8000-op

60
Operating Instructions for 8000C Fire Alarm Control Panel

Transcript of 8000-op

Page 1: 8000-op

Operating Instructionsfor

8000C Fire Alarm Control Panel

Page 2: 8000-op

Page 2 Fire Alarm Control Panel 8000C

ScopeThis manual describes how to use the 8000C Fire Alarm Control Panel, it recommends andtherefore assumes that the 8000C System has been installed and commissioned using productsapproved by Caradon GENT Limited.

Warning

All guidelines concerning safety during transport, storage, installation and operation must beobserved.

Safety information

This manual includes all the information required for the proper use of the System 8000C firealarm control panel.

The term `responsible person’ refer to trained on site personnel who has the day to dayresponsibility for the fire detection and alarm system.

The term 'qualified personnel' refer to employee from the organisation servicing the firedetection and alarm system, such as project engineers, trained service engineers and trainedinstallation or service personnel. All qualified personnel must be familiar with the safetyinformation included in this manual and on the product itself:

Safety warnings

The following information is given in the interest of personal safety and to prevent damage tothe product described in this manual and all equipment connected to it.

! Danger - Death, severe injury or considerable damage to the system equipment willoccur if the relevant safety precautions are not observed.

Important information which should be read with particular attention.

Safety

Page 3: 8000-op

Fire Alarm Control Panel 8000C Page 3

1 General System Description .................................................................................................................. 4

1.1 User Responsibility ............................................................................................................................... 5

2 User controls and indications................................................................................................................. 6

2.1 Key-switch / enabling operation ........................................................................................................... 7

2.2 Description of the display and keyboard.............................................................................................. 8

3 Operating condition of the fire alarm control panel .............................................................................17

3.1 Normal condition .................................................................................................................................17

3.2 Fire condition.......................................................................................................................................17

3.3 Fault Condition ....................................................................................................................................18

3.4 System fault.........................................................................................................................................18

3.5 Disablement ........................................................................................................................................19

3.6 Test mode............................................................................................................................................19

4 Operation...............................................................................................................................................20

4.1 Function keys / menu options.............................................................................................................204.1.1 Event display and menu options .................................................................................. 224.1.2 Display priority of the messages.................................................................................. 244.1.3 Info text (Label), additional text (auxiliary text) and parameter display......................... 25

4.2 Entering time/date...............................................................................................................................26

4.3 Zones...................................................................................................................................................274.3.1 Enabling a zone........................................................................................................... 274.3.2 Disablement of a zone................................................................................................ 284.3.3 Status of a zone .......................................................................................................... 29

4.4 Devices................................................................................................................................................304.4.1 Enabling a devices ...................................................................................................... 304.4.2 Disabling a device ....................................................................................................... 314.4.3 Status of a device........................................................................................................ 32

4.5 Control and status of Output...............................................................................................................334.5.1 Enabling outputs.......................................................................................................... 334.5.2 Disabling outputs......................................................................................................... 344.5.3 Status of Outputs......................................................................................................... 35

4.6 Display of system status.....................................................................................................................36

4.7 Delay and Verify Alarms .....................................................................................................................374.7.1 Delay Alarms ............................................................................................................... 384.7.2 Verify Alarm................................................................................................................. 38

4.8 Alarm counter ......................................................................................................................................39

4.9 Test `Display test’................................................................................................................................40

5 Service Level.........................................................................................................................................41

5.1.1 Analog loop functions .................................................................................................. 425.1.2 Sensor functions (loop)................................................................................................ 455.1.3 Sensor functions (zone/detector) ................................................................................. 47

6 Log book................................................................................................................................................48

6.1 Log Sheets ..........................................................................................................................................49

Table of Contents

Page 4: 8000-op

Page 4 Fire Alarm Control Panel 8000C

1 General System Description

It is assumed that the 8000C fire alarm control panel and the associated system equipment havebeen installed in accordance with the manufacturer instructions and guidance given inBS5839 Part 1.

The System 8000C is suitable for installation in commercial and industrial facilities. The modulardesign of products allows the fire detection and alarm system to be expanded to meet futurecustomer needs. The application of intelligent fire detectors connect to the panels’ analog loopprovide an early and reliable warning of fire.

An analog loop can have up to 127 devices and each device can be assigned to up to 127 zones,with an overall loop cable length of up to one kilometre. An analog loop is a two-wire circuit that ismonitored at both ends. The 8000C fire alarm control panel automatically registers the wiring of theloop and determines the logical addresses of the individual devices on the analog loop.

A range of devices can be connected to an analog loop circuit, such as fire detectors, technicalalarm modules (TAL) and transponders. The transponders are loop devices with programmableinputs and outputs, for activating and monitoring external equipment such as display panels, alarmdevices, door closer unit and other equipment.

The network module allows up to 31 fire alarm control panels (8000C) to be connected in anetwork. At any fire alarm control panel in the network it is possible to view indications of fireevents of the entire networked system and operate essential controls under emergency conditionsand operate other control functions, such as disablement of zone. Events such as fire, fault,disablement and others events are transmitted to all fire alarm control panels in the network.

These Operating Instructions are intended to aid users of the 8000C fire alarm control panel andshould be read in conjunction with the instructions provided by your specialised installer. All thedocumentation associated with the fire alarm system should be kept together near the fire alarmcontrol panel. If you have any questions, please consult your specialised installer.

The operation of the fire alarm control panel may only be carried out by authorised and trainedpersons observing safety precautions and, if necessary, in collaboration with the otherorganisations (e.g. fire department).

General system description

Page 5: 8000-op

Fire Alarm Control Panel 8000C Page 5

1.1 User Responsibility

It is recommended that the persons responsible for the fire alarm system should become familiarwith:

how to operate the controls.

and interpret the indications given.

DailyBS 5839:Part 1:1988, states that the system should be inspected daily to ensurethat a normal indication is given at the control and indicating equipment and:

that any previously indicated fault and disablement condition has received appropriateattention.

all the system events are entered into the Log Book for future reference.

that the use of the area(s) inspected has not changed since the system was designed.

and no unsafe practices that could lead to fire are being undertaken.

Weekly A different Fire detector or Manual Call Point of the system should be tested to ensure the

system is capable of operating under alarm condition.

The operation of the alarm sounders should be checked to also remind those occupying thepremises that there is a fire alarm system with a particular sound.

The test should be performed at a regular time to avoid confusion between a test and agenuine fire alarm.

Quarterly

At quarterly intervals the system should be inspected and a trained maintenance engineershould carry out any work necessary.

Contact your servicing organisation for help with service and maintenance work.

User Responsibility

Page 6: 8000-op

Page 6 Fire Alarm Control Panel 8000C

2 User controls and indications

Fig. 1: View of the display, LED indicators and keyboard (cdm320)

1 Zonal indicators

2 Common FIRE indicator

3 Common PRE-ALARM indicator

4 Common FAULT indicator

5 Common DISABLEMENT indicator

6 Display (LCD)

7 Key-switch

8 Essential controls keys

9 Function and numeric keyboard

General view

Page 7: 8000-op

Fire Alarm Control Panel 8000C Page 7

2.1 Key-switch / enabling operation

The key-switch operation disables and enables the keyboard of the 8000C fire alarm control panel,to provide access to controls of the local and networked systems.

Key-switch in horizontal position

Fig. 2: Keyboard unlocked (cdm323)

With the key-switch in horizontal position:

the display shows the menu options

and access is available to all the controls

the key cannot be removed from the keyboard

Key switch in vertical position

Fig. 3: Keyboard blocked (cdm324)

With the key-switch in vertical position:

the keyboard is disabled

only `Verify Alarm/Cancel Buzzer’ and the Scroll buttons remains active

the key can be removed from the key-switch.

Key-switch / enabling operation

Page 8: 8000-op

Page 8 Fire Alarm Control Panel 8000C

2.2 Description of the display and keyboard

Fig. 4: Description of display and keyboard (cdm325)

1 Display

2 Menu options on display

3 Function buttons to select Menu option

4 Scroll keys

Events are indicated and displayed on the fire alarm control panel. The LEDs provide colour codedindications of FIRE, PRE-ALARM, FAULT and DISABLEMENT events coupled with messages onthe 8 lines of 40 characters per line display.

KeyboardBy operating the key-switch to `Controls Enabled’ position the keyboard is unlocked for normaloperation. The keyboard has buttons to access to system controls to carryout functions such as toenable and disable zones and loop devices.

Menu option / Function buttonsFor the four menu options shown on the display there are corresponding function buttons locatedbelow the display. The menu options shown are dependent on the current state of the fire alarmcontrol panel or the operating level.

Function of the display and keyboard

Page 9: 8000-op

Fire Alarm Control Panel 8000C Page 9

Fig. 5: Common indicator for fire (cdm326)

The Common Fire indicator is lit when there is at least one fire detected in the system. The displaywill provide information on the initiating fire detection device or fire zone in a fire condition.

Where site specific fire evacuation procedure exists then these must be followed. Theresponsible persons must be familiar with escape routes and measures in case of a fire.

Fire indicator

Red LED is Lit (On)(steady indication)

Fire alarm !At least one detector and / transponder input / one call point / ora loop is signalling a fire condition.

Function of the display and keyboard

Page 10: 8000-op

Page 10 Fire Alarm Control Panel 8000C

Fig. 6:Common indicator for pre-alarm (cdm327)

The Pre-alarm indicator is lit when an intelligent fire detector reaches pre-alarm level, or where twindetector dependency (coincidence detection) is configured and a detector is in a fire condition. Thecustomer data is configured to control outputs to actuate alarm devices.

A Pre-alarm is automatically reset if no further signals are transmitted and the Pre-alarm indicatoris extinguished and any activated alarm devices are switched off. If further alarm signals occur, afire alarm is automatically initiated.

Pre-alarm indicator

Red LED is lit(steady indication)

At least one detector or zone is signalling the pre-alarmcondition.

The information on the activated detector or the activated zoneis shown on the display.

If configured in the customer data a pre-alarm event will action outputs to activate internalsignalling devices and evacuation signals.

Function of the display and keyboard

Page 11: 8000-op

Fire Alarm Control Panel 8000C Page 11

Alarm Delayed indicator

Yellow LED is lit(steady indication)

The switching on of the sector sounder alarm is delayed for theduration programmed in the customer data.

Yellow LED is lit(Flashing indication)

Indicates an alarm signal has been detected during an activedelay time. There can be a maximum of up to 600 secondsdelay programmed.

Alarm Verification indicator

Yellow LED lit(Steady indication)

Indicates the activation of Alarm Verification by the pressing ofthe `Verify Alarm’ button. This allows responsible persons onsite to verify the cause of alarm.

The function Alarm delay/Verify Alarm is described in Section 4.7.

Function of the display and keyboard

Page 12: 8000-op

Page 12 Fire Alarm Control Panel 8000C

Fig. 7: Common indicator for FAULT (cdm328)

The Fault LED is lit if there is at least one malfunction detected in the system. A fault message willbe shown on the display.

Fault indicator

Yellow LED is Lit(Steady indication)

A component of the fire alarm control panel or system device ora monitored output has malfunctioned.

Power Healthy indicator

Green LED is Lit(Steady indication)

The power supply connected to the fire alarm control panel, thatis either battery or mains supply, is healthy. The fire alarmcontrol panel is in an operative condition.

System Fault indicator

Yellow LED is Lit(Steady indication)

The fire alarm control panel is only partially operative due to amalfunction of the control panel functions. Display or operationof the control panel is no longer possible (The exception is the`Cancel Buzzer’ button.

Power Fault indicator

Yellow LED is Lit(Steady indication)

There is a battery or mains supply failure at the fire alarmcontrol panel.

In case of fault or after an emergency condition the fire alarm control panel may not functioncorrectly, in which case contact the servicing organisation immediately.

Function of the display and keyboard

Page 13: 8000-op

Fire Alarm Control Panel 8000C Page 13

Fig. 8: Common indicator for Disablement (cdm329)

The Disablement LED is lit when at least one output, input, or other component of the fire alarmcontrol panel has been disabled. The disablement message will also be shown on the display.

Disablement indicator

Yellow LED is Lit(Steady indication)

At least one input or output of a zone has been disabled.

Sounder indicator

Yellow LED is Lit(Steady indication)

At least one sector sounder output of a transponder has beendisabled.

Device indicator

Yellow LED is Lit(Steady indication)

At least one device has been disabled.

Test mode indicator

Yellow LED is Lit A component of the control panel such as a zone has been setto `Test mode’ for servicing and maintenance work.

!A zone in `Test mode’ will not transmit an alarm in the event of a fire.

Function of the display and keyboard

Page 14: 8000-op

Page 14 Fire Alarm Control Panel 8000C

Fig. 9: Zonal indicator units (cdm330)

Optionally there can be up to 64 zonal (zone) indications added to the fire alarm control panel. Onthe zonal indicator a red LED gives a fire indication and a yellow LED gives fault or disablementindication. There is a labelling field for each zone, which can be marked with the name of the zonalarea.

Fire indicator

Red LED is Lit(Steady indication)

At least one detector and/or call point in the zone is signalling afire alarm.

Red LED is Lit(Flashing indication)

This is the initial (first) zone that has signalled a fire.

Disabled / Fault indicator

Yellow LED is Lit(Steady indication)

The zone has been disabled, see Section 4.3.

Yellow LED is Lit(Flashing indication)

At least one detector of the zone has malfunctioned. Inform theservicing organisation.

! The zones that are disabled or have a fault will not transmit an alarm of fire.

Function of the display and keyboard

Page 15: 8000-op

Fire Alarm Control Panel 8000C Page 15

Panel Reset

cdm331

Pressing the `Panel Reset’ button all detected fire alarms, zones,displays and technical alarm signals (TAL alarm) are reset tonormal condition.

Silence Alarms

(cdm332)

Pressing the `Silence Alarm’ button will cause all sector sounderoutputs to switch off.

Sound Alarms

(cdm333)

Pressing the `Sound Alarm’ button will activate all sector sounderoutputs in the system.

! Disabled sector sounder devices will not transmit an alarm output.

Weekly Test

(cdm334)

Pressing the `Weekly Test’ will allow detectors and manual callpoints in the system to be tested to cause activation of sectorsounders alarm outputs in the system, no other outputs areaffected..

! Disabled alarm devices will not transmit an alarm output.

Function of the display and keyboard

Page 16: 8000-op

Page 16 Fire Alarm Control Panel 8000C

Delay Alarms

(cdm335)

Pressing the `Delay Alarms’ button will cause a pre-programmeddelay to be activated/deactivated (toggle function) on sectorsounder outputs in the system.

See Section 4.7 for information on Delay Alarms / Verify Alarm.

Verify Alarms / Cancel Buzzer

(cdm336)

Verify AlarmsPressing this button will increase the time delay before the sectorsounder outputs are activated in the system.The Verify Alarms function is explained in section 4.7.

Cancel BuzzerPressing this button is an acknowledgement of the control panelbuzzer. This key remains active even when the keyboard controlsare disabled. The buzzer is reactivated with an event.

Function of the display and keyboard

Page 17: 8000-op

Fire Alarm Control Panel 8000C Page 17

3 Operating condition of the fire alarm control panel

The operating condition of the fire alarm control panel 8000C is shown on the fire alarm controlpanel. There are various different operating conditions possible:

3.1 Normal conditionThe normal condition refers to a control panel with no active events.

The green `Power healthy’ LED is lit (steady indication).

No other LED indications are given and there are no event messages on the display.

The panel keyboard controls are disabled by the key-switch.

3.2 Fire condition

The control panel is in fire condition, i.e. it is signalling a fire alarm.

The FIRE indicator (red LED) is Lit.

The internal control panel buzzer sounds.

External alarm devices are activated.

The zone which has detected the fire is indicated and the display shows the fire eventmessages.

The red LED of the corresponding optional zonal indicator(s) is lit. If several zones signal a firealarm, the red LED of the first zone in fire condition will give a flashing indication.

The manned centre link facility if applicable will be activated.

Operating condition of the fire alarm control panel

Page 18: 8000-op

Page 18 Fire Alarm Control Panel 8000C

3.3 Fault ConditionThe control panel is in a fault condition, the yellow fault LED is lit and the control panel buzzersounds intermittently.

At least one control panel function has failed

A message is shown on the display describing the failure

The optional yellow LED of the zonal indicator may give a flashing indication.

! Fires may not be detected or signalled in the event of a fault, inform the servicingorganisation!

3.4 System fault

The fire alarm control panel is only partially operative!

No messages are given on the display.

There is no activation of external equipment, such as alarm sounders.

! The comprehensive operation of the fire alarm control panel is no longer provided. Contactthe servicing organisation immediately.

Operating condition of the fire alarm control panel

Page 19: 8000-op

Fire Alarm Control Panel 8000C Page 19

3.5 Disablement

The disablement (yellow LED) is Lit

Possibly, a further indicator is on to show what has been disabled, for example Device orSounder LED may be lit.

The disablement message is shown on the display.

The optional zonal (yellow) LED is lit, a steady indication indicates a disabled zone.

! If zones, detectors or outputs are disabled then they will not signal in the event of a fire.

3.6 Test mode

The yellow LED Test mode is lit. The Test mode of the control panel is activated for service andmaintenance purposes:

The detectors/zones are under inspection when this mode is in operation.

!A zone in Test mode will not signal an alarm in the event of a fire.

Operating condition of the fire alarm control panel

Page 20: 8000-op

Page 20 Fire Alarm Control Panel 8000C

4 Operation

This section describes the most important operating instructions that can be carried out from asingle fire alarm control panel 8000C. If several fire alarm control panels are connected in anetwork then the instructions given may be slightly different, in which case please ask yourinstaller or servicing organisation.

Authorised and trained personnel who are responsible for the fire alarm system mayoperate the controls at a fire alarm control panel. It is important that safety precautions areobserved and, if necessary, the fire fighting services are informed of test operation carriedout on the system.

4.1 Function keys / menu options

Fig. 10: Function keys / menu options (cdm337)

Summary of the various menus

There are four logically grouped menu options. When the keyboard is enabled the menu optionsare displayed, each menu option can be selected using the function key located below it.

Overview Displays the active event counts, such as Fire, Fault, Disablement etc.

Details Displays two highest priority active events.

Service Displays the service level screen for the control of the loop and sensors,including enablement and disablement.

Operation

Page 21: 8000-op

Fire Alarm Control Panel 8000C Page 21

Installer After entry of an access code the screen shows selections to allow the user tocontrol the analog loop, perform event simulation, control outputs and theprinter. This menu option is usually used by the installer or servicingorganisation.

Time fctn. Allows entry of time/date and a display of the switching times of the `DelayAlarms /Verify Alarm’ functions.

Quit Terminates the current input and returns the display to the status page,without storing or executing the function.

Enter Acknowledge the selected menu option

Increment Increments the number on the display.

Rem. text `Remote text’ menu option allows display of `text label’ of other fire alarmcontrol panels in the network . In a network system an event detected by a firealarm control panel its `text label’ can be displayed at any other control panel inthe network by selecting the `remote text’ function. This option is onlyapplicable in a network system.

Information and additional text

Info(message text)

This option displays the pre-programmed information text (message text)message relating to the event that appears on the display. The `info text’ menuoption is only displayed when the text has been programmed.

Param/TXT(Label or Param)

This menu option displays the text label or parameter programmed for thecurrent message. Parameters are factory programmed information text for thecurrent message shown on the display. It is possible to switch between textlabel and parameter by selecting this menu option. If text label has not beenprogrammed then menu option `TXT’ is not displayed.

If information text (message text) or label text has been programmed for an event, thenthese are always displayed first. Pressing the function key `Param./AT will toggle betweenInformation text (message text) and parameter.

Operation

Page 22: 8000-op

Page 22 Fire Alarm Control Panel 8000C

4.1.1 Event display and menu options

Fig. 11: Example a fire event display with info menu option (cdm338)

À In all there are three fire events detected. The display shows the first event (1.) and the lastevent (in this case 3.) respectively. Pressing the cursor key scrolls the display, and thenext signal (2.) is displayed.

Á Time of the fire event

 Date of the fire event

à Label describing the location of the Zone(the text label programmed for the triggered zone or detector will be displayed)

Ä Message text (auxiliary text) : menu option is `Info’

and for Text label / parameters : the menu option is `Param/AT’.

Priority of the display for `1. Fire’ :

First Fire event was on 28.07 at 15:10 hours.

the detector No. 02 in the zone No. 02 signalled the FIRE event.

The text label programmed for this zone is: "Office 1 Room 17 1st floor" and it providesinformation on the location of the fire.

Selecting the Info menu option will show message text (auxiliary text) associated with theevent, if it has been programmed for this zone.

Operation

Page 23: 8000-op

Fire Alarm Control Panel 8000C Page 23

Fig. 12: Scroll keys (cdm339)

Further Displays / MessagesThe following messages (if applicable) are shown on the display:

Sounder fault when at least one sector sounder output has malfunctioned and is faulty.

Sounders Disabled when at least one sector sounder output has been disabled.

Operation

Page 24: 8000-op

Page 24 Fire Alarm Control Panel 8000C

4.1.2 Display priority of the messages

The first and last messages with the highest priority are shown on the display of the fire alarmcontrol panel 8000 C.

Priority stage Condition Display

1 Fire alarm FIRE

2 Fire alarm analog loop FIRE

3 Technical alarm T-ALARM

4 Pre-alarm PRE-ALARM

5 Fault FAULT

6 Fault analog loop LINE FAULT

7 Transfer route switched on (analog loop) LINE ON

8 System Fault SYS FAULT

9 Disablement DISABLEMENT

10 Disable loop LINE OFF

11 Fault output AE FAULT

12 Switch-off output AE O/P OFF

13 Activate AE ACTIVATE

14 Test mode TEST

If the controls at the panel are operated during an event display, the corresponding functionis carried out. After the function is executed and 20 seconds after the last key press themessages having highest priority reappear on the display automatically.

Operation

Page 25: 8000-op

Fire Alarm Control Panel 8000C Page 25

4.1.3 Info text (Label), additional text (auxiliary text) and parameter display

Fig. 13: Info text display (cdm340)

À Param/TXT

(Parameter /auxiliary text)

This is a message text `auxiliary text’ that is programmed for active event or itcan be parameter text. If it is parameter text then they are factory-programmed.It is possible to switch between message text (auxiliary text)/parameter by usingthe function key. If additional text has not been programmed, the menu optionAdd. text is not displayed.

Á Info (Label) This is a programmed text label relating to the message on the display. If textlabel exist and was programmed for the event, then only will there be a menuoption `Info’ . If text labels are not programmed then the menu option Info is notdisplayed.

If text label and additional text (auxiliary text) and parameter are programmed for an event, then onlywill they be displayed. Pressing the Param./AT function key during the display of the additional text(auxiliary text) will show `parameter’ message.

Example of info text display (Fig. 14)The programmed information text (auxiliary text) for each zone is maximum 4 lines by 40characters per line, which can be displayed by pressing the function key `Info’. The information text(auxiliary text) is programmed using the customer data editor.

In this example the two-line info text was programmed for zone 02 in a fire condition:

Access via stairway right !Inform Mr. J. Smith (Tel. 02137/ 99152)

Pressing the Condition function key returns the panel to the condition display. The displayswitches automatically to the preceding menu options approximately 20 seconds after thelast operation.

Operation

Page 26: 8000-op

Page 26 Fire Alarm Control Panel 8000C

4.2 Entering time/date

Fig. 14: Entering time/date (cdm341)

Year 2000 compliance : All functions of the 8000 panels work correctly inaccordance with the LPS 2000 requirement.There are no action recommended on reaching the enddate.

The end-date of the implemented real time clock is theyear 2099. After year 2099, leap years will not becompensated and events will be displayed or printedwith an incorrect date, however time will remain accurate. Also anyelements operated on specific dates or certain days of the week willbe actioned on the wrong day.

Entering the time and date is carried out under the menu option `Time functions’.

The corresponding input field (hour, minute, day, etc.) is marked using the cursor keys and byentering the desired value using the numeric keypad. When a date is entered DD.MM.YY, the dayof the week (Mo, Tu, We...) is automatically calculated.

Quit Exits the menu options without storing the changes.

Enter The numeric values entered as shown on the display are stored.

For information on delay times for the function Delay Alarms and Verify Alarm; see Section 4.7 !

Approximately 20 seconds after the last operating action, the display switches backautomatically to the last menu options without storing the changes/inputs !

Operation

Page 27: 8000-op

Fire Alarm Control Panel 8000C Page 27

4.3 Zones

4.3.1 Enabling a zoneWith enablement, a zone that was previously disabled will be in an operative status and thisincludes enablement of all fire alarm sounders in the zone, if there are Fire or Fault events presentthese are deleted.

Press Key

Fig. 15: Enabling a zone 4 (example) (cdm361)

Fig. 16: Display of Enablement of zone 4 (cdm342)

Operation

Page 28: 8000-op

Page 28 Fire Alarm Control Panel 8000C

4.3.2 Disablement of a zoneWith disablement, the corresponding zone will become inoperative and this includes disablementof all fire alarm sounders in the zone. The zone is selected by means of the corresponding zonenumber.

Press Key

Fig. 17: Disablement of zone 4 (example) cdm343

Fig. 18: Display of disablement of zone 4 (cdm343)

In addition to the message on the display, the Disablement LED is lit on the control panel and thecorresponding steady indication of the yellow LED zonal LED if applicable.

Fig. 19: Disablement status display (cdm344)

!A disabled zone will not signal an alarm in the event of fire!

Zones

Page 29: 8000-op

Fire Alarm Control Panel 8000C Page 29

4.3.3 Status of a zone

With this function, the current status of the corresponding zone can be interrogated directly, e.g.Normal, Alarm and Fault.

Press Key

Fig. 20: Status zone 2 (example) cdm363

Fig. 21: Display Status zone 2 cdm346

Operation

Page 30: 8000-op

Page 30 Fire Alarm Control Panel 8000C

4.4 DevicesFunctions relating to devices are only possible for addressable fire detector series 9200. These firedetectors can be selected and controlled using device addresses.

4.4.1 Enabling a devicesWith enablement, the disabled devices in a zone are switched into the operative status. Any activemessages such as Fire or Fault relating to the devices will be deleted.

Please note that the zone number has to be entered before the device number.

Press Key

Fig. 22: An example of enabling device 12 in zone 2 (cdm364)

Fig. 23: Display of Enablement of device 12 in zone 2 (cdm346)

Operation

Page 31: 8000-op

Fire Alarm Control Panel 8000C Page 31

4.4.2 Disabling a deviceWith disablement, a device in the selected zone is disabled. In addition to this a message appearson the display and the Fault and device indicators are lit.

Detectors within a zone can only be disabled if addressable GENT series 9200 devices are used.

Please note that the zone number has to be entered before the device number.

Press Key

Fig. 24: Disablement of device 12 in device zone 12 (example) (cdm365)

Fig. 25: Display disablement of device 12 in device zone 2

!A disabled device will not signal an alarm in the event of a fire!

Operation

Page 32: 8000-op

Page 32 Fire Alarm Control Panel 8000C

4.4.3 Status of a deviceWith this function, the current status of the corresponding device can be interrogated directly, e.g.Normal, Alarm and Fault.

Individual status query can only be carried out if addressable GENT series 9200 devices are used.

Please note that the zone number has to be entered before the device number.

Press Key

Fig. 26: Status of device 12 in zone 2 (example) (cdm366)

Fig. 27: Display Status device 12 in device zone 2 (cdm345)

Operation

Page 33: 8000-op

Fire Alarm Control Panel 8000C Page 33

4.5 Control and status of Output

4.5.1 Enabling outputsBy enabling an output, a previously disabled output (relay, open collector output) is switched backon. In the event of a fire, the enabled output will be controlled in accordance with the programmedcustomer data in the fire alarm control panel.

Press Key

Fig. 28: Enabling Output 2 (example) (cdm367)

Fig. 29: Display enabling Output 2 (cdm348)

Operation

Page 34: 8000-op

Page 34 Fire Alarm Control Panel 8000C

4.5.2 Disabling outputsBy disabling outputs, the outputs (relay, open collector) are disabled. In addition to this a messageappears on the display. The Disablement is indicated by a lit `Disablement’ LED on the controlpanel.

Press Key

Fig. 30: Disablement of Output 2 (example) cdm368

Fig. 31: Display disablement of Output 2 (cdm349)

Outputs may be set for inverse operation in the customer data of the fire alarm control panel. In thiscase, the outputs will be active in normal condition of the panel and is deactivated with anassociated event.

If output is set up for inverse operation and is disabled, then the output becomes deactivated. Thecontrol of external equipment is determined by the NO/NC contacts of the relay.

! Disabled outputs are not activated in the event of fire, therefore the equipment connectedto the outputs are not activated (e.g. alarm devices).

Operation

Page 35: 8000-op

Fire Alarm Control Panel 8000C Page 35

4.5.3 Status of Outputs

With this function, the current status of corresponding output can be interrogated directly, e.g.Normal, Activated, Disabled or Faulty.

Press Key

Fig. 32: Status Output 2 (example) (cdm369)

Fig. 33: Display status Output 2 (cdm350)

Output may be set for inverse operation in the customer data of the fire alarm control panel. In thiscase, the output will be active in the normal condition and will be deactivated with an associatedevent.

In normal condition outputs programmed for inverse activation are indicated as 'active'.

Operation

Page 36: 8000-op

Page 36 Fire Alarm Control Panel 8000C

4.6 Display of system statusThe Overview display shows all active event counts, events like Fire, disablement, Fault and otherevents of the fire alarm control panel sorted by priority.

If more events occur than can be shown in the display, it is possible use the "scroll" buttons to viewother events.

Fig. 34: Summary display (cdm351)

For details of a particular message, scroll to the message and press the function key Detail.

Fig. 35: Display for a detailed status message of a fire alarm (example) (cdm352)

� Text Label line associated with the triggered zone/detector (example)

� Additional information (auxiliary text) or Parameters may be displayed by pressing functionkey Info.

Operation

Page 37: 8000-op

Fire Alarm Control Panel 8000C Page 37

4.7 Delay and Verify AlarmsA switching time can be viewed under the menu option Time functions by the operator of the firealarm control panel. The Delay and Verify Alarms switching times are programmed in the customerdata by the installer.

If a fire alarm occurs during the active delay period and the Verify button is pressed during thedelay time, the delay time extended by the verification time. Both delay and verification times areprogrammed in the customer data (max. 600 seconds) of the fire alarm control panel. During thedelay time the cause of the alarm can be investigated.

After the expiry of the delay and the verification times the alarms are activated can be inhibited bypressing the panel reset button once the emergency is over.

Fig. 36: Entering the switching delay time (cdm353)

If the switching time for Alarm delay / Verify alarm has been programmed in the customer data bythe installer, the first switch-on time and the first switch-off time is accepted as valid switchingtime. The additional switching time is entered under this menu option Time functions are not valid.Exceptional days can be specified in the customer data programming on which the automatic delayalarms / Verify Alarm times programmed by the installer will not take effect.

Example:

Customer data programming: Switch on 06.30, switch off 21.30

Operator's entry under this menu option: Switch on 10.00, switch off 15.00

Valid switching time: Switch on 06.30, switch off 15.00

Please consult your installer to find out whether the function Delay/Verify has beenprogrammed in the customer data of your fire alarm control panel. If this function is notactivated, e.g. for technical reasons or other requirements, the functions described in thissection can not be used.

Operation

Page 38: 8000-op

Page 38 Fire Alarm Control Panel 8000C

4.7.1 Delay Alarms

By pressing the Delay Alarms button, the function delay is started or ended manually (togglefunction). The activated delay is indicated by the continuously illuminated yellow `Alarms Delayed’LED.

Fig. 37: Delay Alarms button (cdm335)

If a fire alarm occurs when the delay function is active, alarms can be delayed by a maximum of upto 600 seconds. The initiated delay time is indicated in the operating panel by the flashing yellow`Alarms Delayed ‘ LED.

4.7.2 Verify Alarm

If the delay time has started due to a fire alarm, the verify alarms adds a further delay a maximumof up to 600 seconds, thus allowing the alarm to be investigated.

Fig. 38: Verify Alarm button (cdm336)

The guidelines of Fire detection and fire alarm systems EN54-2:1998 must be observed for thefunction Delay and Verify

Operation

Page 39: 8000-op

Fire Alarm Control Panel 8000C Page 39

4.8 Alarm counterThis display gives the event counts of the fire and technical alarms in the local system and that ofall the networked systems.

Fig. 39: Display of alarm counters (cdm354)

Example displayThe above figure shows 6 Fire alarms and 2 technical the local fire alarm control panel hasdetected alarms. The sum of all alarm signals detected in the network amounts to 50 fire alarmsand 7 technical alarms (TAL alarms).

The alarm counter cannot be reset to zero -0000-.

Operation

Page 40: 8000-op

Page 40 Fire Alarm Control Panel 8000C

4.9 Test `Display test’The Display test function is activated for approximately 10 seconds and illuminates the all the LEDindicators and the alphanumeric display.

Press Key

Fig. 40: Display Test button (cdm355)

All the LED indicators and displays of the fire alarm control panel, including the zonal indicatorsif applicable.

The alphanumeric display is completely darkened.

The control panel buzzer sounds.

The version number of the panel software is then shown on the display.

This function ends automatically after approx. 10 seconds!Pressing the Test key stops the lamp test before the expiry of 10 seconds!

Operation

Page 41: 8000-op

Fire Alarm Control Panel 8000C Page 41

5 Service Level

The service level allows the authorised user to switch off individual loop devices and completeloops of a local fire alarm system. These functions can also be performed on the panels in anetworked system.

Fig. 41: Service menu option in the status level (cdm356)

Fig. 42: Display of the service options (cdm357)

The following functions can be carried out using the service options of the fire alarm control panel,without having to enter an authorisation code:

Analog loop functions (see Section 5.1.1)

Sensor function (loop) (see Section 5.1.2)

Sensor function (zone/detector) (see Section 5.1.3)

Scroll to the desired function or enter the number of the desired function and then select the `Enter’option.

The service level is protected from unauthorised access by means of an access code. Anyoperation of the fire alarm control panel may only be carried out by authorised and trained persons,observing safety precautions and, if necessary, in co-operation with the emergency services (e.g.fire department).

Operation

Page 42: 8000-op

Page 42 Fire Alarm Control Panel 8000C

5.1.1 Analog loop functionsUsing this function the subassemblies of the fire alarm control panel, including the analog loopswith its connected zones and loop devices can be Enabled/Reset or Disabled using the keyboard.The Loop State is indicated on the panel’s display.

Fig. 43: Entering the analog loop number (cdm358)

Analog loop refers to:

all analog loop modules installed in the fire alarm control panel(including the analogue loop circuit with all associated its devices)

all 4-zone-modules included in the fire alarm control panel(including all zones and devices connected to this module)

certain modules such as relays or the interface on the basic/peripheral module

Definition of Analog Loop identification numberThe loop identification number for a 8000C Panel will be as follows: Where the Analog loop module in fitted in the slot of the Field device module,

this is Loop 121.

The loop number is derived from the individual subassemblies of the 8000C fire alarm controlpanel. The subassemblies can be switched on/off using the internal analog (primary) loopnumber, which is entered on the panel keyboard and is also programmed with the customer dataeditor. This internal primary loop number is composed of the panel number, the slot and thesubassembly number.

0 1 2 3Subassembly number of the Basic-, Field device- other extensionmodue

Slot no.: Basic modue = no. 1Basic modue slot 1 = no. 2Basic modue slot 2 = unused

Number of the Fire Alarm Panel (01 to maximum 31)

Operation

Page 43: 8000-op

Fire Alarm Control Panel 8000C Page 43

Examples of analog (primary) loop numbers

Basic module (Panel no. 01)Primary loopnumber

subassembly

0111 common fault relay of the basic module0112 interface of the basic module0113 micro module slot of the basic module

Field device module in slot 1 (panel no. 01)Primary loopnumber

subassembly

0121 relays K2, K3 and K4 of the field device module0122 Relay K1 of the field device module0123 micro module slot of the Field device module0124 internal primary loop of the Field device module

Extension module in slot 1 (Panel 01)Primary loopnumber

subassembly

0121 no module available0122 no module available0123 micro module slot of the extension module0124 no module available

Operation

Page 44: 8000-op

Page 44 Fire Alarm Control Panel 8000C

Enable (reset) or disable an Analog loop

Enter the number of the Sub-assembly analog loop number which is to be enabled (reset andpress the Enter function key

Enter the desired number (1 = Enable/reset, 2 = Disable) or make a selection using the buttonsand press the Enter function key

In case of an input error, pressing the Zone key can erase the display and the sub-assemblynumber can be re-entered.

! When a Sub-assembly, such as 4-zone module or an analog loop module is disabled, allzones and fire devices connected to the module are disabled. Disabled fire devices andcall points will not activate an alarm in the event of a fire. The equipment connected tooutputs, such as alarm devices, will not be activated in the event a fire.

Operation

Page 45: 8000-op

Fire Alarm Control Panel 8000C Page 45

5.1.2 Sensor functions (loop)This function allows sensing elements of the multi-sensor fire device on a loop to be switched off(disabled). For example it is possible to switch off (disable) all O sensing element(Optical = photoelectric sensor) or all I sensing element (I = ionisation smoke sensors) or in OHImulti-sensor fire devices the OI sensing element installed on an analog loop.

Disabling sensing elements is only possible for OH and OHI multi-sensor fire devices. Thesesensing elements are only fitted on two or three different type of sensors.

If all the OI sensing elements are required to be switched off (disabled) on the loop then select 2.OI – Sensor off. For OHI multi-sensor detectors on a loop the OI sensing elements are switched off(disabled). The third element remains active, which is the heat sensor element. Disabling the heat-sensing element (H sensors) is not possible.

Fig. 44: Sensor functions related to analog loop (cdm359)

O detector Optical fire detector with a smoke sensing element (optical sensor)

T detector Heat detector with a heat sensing element (thermal sensor)

I detector Ionisation smoke sensing element (Ionisation sensor)

OT detector Multi-sensor fire detectors with two sensing elements(OT= Optical and thermal sensor)

OTI detector Multi-sensor fire detectors with three sensing elements(OTI= Optical-, Thermal- and ionisation sensors)

Switching off sensors is only possible for OH and OHI multi-sensor fire detectors. If multi-sensor fire detectors and standard detectors (detectors with a single sensor) are installedtogether in an analog loop, only the sensor in multi-sensor detectors are switched off.

Operation

Page 46: 8000-op

Page 46 Fire Alarm Control Panel 8000C

Example to switch off (disable) sensors on analog loop

Press key "2" to select the `Sensor function (loop)’ or use the scroll keys to highlight and enterthe selection.

Enter the analog loop number on which the sensors are required to be switched.

Enter the number of the desired function (1 = O sensor off, 2 = OI sensor off, 3 = I sensor off, 4= all sensors on) or make the selection using the scroll keys and press Enter key.

The switching off (disabling) of sensors is only possible for OH and OHI multi-sensor firedetectors. Note only the selected sensing element is switched off (disabled).

Switching on/off not permitted

The switching on/off of the detector sensing elements on an analog loop is indicated on the displayof the fire alarm control panel.

If sensors have already been switched off on an analog loop and there are no further sensors toswitch off, then the display will show a message "Switch on/Disablement not permitted". This will bethe case for example if I sensors have been switched off and there are no I sensors left to switchoff or a zone disablement has been detected.

In an analog loop, it is generally possible to execute a disconnection function, e.g. disabledetectors or call points, when no further lower-order disable functions have been carried out. Thatis when individual detectors within a zone have been disabled, this zone cannot be additionallydisabled, as the disabled functions for this zone has been carried out. However, it is possible toswitch off other zones of this analog loop in which sensors/detectors have not been disabled.

In order to change the existing sensor switching status, all switched off (disabled) detector sensorsmust first be switched on, using the command `All sensors on’. After all detector sensors have beenswitched on, a further switching off (disablement) can be performed.

Operation

Page 47: 8000-op

Fire Alarm Control Panel 8000C Page 47

5.1.3 Sensor functions (zone/detector)This function allows individual devices or entire zones to be switched off on an analog loop.

By entering the zone and/or detector number(s) and by making the required `switch off’/on’ theappropriate device(s) are switched.

If a zone number is entered (device number = 0) and the desired sensor switch-off is performed onall the multi-sensor detectors in this zone. All sensors must first be switched on in the zone beforedesired sensors can be switched off.(See also above Sensor function loop)

Fig. 45: Sensor function related to zones/detectors (cdm360)

Switching off sensors is only applicable for OH and OHI multi-sensor fire detectors. If multi-sensor fire detectors and single function detectors are installed on an analog loop, then onlythe detectors having multi-sensors are switched off.

If a switch-off has already been performed, e.g. the sensors of a zone have been switchedoff, the zone or the entire analog loop cannot be subsequently switched off. It is possible toswitch off other zones of this analog loop in which detectors or sensors have not beenswitched off.

Service Level

Page 48: 8000-op

Page 48 Fire Alarm Control Panel 8000C

6 Log book

Site name:_______________________________________________

Site Address________________________________________________________

________________________________________________________

________________________________________________________

________________________________________________________

Servicing organisation Contract number:_____________________

For ServiceNormal hours Monday to Friday Tel:___________________________

Outside normal hours Tel:___________________________________

Manned CentreManned Centre Link station Telephone:________________________

Manned Centre Link Code:__________________________________

Responsible person on Site

This log book must be kept by the responsible person(s) on site and must be available at alltimes together with the panel operating keys.

Log Book

Page 49: 8000-op

Fire Alarm Control Panel 8000C Page 49

6.1 Log SheetsDate Time Event Action required Date

completedName

Log Book

Page 50: 8000-op

Page 50 Fire Alarm Control Panel 8000C

Date Time Event Action required Datecompleted

Name

Log Book

Page 51: 8000-op

Fire Alarm Control Panel 8000C Page 51

Date Time Event Action required Datecompleted

Name

Log Book

Page 52: 8000-op

Page 52 Fire Alarm Control Panel 8000C

Date Time Event Action required Datecompleted

Name

Log Book

Page 53: 8000-op

Fire Alarm Control Panel 8000C Page 53

Date Time Event Action required Datecompleted

Name

Log Book

Page 54: 8000-op

Page 54 Fire Alarm Control Panel 8000C

Date Time Event Action required Datecompleted

Name

Log Book

Page 55: 8000-op

Fire Alarm Control Panel 8000C Page 55

Date Time Event Action required Datecompleted

Name

Log Book

Page 56: 8000-op

Page 56 Fire Alarm Control Panel 8000C

Date Time Event Action required Datecompleted

Name

Log Book

Page 57: 8000-op

Fire Alarm Control Panel 8000C Page 57

Date Time Event Action required Datecompleted

Name

Log Book

Page 58: 8000-op

Page 58 Fire Alarm Control Panel 8000C

Date Time Event Action required Datecompleted

Name

Log Book

Page 59: 8000-op

Fire Alarm Control Panel 8000C Page 59

NOTES

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

______________________________________________________________________________

Notes

Page 60: 8000-op

Caradon Gent LimitedHead Office, 140 Waterside Road, hamilton Industrial Park, Leicester, LE5 1TN, UK. Tel 0116 2462200 www.gent.co.uk

798374/ 1.2000