93reverse Return
-
Upload
gatot-nugroho -
Category
Documents
-
view
217 -
download
0
Transcript of 93reverse Return
8/8/2019 93reverse Return
http://slidepdf.com/reader/full/93reverse-return 1/1
11
Primary Variable Speed Flow
QIn a constant volume chilled
water system, with two way con-
trol valves in the chilled water
cooling coils, can I use a bypass line
between supply and return piping with a
control valve to maintain constant flow
through the chiller? If so, what should be
the pressure settings of the control valve
and the percentage of flow through the
bypass line?
A
The quick answer is “yes”, you
probably could add a by-pass linewith modulating control to main-
tain flow across the chiller. This is the set
up used in Primary Variable Speed/Flow
applications. But there are a lot of cau-
tions to consider before attempting to
retrofit this system, among them the sys-
tem volume, rate of change, pump and
chiller selections and probably the most
important - the control complexity and
operator ability.
Before blessing a system like that, we
would want to know more of the details
concerning the chillers and the total sys-
tem. Depending on the system staging,
the common pipe may have to be sized
either for the largest chiller flow or possi-
bly multiple chiller flows. The
modulating control would be reacting to
differential pressure sensors across each
chiller and would require an algorithm
type controller.
Because of these issues you may want to
consider primary/secondary pumping,
proven over the years as the most simple
and efficient way to control a variable
volume, two-way control valve system.
Variable Flow System
QIn a variable flow system (one
using variable frequency drive)
should the Triple Duty® Valves
be in the 100% open position? I have an
installation that used VFDs but the Triple
Duty Valves are in the 20% and 40%
open position. It seems to me that energy
savings may increase by letting VFD do
the flow regulating.
A “Variable flow” systems are those
that control coil operation using
two-way valves. A “variable
speed” system uses an AFD to adjustpump speed to load, and they usually
have two-way valves. If your pump can
meet the load with those Triple Duty
Valves throttling, they are telling you
that the pump is oversized. Check with a
B&G Representative about trimming the
impellers so that you can open up the
Triple Duty Valves. The system will
work better, and at lower cost, that way.
Steam Pressure
QWhen my condensate return
pumps shut down from a pump
cycle there is a very loud “clunk-
ing” noise in the overhead piping. It
almost sounds like someone inside the
wall hitting the pipe with a hammer or
metal pipe. The piping is 20 yrs. old but
the receiver and pumps are only about
four years old. Is this water hammer?
A If the condensate goes down-
stream of the elevated section of
pipe and it flows into a vented
tank, the noise is probably caused by a
type of water hammer as follows: when
the pump is on, the elevated section of
pipe is full of warm water at some posi-
tive pressure. When the pump stops,
water drains out of the elevated section
into the open tank at a lower level. This
reduces the pressure on the water in the
higher sections of pipe causing some of it
to “flash”, or form steam bubbles. The
collapse of these bubbles as they con-
dense causes the noise. Fix this by
installing a vacuum breaker at the top of
the piping, or a minimum pressure valve
at the tank to keep the pipe full when the
pump stops.
Pressure Sensor
QI am designing the HVAC sys-
tem for a 300 bed hospital.
Chiller capacity is 5,000 tons.
The chilled water hydraulic system is of
the primary chilled water loop type using
a variable speed pumping system. Which
piping system is the best to use in a vari-
able speed pumping system - reverse or
direct return piping?
A Most designers use the direct
return to avoid the cost of the
extra pipe. If you chose to do it
that way, you will have to insure that thesystem is balanced so that the last coils
will get acceptable flow. Reverse return
piping can ease the balance problem a lit-
tle, assuming that the coils are all within
25% of each other in terms of pressure
drop. Be careful to install the pressure
differential sensors properly.
Pressure Regulator
QI have a closed-loop chilled
water hydronic system. The
operating temperature is 42 ºF
with a system water temperature rise of
14 ºF (max temperature of 56 ºF).
I am trying to size an expansion tank for
this system using the Bell & Gossett
ESP-PLUS® selection software, but it
will not let me select a unit for these sys-
tem conditions. Can I conclude that an
expansion tank is not needed? If not, why
not? Does the loop need an expansion
tank to act as a pressure regulator?
A
Your chilled water system defi-
nitely needs a compression tank,
but not for the same reason that ahot water system needs one. Normal
“design” temperature changes in your
system will not change the specific vol-
ume very much, but if the system is idle
during a very hot period, you could get
enough net expansion to cause damage,
or at least open the system relief valve.
The compression tank guards against that
problem. ESP-PLUS® selection software
is based on hot water systems. For your
application, use the highest likely ambi-
ent temperature, and a temperature drop
of 1 degree to size the tank.
FREQUENTLY ASKED QUESTIONS
www.bellgossett.com
To view more FAQ’s, go to
www.bellgossett.com, click
on “Knowledge Base”, and
then enter a key word in the
search box.