    Bulletin 825-P

    User Manual

  • 7/22/2019 825 User Manual

    2/232

    Important User Information Because of the variety of uses for the products described in this publication,those responsible for the application and use of this control equipment mustsatisfy themselves that all necessary steps have been taken to assure that eachapplication and use meets all performance and safety requirements, includingany applicable laws, regulations, codes and standards.

    The illustrations, charts, sample programs and layout examples shown in thisguide are intended solely for purposes of example. Since there are manyvariables and requirements associated with any particular installation, RockwellAutomation does not assume responsibility or liability (to include intellectualproperty liability) for actual use based upon the examples shown in thispublication.

    Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application,Installation and Maintenance of Solid-State Control(available from your localAllen-Bradley distributor), describes some important differences betweensolid-state equipment and electromechanical devices that should be taken intoconsideration when applying products such as those described in thispublication.

    Reproduction of the contents of this copyrighted publication, in whole or part,without written permission of Rockwell Automation, is prohibited.

    Throughout this manual we use notes to make you aware of safetyconsiderations:

    Attention statements help you to:

    Identify a hazard

    Avoid a hazard

    Recognize the consequences

    Trademark ListDeviceNet and the DeviceNet logo are trademarks of the Open Device Vendors Association (ODVA).Microsoft Windows is a registered trademark of the Microsoft Corporation.

    ATTENTION

    !

    Identifies information about practices or circumstancesthat can lead to personal injury or death, property damageor economic loss.

    IMPORTANT Identifies information that is critical for successfulapplication and understanding of the product.

  • 7/22/2019 825 User Manual

    3/232

    European Communities (EC)Directive Compliance

    If this product has the CE mark it is approved for installation within theEuropean Union and EEA regions. It has been designed and tested to meetthe following directives.

    EMC Directive

    This product is tested to meet the Council Directive 89/336/EECElectromagnetic Compatibility (EMC) by applying the following standards, in

    whole:

    EN 60947-4-1 Low-Voltage Switchgear and Controlgear: Part 4:Contactors and Motor Starters - Section 1: ElectromechanicalContactors and Motor Starters

    EN 60947-5-1 Low-Voltage Switchgear and Controlgear: Part 5:Control Circuit Devices and Switching Elements - Section 1:Electromechanical Control Circuit Devices

    This product is intended for use in an industrial environment.

    Low Voltage Directive

    This product is tested to meet Council Directive 73/23/EEC Low Voltage asamended by 93/68/EEC by applying the safety requirements ofEN 60947-4-1 and EN 60947-5-1. For specific information required byEN 60947-4-1 and EN 60947-5-1, see the appropriate sections in thispublication.

    Notice

    This product has been designed for environment A. Use of this product inenvironment B can cause unwanted elctromagnetic disturbances in whichcase the user could be required to take adequate mitigation measures.

  • 7/22/2019 825 User Manual

    4/232

  • 7/22/2019 825 User Manual

    5/232

    Publication 825-UM004C-EN-P May 2004

    Table of Contents i

    PrefaceManual Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1

    Typographic Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2

    Chapter 1: IntroductionOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

    Standard Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Optional Protection Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Monitoring Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

    Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3

    Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3

    Chapter 2: InstallationRelay Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

    Physical Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Relay Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2

    Rear-Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Rear-Panel Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Top-Panel Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5I/O Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6

    AC/Control Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7Fail-Safe/Non-Fail-Safe Tripping . . . . . . . . . . . . . . . . . . . . . . . . . 2-7Converter Module Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9Core Balance Current Transformer Connections . . . . . . . . . . . . 2-10Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11Across the Line Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12Star-Delta Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14Two-Speed Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16

    Field Serviceability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18Fuse Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19Real-Time Clock Battery Replacement . . . . . . . . . . . . . . . . . . . . 2-20

    Chapter 3: Front-Panel OperationFront-Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Normal Front-Panel Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Front-Panel Automatic Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2

    Front-Panel Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3Alarm or Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Lockout Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5

  • 7/22/2019 825 User Manual

    6/232

    Publication 825-UM004C-EN-P May 2004

    ii Table of Contents

    Front-Panel Menus and Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5Front-Panel Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6

    Front-Panel Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9

    Main Menu > Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10Main Menu > Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11Main Menu > Motor Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12Main Menu > Targets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13Main Menu > Set/Show. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14Main Menu > Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17Main Menu > Reset Thermal Capacity . . . . . . . . . . . . . . . . . . . . 3-18Main Menu > Reboot/Restore . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18

    View or Change Settings Using the Front Panel . . . . . . . . . . . . . . . . 3-20Setting Entry Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22

    Chapter 4: ASCII Serial CommunicationsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1ASCII Serial Port Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Connect Your PC to the Relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2Configure Your Terminal Emulation Software . . . . . . . . . . . . . . 4-3

    Serial Port Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3Using Terminal Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4Serial Port Access Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5Command Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6

    Description of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7ACC and 2AC (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7ANALOG (Level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7DATE (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8METER (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8MOTOR (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11PASSWORD (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11QUIT (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12SER (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12SET (Level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13SHOW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14STATUS (Level 1 or 2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16STOP (Level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18STR (Level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18SUMMARY (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19TARGET (Level 1 or 2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19TIME (Level 1 or 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23

    View or Change Settings With Front-Panel Serial Port . . . . . . . . . . 4-23View Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23Enter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24

  • 7/22/2019 825 User Manual

    7/232

    Publication 825-UM004C-EN-P May 2004

    Table of Contents iii

    Chapter 5: Protection and Logic FunctionsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2Main Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3

    Identifier Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3Phase Rotation, Nominal Frequency Settings . . . . . . . . . . . . . . . . 5-3Current Transformer (CT) Configuration,Full Load Current Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4Voltage Transformer (VT) Configuration Settings . . . . . . . . . . . . 5-5

    Basic Motor Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6Overload (Thermal Model) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6Short Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11

    Ground Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12Jam. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14Undercurrent (Load Loss) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14

    Current Imbalance/Phase Loss . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15Protection Disable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16Start Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16Start Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18Phase Reversal Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18Speed Switch (Stalling During Start) . . . . . . . . . . . . . . . . . . . . . . 5-19Thermistor (PTC) Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20

    RTD-Based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21RTD Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21

    Voltage-Based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24Undervoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24

    Overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24VAR Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25Underpower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25Power Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26Load Control Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27

    I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28Trip Inhibit (Block) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29Output Relay Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30Timer Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31

    Front-Panel Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-32Display Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-32I/O Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-33

    Logic Explanation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38Stop/Trip Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38Initiate Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38Unlatch Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38Start and Emergency Restart Logic . . . . . . . . . . . . . . . . . . . . . . . 5-39

  • 7/22/2019 825 User Manual

    8/232

    Publication 825-UM004C-EN-P May 2004

    iv Table of Contents

    Chapter 6: Metering and MonitoringOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1

    Instantaneous Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2

    Thermal Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2Power Measurement Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3Motor Operating Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4

    Chapter 7: Analyzing EventsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1Event Summary Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1

    Report Triggering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2Retrieving Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2Resetting the Buffer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2

    Serialized Events Recording (SER) Report . . . . . . . . . . . . . . . . . . . . . 7-2

    SER Triggering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2Retrieving SER Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3Resetting the SER Report Buffer. . . . . . . . . . . . . . . . . . . . . . . . . . 7-4

    Example Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4Event Summary Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4Serialized Events Recording (SER) Report . . . . . . . . . . . . . . . . . . 7-5

    Chapter 8: Testing and TroubleshootingOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1

    Commissioning Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1Selected Functional Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7Periodic Tests (Routine Maintenance). . . . . . . . . . . . . . . . . . . . . 8-12

    Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-15

    Appendix A: SpecificationsElectrical Ratings: Main Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Electrical Ratings: Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . A-2Mechanical Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3RTD Scanner Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5

    Metering Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6Primary Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6825-CBCT Core Balance Current Transformer. . . . . . . . . . . . . . . . . A-7

  • 7/22/2019 825 User Manual

    9/232

    Publication 825-UM004C-EN-P May 2004

    Table of Contents v

    Appendix B: Firmware Upgrade InstructionsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

    Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1Upgrade Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

    Appendix C: Relay Word BitsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-4

    Appendix D: ASCII Port Relay Command Summary

    Appendix E: 825-P Settings RecordSET Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-2SET M Command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-13

    I/O Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-13SET P Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-21DeviceNet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-21

    Appendix F: Linear Parameter ListOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1

    Appendix G: Modbus RTU Communications ProtocolOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-1Modbus Queries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-1

    Modbus Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2Supported Modbus Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . G-2Modbus Exception Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-3Cyclical Redundancy Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-303h Read Holding Register Command . . . . . . . . . . . . . . . . . . . . . . . G-406h Preset Single Register Command . . . . . . . . . . . . . . . . . . . . . . . . G-510h Preset Multiple Registers Command. . . . . . . . . . . . . . . . . . . . . . G-660h Read Parameter Information Command . . . . . . . . . . . . . . . . . . G-761h Read Parameter Text Command. . . . . . . . . . . . . . . . . . . . . . . . . G-962h Read Enumeration Text Command . . . . . . . . . . . . . . . . . . . . . G-107Dh Encapsulated Packet With Control Command. . . . . . . . . . . . G-11

    7Eh NOP Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-12Modbus Password Control and Parameter Modification . . . . . . . . G-12Modbus Serialized Events Recording Register Operation . . . . . . . G-13Modbus Load Profile Register Operation . . . . . . . . . . . . . . . . . . . . G-13

  • 7/22/2019 825 User Manual

    10/232

    Publication 825-UM004C-EN-P May 2004

    vi Table of Contents

  • 7/22/2019 825 User Manual

    11/232

    Preface

    Manual Overview The 825-P Relay User Manual describes common aspects of motor relayapplication and use. It includes the necessary information to install, set,test, and operate the relay and more detailed information about settingsand commands. The chapter descriptions are as follows:

    PrefaceDescribes the manual organization and conventions used topresent information.

    Chapter 1: IntroductionDescribes the basic features and functions of the 825-P.

    Chapter 2: InstallationDescribes how to mount and wire the 825-P; illustrates wiringconnections for various applications.

    Chapter 3: Front-Panel OperationExplains features and use of the front panel, including front-panelcommand menu, default displays, and automatic messages.

    Chapter 4: ASCII Serial CommunicationsDescribes how to connect the 825-P to a PC for communication;shows serial port pinouts; lists and defines serial port commands.

    Chapter 5: Protection and Logic FunctionsDescribes the operating characteristic of each protection elementand explains how to calculate their settings; describes contactoutput logic.

    Chapter 6: Metering and MonitoringDescribes the operation of each metering function; describes themonitoring functions.

    Chapter 7: Analyzing EventsDescribes front-panel LED operation, trip-type front-panelmessages, event summary data, standard event reports, andSerialized Events Recording (SER) report.

    Chapter 8: Testing and TroubleshootingDescribes protection element test procedures, relay self-test, andrelay troubleshooting.

    Appendix A: SpecificationsProvides detailed specification and certification information forall components of the 825-P Modular Protection System.

    Appendix B: Firmware Upgrade InstructionsProvides detailed specification and certification information forall components of the 825-P Modular Motor Protection Relay.

    Appendix C: Relay Word BitsLists and describes the Relay Word bits (e.g., real-time status ofrelay I/O, protection functions).

    Appendix D: ASCII Port Relay Command SummaryBriefly describes the serial port commands that are fully describedin Chapter 4: ASCII Serial Communications.

  • 7/22/2019 825 User Manual

    12/232

    Publication 825-UM004C-EN-P May 2004

    P-2 Preface

    Appendix E: 825-P Settings RecordProvides the setting sheets that include the definition and input rangefor each setting in the relay. Space is provided for recording settingvalues for future reference.

    Appendix F: Linear Parameter ListThis appendix lists all accessible parameters of the 825-P relay innumerical order. The setting range for each parameter is provided toassist, especially for applications where you want to set values from alogic controller via a network connection.

    Appendix G: Modbus RTU Communications ProtocolThis appendix describes the communications features supported by the

    825-P Modbus RTU option card.

    Conventions Typographic Conventions

    The primary ways to configure the 825-P are:

    Using a command line interface on a PC terminal emulation window,

    such as Microsoft HyperTerminal.

    Using the front-panel menus and push buttons.

    The instructions in this manual indicate these options with specific font andformatting attributes.

    Examples

    This instruction manual uses several example illustrations and instructions toexplain how to effectively operate the 825-P. These examples are fordemonstration purposes only; the firmware identification information orsettings values included in these examples may not necessarily match those inthe current version of your 825-P.

    Example Description

    STATUS Commands typed at a command line interface on a PC.

    Enter Single keystroke on a PC keyboard.Ctrl+D Multiple/combination keystroke on a PC keyboard.

    Start > Settings PC dialog boxes and menu selections.The > character indicates submenus.

    CLOSE Relay front-panel push buttons.

    ENABLE Relay front-panel or rear-panel labels.

    MAIN > METER Relay front-panel LCD menus and relay responses.The > character indicates submenus.

  • 7/22/2019 825 User Manual

    13/232

    Chapter1

    Introduction

    Overview The 825-P Motor Relay is designed to protect three-phase motors. Thebasic relay provides locked rotor, overload, unbalance, and short circuitprotection. Voltage-based and RTD-based protection is available as anoption. All relay models provide monitoring functions.

    This manual contains the information for installing, setting, testing,operating, and maintaining an 825-P. It is not necessary to review theentire manual to perform specific tasks.

    A Quick Start guide, Publication 825-QS001_-EN-P is also available. Itwill help to step the first-time user through the device commissioningprocess.

    Features Standard Protection Features

    Thermal Overload (thermal model)

    PTC (positive temperature coefficient) Overtemperature

    Undercurrent (Load Loss)

    Current Imbalance and Phase Loss

    Overcurrent (Load Jam)

    Short Circuit

    Ground Fault

    Ground Fault (uses core balance CT)

    Motor Starting/Running

    Protection Inhibit During Start

    Start Motor Timer

    Notching or Jogging Device TCU (Thermal Capacity Utilization) Start Inhibit

    Anti-Backspin Timer

    Emergency Start

    Two Speed Protection

    Reduced Voltage Starting (Star-Delta)

    StallSpeed Switch

    Frequency

  • 7/22/2019 825 User Manual

    14/232

    Publication 825-UM004C-EN-P May 2004

    1-2 Introduction

    Optional Protection Features

    Voltage-Based Protection

    Undervoltage Overvoltage

    Underpower

    Reactive Overpower

    Phase Reversal

    Power Factor

    RTD-Based Protection

    Up to 12 RTDs can be monitored when an external 825-PR12D RTD Scanner

    is used. There are separate trip and warn settings for each RTD.

    Monitoring Features

    The monitoring features of the 825-P are as follows:

    Event summaries that contain relay ID, date and time, trip cause, andcurrent/voltage magnitudes. The last five trip causes are saved innonvolatile memory.

    Serialized Events Recording (SER). Motor running time since the last reset.

    Start cycles since the last reset.

    Emergency start cycles since the last reset.

    A complete suite of accurate metering functions.

    Options and Accessories Options

    The 825-P has the following options:

    Voltage Option: four-wire wye or open-delta connected VTs.

    Input/Output (I/O) Option: one 420 mA analog (transducer) output,three additional control inputs, and four additional contact outputs.

    Network Communications options.

  • 7/22/2019 825 User Manual

    15/232

    Publication 825-UM004C-EN-P May 2004

    Introduction 1-3

    Accessories

    Phase current inputs require one of the following external 825-MCMconverter modules:

    A separate zero-sequence current input requires an external 825-CBCT CoreBalance Current Transformer, or equivalent.

    The following devices are required to add RTD protection:

    An external 825-PR12D RTD.

    A simplex 62.5/125 m fiber-optic cable with ST connector forconnecting the external RTD module to the 825-P.

    Applications Chapter 2: Installation includes AC and DC connection diagrams for variousapplications. The following are possible scenarios:

    With or without phase current transformers

    With or without zero-sequence core balance current transformer

    With or without external RTD module

    Across the line starting

    Star-delta starting

    Two-speed motors

    Figure 1.1 shows across the line starting AC connections for the case whereexternal current transformers are not required. Refer to Chapter 2: Installationfor additional applications and the related connection diagrams.

    Table 1.1 Converter Module List

    Cat. No. Description

    825-MCM2 0.52.5 A Converter Module

    825-MCM20 2.520.0 A Converter Module

    825-MCM180 20.0180.0 A Converter Module

    825-MCM630 160.0630.0 A Converter Module

    825-MCM630N 160.0630.0 A Converter Module

  • 7/22/2019 825 User Manual

    16/232

  • 7/22/2019 825 User Manual

    17/232

    Chapter2

    Installation

    Relay Placement Proper placement of the 825-P Motor Relay helps make certain that youreceive years of trouble-free motor protection. Use the followingguidelines for proper physical installation of the 825-P.

    Physical Location

    You can mount the 825-P in a sheltered indoor environment (a buildingor an enclosed cabinet) that does not exceed the temperature andhumidity ratings for the relay. The relay can be mounted indoors or in anoutdoor (extended) enclosure where the relay is protected againstexposure to direct sunlight, precipitation, and full wind pressure, butneither temperature nor humidity are controlled.

    Refer to Appendix A: Specifications for environmental ratings.

  • 7/22/2019 825 User Manual

    18/232

    Publication 825-UM004C-EN-P May 2004

    2-2 Installation

    Relay Mounting

    To flush mount the 825-P in a panel, cut a rectangular hole with thedimensions shown in Figure 2.1.

    Figure 2.1 Relay Mounted In a Panel

    20.8(0.82)

    147.4(5.80)

    Legendmm(in)

    192.0(7.56)

    186.0(7.32)

    138.0(5.43)

    144.0

    (5.67)

    Mounting Panelmaximum thickness 6.5 mm #8 x 1/2 inch mounting screw;

    Torque specification = 0.9...1.3 N.m (8...12 Lb-in) Gasket

  • 7/22/2019 825 User Manual

    19/232

    Publication 825-UM004C-EN-P May 2004

    Installation 2-3

    Rear-Panel Connections Rear-Panel Diagram

    The physical layout of the connectors on the rear-panel of a fully configured825-P is shown in Figure 2.2.

    Figure 2.2 Rear-Panel Layout

  • 7/22/2019 825 User Manual

    20/232

    Publication 825-UM004C-EN-P May 2004

    2-4 Installation

    Top-Panel Diagram

    The input and output designations for the rear-panel connectors of a fullyconfigured 825-P are shown in Figure 2.3. This diagram is located on the top

    panel of the relay.

    Figure 2.3 Top-Panel Input and Output Designations

  • 7/22/2019 825 User Manual

    21/232

    Publication 825-UM004C-EN-P May 2004

    Installation 2-5

    Power Connections

    The power terminals on the rear panel (A1+ and A2-) must connect to110240V AC or 110250V DC. For complete power input specifications,

    see Appendix A: Specifications.

    The power terminals are isolated from chassis ground. Use 16 AWG

    (1.5 mm2) size or heavier wire to connect to the POWER terminals.Connection to external power must comply with IEC 947-1 and IEC 947-3.

    Place an external switch, circuit breaker, or overcurrent device in the powerleads for the 825-P; this device must interrupt both the hot (H) and neutral(N) power leads. The maximum current rating for the power disconnect circuitbreaker or overcurrent device (fuse) must be 20 A. Be sure to locate this devicewithin 3.0 m (9.8 ft.) of the relay.

    Operational power is internally fused by power supply fuse. See FieldServiceability on page 2-18 for details. Be sure to use fuses that comply withIEC 127-2.

  • 7/22/2019 825 User Manual

    22/232

  • 7/22/2019 825 User Manual

    23/232

  • 7/22/2019 825 User Manual

    24/232

  • 7/22/2019 825 User Manual

    25/232

    Publication 825-UM004C-EN-P May 2004

    Installation 2-9

    Converter Module Connection

    Figure 2.7 Converter Module Connection

    Note:The 825-P relay is not EMC-tested for converter module connectingcable lengths greater than the 4-meter cable that is supplied.

    Figure 2.8 Converter Module Dimensions

    MCM

    4-meter cable is supplied

    with MCM converter module

    d3b b

    2

    e2 e2

    d2

    a

    c1

    c

    e

    d1

    d

    b1

    e3

    Cat. No. 825-MCM2...825-MCM180 Cat. No. 825-MCM420

    Cat. No. 825-MCM630N

  • 7/22/2019 825 User Manual

    26/232

    Publication 825-UM004C-EN-P May 2004

    2-10 Installation

    Core Balance Current Transformer Connections

    Figure 2.9 Core Balance Current Transformer Connections

    Figure 2.10 825-CBCT Dimensions

    825-CBCT GroundFault Sensor (or

    customer-suppliedequivalent)

    Cat. No. 825-CBCT

  • 7/22/2019 825 User Manual

    27/232

  • 7/22/2019 825 User Manual

    28/232

    Publication 825-UM004C-EN-P May 2004

    2-12 Installation

    Across the Line Starting

    Figure 2.12 AC Connections Without CTs

    Figure 2.13 AC Connections With Core Balance CT

    825-P825-MCM

    L3L2L1A1

    1 3 5

    642

    A2

    M3 ~

    U1 Converter Module

    Cat. No. 825-MCM2Cat. No. 825-MCM20Cat. No. 825-MCM180Cat. No. 825-MCM630Cat. No. 825-MCM630N

    825-P825-MCM Converter Module825-MCM2825-MCM20825-MCM180825-MCM630825-MCM630N

    T2 core balance transformerCurrent ratio of core

    balance current transformerOutput from core

    balance current transformer

    1...2000:1

    0...500 mA

    L3L2L1

    T2

    S1 S2

    1 3 5

    642

    M3 ~

  • 7/22/2019 825 User Manual

    29/232

  • 7/22/2019 825 User Manual

    30/232

  • 7/22/2019 825 User Manual

    31/232

  • 7/22/2019 825 User Manual

    32/232

    Publication 825-UM004C-EN-P May 2004

    2-16 Installation

    Two-Speed Motor

    Figure 2.18 AC connections for a Two-Speed Motor

    The two-speed motor applications in Figure 2.18 and Figure 2.19 require thefollowing input setting:

    IN1 = 0 0 0 0 0 0 0 1 0 0 (SPEED2)

    1 3 5L N

    Y12 Y1

    642

    (II)(I)

    825-P

    825-P

    825-MCM

    24 V AC/V DC

    M3 ~

  • 7/22/2019 825 User Manual

    33/232

    Publication 825-UM004C-EN-P May 2004

    Installation 2-17

    Figure 2.19 AC Connections for a Two-Speed Motor With Primary CTs

    825-P

    825-P

    825-MCM

    L3L2L1

    K1

    I

    (I) (II) K1

    Y1 Y12

    II

    ... A / 1 (5) A ... A / 1 (5) A

    K2

    K2

    M3 ~

    L3 L NL2L1

    24 V AC/V DC

  • 7/22/2019 825 User Manual

    34/232

  • 7/22/2019 825 User Manual

    35/232

  • 7/22/2019 825 User Manual

    36/232

    Publication 825-UM004C-EN-P May 2004

    2-20 Installation

    Real-Time Clock Battery Replacement

    To replace the real-time clock battery, do the following:

    1. De-energize the relay.

    2. Remove the eight rear-panel screws, the ground screw, and the relayrear-panel.

    3. Remove the Slot B printed circuit board.

    4. Locate the battery clip (holder) on the board.

    5. Remove the battery from beneath the clip.

    6. Properly dispose of the old battery.

    7. Install the new battery with the positive (+) side facing up.

    8. Insert the printed circuit board into Slot B.

    9. Reinstall the relay rear-panel and ground screw, and then energize therelay.

    10. Set the relay date and time.

  • 7/22/2019 825 User Manual

    37/232

    Chapter3

    Front-Panel Operation

    Front-Panel Layout The 825-P Relay front-panel interface consists of two LEDs, an LCDdisplay, a seven-button keypad, and an EIA-232 serial port connector.The front-panel layout is shown in Figure 3.1.

    Figure 3.1 Relay Front Panel

    Normal Front-Panel Display In normal operation, the relay ENABLE LED is illuminated and theLCD display screen is on. The LCD screen rotates displays showingeach screen for about two seconds before moving to the next. Thedefault rotating display screens include Unit ID Line 1, Unit ID Line 2,line currents, and voltages (if available). Enable the relay to add displaymessages as noted in the Display Enable settings in Table 5.35.

    ENABLE LEDLit when relayis operational.

    TRIP LEDFlashes to indicatealarm conditions;steady on toindicate trip.

    TEST/RESET PushbuttonReset the TRIP or

    TRIP TEST the relay.

    Arrow PushbuttonsFacilitate navigation

    left, right, up, and down.

    EIA-232 Serial PortQuick access to all relay data,

    control, and setting functions usinga PC, serial cable, and software.

    Front-PanelPushbuttons

    Control the front-panel display.

    LCD DisplayDisplays real time and

    historic information;relay settings menus.

    {Enter} Pushbutton

  • 7/22/2019 825 User Manual

    38/232

    Publication 825-UM004C-EN-P May 2004

    3-2 Front-Panel Operation

    Figure 3.2 Default Display Screen

    Use the UNIT ID LINE 1 (RID) and UNIT ID LINE 2 (TID) settingsdescribed in Identifier Settings on page 5-3 to change the contents of theinformation shown in Figure 3.2.

    If the front panel was in Access Level 2, it automatically returns to the defaultdisplay when the display times out. For more information, see Table 5.34.

    The display changes for the following relay conditions in the order ofprecedence (see Table 3.1):

    Status failure

    Trip condition time to trip (if under 10000 seconds)

    Warning Lockout start request

    Emergency start in progress

    Front-Panel AutomaticMessages

    The relay displays automatic messages under the conditions described inTable 3.1.

    Front-Panel Messages

    Each time the relay trips, it automatically displays a front-panel message andthe Trip LED illuminates. If a trip occurs during a critical alarm statuscondition, the Trip LED flashes (see Self-Tests on page 8-11).

    825-P Modular

    Prot. System

    Table 3.1 Front-Panel Automatic Messages

    Condition Front-Panel Message

    Relay detecting any failure Displays the type of latest failure (see Testing andTroubleshooting on page 8-1.)

    Relay trip has occurred Displays the type or cause of the trip. (See the list ofthe types of Trip messages under the headingFront-Panel Messages on page 3-2.

    Motor running overload Displays the predicted time to thermal element trip inseconds

    Relay alarm condition hasoccurred

    Displays the type of alarm (see Alarm or WarningMessages on page 3-3)

    When a start is requestedduring a lockout condition

    Displays the type of lockout condition (seeLockout Messages on page 3-4)

    Control input set to

    disable protection

    Displays Protect Disabled By Control Input

    During emergency start Displays Emergency Start

  • 7/22/2019 825 User Manual

    39/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-3

    Trip message

    The Trip message describes the type of trip that occurred:

    Overload Trip

    Locked Rotor Trip Undercurrent Trip

    Jam Trip

    Current Imbalance Trip

    Short Circuit Trip

    Ground Fault Trip

    Speed Switch Trip

    Undervoltage Trip

    Overvoltage Trip

    Underpower Trip

    Power Factor Trip

    Reactive Power Trip

    Phase Reversal Trip

    Underfrequency Trip

    Overfrequency Trip

    RTD Trip

    PTC Trip

    Start Time Trip

    RTD Fail Trip

    PTC Fail Trip Comm Idle Loss Trip

    Remote Trip

    Comm Fail Trip

    Alarm or Warning Messages

    Each time the relay is in a warning condition with the Trip LED flashing, thefront-panel displays the corresponding warning message.

  • 7/22/2019 825 User Manual

    40/232

    Publication 825-UM004C-EN-P May 2004

    3-4 Front-Panel Operation

    The Warning message describes the type of warning that is occurring:

    Overload Warning

    Undercurrent Warning

    Jam Warning

    Current Imbalance Warning

    Ground Fault Warning

    Short Circuit Warning

    Speed Switch Warning

    Undervoltage Warning

    Overvoltage Warning

    Underpower Warning

    Power Factor Warning

    Reactive Power Warning

    Underfrequency Warning Overfrequency Warning

    RTD Warning

    RTD Failure

    MCM/CWE Failure

    PTC Failure

    Comm. Loss Warning

    Comm. Idle Warning

    Comm. Fault Warning

    The relay automatically displays a thermal time to trip for an impendingthermal overload. See Figure 3.3.

    Figure 3.3 Trip Message Sample

    Lockout Messages

    TCU Lockout

    Start/Hr Lockout Min Off Lockout

    Restart Lockout

    Front-Panel Menus andOperations

    The 825-P front panel gives you access to most of the information that therelay measures and stores. You can also use front-panel controls to view ormodify relay settings.

    Thermal Trip In

    1234 sec

  • 7/22/2019 825 User Manual

    41/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-5

    All of the front-panel functions are accessible using the seven-button keypadand LCD display. Use the keypad, shown in Figure 3.4, to maneuver within thefront-panel menu structure, described in detail throughout the remainder ofthis section. Table 3.2 describes the function of each front-panel push button.

    Figure 3.4 Front-Panel Push Buttons

    The Test/Reset push button has two functions if it has not been disabled.

    Pressing the Test/Reset push button resets the Trip LED and the Trip outputof the relay. If a trip condition is active, the front-panel message displays thefollowing:

    Reset Failed

    TRIP is active

    To test the trip output, press the Test/Reset push button for longer than twoseconds.

    The Test/Reset push button is disabled when Disable settings are active (seeTable 5.38).

    Table 3.2 Front-Panel Push Button Functions

    Push Button Function

    UpArrow Move up within a menu or data list.While editing a setting value, increase the value of theunderlined digit.

    DownArrow Move down within a menu or data list.While editing a setting value, decrease the value of theunderlined digit.

    LeftArrow Move the cursor to the left.While viewing event data, move to data for a newer event.

    RightArrow Move the cursor to the right.While viewing Event data, move to the data for an olderevent.

    Esc Re-activate the front-panel display back-lighting.Escape from the current menu or display.

    Enter Move from the default display to the main menu.Select the menu item at the cursor.Select the displayed setting to edit the setting.

    Trip/Reset Trip test the device.Reset the trip.

  • 7/22/2019 825 User Manual

    42/232

    Publication 825-UM004C-EN-P May 2004

    3-6 Front-Panel Operation

    Front-Panel Security

    Front-Panel Access Levels

    The relay front panel typically operates at Access Level 1 and allows any userto view relay measurements and settings. Some activities, such as editingsettings and controlling output contacts, are restricted to those operators whoknow the relay Access Level 2 password when enabled. The factory defaultsetting for the Access Level 2 password is DISABLED, which providesunrestricted access.

    In the figures that follow, restricted activities are marked with the padlocksymbol shown in Figure 3.5.

    Figure 3.5 Access Level Security Padlock Symbol

    Before you can perform a front-panel menu activity that is marked with thepadlock symbol, you must enter the correct Access Level 2 password. Afteryou have correctly entered the password, you can perform other Access Level2 activities without reentering the password.

    Access Level 2 Password Entry

    When you try to perform an Access Level 2 activity, the relay determineswhether you have entered the correct Access Level 2 password since thefront-panel inactivity timer expired or since the "Reset Access Lvl" commandhas been executed from the Main Menu. If you have not, the relay displays thescreen shown in Figure 3.6 for you to enter the password.

  • 7/22/2019 825 User Manual

    43/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-7

    Figure 3.6 Password Entry Screen

    To Enter Password

    Perform these steps to enter the correct password to issue an Access Level 2function or to change the Access Level 2 password, as described in Figure 3.23on page 3.16.

    1. Press the DownArrow push button twice. A blinking cursor appears inthe first character position of the password and an underline appearsbeneath the character (letter) A in the lower line of the display.

    2. Underline the first character of the password by moving through thecharacters shown in Figure 3.6. Use the LeftArrow and RightArrowpush buttons to move the underline to the left and right and theUpArrow and DownArrow push buttons to move to other characterrows.

    3. With the correct first character underlined, press the Enter push button.The first character appears in the upper line of the display and theblinking cursor moves one character to the right.

    4. Using the arrow push buttons, continue to move within the charactertable and select each of the characters to build the Access Level 2password.

    Password=

    Del Clr Accept

    A B C D E F G H

    I J K L M N O P

    Q R S T U V W X

    Y Z . . . . . .

    a b c d e f g h

    i j k l m n o p

    q r s t u v w x

    y z . . . . . .

    0 1 2 3 4 5 6 7

    8 9 . . . . . .

    ! " # $ % ^ ' (

    ) * + , - . / :

    ; < = > ? @ [ \

    ] ^ _ ` { | } ~

  • 7/22/2019 825 User Manual

    44/232

  • 7/22/2019 825 User Manual

    45/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-9

    6. Press the Enter push button to accept the password shown in the upperline of the display.

    7. If the password is correct, the relay continues the task.

    8. Press the Enter push button to continue your task. If the password wasincorrect, the relay displays the message Invalid Password.

    9. Press the Enter push button to return to your password entry.

    10. Repeat Steps 19 until you enter the correct password.

    11. When you have completed changing settings, use the Main Menucommand Reset Access Lvl (described in the next section) to reset theAccess Level to Level 1 so that unauthorized access is prevented. (Theaccess level will remain at Level 2 until the front panel backlight times

    out or the Reset Access Lvl command is executed.)

    Front-Panel Main Menu All access to information and relay settings through the front panel starts atthe relay main menu. The remainder of this section describes the use of themain and lower level menus.

    Main Menu

    Note:The LCD display is dark if it is timed out from inactivity. Press any key

    to activate the LCD display.

    Figure 3.7 Front Panel Main Menu

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    CET 5 Modular

    Prot. System

    LCD Display Main Menu

    MAIN

    Meter

    Events

    Motor Monitor

    Targets

    Set/Show

    Status

    Reset TCU

    Reboot/Restore

    Reset Access Lvl

  • 7/22/2019 825 User Manual

    46/232

    Publication 825-UM004C-EN-P May 2004

    3-10 Front-Panel Operation

    Main Menu > Meter

    Figure 3.8 Main Menu > Meter Function

    The Meter menu includes functions to display meter data. Display functions

    are Instantaneous and Thermal. When you select a display function, such asInstantaneous in Figure 3.9, the relay displays a list of instantaneous metervalues you can move through using the UpArrow and DownArrow pushbuttons.

    The Thermal display function operates similarly to the Instantaneous displayfunction with the applicable thermal values displayed.

    Figure 3.9 Meter Menu > Instantaneous Meter Display Functions

    Meter

    Events

    Main Menu Item Meter Values MenuMETER

    Instantaneous

    Thermal

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    METER

    Instantaneous

    Meter Values Menu Item Instantaneous Meter Display

    L1 Current

    5.4 A

    L1 Angle

    2.3 deg

    L2 Current

    6.3 A

    Frequency

    60.0 Hz

    Press these keysto move within the list.

  • 7/22/2019 825 User Manual

    47/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-11

    Main Menu > Events

    Figure 3.10 Main Menu > Events Function

    Figure 3.11 Events Menu > Display Events Function

    Events

    Motor Monitor

    Main Menu Item Events Display

    EVENTS

    Display Events

    Reset Events

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    EVENTS

    Display Events

    Events Menu Item Events Display

    03/12/2003

    13:48:09.902

    Press these keysto move among events.

    Press this keyto select an event.

    Press this key

    to select event data.

    03/12/2003

    13:48:09.902

    Display Events Menu Item Display Events Display

    Date

    03/12/2003

    Time

    13:48:09.902

    Type

    Lockd Rotor Trip

    L1 Current

    4.1 A

    VCA

    0 V

    Move amongdata for this event.

  • 7/22/2019 825 User Manual

    48/232

    Publication 825-UM004C-EN-P May 2004

    3-12 Front-Panel Operation

    Figure 3.12 Events > Reset Events

    Main Menu > Motor Monitor

    Figure 3.13 Main Menu > Motor Monitor Function

    Figure 3.14 Motor Monitor > Use Data Function

    Display Events

    Reset Events

    Events Menu Item Reset Events Display

    Reset Evnt Data?

    No Yes

    To move between Yes and No.Yes: Resets Event Data Buffer;No: Returns to EVENTS Menu.

    To select underlined option.

    Motor Monitor

    Targets

    Main Menu Item Motor Monitor Menu

    MOTOR MONITOR

    Use Data

    Reset Statistics

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    Use Data

    Reset Statistics

    Motor Monitor Menu Item Motor Use Data Function

    Last Reset Date

    03/24/2003

    Last Reset Time

    13:28:21

    Running Time

    0:00:00

    Stopped Time

    1:03:49

    Time Running0.0 %

    Number of Starts

    0

    Emergency Starts

    0

    Press these keysto move within the list.

  • 7/22/2019 825 User Manual

    49/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-13

    Figure 3.15 Motor Monitor > Reset Statistics Function

    Main Menu > Targets

    The Target values provide real-time status of relay I/O, protection functions,etc. For detailed descriptions, see Appendix C: Relay Word Bits.

    Figure 3.16 Main Menu > Targets Function

    Use Data

    Reset Statistics

    Motor Monitor Menu Item Reset Statistics Function

    Reset Stats?

    No Yes

    To move between Yes and No.Yes: Resets Event Data Buffer;No: Returns to MOTOR MONITOR Menu.

    To select underlined option.

    Targets

    Set/Show

    Main Menu Item Targets Function

    TARGETS

    Row 1=00000000

    Row 2=00000000

    Row 3=00000010

    Row 10=01000000

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    Row 1=00000000

    Row 2=00000000

    Targets Menu Item Targets Function

    49T

    0

    LOSSTRIP

    0

    JAMTRIP

    0

    50G1T

    0

    Press these keysto move within thelist of Relay Word targets.

    Press this key to returnto the previous menu.

  • 7/22/2019 825 User Manual

    50/232

    Publication 825-UM004C-EN-P May 2004

    3-14 Front-Panel Operation

    Main Menu > Set/Show

    Figure 3.17 Main Menu > Show/Set Function

    Figure 3.18 SET/SHOW > RELAY Function

    Figure 3.19 RELAY > Main Settings Function

    Set/Show

    Status

    Main Menu Item Set/Show FunctionSET/SHOW

    RELAY

    PORT

    IO ASSIGN

    DATE/TIME

    PASSWORD

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    SET/SHOW

    RELAY

    Set/Show Menu Item Relay Function

    RELAY

    Main Settings

    Overload Set

    Short Ckt Set

    Timer Settings

    Front Panel Set

    Display Enable

    Press these keysto move within the list.

    Press this key toselect a settingsgroup to set or show.

    RELAY

    Main Settings

    Set/Show Menu Item Main Settings Function

    UNIT ID LINE 1

    825-P Modular

    Unit ID LINE 2

    Prot. System

    PHASE ROTATION

    ABC

    XFMR CONNECTION

    WYE

    Press these keysto move within the list.

    Press this keyto select and edit.

  • 7/22/2019 825 User Manual

    51/232

  • 7/22/2019 825 User Manual

    52/232

  • 7/22/2019 825 User Manual

    53/232

  • 7/22/2019 825 User Manual

    54/232

    Publication 825-UM004C-EN-P May 2004

    3-18 Front-Panel Operation

    Main Menu > Reset Thermal Capacity

    Figure 3.26 Main Menu > Reset Thermal Capacity Function

    Main Menu > Reboot/Restore

    Figure 3.27 Main Menu > Reboot/Restore Function

    Figure 3.28 Reboot/Restore > Reboot Relay Function

    Reset TCU

    Reboot/Restore

    Reset Thermal CapacityMenu Item Reset Thermal CapacityFunction

    Reset TCU?

    No Yes

    To Move between Yes and No.Yes: Resets thermal modeldata and timer;No: Cancels command.Press this key toselect an underlined option.

    Reset TCU

    Reboot/Restore

    Main Menu Item Reset/Restore Function

    REBOOT/RESTORE

    Reboot Relay

    Restore Defaults

    Press these keysto move within the list.

    Press this key to selectan underlined menu item.

    Reboot Relay

    Restore Defaults

    Reset Relay Menu Item Reset Relay Function

    Reboot Relay?

    No Yes

    To move between Yes and No.Yes: Reboots the relay;No: Returns to previous menu.

    Press this key to

    select an underlined option.

  • 7/22/2019 825 User Manual

    55/232

  • 7/22/2019 825 User Manual

    56/232

    Publication 825-UM004C-EN-P May 2004

    3-20 Front-Panel Operation

    Record. Use the UpArrowand DownArrow and the LeftArrowandRightArrow push buttons to scroll through the relay settings and view orchange them as required by selecting them and editing them. After viewing orchanging the Relay settings, press the Esc push button until the followingmessage appears:

    Select and enter the appropriate command by pressing the Enterpush button.Select Yes to save the settings changes and No to discard the changes.

    Note: Each 825-P is shipped with default factory settings. Calculate thesettings for your motor to ensure secure and dependable protection.Document the settings on the 825-P Settings Record before entering newsettings in the relay (see Appendix E: 825-P Settings Record).

    Figure 3.31 shows a front-panel menu navigation example for the relay toenter the Phase Rotation (ABC, ACB) setting.

    Save Changes?

    Yes No

  • 7/22/2019 825 User Manual

    57/232

    Publication 825-UM004C-EN-P May 2004

    Front-Panel Operation 3-21

    Figure 3.31 Front-Panel Setting Entry Example

    Main Menu

    Meter

    Events

    Motor Monitor

    Targets

    Set/Show

    Status

    Reset TCU

    Set/Show Menu

    RELAY

    PORT

    IO ASSIGN

    DATE/TIME

    PASSWORD

    RELAY Menu

    Main Settings

    Overload Set

    Front Panel Set

    Display Enable

    Main Settings Menu

    UNIT ID LN 1

    UNIT ID LN 2

    PH ROTATION

    RATED FREQ

    LINE VOLTAGE

    XFMR CON

    PHASEROTATION Menu

    PHROT=ABC

    Press to move

    within the list.

    Press to returnto the previous list.

    Press to select an

    underlined menu item.

  • 7/22/2019 825 User Manual

    58/232

    Publication 825-UM004C-EN-P May 2004

    3-22 Front-Panel Operation

    Setting Entry ErrorMessages

    As you enter relay settings, the relay checks the setting entered against thesettings own range as published on the relay setting sheet. If an entered settingfalls outside its range, the relay immediately responds with the message Out ofRange and prompts you to reenter the setting.

    In addition to the immediate range check, several of the settings haveinterdependency checks with other settings. The relay checks settinginterdependencies after you answer Y to the Saves Settings? prompt, butbefore the settings are stored. If any one of these checks fail, the relay issuesone of the error messages shown in the Table 3.3, and returns you to thesettings list for a correction.

    Table 3.3 Setting Interdependency Error Messages

    Error Message Setting /Function Correct the Condition

    50NnP must be within xx.xx and yy.yy(n= 1 or 2)

    Ground FaultCoreBalance

    Modify the 50N1P or 50N2P setting to satisfy therequirement shown in the error message.

    50PnP must be less than xx.xx(n= 1 or 2)

    Short Circuit Modify the 50P1P or 50P2P setting to satisfy therequirement shown in the error message.

    CTRn,FLAnSetting Combination Out ofRange(n= 1 or 2)

    Main Settings Modify the CTRnor FLAnsetting to satisfy:0.5 (FLAn/CTRn) 2.5 when MCM2 is used2.5 (FLAn/CTRn) 20 when MCM20 is used20 (FLAn/CTRn) 180 when MCM180 is used160 (FLAn/CTRn) 630 when MCM630 is used

    LRAnmust be less than: xxx(n= 1 or 2)

    Overload Modify the LRA1 or LRA2 setting to satisfy therequirement shown in the error message.

    Minimum STOP COOL TIME: xxxx min Overload Modify the COOLTIME setting to satisfy the requirementshown in the error message.

    Only one ambient RTD allowed(n= 112)

    RTD Modify the RTD location setting (RTDnLOC) to satisfy therequirement shown in the error message.

    PTR Setting Out of Range Main Settings Modify VNOM or PTR setting to satisfy:100 (VNOM/PTR) 250

    Warning: Duplicate Assignment. Input Mapping Modify INnassignment ensuring that input is notassigned to more than one element.

    Warning: Verify 50PnP is lower than MCM/CWE saturation current.Save Changes (Y/N)?(n= 1 or 2)

    Short Circuit Answer Y if you are using MCM630N.If you are using MCM630, you must modify the 50P1P or50P2P setting below its saturation current to ensureproper protection.

    Warning: Verify LRAnis lower than MCM/

    CWE saturation currentSave Changes (Y/N)?(n= 1 or 2)

    Overload Answer Y if you are using MCM630N.

    If you are using MCM630, you must modify the LRA1 orLRA2 setting below its saturation current to ensure properprotection.

  • 7/22/2019 825 User Manual

    59/232

    Chapter4

    ASCII Serial Communications

    Overview The 825-P Relay has the following communications interfaces: Front-panel HMI interface (see Chapter 3: Front-Panel Operation).

    Rear fiber-optic port RTD-RX (for fiber-optic interface to theoptional external 825-PR12D RTD Scanner). This port receives theRTD measurement information from the 825-PR12D RTDScanner. Refer to the 825-PR12D RTD Scanner Instruction

    Manual for information on the fiber-optic interface. PORT F communication card slot C for optional DeviceNet and

    Modbus network communications.

    PORT FFront-panel EIA-232 serial port (supports RockwellAutomation ASCII protocol).

    The remainder of this chapter describes the connections and commandsused with the ASCII front-panel EIA-232 serial port.

    ASCII Serial PortOperation

    Introduction

    The serial port interface provides an efficient way to communicate withthe relay using a PC to review and enter the settings, access metering data,review self-test status, retrieve event summaries, and obtain motoroperating statistics reports.

    Required Equipment

    To connect a PC serial port to the relay front-panel serial port and enterrelay commands, you need the following:

    A personal computer equipped with one available EIA-232 serialport.

    A standard null-modem communication cable to connect thecomputer serial port to the relay serial port.

    Terminal emulation software to control the computer serial port.

    The 825-P Relay.

    On most personal computers, the connector for the EIA-232 serial portis a 9-pin D subconnector. You can purchase the cable to connect thecomputer port to the relay port from most computer hardware retailers,

  • 7/22/2019 825 User Manual

    60/232

  • 7/22/2019 825 User Manual

    61/232

    Publication 825-UM004C-EN-P May 2004

    ASCII Serial Communications 4-3

    Configure Your Terminal Emulation Software

    Personal computers use terminal emulation software to send and interpretreceived characters at the EIA-232 serial port. This software allows you to typeletters and numbers to form commands at the computer keyboard and to seethe characters you type and the relay responses on the computer screen. Toensure the PC communicates correctly with the relay, configure the terminalemulation software connection properties to match the relay serial portconfiguration.

    Configure the terminal emulation software to match the default settings shownin Table 4.2. For the best display, use VT-100 terminal emulation. If VT-100 isnot available, WYSE-100 and ANSI terminal emulations also work.

    To change the port settings, use the front-panel SET/SHOW > PORT settingsmenu item.

    Serial Port Settings The 825-P provides settings that allow you to configure the communicationparameters for the front-panel serial port. The front-panel serial port supportsonly ASCII communications, described in detail in Appendix D: ASCII PortRelay Command Summary.

    7 RTS Request to send

    8 CTS Clear to send

    Table 4.2 825-P Relay Serial Communications Default Settings

    Setting Default

    Speed (bps) 9600

    Data Bits 8

    Parity N

    Stop Bits 1

    Flow Control XON/XOFF(software flow control)

    Table 4.1 Pin Functions and Definitions for EIA-232 Serial Port (Port F)

    Pin Pin Function Definition

    Table 4.3 Front-Panel Serial Port Settings

    Setting Prompt Setting Range Factory Default

    SPEED 30038400 bps 9600

    DATA BITS 7, 8 bits 8

    PARITY O, E, N N

    STOP BITS 1, 2 bits 1

    PORT TIMEOUT 030 min 15

    HDWR HANDSHAKING Y, N N

  • 7/22/2019 825 User Manual

    62/232

  • 7/22/2019 825 User Manual

    63/232

  • 7/22/2019 825 User Manual

    64/232

  • 7/22/2019 825 User Manual

    65/232

  • 7/22/2019 825 User Manual

    66/232

    Publication 825-UM004C-EN-P May 2004

    4-8 ASCII Serial Communications

    To set the date (and the date format setting is MDY), type DATE mm/dd/yyyyand then press Enter.

    To set the date for a date format setting of YMD, type DATE yyyy/mm/ddandthen press Enter.

    To set the date for a date format setting of DMY, type DATE dd/mm/yyyyandthen press Enter.

    You can separate the month, day, and year parameters with spaces, commas,slashes, colons, or semicolons.

    METER (Level 1 or 2)

    The METERcommands provide access to the relay metering data. The relaydivides the displayed information into two groups:

    Note:All ASCII command responses in this section are examples only. Your

    specific relay has differences based on model number, firmware revisionnumber, and application.

    Instantaneous

    Thermal and RTD

    METER k (Instantaneous Metering)

    The METERk command displays instantaneous magnitudes (and angles, ifapplicable) of the measured and calculated analog quantities.

    All angles are displayed between 180 and +180 degrees. For delta-connected

    PTs, angles are referenced to VAB or L1 and for wye-connected PTs angles arereferenced to VAN or L1.

    If the voltage channels are not supported, or VAB < 13V (for delta) orVAN < 13V (for wye), angles are referenced to L1 current.

    To view the instantaneous meter values once, use the METERcommand (see

    the example in Figure 4.3). To view the meter values k times, use the

    METERk command, wherek is a number between 1 and 32767.

  • 7/22/2019 825 User Manual

    67/232

    Publication 825-UM004C-EN-P May 2004

    ASCII Serial Communications 4-9

    Figure 4.3 METER Command Example

    =>>MET

    825-P Modular Date: 03/05/2003 Time: 16:44:08.404

    Prot. System

    L1 L2 L3Current Magnitude (A) 21.2 21.3 21.5

    Current Angle (deg) -42.0 -162.5 78.2

    Average Current Magnitude (A) 21.3

    Motor Load (x Ie) 0.9

    GF Current-Core Balance (A) 0.00

    GF Current-Core Balance Angle (deg) -76.6

    GF Current-Residual (A) 0.0

    GF Current-Residual Angle (deg) 72.3

    Current Imbalance (%) 1.0

    VAN VBN VCN VG

    Voltage Magnitude L-N (V) 334 334 334 4

    Voltage Angle (deg) 0.0 -119.6 120.8 -116.1

    Average Phase (V) 334

    Voltage Imbalance (%) 0.0

    Real Power (kW) 16

    Reactive Power (kVAR) 14

    Apparent Power (kVA) 21

    Power Factor 0.74 LAG

    Frequency (Hz) 60.0

    =>>

  • 7/22/2019 825 User Manual

    68/232

  • 7/22/2019 825 User Manual

    69/232

  • 7/22/2019 825 User Manual

    70/232

  • 7/22/2019 825 User Manual

    71/232

    Publication 825-UM004C-EN-P May 2004

    ASCII Serial Communications 4-13

    When you issue the SET command, the relay presents a list of settings one at atime. Enter a new setting or press Enter to accept the existing setting. Editingkeystrokes are shown in Table 4.8.

    The relay checks each entry to ensure that it is within the setting range. If it isnot, an Out of Rangemessage is generated, and the relay prompts you forthe setting again.

    When all the settings are entered, the relay displays the new settings and

    prompts you for approval to enable them. Type Y and then press Enter toenable the new settings. The relay is disabled for as long as five seconds whileit saves the new settings. The SALARM Relay Word bit is set momentarily andthe ENABLE LED extinguishes while the relay is disabled.

    To change a specific setting, enter the command shown in Table 4.9.

    SHOW

    Use the SHOW command to view relay settings and serial port settings (seeFigure 4.5 on page 4.15).

    The SHOW command options are listed in Table 4.10.

    Table 4.8 SET Command Editing Keystrokes

    Do the Following Results

    Press Enter Retains setting and moves to next setting.

    Type ^ and then press Enter Returns to previous setting.

    Type < and then press Enter Returns to previous setting category.

    Type > and then press Enter Moves to the next setting category.

    Type END and then pressEnter

    Exits editing session, then prompts you to savesettings.

    Press Ctrl+ X Aborts editing session without saving changes.

    Table 4.9 SET Command Format

    SET n s TERSE

    Where:

    n is left blank to enter relay settings.n is P to enter front serial port settings.

    n is M to enter I/O mapping settings.

    s is the short parameter name of the specific setting you want to jump to andbegin setting.If sis not entered, the relay starts at the first setting (e.g., enter 50PIP tostart at Short Circuit Trip level setting).(Refer to Appendix E: 825-P Settings Record, to obtain the short parameternames.)

    TERSE instructs the relay to skip the settings display after the last setting.Use this parameter to speed up the SET command.If you want to review the settings before saving, do not use the TERSEoption.

  • 7/22/2019 825 User Manual

    72/232

    Publication 825-UM004C-EN-P May 2004

    4-14 ASCII Serial Communications

    You can append a setting name to each of the commands to specify the firstsetting to display (e.g., SHO 50P1P displays the relay settings starting withsetting 50P1P). The default is the first setting.

    The SHOW command displays only the enabled settings. To display all thesettings, including disabled/hidden settings, append anAto the SHOWcommand (e.g., SHOW A).

    Table 4.10 SHOW Command Options

    Command Description

    SHOW Show relay settings.

    SHO A Show all relay settings: enabled, disabled/hidden.

    SHO P Show serial port settings.SHO M Show I/O mapping settings.

  • 7/22/2019 825 User Manual

    73/232

  • 7/22/2019 825 User Manual

    74/232

  • 7/22/2019 825 User Manual

    75/232

    Publication 825-UM004C-EN-P May 2004

    ASCII Serial Communications 4-17

    Figure 4.6 STATUS Command Example=>>STA

    825-P Modular Date: 03/03/2003 Time: 11:54:40.361

    Prot. System

    FID=825-P-R100-V0-Z001001-D20030225 CID=010C

    Identity Code 1522001BCX0X1X1X

    SELF TESTS

    Current L1 L2 L3 RES CB

    Offset: OK OK OK OK OK

    Voltage VA VB VC

    Offset: OK OK OK

    PS_Vdc FPGA GPSB HMI

    OK OK Ok Ok

    RAM ROM CR_RAM Non_Vol Clk_Bat ClockOK OK OK OK Ok OK

    PTC RTD MCM/CWE Voltage I/O_Crd Com_Crd

    OK Ok OK OK OK OK

    MAC_ID ASA DN_Rate DN_Status

    0 0000 0000h 0kbps 0000 0000

    Relay Enabled

    =>>

    Figure 4.7 Identity Code Explanation

    Note: Refer to Figure 4.6

    X None

    A 825-MCM2

    B 825-MCM5

    C 825-MCM20

    D 825-MCM180

    E 825-MCM420

    F 825-MCM630N

    0 None

    3 DeviceNet

    0 None

    1 Installed

    0 None

    1 Installed

    1 5 5 2 0 0 1 B A X 0 X 0 A 0 X

    Converter Module Communication Card Expansion I/O Card Voltage Sensing Card

  • 7/22/2019 825 User Manual

    76/232

    Publication 825-UM004C-EN-P May 2004

    4-18 ASCII Serial Communications

    Figure 4.8 DN_Status Explanation

    Note: Refer to Figure 4.6

    STATUS R or C (Level 2)

    To reset the self-test status and restart the relay, enter the STA Rcommand

    from Access Level 2.The relay then restarts (like powering down and then powering up the relay)and all diagnostics are rerun before the relay is enabled.

    STOP (Level 2)

    The STOP command causes the relay to trip, opening the motor contactor orcircuit breaker and stopping the motor. For more details refer to Chapter 5:Protection and Logic Functions.

    STR (Level 2)The STR(START) command initiates a motor start using the relay's internallogic. For more details refer to Chapter 5: Protection and Logic Functions.

    SUMMARY (Level 1 or 2)

    The SUM n command displays a summary list, in reverse chronological order,of all the archived event summary reports (maximum of five events).

    An example event summary report is in Figure 4.9. Each event summaryreport shows the date, time, current magnitudes (primary values) and, if the

    relay has the voltage option, voltage magnitudes (primary values). The currentand voltage values are at the trigger instant. The event summary report alsoshows the event type (e.g., OVERLOAD TRIP).

    The nparameter with the SUM n command can have a value up to 5 anddefines the number of events requested. Ifn is not specified, then up to five ofthe most recent reports are listed.

    For more information on events, refer to Chapter 7: Analyzing Events.

    Undefined

    I/O Idle

    I/O Fault

    Explicit Fault

    I/O Connection

    Explicit Connection

    0 0 0 0 0 0 0 0

  • 7/22/2019 825 User Manual

    77/232

    Publication 825-UM004C-EN-P May 2004

    ASCII Serial Communications 4-19

    Figure 4.9 SUMMARY Command Example=>>SUM 2

    825-P Modular Date: 02/04/2003 Time: 17:20:46.439

    Prot. System

    Event #: 1 Event: OVERLOAD TRIP

    Event Date: 01/29/2003 Event Time: 14:14:01.930

    L1 L2 L3 RES CBCURRENT MAG (A) 8.2 8.1 8.2 0.0

    0.00

    Event #: 2 Event: OVERLOAD TRIP

    Event Date: 01/29/2003 Event Time: 14:13:05.931

    L1 L2 L3 RES CB

    CURRENT MAG (A) 8.2 8.2 8.2 0.0

    0.00

    =>>

    SUMMARY R (Level 1 and 2)

    The SUMMARY Rcommand clears all the events in the event buffer.

    TARGET (Level 1 or 2)

    TheTARGET command displays the status of relay elements whether theyare asserted or de-asserted. The elements are represented as Relay Word bitsand are listed in rows of eight, called Relay Word rows. For additionalinformation on individual Relay Word bits, refer to Appendix C: Relay WordBits.

    A Relay Word bit is either at logical 1 (asserted) or at logical 0 (de-asserted).

    TheTARcommand options are listed in Table 4.12.

    Table 4.12 TARGET Command Options

    Commands Descriptions

    TAR n k Shows Relay Word Row n (010).k is an optional parameter to specify the number of times (132767) torepeat the Relay Word row display.If k is not specified, the Relay Word row is displayed once.See Table 4.13 for the definition of Row 0.See Table 4.14 for a list of the Relay Word bits in each row (n = 110).

    TAR name k Shows the Relay Word bit row containing the Relay Word bit name (e.g.,TAR 50P1T displays Relay Word Row 1).Valid names are shown in Table 4.14.k is an optional parameter to specify the number of times (132767) to

    repeat the Relay Word bit row display.If k is not specified, the Relay Word row is displayed once.

    Table 4.13 Front-Panel LEDs and the TAR 0 Command

    LED Number/State

    7 6 5 4 3 2 1 0

  • 7/22/2019 825 User Manual

    78/232

  • 7/22/2019 825 User Manual

    79/232

  • 7/22/2019 825 User Manual

    80/232

  • 7/22/2019 825 User Manual

    81/232

  • 7/22/2019 825 User Manual

    82/232

    Publication 825-UM004C-EN-P May 2004

    4-24 ASCII Serial Communications

    To change a specific setting, enter the command shown in Table 4.18.

    Table 4.18 SET Command Format

    SET n s TERSE

    Where:

    n is left blank to enter RELAY settings.

    n is P to enter front-panel serial port settings.

    n is M to enter I/O mapping settings.

    s is the name of the specific setting you want to jump to and beginsetting.If s is not entered, the relay starts at the first setting (e.g., enter 50P1Pto start at Short Circuit Trip level setting).

    TERSE instructs the relay to skip the settings display after the last setting.Use this parameter to speed up the SET command.If you want to review the settings before saving, do not use the TERSEoption.

  • 7/22/2019 825 User Manual

    83/232

    Chapter5

    Protection and Logic Functions

    Overview This chapter describes the 825-P Relay settings, including the motorprotection elements and basic functions, control I/O mapping, as well asthe settings that control the communications ports and front-paneldisplays.

    Note: Each 825-P is shipped with default factory settings. Calculate thesettings for your motor to ensure secure and dependable protection.

    Document and enter the settings using the worksheets provided inAppendix E - 825-P Settings Record.

    This chapter includes the following subsections:

    Application Data lists information that is required about theprotected motor before calculating the relay settings.

    Main Settings lists settings that configure the relay inputs toaccurately measure and interpret the AC current and optionalvoltage input signals.

    Basic Motor Protection lists settings for protection elementsincluded in all models of the 825-P, including the thermal element,overcurrent elements, load-loss functions, and load-jam functions.

    RTD-Based Protection lists settings associated with the RTDinputs (requires RTD Scanner Module). Skip this subsection if yourapplication does not include RTD measuring.

    Voltage-Based Protection (Relays With Voltage Inputs) listssettings associated with the optional AC voltage-based protectionelements. You can skip this subsection if your relay is not equippedwith optional voltage inputs.

    I/O Configuration lists settings for the front-panel display control,control inputs/outputs, and analog output for all relay models.

    Serial Port Settings lists settings that configure the relay front- and

    rear-panel serial ports. DeviceNet Port Settings lists settings that configure the relay

    rear-panel DeviceNet port.

    Selected Relay Logic Diagrams show selected logic diagrams forprotection, control, and outputs.

    When you calculate the protection element settings to protect yourmotor, proceed through the subsections listed earlier. Skip the RTD- andvoltage-based protection subsections if they do not apply to your specificrelay model or installation. As you calculate settings, record them on a

  • 7/22/2019 825 User Manual

    84/232

    Publication 825-UM004C-EN-P May 2004

    5-2 Protection and Logic Functions

    photocopy of the settings worksheets. (See Appendix E: 825-P Settings Recordfor more information.)

    DeviceNet port parameters can only be set at the rear of the relay on theDeviceNet card (see Figure 2.2 and Figure 2.3).

    You can enter settings using the front-panel SET RELAY function (seeChapter 3: Front-Panel Operation), the front-panel serial port (see Chapter 4:ASCII Serial Communications), or the rear-panel DeviceNet port.

    Application Data It is quicker and easier for you to calculate settings for the 825-P if you collectthe following information before you begin (collect the information for eachspeed for a two-speed motor application):

    Specifications of the protected motor, including the following details:

    Rated full load current.

    Service factor.

    Locked rotor current. Maximum locked rotor time with the motor at ambient and/or

    operating temperature.

    Maximum motor starts per hour, if known.

    Minimum time between motor starts, if known.

    Additional data regarding the motor application, including the followinginformation:

    Minimum no load current or power, if known.

    Motor accelerating time. This is the normal time required for themotor to reach full speed.

    Maximum time to reach motor full load.Note:This time could be significantly longer than the motoraccelerating time, particularly in pump motor applications where themotor could run at full speed for some time before the pump reachesfull head and full load.

    Current transformer primary and secondary ratings and connections, ifused.

    System phase rotation and nominal frequency.

    Voltage transformer ratios and connections, if used.

    Type and location of resistance temperature devices (RTDs), if used.

    Expected fault current magnitudes for motor or cable ground andthree-phase faults.

  • 7/22/2019 825 User Manual

    85/232

    Publication 825-UM004C-EN-P May 2004

    Protection and Logic Functions 5-3

    Main Settings Identifier Settings

    All models of the 825-P have the identifier settings described in Table 5.1.

    The 825-P prints the Relay and Terminal Identifier strings at the top ofresponses to serial port commands to identify messages from individual relays.

    Enter up to 16 characters, including capital letters AZ, numbers 09,periods (.), dashes (-), and spaces. Suggested identifiers include the location,process, circuit, size, or equipment number of the protected motor.

    Phase Rotation, Nominal Frequency Settings

    The phase rotation setting tells the relay your phase labeling standard. SetPhase Rotation equal to ABC when B-phase current lags A-phase current by

    120. Set Phase Rotation equal to ACB when B-phase current leads A-phasecurrent by 120.

    Figure 5.1 Phase Rotation Setting

    Set the Rated Freq. equal to your system nominal frequency.

    The Date Format setting allows you to change the relay date presentationformat to either North American standard (Month/Day/Year), engineeringstandard (Year/Month/Day), or European standard (Day/Month/Year).

    Table 5.1 Identifier Settings

    Setting Prompt Setting Range Factory Default

    UNIT ID LINE 1 16 Characters 825-P Modular

    UNIT ID LINE 2 16 Characters Prot. System

    Table 5.2 Phase Rotation, Nominal Frequency Settings

    Setting Prompt Setting Range Factory Default

    PHASE ROTATION ABC, ACB ABC

    RATED FREQ. 50, 60 Hz 60

    DATE FORMAT MDY, YMD, DMY MDY

    B

    C

    A

    C

    PHROT = ABC

    A

    PHROT = ACB

    B

  • 7/22/2019 825 User Manual

    86/232

    Publication 825-UM004C-EN-P May 2004

    5-4 Protection and Logic Functions

    Current Transformer (CT) Configuration, Full Load CurrentSettings

    Note the following:

    Motor FLA settings are in Primary Amperes.

    The allowed setting range is dependent on the MCM module that isconnected to the relay. The MOTOR FLA and PHASE CT RATIOsetting ranges will be a subset of the full ranges shown in Table 5.3.

    When Two Speed Enable = Y and a Speed 2 control input is specified,the relay uses CT Ratio-2nd and Motor FLA-2nd for the overloadthermal model.

    CTs with a 1 or 5 A rated secondary current can be used with theConverter Module MCM2 or MCM20, respectively. If another MCMmodule is used, the relay automatically sets CT Ratios = 1.

    The CT ratio and full load current settings, along with the connected MCMmodule, configure the relay to accurately scale measured values and report theprimary quantities. Calculate the phase and neutral CT ratios by dividing theprimary rating by the secondary rating.

    The relay runs interdependency checks on the FLA and CT ratios based uponthe ratings of the MCM module that is connected. If a value is set that violatesthe interdependency rules, then the user will be prompted to adjust settings toeliminate conflicts.

    EXAMPLE

    Phase CT Ratio Setting Calculation:

    Consider an application where Phase CT Rating = 100:5A.

    Set the CT Ratio :=100/5 := 20

    Voltage Transformer (VT) Configuration Settings

    Relays that are not equipped with phase voltage inputs hide these settings anddisable voltage-based protection and metering functions.

    Table 5.3 CT Configuration and Full Load Current Settings

    Setting Prompt Setting Range Factory Default

    PHASE CT RATIO 15000 1

    MOTOR FLA (Ie) 0.55000 A 0.5

    TWO SPEED ENABLE Y, N N

    CT RATIO2nd 15000 1

    MOTOR FLA2nd 0.55000 A 0.5

    CORE B. CT RATIO 12000 100

  • 7/22/2019 825 User Manual

    87/232

  • 7/22/2019 825 User Manual

    88/232

    Publication 825-UM004C-EN-P May 2004

    5-6 Protection and Logic Functions

    Locked Rotor Starts

    Running Overload

    Imbalance Current/Negative-Sequence Current Heating

    Repeated or Frequent Starting

    Note:You can set Run State Time Constant of the thermal overload curve. Ifnot known, set t to Auto; the relay configures the overload curve continuouswith the locked rotor curve.

    When overload protection is enabled, the relay configures a thermal curvebased on the motor Full Load Amps, Service Factor, Locked Rotor Amps, HotLocked Rotor Time, and Acceleration Factor settings. See Figure 5.5 forselected settings of Thermal Overload curves.

    The relay operates a thermal model with a trip value defined by the relaysettings and a present heat estimate that varies with time and changing motorcurrent. The relay expresses the present motor thermal estimate as a

    % Thermal Capacity. When the % Thermal Capacity reaches 100%, the relaytrips. You can see the present % Thermal Capacity value using the relayfront-panel METER > THERMAL function or the serial port METER Tcommand.

    If the thermal model is turned off (Overload Enable := N), the thermal modelis disabled, the output of the thermal model is blocked, and the relay reportsthe % Thermal Capacity as 999 as noted in Chapter 6: Metering andMonitoring.

    Table 5.5 Overload (Thermal Model) Settings

    Setting Prompt Setting Range Factory Default

    OVERLOAD ENABLE Y, N Y

    OL RESET MODE Man, Auto Man

    OL RESET LEVEL 1099%TCU 75

    SERVICE FACTOR 1.011.50 1.01

    MOTOR LRC 2.512.0 xIe 6.0

    LOCKD ROTOR TIME 1.0600.0 s 10.0

    ACCEL FACTOR 0.101.50 1.00

    RUN STATE TIME K Auto, 12000 min Auto

    MOTOR LRC2nd 2.512.0 xIe 6.0

    MOTOR LRT2nd 1.0600.0 s 10.0

    ACCEL FACT2nd 0.101.50 1.00

    RUN ST TC2nd Auto, 12000 min Auto

    OL WARN LEVEL Off, 5099%TCU 85

    START INH. LEVEL Off, 199%TCU Off

    STOP COOL TIME 12200 min 18

    OL RTD BIASING Y, N N

  • 7/22/2019 825 User Manual

    89/232

    Publication 825-UM004C-EN-P May 2004

    Protection and Logic Functions 5-7

    When you enable overload protection, the relay requests information aboutthe protected motor capabilities. Obtain the requested information (except theacceleration factor) from the motor specifications.

    The 825-P thermal element always operates in one of two modes: starting andrunning. In starting mode, the thermal element trips in Locked Rotor Time atLocked Rotor Current whether the motor is at ambient or at normal operatingtemperature. In running mode, the thermal element provides overloadprotection by limiting the motor heat energy estimate to a value represented bythe overload settings.

    The locked rotor time setting is for a hot motor condition. If only one lockedrotor time is specified for a particular motor, unless the specification statesotherwise, assume the time is the cold locked rotor time. Multiply the coldlocked rotor time by 0.833 to determine a hot locked rotor time that isacceptable for most motors.

    Note:When Two Speed Enable = Y and a Speed 2 control input is specified,the relay uses the 2nd FLA-related settings for the overload thermal model.

    EXAMPLE

    Thermal Element Setting

    A 4000V 600 Hp motor is protected using the 825-P Thermal OverloadElement. Motor dat