 17 16200 18 16

WG 20 . . . /1-C with W-MF 5xx SE / SLEBurner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax = 300 mbar

[kW] 1˝ 1 1˝ 2

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

80 15 1390 15 13

100 15 14110 16 14120 16 15130 17 16140 18 16150 18 17160 19 17170 20 18180 21 18190 22 19200 23 20

Burner Low pressure supplyrating (Supply pressure in mbar

into isolating valve)pemax = 300 mbar

[kW] 3/4˝

LPG B/P, Hi = 93.20 MJ/mn3 (25.89 kWh/mn

3),d = 1.555, Wi = 74.73 kWh/mn

3

80 1390 13

100 13110 14120 14130 14140 14150 15160 15170 16180 17190 18200 19

Page 13: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

13

Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

130 15 14 13160 17 15 14190 18 15 13210 19 15 13240 21 15 13270 23 16 13300 26 17 14350 33 20 16

WG 30. . . /1-C, LN version with W-MF 5xx SE Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝

LPG B/P, Hi = 93.20 MJ/mn3 (25.89 kWh/mn

3), d = 1.555, Wi = 74.73 kWh/mn

3

130 13160 14190 14210 15240 15270 17300 18350 21

Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

130 18 15 14160 20 16 15190 22 17 15210 23 17 15240 26 18 15270 30 19 15300 34 21 17350 44 26 21

Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝ 2˝ 65 80

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

240 19 14 12 11 11 11270 22 14 12 12 11 11300 25 15 13 12 11 11350 30 17 13 13 12 11400 36 19 14 13 12 11450 42 22 15 14 12 12500 52 27 18 17 15 14550 61 31 21 19 16 15

WG 40. . . /1-A, LN version with W-MF 5xx SE or DMV + FRSBurner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝

LPG B/P, Hi = 93.20 MJ/mn3 (25.89 kWh/mn

3), d = 1.555, Wi = 74.73 kWh/mn

3

240 13270 14300 16350 19400 22450 26500 29550 33

Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝ 2˝ 65 80

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

240 26 17 15 14 13 13270 29 18 15 14 13 13300 33 19 15 14 13 13350 40 22 16 15 13 13400 49 26 18 17 15 14450 60 30 21 19 16 15500 72 35 23 21 18 17550 86 42 27 25 21 19

Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝ 2˝

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

130 18 6 6 5160 21 9 8 7190 25 12 10 10220 29 15 13 12250 32 18 15 14280 37 24 16 14310 43 28 17 16350 51 33 19 18

WG 30. . . /1-C with DMV–VEF (speed controlled burnerBurner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝ 2˝

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

130 23 8 7 6160 28 11 9 9190 34 14 12 11220 40 17 15 14250 46 20 17 16280 52 26 19 17310 61 32 20 19350 73 40 23 21

Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝ 2˝

Nat. gas E, Hi = 37.26 MJ/mn3 (10.35 kWh/mn3),

d = 0.606, Wi = 47.84 kWh/mn3

240 30 11 10 9300 40 14 13 11360 54 18 15 13400 64 20 17 15440 75 23 20 16480 88 26 24 18520 101 29 28 20550 111 31 30 22

WG 40. . . /1-A with DMV–VEF (speed controlled burner)Burner Low pressure supplyrating (Supply pressure in mbar into isolating

valve) pemax = 300 mbar[kW] 3/4˝ 1˝ 11/2˝ 2˝

Nat. gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn

3), d = 0.641, Wi = 39.67 kWh/mn

3

240 42 13 11 10300 57 18 15 13360 74 22 19 16400 92 25 22 18440 109 29 24 20480 126 34 28 22520 144 36 34 25550 157 38 37 27

The flue gas resistance must be added to the minimum supply pressure calculated.

The minimum supply pressureshould be no less than 15 mbar.

Notes:

1/2˝ to 2 ˝ valve trains have screwed connections,DN65 and DN80 have flanged connections.

The valve trains can be equipped with thermalshut offs at extra cost.

Clarification of designation

W G 20 N . . . /1-C LNF

N = Natural gas E and LLF = LPG B/P

Weishaupt W Series burnerG = Gas burner

Size

IndexLN = Low NOx

Page 14: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

14

Technical data

d1 h3

h2

Rp

I2 I1

b2

b3

I3

I4

b1

h1

α°

d3

d4

d2

Burner dimensionsBurner type Dimensions in mm

I1 I2 I3 I4 b1 b2 b3 h1 h2 h3 d1 d2 d3 d4 Rp α°

WG 10 140 349 31,5 115 330 165 164 353 270 165 108 M8 150 –170 110 3/4” 45°

WG 20 140 397 32 158 358 182 178 376 284,5 182 120 M8 170 130 1” 45°

WG 30 166 480 62 197 420 226 196 460 342 226 127 M8 170 –186 130 1 1/2” 45°

WG 40 235 577 72 235 450 245 207 480 360 245 154 M10 186 –200 160 1 1/2” 45°

Page 15: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

15

Technical dataBurner type Combust. Motor Servomotor Air pressure Burner Gas valve train Flame

manager switch weight 1 Size Type Weight 1 monitoring

WG 10 . . ./0-D

Vers. ZM-LN W-FM 20 ECK 02/F – 2/1 STE 4.5 * LGW 3/A1 13.5 kg 1/2˝ W-MF 055 6 kg Ionisation230 V, 50 Hz0.04 kW, Cap. 2 µF

WG 10 . . ./1-D

Vers. LN W-FM 05 ECK 03/F – 2/1 none LGW 10/A2 13.5 kg 3/4˝ W-MF SLE 507 6 kg IonisationVers. Z-LN W-FM 10 230 V, 50 Hz STD 4.5 ** 3/4˝ W-MF SE 507Vers. ZM-LN W-FM 20 0.095 kW, Cap. 4 µF STE 4.5 * 3/4˝ W-MF SE 507

WG 20 . . . /1-C

Vers. LN W-FM 05 ECK 04/F – 2/1 none LGW 10/A2 20 kg 1˝ W-MF SLE 507/512 6 kg / 7 kg IonisationVers. Z-LN W-FM 10 230 V, 50 Hz STD 4.5 ** 1˝ W-MF SE 507/512Vers. ZM-LN W-FM 20 0.21kW, Cap. 8 µF STE 4.5 * 1˝ W-MF SE 507/512

WG 30. . ./1-C

Vers. ZM-LN W-FM 20 ECK 05/F-2 STE 4.5 * LGW 10A2 27 kg 3/4˝ W-MF SE 507 5.5 kg Ionisation230 V; 50 Hz BO.36/6-01L 1˝ W-MF SE 512 9.0 kg2900 rpm 11/2˝ W-MF SE 512 13.5 kg0.42 kW; Cap. 12 µF

Vers. ZM-LN W-FM 20 DK 05/F-2 STE 4.5 * LGW 10A2 30 kg 3/4˝ DMV-VEF 507 6.5 kg Ionisationwith speed 3~; 230 V; 50 Hz BO.36/6-01L 1˝ DMV-VEF 512 10.0 kgcontrol 2880 rpm 11/2˝ DMV-VEF 512 12.0 kg

0.42 kW; 2.6 A 2˝ DMV-VEF 520 15.0 kg

WG 40. . ./1-A

Vers. ZM-LN W-FM 20 ECK 06/F-2 STE 4.5 * LGW10A2 35 kg 3/4˝ W-MF SE 507 5.5 kg Ionisation230 V; 50 Hz BO.36/6-01L 1˝ W-MF SE 512 9.0 kg2900 rpm 11/2˝ W-MF SE 512 13.5 kg0.62 kW; 2 ˝ DMV+FRS 520 17.5 kgCap. 16 µF 65 DMV+FRS 5065 50.0 kg

80 DMV+FRS 5080 67.0 kg

Ausf. ZM-LN W-FM 20 DK 06/F-2 STE 4.5 * LGW10A2 38 kg 1˝ DMV-VEF 512 10.0 kg Ionisationwith speed 3~; 230 V; 50 Hz BO.36/6-01L 11/2˝ DMV-VEF 512 12.0 kgcontrol 2900 rpm 2˝ DMV-VEF 520 15.0 kg

0.62 kW; 4 A

* Runtime during operation: with full setting movement max. 50 s/with reduced setting movement min. 25 s/Runtime during pre-purge approx.1–2 s.** Runtime during operation: with full setting movement approx. 3 s/with reduced setting movement < 3 s/Runtime during pre-purge approx. 3 s.

1 All weights are approximate.

Page 16: 9W 01 Weishaupt Gaasip6letid WG10 - WG40 ENG

Max Weishaupt GmbHD-88475 SchwendiTel (073 53) 8 30, Fax (073 53) 8 33 58www.weishaupt.de

Print No. 83205502, April 2006Printed in Germany. All rights reserved.

Neachells Lane, Willenhall, WV13 3RGTel (01902) 609841, Fax (01902) 633343

63 Carlton Place, Glasgow, G5 9TWTel (0141) 420 2030, Fax (0141) 420 2088

A strong sevice network gives peaceof mindWeishaupt equipment is available fromgood heating companies, with whomWeishaupt works in partnership. Tosupport the specialists, Weishauptmeintains a large sales and service network. Delivery, spares and serviceare thus contiunally ensured.

Even in an emergency, Weishaupt ison the job. The service department isavailable to Weishaupt customers around the clock, 365 days a year. AWeishaupt branch office or agencynear you can answer all your questions on heating and Weishauptburners and heating systems.

We’re right where you need us