900 SERIES PANEL SHEET INDEX CI-DS-01-900 C & I DISCLAIMER CI-PJ-01-900 PANEL JOINT CI-PJ-02-900 INTERMEDIATE SUPPORT CI-EL-01-900 ENDLAP CI-EL-02-900 ENDLAP CONDITIONS CI-EL-03-900 4-WAY INTERSECTION CI-EL-04-900 CONTINUOUS MALE LEG AT STAGGERED ENDLAP CI-EL-05-900 STAGGERED MALE LEG AT ENDLAP CI-EL-06-900 MALE LEG ENDLAP AT CONTINUOUS FEMALE CI-EL-07-900 ENDLAP INSTALLATION SEQUENCE CI-EL-08-900 STAGGERED ENDLAP ASSEMBLY CI-RD-01-900 RIDGE CI-RD-02-900 RIDGE ASSEMBLY CI-RD-03-900 RIDGE CLOSURE ASSEMBLY CI-EV-01-900 LOW EAVE W/O GUTTER CI-EV-02-900 LOW EAVE W/ GUTTER CI-EV-03-900 HIGH EAVE CI-RK-01-900 RAKE CI-VL-01-900 VALLEY CONDITION CI-VL-02-900 VALLEY ASSEMBLY CI-WR-01-900 WALL TO ROOF HIGH EAVE CI-WR-02-900 CONCRETE WALL TO HIGH EAVE CI-WR-03-900 WALL TO RAKE CI-WR-04-900 CONCRETE WALL TO ROOF

Transcript of 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer...

Page 1: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

900 SERIES PANEL

SHEET INDEX

CI-DS-01-900 C & I DISCLAIMER

CI-PJ-01-900 PANEL JOINT

CI-PJ-02-900 INTERMEDIATE SUPPORT

CI-EL-01-900 ENDLAP

CI-EL-02-900 ENDLAP CONDITIONS

CI-EL-03-900 4-WAY INTERSECTION

CI-EL-04-900 CONTINUOUS MALE LEG AT

STAGGERED ENDLAP

CI-EL-05-900 STAGGERED MALE LEG AT ENDLAP

CI-EL-06-900 MALE LEG ENDLAP AT

CONTINUOUS FEMALE

CI-EL-07-900 ENDLAP INSTALLATION SEQUENCE

CI-EL-08-900 STAGGERED ENDLAP ASSEMBLY

CI-RD-01-900 RIDGE

CI-RD-02-900 RIDGE ASSEMBLY

CI-RD-03-900 RIDGE CLOSURE ASSEMBLY

CI-EV-01-900 LOW EAVE W/O GUTTER

CI-EV-02-900 LOW EAVE W/ GUTTER

CI-EV-03-900 HIGH EAVE

CI-RK-01-900 RAKE

CI-VL-01-900 VALLEY CONDITION

CI-VL-02-900 VALLEY ASSEMBLY

CI-WR-01-900 WALL TO ROOF HIGH EAVE

CI-WR-02-900 CONCRETE WALL TO HIGH EAVE

CI-WR-03-900 WALL TO RAKE

CI-WR-04-900 CONCRETE WALL TO ROOF

Page 2: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

900 SERIES PANEL

COMMERCIAL/INDUSTRIAL

DISCLAIMER

DISCLAIMER:

THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED

COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.

LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED

ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR

BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).

PROJECTS LOCATED IN SPECIFIC AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW

LOADS MAY REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL

SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS.

Page 3: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

1

1

2

" - 6

"

1

1

2

"

39

3

8

" (1000mm)

EXTERIOR

INTERIOR

HIGH RIB PROFILE

V-GROOVE PROFILE

CORE DEPTHS:

1.5", 2", 2.5", 3", 4", 5", 6"

STEEL GAUGES:

EXTERIOR: 26, 24, 22

INTERIOR: 26, 24, 22

MODULE WIDTH:

39.375" (39

3

8

")

PANEL ORIENTATION:

ROOF

EMBOSSING:

EXTERIOR: STUCCO / SMOOTH

INTERIOR: STUCCO / SMOOTH

LENGTHS:

MINIMUM: 8'-0"

MAXIMUM: 53'-0"

900 ROOF

PANEL PROFILE

900 SERIES ROOF PANEL

Page 4: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

DIRECTION OF INSTALLATION

FIELD APPLIED BUTYL

TAPE ENTIRE LENGTH

OF LAP JOINT

SIPHON GROOVE

1

4

" - 14 X

7

8

" LOW PROFILE TEK SCREWS

* FOR SLOPES ≥ 1:12 INSTALL AT

20" O.C. BETWEEN MAIN FASTENERS

* FOR SLOPES < 1:12 INSTALL AT 12"

O.C. BETWEEN MAIN FASTENERS

16 GA. PAINTED SADDLE CLIP

STAND ON THIS PANEL

WHEN FASTENING

HEAVY BEAD OF FIELD

APPLIED CONTINUOUS

BUTYL SEALANT

1

4

" - THROUGH

FASTENER WITH WASHER

ROOF SADDLE CLIPS WITH

1

4

" - THROUGH

FASTENER WITH WASHER LOCATED AT HIGH RIBS

AS REQUIRED FOR WIND LOADS

PATTERN NO. 3

PATTERN NO. 2

1

4

" - THROUGH

FASTENERS WITH

NEOPRENE WASHER

PANEL JOINT

900 SERIES ROOF PANEL

Page 5: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

1

4

" - THROUGH FASTENERS

WITH NEOPRENE WASHER

PURLIN (BY OTHERS)

16 GA. PAINTED SADDLE CLIP

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

INTERMEDIATE

SUPPORT

900 SERIES ROOF PANEL

Page 6: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

CONTINUOUS

BUTYL SEALANT W/

MARRIAGE BEAD TO

PANEL JOINT

3" X 4" CONTINUOUS ANGLE,

GAUGE TO MATCH PURLINS

(NOT BY KINGSPAN)

1

4

" - 14 X

7

8

" LOW PROFILE

TEK SCREWS FASTEN

BETWEEN EVERY MINOR RIB

CONTINUOUS HEAVY BEAD

BUTYL SEALANT

2

1

2

" WIDE BUTYL TAPE

CONTINUOUS ALONG

ENDLAP

1

4

" - THROUGH FASTENER

WITH NEOPRENE WASHER

FIELD REMOVE FOAM

AND INSIDE SKIN

FACTORY CUT

LINER SIDE

JOINT TO BE CENTERED

ON STRUCTURAL SUPPORT

6" E

ND

LA

P

1"

NOTE:

MIN. 5" WIDE SUPPORT

AT EACH ENDLAP FOR

PROPER PANEL

ATTACHMENT

6" LAP

MAX.

1

8

" ALLOWABLE "GAP"

BETWEEN PANELS FILLED

WITH EMSEAL BACKSEALER

ADDITIONAL CLIP

LOCATION FOR HIGH WIND

LOAD AREAS

16 GA. PAINTED SADDLE

CLIP

(USE VIBRATION RESISTANT/

ANTI-BACKOUT TYPE)

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

2

1

2

"

2

1

2

"

MIN

.

MIN

.

CONTINUOUS BUTYL

SEALANT TO SEAL

POTENTIAL GAP

BETWEEN STEEL

MEMBERS

CONTINUOUS BUTYL

SEALANT AT JOINT

LOCATIONS

ENDLAP

900 SERIES ROOF PANEL

Page 7: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

PA

NE

L LE

NG

TH

*

3" C

UT

BA

CK

(M

OD

ES

TO

)

4

1

4

" C

UT

BA

CK

(D

ELA

ND

)

SIN

GLE

R

OO

F P

AN

EL LA

YO

UT

WIT

H N

O E

ND

LA

PS

TW

O P

AN

EL LA

YO

UT

WIT

H E

ND

LA

PS

TH

RE

E P

AN

EL LA

YO

UT

WIT

H E

ND

LA

PS

(*) A

DD

W

ALL P

AN

EL T

HIC

KN

ES

S T

O P

AN

EL LE

NG

TH

3" C

UT

BA

CK

(M

OD

ES

TO

)

4

1

4

" C

UT

BA

CK

(D

ELA

ND

)

3" C

UT

BA

CK

(M

OD

ES

TO

)

4

1

4

" C

UT

BA

CK

(D

ELA

ND

)

PA

NE

L LE

NG

TH

6" E

ND

LA

P

PA

NE

L LE

NG

TH

S*

PA

NE

L LE

NG

TH

6" E

ND

LA

P

PA

NE

L LE

NG

TH

6" E

ND

LA

P

PA

NE

L LE

NG

TH

S*

ENDLAP CONDITIONS

900 SERIES ROOF PANEL

Page 8: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

BUTYL SEALANT FOR

VAPOR BARRIER

CONTINUOUS

BUTYL TAPE AT

LAP JOINT

REMOVE 6" MALE LEG ON THE LOWER

END OF THE UPPER PANEL, THEN ALIGN

INSTALL AND ALIGN UPPER COURSE,

FASTEN AND SEAL AS DETAILED

CONTINUOUS BUTYL

TAPE

1

2

NOTES:

1. SET LOWER COURSE ROOF PANEL IN PLACE. UPPER END OF PANEL AT THE ENDLAP MUST ALIGN

WITH THE WEB OF THE ENDLAP PURLIN AND REST ON THE 3" X 4" SUPPORT ANGLE.

2. CHECK PANEL MODULE, ADJUST IF NECESSARY BEFORE ATTACHING PANEL TO THE SUPPORT

ANGLE WITH FASTENING SYSTEM.

3. SET THE UPPER PANEL IN PLACE, FASTEN PANELS TO THE SUPPORT STRUCTURE USING A SINGLE

HEX HEAD FASTENER WITH PAINTED SADDLE CLIP WHICH MUST PASS THROUGH ALL FOUR PANELS.

4. KINGSPAN DOES NOT RECOMMEND INSTALLING ALL LOWER COURSE PANELS FIRST.

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD

CONTINUOUS BUTYL

SEALANT

CONTINUOUS BUTYL SEALANT TO

SEAL POTENTIAL GAP BETWEEN

STEEL MEMBERS

MAX.

1

8

" ALLOWABLE

"GAP" BETWEEN

PANELS FILLED WITH

EMSEAL BACKSEALER

EMSEAL BACKSEALER

CONTINUOUS BUTYL

SEALANT AT JOINT

LOCATIONS

4-WAY INTERSECTION

900 SERIES ROOF PANEL

Page 9: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

BUTYL SEALANT FOR

VAPOR BARRIER

CONTINUOUS

BUTYL TAPE AT

LAP JOINT

REMOVE 6" MALE LEG ON THE LOWER

END OF THE UPPER PANEL, THEN ALIGN

INSTALL AND ALIGN UPPER COURSE,

FASTEN AND SEAL AS DETAILED

CONTINUOUS BUTYL

TAPE

1

2

NOTES:

1. SET LOWER COURSE ROOF PANEL IN PLACE. UPPER END OF PANEL AT THE ENDLAP MUST ALIGN

WITH THE WEB OF THE ENDLAP PURLIN AND REST ON THE 3" X 4" SUPPORT ANGLE.

2. CHECK PANEL MODULE, ADJUST IF NECESSARY BEFORE ATTACHING PANEL TO THE SUPPORT

ANGLE WITH FASTENING SYSTEM.

3. SET THE UPPER PANEL IN PLACE, FASTEN PANELS TO THE SUPPORT STRUCTURE USING A SINGLE

HEX HEAD FASTENER WITH PAINTED SADDLE CLIP WHICH MUST PASS THROUGH ALL FOUR PANELS.

4. KINGSPAN DOES NOT RECOMMEND INSTALLING ALL LOWER COURSE PANELS FIRST.

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD

CONTINUOUS BUTYL

SEALANT

CONTINUOUS BUTYL SEALANT TO

SEAL POTENTIAL GAP BETWEEN

STEEL MEMBERS

EMSEAL BACKSEALER

CONTINUOUS MALE LEG

AT STAGGERED ENDLAP /

FEMALE ENDLAP

900 SERIES ROOF PANEL

Page 10: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

BUTYL SEALANT FOR

VAPOR BARRIER

CONTINUOUS

BUTYL TAPE AT

LAP JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD

CONTINUOUS BUTYL SEALANT TO

SEAL POTENTIAL GAP BETWEEN

STEEL MEMBERS

MAX.

1

8

" ALLOWABLE "GAP"

BETWEEN PANELS FILLED WITH

EMSEAL BACKSEALER

3" X 4" ANGLE, GAUGE TO MATCH

PURLINS

(NOT BY KINGSPAN)

CONTINUOUS BUTYL

SEALANT

NOTES:

1. SET LOWER COURSE ROOF PANEL IN PLACE. UPPER END OF PANEL AT THE ENDLAP MUST ALIGN

WITH THE WEB OF THE ENDLAP PURLIN AND REST ON THE 3" X 4" SUPPORT ANGLE.

2. CHECK PANEL MODULE, ADJUST IF NECESSARY BEFORE ATTACHING PANEL TO THE SUPPORT

ANGLE WITH FASTENING SYSTEM.

3. SET THE UPPER PANEL IN PLACE, FASTEN PANELS TO THE SUPPORT STRUCTURE USING A SINGLE

HEX HEAD FASTENER WITH PAINTED SADDLE CLIP WHICH MUST PASS THROUGH ALL FOUR PANELS.

4. KINGSPAN DOES NOT RECOMMEND INSTALLING ALL LOWER COURSE PANELS FIRST.

REMOVE 6" MALE LEG ON THE LOWER

END OF THE UPPER PANEL, THEN ALIGN

INSTALL AND ALIGN UPPER COURSE,

FASTEN AND SEAL AS DETAILED

1

2

STAGGERED MALE LEG AT

ENDLAP

900 SERIES ROOF PANEL

Page 11: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

BUTYL SEALANT FOR

VAPOR BARRIER

CONTINUOUS

BUTYL TAPE AT

LAP JOINT

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD

CONTINUOUS BUTYL SEALANT TO

SEAL POTENTIAL GAP BETWEEN

STEEL MEMBERS

MAX.

1

8

" ALLOWABLE

"GAP" BETWEEN

PANELS FILLED WITH

EMSEAL BACKSEALER

3" X 4" ANGLE, GAUGE TO MATCH

PURLINS

(NOT BY KINGSPAN)

STAGGERED MALE LEG AT

ENDLAP / CONTINUOUS

FEMALE LEG

900 SERIES ROOF PANEL

Page 12: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

12

46

35

78

EA

VE

R

A

K

E

RID

GE

PU

RL

IN

T

YP

E M

AY

V

AR

Y

DIR

EC

TIO

N O

F IN

ST

AL

LA

TIO

N

NO

TE

: IN

TE

RM

ED

IA

TE

R

IB

S A

RE

N

OT

S

HO

WN

F

OR

C

LA

RIT

Y

ENDLAP INSTALLATION

SEQUENCE

900 SERIES ROOF PANEL

Page 13: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

1F

AS

TE

N A

T E

VE

RY

M

IN

OR

R

IB

V

AL

LE

Y

2S

TA

GG

ER

ED

E

ND

LA

PS

3S

EE

M

AL

E L

EG

E

ND

LA

P D

ET

AIL

4S

EE

C

ON

TIN

UO

US

M

AL

E L

EG

D

ET

AIL

5S

EE

F

EM

AL

E L

EG

E

ND

LA

P D

ET

AIL

15

43

ST

AG

GE

RE

D E

ND

LA

P A

SS

EM

BL

Y

(IS

OM

ET

RIC

V

IE

W - T

YP

IC

AL

)

STAGGERED ENDLAP

ASSEMBLY

900 SERIES ROOF PANEL

Page 14: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

1

4

" - 14 X

7

8

" LOW PROFILE TEK

SCREWS AT EACH HIGH RIB AND

BETWEEN HIGH RIBS

FIELD FILL WITH COMPRESSIBLE

INSULATION OR FIELD FOAM WITH

2-PART URETHANE (NOT BY KINGSPAN)

OUTSIDE RIDGE TRIM

(SET IN BUTYL TAPE)

RIDGE CLOSURE TRIM

INSIDE RIDGE TRIM

900 FOAM CLOSURE SET IN

BUTYL TAPE TOP AND BOTTOM

1

4

" - THROUGH FASTENER

WITH NEOPRENE WASHER

(AS REQUIRED FOR WIND LOADS)

CONTINUOUS BUTYL

SEALANT W/ MARRIAGE

BEAD TO PANEL JOINT

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

1

4

" - 14 X

7

8

" LOW

PROFILE TEK SCREWS

BETWEEN EVERY

MINOR RIB

CONTINUOUS

BUTYL TAPE

CONTINUOUS

BUTYL TAPE

CONTINUOUS BUTYL

SEALANT AT JOINT

LOCATIONS

RIDGE

900 SERIES ROOF PANEL

Page 15: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

1

4

" - 14 X

7

8

" LOW

PROFILE TEK

SCREWS AT

EACH HIGH

RIB AN

BETWEEN HIGH

RIBS

OUTSIDE RIDGE TRIM

5

5

NOTE: SEE 900 CLOSURE

ASSEMBLY DETAIL

BUTYL TAPE

RIDGE CLOSURE TRIM W/

1

4

" - 14 x

7

8

" LOW PROFILE

TEK SCREWS BETWEEN EVERY MINOR RIB

900 FOAM CLOSURE

FOUR REQUIRED PER PANEL

5

4

3

3

3

2

2

1

FIELD FILL WITH COMPRESSIBLE

INSULATION OR FIELD FOAM WITH

2-PART URETHANE (NOT BY

KINGSPAN)

SET IN BUTYL TAPE

TOP AND BOTTOM

1

4

" - THROUGH FASTENER

WITH NEOPRENE WASHER

(AS REQUIRED FOR WIND

LOAD)

INSIDE RIDGE TRIM

NOTE: # 'S REFER TO SEQUENCE

OF INSTALLATION

SET IN CONTINUOUS BUTYL

SEALANT W/ MARRIAGE

BEADS TO PANEL JOINT

RIDGE ASSEMBLY

900 SERIES ROOF PANEL

Page 16: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

900 STANDARD ROOF CLOSURE SET

ROOF CLOSURE TO BE FIELD CUT FOR HIP AND VALLEY CONDITIONS

BUTYL TAPE

RIDGE CLOSURE TRIM (NOTCH AS NECESSARY AT HIGH RIB)

OUTSIDE CLOSURE

BUTYL TAPE

900 ROOF PANEL

COMPLETELY FILL

VOIDS AROUND FOAM

CLOSURE AT BATTEN

RIB WITH SEALANT

(NOT BY KINGSPAN)

BUTYL TAPE

BUTYL SEALANT

COMPLETELY FILL

VOIDS AROUND FOAM

CLOSURE AT BATTEN

RIB WITH SEALANT

(NOT BY KINGSPAN)

BUTYL TAPE

RIDGE CLOSURE

ASSEMBLY

900 SERIES ROOF PANEL

Page 17: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

CONTINUOUS

BUTYL SEALANT W/

MARRIAGE BEAD TO PANEL

JOINT

(2)

1

4

" - HEX HEAD

FASTENERS PER PANEL

CLIP

CONTINUOUS BUTYL

SEALANT W/ MARRIAGE

BEAD TO VERTICAL

PANEL JOINT

POP RIVETS @ 8" O.C.

14 GA. GALVANIZED

HIDDEN CLIP

(1 PER PANEL, PER GIRT)

(SET CLIP IN BED OF BUTYL

SEALANT)

CONTINUOUS

BUTYL TAPE

16 GA. PAINTED SADDLE CLIP

INSIDE FOAM CLOSURE W/

BUTYL TAPE TOP, BOTTOM

AND SIDES

1

4

" - 14 X

7

8

" LOW PROFILE

TEK SCREWS @ 8" O.C.

LOW EAVE TRIM

1

4

" - THROUGH FASTENER

WITH NEOPRENE WASHER

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

HEAVY BEAD OF BUTYL

SEALANT AT LAP JOINT TO

MARRY BUTYL TAPE AND

SEALANT AT PANEL JOINT

BUTYL TAPE AT

LAP JOINT

COMPRESSIBLE

INSULATION OR FIELD

FOAM WITH 2-PART

URETHANE (NOT BY

KINGSPAN)

LOW EAVE W/O

GUTTER

900 SERIES ROOF PANEL

Page 18: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

12"

1

2

"

4"

CONTINUOUS

BUTYL TAPE

GUTTER TRIM

EAVE CLOSURE TRIM

(PRE-ASSEMBLED TO GUTTER)

1

4

" - 14 X

7

8

" LOW

PROFILE TEK SCREWS @ 8" O.C.

GUTTER HANGER*

INTERMEDIATE

GUTTER HANGERGUTTER

HANGER

FOR SNOW LOAD AREAS, ADD

INTERMEDIATE GUTTER

HANGERS, TWO PER PANEL

MAXIMUM / AS REQUIRED

(LOCATE AT HIGH RIBS)

* LOCATE GUTTER HANGER AT EACH

"LAPPING" RIB

NOTE: STANDARD EAVE CUTBACK IS

3" MODESTO, 4

1

4

" DELAND

INSIDE FOAM

CLOSURE

CONTINUOUS

BUTYL TAPE

BUTYL TAPE AT

LAP JOINT

POP RIVETS @ 8" O.C.

CONTINUOUS

BUTYL SEALANT W/

MARRIAGE BEAD TO

PANEL JOINT

CONTINUOUS BUTYL

SEALANT W/ MARRIAGE

BEAD TO VERTICAL

PANEL JOINT

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

COMPRESSIBLE

INSULATION OR FIELD

FOAM WITH 2-PART

URETHANE (NOT BY

KINGSPAN)

1

4

" - THROUGH

FASTENER

WITH

NEOPRENE

WASHER

HEAVY BEAD OF BUTYL SEALANT

AT LAP JOINT TO MARRY BUTYL

TAPE AND SEALANT AT PANEL

JOINT

(2)

1

4

" - HEX HEAD

FASTENERS PER

PANEL CLIP

14 GA. GALVANIZED HIDDEN CLIP

(1 PER PANEL, PER GIRT)

(SET CLIP IN BED OF BUTYL

SEALANT)

LOW EAVE W/ GUTTER

900 SERIES ROOF PANEL

Page 19: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

HIGH EAVE TRIM

RIDGE CLOSURE TRIM WITH

OUTSIDE FOAM CLOSURE SET IN

BUTYL TAPE TOP AND BOTTOM

W/

1

4

" - 14 X

7

8

" LOW PROFILE TEK

SCREWS BETWEEN EVERY

MINOR RIB

1

4

" - 14 X

7

8

" LOW PROFILE

TEK SCREWS @ EACH HIGH

RIB AND BETWEEN HIGH RIB

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

1

4

" - THROUGH FASTENER WITH

NEOPRENE WASHER

HEAVY BEAD OF BUTYL SEALANT

AT LAP JOINT TO MARRY BUTYL

TAPE AND SEALANT AT PANEL

JOINT

OUTSIDE FOAM CLOSURE

SET IN BUTYL TAPE TOP

AND BOTTOM

COMPRESSIBLE

INSULATION OR FIELD

FOAM WITH 2-PART

URETHANE (NOT BY

KINGSPAN)

(2)

1

4

" - HEX HEAD FASTENERS

PER PANEL CLIP

CONTINUOUS BUTYL SEALANT

W/ MARRIAGE BEAD TO PANEL

JOINT

14 GA. GALVANIZED HIDDEN CLIP

(1 PER PANEL, PER GIRT)

(SET CLIP IN BED OF BUTYL

SEALANT)

POP RIVETS @ 8" O.C.

BUTYL TAPE AT

LAP JOINT

CONTINUOUS

BUTYL TAPE

HIGH EAVE

900 SERIES ROOF PANEL

Page 20: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

1

4

" - 14 THROUGH FASTENER

WITH 1

1

8

" BONDED WASHER

RAKE FASCIA

1

4

" - 14 X

7

8

" LOW PROFILE

TEK SCREWS @ 8" O.C.

BUTYL TAPE

CONTINUOUS BUTYL SEALANT

SHEETING OR RAKE ANGLE

REQUIRED (NOT BY KINGSPAN)

POP RIVETS @ 8" O.C.

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

COMPRESSIBLE

INSULATION OR FIELD

FOAM WITH 2-PART

URETHANE (NOT BY

KINGSPAN)

(2)

1

4

" - HEX HEAD FASTENERS

PER PANEL CLIP

14 GA. GALVANIZED HIDDEN CLIP

(1 PER PANEL, PER GIRT)

(SET CLIP IN BED OF BUTYL

SEALANT)

CONTINUOUS BUTYL SEALANT

W/ MARRIAGE BEAD TO PANEL

JOINT

RAKE

900 SERIES ROOF PANEL

Page 21: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

FIE

LD

CU

T

BA

CK

*

UPPER VALLEY FLASHING

(FIELD BREAK FROM FLATSTOCK)

1

4

" - 14 X

7

8

" LOW PROFILE

TEK SCREWS 4" O.C.

(IN LOWS)

1

4

" - 14 X

7

8

" LOW PROFILE

TEK SCREWS W/O WASHER

SEE BELOW FOR

ADDITIONAL INFO.

1

4

" - 14 X

7

8

" LOW

PROFILE TEK SCREWS

W/O WASHER 18" O.C

COMPLETELY FILL

VOID W/ COMPRESSIBLE

INSULATION (NOT BY

KINGSPAN)

LOWER VALLEY

FLASHING (NOT BY

KINGSPAN) GAUGE TO

MATCH PURLIN

1

4

" - THROUGH

FASTENER WITH

NEOPRENE WASHER

VALLEY SUPPORT ("Z"

SHAPE) SET IN

BUTYL SEALANT

6

7

5

4

3

12

SEQUENCE OF INSTALLATION:

1 LOWER VALLEY PAN

2 "Z" SHAPED VALLEY SUPPORT

3 FILL VOID W/ INSULATION

4 INSTALL SECONDARY & UPPER VALLEY PAN

5 APPLY TAPE MASTIC TO TOP OF UPPER VALLEY PAN

6 CUT ROOF PANELS. REMOVE CUT BACK & FOAM AT HIGH RIB

7 FASTEN ASSEMBLY

* FIELD CUT ROOF PANELS FOR 4

1

4

" OR 3" CUTBACK. CUTBACK SIZE

TO MATCH THE EAVE CONDITION

FIE

LD

CU

T

BA

CK

FIELD CUT PANEL FOAM AT HIGH

RIB INSIDE FOAM CLOSURE AS

NECESSARY TO FIT HIGH RIB

LOCATIONS

16 GA. PAINTED

SADDLE CLIP

FIELD CUT INSIDE

FOAM CLOSURE SET

IN BUTYL TAPE TOP

AND BOTTOM

CONTINUOUS

BUTYL SEALANT

VALLEY CONDITION

900 SERIES ROOF PANEL

Page 22: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

PURLIN

AND FLASHINGS

VALLEY SUPPORT STEEL

GUTTERS

AT VALLEY CONDITION

FIELD CUTBACK

HIGH RIB AT

PANEL JOINT

ROOF VALLEY PLAN

TO MATCH FACTORY

CUTBACK AT EAVE

CONDITION

4

1

4

" CUTBACK (DELAND)

3" CUTBACK (MODESTO)

V

A

L

L

E

Y

SL

OP

E

SLOPE

VALLEY ASSEMBLY

900 SERIES ROOF PANEL

Page 23: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

CONTINUOUS BUTYL

SEALANT BOTH

SIDES OF TRIM W/

MARRIAGE BEAD TO

VERTICAL PANEL

JOINT

RIDGE CLOSURE TRIM WITH

OUTSIDE FOAM CLOSURE SET IN

BUTYL TAPE TOP AND BOTTOM

BASE TRIM W/ POP RIVETS

@ 8" O.C.

TRANSITION FLASHING

1

4

" - 14 X

7

8

" LOW PROFILE TEK

SCREWS AT EACH HIGH RIB AND

BETWEEN HIGH RIB

FIELD FILL WITH

COMPRESSIBLE

INSULATION (NOT BY

KINGSPAN)

KINGSPAN TO SUPPLY

FLAT STOCK MATERIAL

(FIELD BREAK BY OTHERS)

CONTINUOUS BUTYL SEALANT

WITH MARRIAGE BEAD TO

PANEL JOINT

16 GA. PAINTED SADDLE CLIP

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

STRUCTURAL FRAMING

W/ MIN. 3" BEARING

SURFACE FOR PANEL

FASTENING

(NOT BY KINGSPAN)

FOAM CLOSURE W/

BUTYL TAPE TOP

AND BOTTOM

(2)

1

4

" - HEX HEAD FASTENERS

PER PANEL CLIP

14 GA. GALVANIZED HIDDEN CLIP

(1 PER PANEL, PER GIRT)

(SET CLIP IN BED OF BUTYL

SEALANT)

1

4

" - THROUGH FASTENER WITH

NEOPRENE WASHER

1

4

" - 14 X

7

8

" LOW PROFILE TEK

SCREWS BETWEEN EVERY

MINOR RIB

CONTINUOUS BUTYL

TAPE

CONTINUOUS BUTYL SEALANT

AT JOINT LOCATIONS

WALL TO ROOF

HIGH EAVE

900 SERIES ROOF PANEL

Page 24: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

RIDGE CLOSURE TRIM WITH

OUTSIDE FOAM CLOSURE SET IN

BUTYL TAPE TOP AND BOTTOM

CONTINUOUS BUTYL SEALANT W/

MARRIAGE BEAD TO PANEL JOINT

FASTENERS TO CONCRETE

(NOT BY KINGSPAN)

POURABLE SEALANT

(NOT BY KINGSPAN)

FIELD CUT MASONRY FOR INSTALLATION OF FLASHING,

FILL VOID WITH SEALANT (NOT BY KINGSPAN)

COUNTER FLASHING

TRANSITION FLASHING

1

4

" - 14 X

7

8

" LOW PROFILE TEK

SCREWS AT EACH HIGH RIB AND

BETWEEN EACH HIGH RIB

1

4

" - THROUGH FASTENER

WITH NEOPRENE WASHER

FILL WITH

COMPRESSIBLE

INSULATION

(NOT BY KINGSPAN)

16 GA. PAINTED SADDLE CLIP

KINGSPAN TO SUPPLY

FLAT STOCK MATERIAL

(FIELD BREAK BY OTHERS)

CONTINUOUS BUTYL

SEALANT AT PANEL JOINT

FOAM CLOSURE W/

BUTYL TAPE TOP

AND BOTTOM

CONCRETE

MASONRY WALL

(NOT BY KINGSPAN)

1

4

" - 14 X

7

8

" LOW

PROFILE TEK

SCREWS BETWEEN

EVERY MINOR RIB

CONTINUOUS BUTYL

TAPE

CONTINUOUS BUTYL

SEALANT AT JOINT

LOCATIONS

CONCRETE WALL

TO HIGH EAVE

900 SERIES ROOF PANEL

Page 25: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

CONTINUOUS BUTYL

SEALANT BOTH SIDES

OF TRIM WITH

MARRIAGE BEAD

TO VERTICAL

PANEL JOINT

BASE TRIM W/ POP RIVETS @ 8"-12" O.C.

TRANSITION FLASHING

FILL WITH

COMPRESSIBLE

INSULATION

(NOT BY KINGSPAN)

1

4

" - 14 X

7

8

" LOW

PROFILE TEK SCREWS

@ 8" O.C.

CONTINUOUS BUTYL TAPE

CONTINUOUS BUTYL SEALANT

1

4

" - THROUGH FASTENER

WITH 1

1

8

" BONDED WASHER

(AS REQUIRED FOR WIND LOAD)

RAKE ANGLE WITH

UP-TURNED LEG FOR

PANEL ATTACHMENT

(NOT BY KINGSPAN)

CONTINUOUS BUTYL

SEALANT AT PANEL

JOINT

(2)

1

4

" - HEX HEAD FASTENERS

PER PANEL CLIP

14 GA. GALVANIZED HIDDEN CLIP

(1 PER PANEL, PER GIRT)

(SET CLIP IN BED OF BUTYL

SEALANT)

WALL TO RAKE

900 SERIES ROOF PANEL

Page 26: 900 SERIES PANEL - az750602.vo.msecnd.net · 900 series panel commercial/industrial disclaimer disclaimer: these details are provided as a guideline for proper panel and associated

FASTENERS TO CONCRETE

(NOT BY KINGSPAN)

POURABLE SEALANT

(NOT BY KINGSPAN)

FIELD CUT MASONRY FOR INSTALLATION OF FLASHING,

FILL VOID WITH SEALANT (NOT BY KINGSPAN)

COUNTER FLASHING

TRANSITION FLASHING

1

4

" - 14 X

7

8

" LOW

PROFILE TEK SCREWS

@ 8" O.C.

BUTYL TAPE

1

4

" - THROUGH FASTENER WITH 1

1

8

" BONDED WASHER

(AS REQUIRED FOR WIND LOAD)

CONTINUOUS BUTYL SEALANT AT RAKE ANGLE TO

MASONRY WALL

CONTINUOUS BUTYL SEALANT

CONCRETE

MASONRY WALL

(NOT BY KINGSPAN)

FILL WITH

COMPRESSIBLE

INSULATION

(NOT BY

KINGSPAN)

RAKE ANGLE FOR

PANEL ATTACHMENT

AND FASTENER

(NOT BY KINGSPAN)

CONCRETE WALL TO

ROOF

900 SERIES ROOF PANEL